Sie sind auf Seite 1von 88

User manual

for AC Generators

Qc4002 control panel


User Manual
for AC Generators

Qc4002 control panel

User manual ............................................................................................ 5

Printed Matter N
2954 3390 00
ATLAS COPCO - PORTABLE AIR DIVISION
07/2008 www.atlascopco.com
Qc4002 control panel

Warranty and Liability Limitation


Use only authorized parts.
Any damage or malfunction caused by the use of unauthorized parts is not covered by Warranty
or Product Liability.
The manufacturer does not accept any liability for any damage arising for modifications, addi-
tions or conversions made without the manufacturer's approval in writing.

Copyright 2008, Atlas Copco Airpower n.v., Antwerp, Belgium.


Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.

4 2954 3390 00
User manual

Contents

1 General .........................................................................6 8 Hardware ...................................................................25

2 Display unit and menu structure .....................7 9 Wirings ........................................................................26


2.1. Display unit ...........................................................7 9.1. Wiring for AMF, peak shaving, fixed
2.2. Menu structure......................................................9 power, mains power export and load
take over application ..........................................26
3 Mode overview .......................................................11 9.2. Wiring for Island and PMS mode
3.1. Auto .....................................................................11 application ...........................................................26
3.2. Semi-auto ............................................................11 9.3. Load sharing lines ..............................................27
3.3. Test mode............................................................11 9.4. Binary inputs .......................................................27
3.4. Manual mode ......................................................11 9.5. Analogue inputs (external set-points)...............27
3.5. Block mode..........................................................12 9.6. Optocoupler outputs for external counter ........27
9.7. Display cable .......................................................28
4 Applications overview ........................................12 9.8. USB cable for PC.................................................28
4.1. AMF (no back synchronisation).........................12
4.2. AMF (with back synchronisation)......................13 10Password levels ......................................................29
4.3. Island operation ..................................................13
11Procedure for parameter setup ......................30
4.4. Fixed power / base load .....................................13
11.1. Parameter descriptions ......................................30
4.5. Peak shaving .......................................................13
11.2. Setup....................................................................30
4.6. Load take over.....................................................13
4.7. Mains power export ...........................................13
12Parameter list ..........................................................31
4.8. Multiple gen-sets with load sharing..................13
12.1. Protection ............................................................32
4.9. Multiple gen-sets with power management ....13
12.2. Control .................................................................42
12.3. Input/output.........................................................51
5 Applications details .............................................15
12.4. System .................................................................63
5.1. Single running gen-set.......................................15
12.5. Power management setup .................................78
5.2. Multi running gen-sets .......................................18
12.6. Jump menus .......................................................81
6 Standard functions & protections ................24
13Technical specifications ....................................83
6.1. Engine Protection ...............................................24
6.2. Alternator Protection ..........................................24
14Dimensions ...............................................................85
6.3. Voltage/var/cos(phi) control...............................24
6.4. Analogue controller outputs..............................24
6.5. Load sharing between gen-sets'
analogue lines.....................................................24
6.6. Engine communication ......................................24
6.7. Configurable I/O extension card........................24
6.8. Power Management System (PMS) ..................24
6.9. Mod-bus Serial communication ........................24

7 Optional functions & protections .................25


7.1. Can-open Serial communication.......................25
7.2. Profi-bus Serial communication........................25
7.3. Analogue Transducer Output of
measured values (2x 420mA).........................25
7.4. 7 Binary Inputs ....................................................25
7.5. 4 Relay Outputs...................................................25
7.6. 4 Analogue Inputs (420mA)............................25
7.7. Ethernet - TCP/IP communication .....................25

2954 3390 00 5
Qc4002 control panel

1 General
The Atlas Copco Qc4002 is a protection and control unit for a
generator driven by a diesel engine. It will carry out all necessary
tasks to control and protect a generator, regardless of the use of the
generator. This means that the Atlas Copco Qc4002 can be used
for several application types.

The Qc4002 measuring system is true RMS 3-phase


measurement of generator voltage, generator current, generator
frequency, mains voltage and mains frequency.

The information contained in this User Manual is to assist you in


the installation of your gen-set. If something is not clear, please do
not hesitate to contact Atlas Copco for further help.

6 2954 3390 00
User manual

2 Display unit and menu structure

2.1 Display unit

This chapter deals with the display unit including the pushbutton and LED functions. In addition, the unit menu structure will be presented.

2.1.1 Pushbuttons

The display unit holds 15 pushbuttons with the following functions.

7 13 12 13

9
2
12
3

5 6 8 10 11

1 INFO Shifts the display 3 lower lines to show the alarm list.
2 JUMP Enters a specific menu number selection. All settings have a specific number attached to them. The JUMP button
enables the user to select and display any setting without having to navigate through the menus (see later).
3 START Start of the gen-set if SEMI-AUTO or MANUAL is selected.
4 STOP Stop of the gen-set if SEMI-AUTO or MANUAL is selected.
5 GB Manual activation of close breaker and open breaker sequence if SEMI-AUTO is selected.
6 MB Manual activation of close breaker and open breaker sequence if SEMI-AUTO is selected.
7 VIEW Shifts the first line displaying in the setup menus.
8 LOG Displays the LOG SETUP window where you can choose between the Event, Alarm and Battery logs. The logs
are not deleted when the auxiliary supply is switched off.
9 SELECT (ENTER) Is used to select the underscored entry in the fourth line of the display.
10 BACK Jumps one step backwards in the menu (to previous display or to the entry window).
11 MODE Changes the menu line (line 4) in the display to mode selection.
12 UP / DOWN Increases/decreases the value of the selected set point (in the setup menu). In the daily use display, this button
function is used for scrolling the View lines in V1 or the second line (in the setup menu) displaying of generator
values.
13 LEFT / RIGHT Moves the cursor left / right for manoeuvring in the menus.

2954 3390 00 7
Qc4002 control panel

2.1.2 LED functions

The display unit holds 10 LED functions. The colour is green or red or a combination in different situations.

2
1
3
4

10

5 6 7 8 9

1 ALARM LED flashing indicates that unacknowledged alarms are present.


LED fixed light indicates that ALL alarms are acknowledged.
2 POWER LED indicates that the auxiliary supply is switched on.
3 SELF CHECK OK LED indicates that the self check is OK.
4 ALARM INHIBIT Please refer to Alarm inhibit in the chapter Additional functions.
5 RUN LED indicates that the generator is running.
6 GENERATOR VOLTAGE LED green light indicates that the voltage/frequency is present and OK.
7 (GB) ON LED green light indicates that the generator breaker is closed.
LED yellow light indicates that the generator breaker has received a command to close on a black BUS,
but the breaker is not yet closed due to interlocking of the GB.
LED is flashing orange if the Spring load time signal from the breaker is missing.
8 (MB) ON LED indicates that the mains breaker is closed.
9 MAINS VOLTAGE LED is green, if the mains is present and OK.
LED is red at a measured mains failure.
LED is flashing green when the mains returns during the mains OK delay time.
10 AUTO LED indicates that auto mode is selected.

8 2954 3390 00
User manual

2.2 Menu structure 2.2.2 View menu

The display includes two menu systems which can be used without The view menus (V1, V2 and V3) are the most commonly used
password entry: menus of the unit.

View menu system: View 1: access to up to 15 selectable windows displaying selectable


This is the commonly used menu system. 15 windows are measurements.
configurable and can be entered by using the arrow push-buttons.
View 2: window displays selectable measurements.
Setup menu system:
View 3: window displays operational status and selectable
This menu system is used for setting up the unit, and if the user
measurements.
needs detailed information that is not available in the view menu
system. Changing of parameter settings is password protected.
In the view menus various measured values are on display.
2.2.1 Entry window The menu navigating starts from the fourth display line in the entry
window and is carried out using the navigating push-buttons.
When the unit is powered up, an entry window appears. The entry
window is the turning point in the menu structure and as such the The entry window displays view 3.
gateway to the other menus. It can always be reached by pressing
the BACK push-button 3 times. 2.2.3 Setup menu

The setup menu system is used for parameter setup of the unit, and
QC4002 if the user needs detailed information that is not available in the
view menu system. So, this menu can be used for both daily use and
setup purposes. The menu is entered from the entry window by
selecting the entry SETUP in the fourth display line.

G 0 0V 0
NOTE: The event and alarm list will appear at power up, if an alarm is present.
f-L1 0.00Hz
PROTECTION SETUP
PROT CTRL I/O SYST

Setup menu access to the following sub-menus:


Protection setup

Control setup

I/O setup

System setup

2954 3390 00 9
Qc4002 control panel

Setup structure:

QC4002 V. 3.00.0

2006-08-25 09.35.54
SETUP V3 V2 V1

G 439 440 440V G 439 440 440V G 439 440 440V G 439 440 440V
f-L1 50.02Hz f-L1 50.02Hz f-L1 50.02Hz f-L1 50.02Hz
PROTECTION SETUP CONTROL SETUP INPUT/OUTPUT SETUP SYSTEM SETUP
PROT CTRL I/O SYST PROT CTRL I/O SYST PROT CTRL I/O SYST PROT CTRL I/O SYST

G 439 440 440V G 439 440 440V G 439 440 440V G 439 440 440V
1000 G P> 1 CONTROL SETUP INPUT/OUTPUT SETUP SYSTEM SETUP
Set point -5.0% SYNCHRONICE SETUP BINARY INPUT SETUP GENERAL SETUP
SP DEL OA OB ENA FC SYNC REG BIN AIN OUT GEN MAINS COMM PM

PROT CTRL I/O SYST

1000-1999 SYNC 2000-2499 BIN 3000-3999 GEN 6000-6999

REG 2500-2999 AIN 4000-4999 MAINS 7000-7499

OUT 5000-5999 COMM 7500-7999

PM 8000-8999

10 2954 3390 00
User manual

3 Mode overview Manual The regulator is deactivated and the


AVR UP governor output is activated as long as
The unit has four different running modes and one block mode. The the AVR input is ON.
required mode can be selected via the MODE puhbutton. Repeat Manual The regulator is deactivated and the
pushing the button until the required mode appears on the display, AVR governor output is activated as long as
DOWN the AVR input is ON.
then press SEL to select or BACK to cancel. See below for detailed
information.
3.3 Test mode
3.1 Auto In this mode it is possible to perform the following tests:
In this mode the Qc4002 controls the gen-set and the circuit Simple test:
breakers (generator breaker GB and mains breaker MB) The simple test will only start the gen-set and run it at nominal
automatically according to the operational state. frequency with the generator breaker open. The test will run until
the timer expires.

3.2 Semi-auto Load test:


The load test will start the gen-set and run it at nominal frequency,
In semi-auto mode the operator has to initiate all sequences. This synchronise the generator breaker and produce the power typed in
can be done via the pushbutton functions, modbus commands or the set point in menu 7041. The test will run until the timer expires.
digital inputs. When started in semi-automatic mode, the gen-set NOTES:
will run at nominal values. To run the load test it is required that Sync to Mains is enabled in menu
7084.
The following sequences can be activated in semi-auto:
When running a load test sequence the overlap function is ignored.
Command Description Comment Full test:
Start The start sequence is initiated and The full test will start the gen-set and run it at nominal frequency,
continues until the gen- set starts or synchronise the generator breaker and transfer the load to the
the maximum number of start generator before opening the mains breaker. When the test timer
attempts has been reached. The
expires, the mains breaker will be synchronised and the load is
frequency (and voltage) will be
regulated to make the GB ready to
transferred back to the mains before the generator breaker is opened
close. and the generator is stopped.
Stop The gen-set will be stopped. After NOTE:
disappearance of the running signal, To run the full test it is required that Sync to Mains and Back
the stop sequence will continue to be synchronisation is enabled in menu 7083 and 7084.
active in the 'extended stop time'
period. Parameter 7042 defines the timer related to the test mode.
Close GB The unit will close the generator When AMF mode
breaker, if the mains breaker is open, is selected, the
synchronise and close the generator unit will not
3.4 Manual mode
breaker, if the mains breaker is closed. regulate after
breaker closure. When manual mode is selected, the gen-set can be controlled with
Open GB The unit will ramp down and open the digital inputs. The following commands are possible:
generator breaker at the breaker open Command Comment
point, if the mains breaker is closed.
Start (input or push Gen-set starts (no regulation).
The unit will open the generator
button)
breaker instantly, if the mains breaker
is open or the gen-set mode is island Stop (input or push Gen-set opens GB and stops without cooling-
mode. button) down.
Close MB The unit will close the mains breaker, Manual increase Unit gives increase signal to speed governor.
if the generator breaker is open, speed
synchronise and close the mains Manual decrease Unit gives decrease signal to speed governor.
breaker, if the generator breaker is speed
closed. Manual increase Unit gives increase signal to the AVR. (Option
Open MB The unit opens the mains breaker voltage D1).
instantly. Manual decrease Unit gives decrease signal to the AVR. (Option
Manual The regulator is deactivated and the voltage D1).
GOV UP governor output is activated as long as
NOTES:
the GOV input is ON.
Manual The regulator is deactivated and the It is necessary to configure the digital inputs through the PC utility software
GOV governor output is activated as long as to use the manual commands. The number of configurable digital inputs is
DOWN the GOV input is ON. option dependent.
It is not possible to open and close the generator breaker or the mains
breaker in manual mode.

2954 3390 00 11
Qc4002 control panel

MAN mode cannot be selected, when AUTO mode is selected. To go from 4 Applications overview
AUTO to MAN it is necessary to go to SEMI-AUTO to make MAN
available.
It is possible to select 9 different applications (via display or
configurator software).
3.5 Block mode
Gen-set mode
When the block mode is selected, the unit is locked for certain Automatic Mains Failure (no back sync.)
actions. This means that it cannot start the gen-set or perform any Automatic Mains Failure (with back sync.)
breaker operations. Island operation
Fixed power/base load
To change the running mode from the display, the user will be Peak shaving
asked for a password before the change can be made. It is not Load take over
possible to select block mode when running feedback is present. Mains power export
Multiple gen-sets, load sharing
The purpose of the block mode is to make sure that the gen-set does Multiple gen-sets, power management
not start for instance during maintenance work. If the digital inputs
are used to change the mode, then it is important to know that the For some applications, an optional Power Transducer is required.
input configured to block mode is a constant signal. So, when it is Power Transducers for these applications are available for:
ON the unit is in a blocked state, and when it is OFF, it returns to
the mode it was in before block mode was selected. 230VAC Supply: 1089 9561 56
400VAC Supply: 1089 9561 57
NOTES:
480VAC Supply: 1089 9561 58
If block mode is selected using the display after the digital block input is 24VDC Supply: 1089 9561 59
activated, the Qc4002 will stay in block mode after the block input is
deactivated. The block mode must now be changed using the display. The
block mode can only be changed locally by display or digital input.
4.1 AMF (no back synchronisation)
Alarms are not influenced by block mode selection.
Auto mode description:

The unit automatically starts the gen-set and switches to generator


supply at a mains failure after an adjustable delay time. It is
possible to adjust the unit to change to gen-set operation in two
different ways.
The mains breaker will be opened at gen-set start-up.

The mains breaker will remain closed, until the gen-set is running,
and the gen-set voltage and frequency is OK.

In both cases, the generator breaker will be closed when the


generator voltage and frequency is OK, and the mains breaker is
open.

When the mains returns, the unit will switch back to mains supply
and cool down and stop the gen-set. The switching back to mains
supply is done without back synchronisation when the adjusted
Mains OK delay has expired.

Semi-auto mode description:

The semi-auto mode is not recommended for AMF.

12 2954 3390 00
User manual

4.2 AMF (with back synchronisation) 4.6 Load take over

Auto mode description: The purpose of the load take over mode is to transfer the load
imported from the mains to the gen-set for operation on generator
The unit automatically starts the gen-set and switches to generator supply only.
supply at a mains failure after an adjustable delay time. It is
possible to adjust the unit to change to gen-set operation in two This application is possible in combination with SEMI-AUTO
different ways: mode or AUTO mode with internal real time clock timer.
The mains breaker will be opened at gen-set start-up. Installation is stand alone or with the Mains.
The mains breaker will remain closed until the gen-set is running Operation of the mains and generator breaker GB
and the gen-set voltage and frequency is OK.
An optional Power Transducer is required.
In both cases, the generator breaker will be closed when the
generator voltage and frequency is OK, and the mains breaker is
open. 4.7 Mains power export
When the mains returns, the unit will synchronise the mains The mains power export mode can be used to maintain a constant
breaker to the busbar when the Mains OK delay has expired. Then level of power through the mains breaker. The power can be
the gen-set cools down and stops. exported to the mains or imported from the mains, but always at a
constant level.
Semi-auto mode description:
This application is possible in combination with SEMI-AUTO
The semi-auto mode is not recommended for AMF. mode or AUTO mode. The internal real time clock timer can only
be used in AUTO mode.
4.3 Island operation Installation is with the Mains.
This application is possible in combination with SEMI-AUTO Operation of generator breaker GB
mode or AUTO mode. The internal real time clock timer can only
be used in AUTO mode. Operation of mains breaker MB (if present)

Installation is stand alone, never with the Mains. An optional Power Transducer is required.

Operation of generator breaker GB.


4.8 Multiple gen-sets with load sharing

4.4 Fixed power / base load In this application the units are enabled to share the active and
reactive load equally in percentage of the nominal power. The load
This application is possible in combination with SEMI-AUTO sharing is active when each gen-set is running in island mode and
mode or AUTO mode. The internal real time clock timer can only the generator breaker is closed.
be used in AUTO mode.

Installation is with the Mains. 4.9 Multiple gen-sets with power


management
Operation of generator breaker GB

Operation of mains breaker MB (if present) This application is only possible in combination with the AUTO
mode.

4.5 Peak shaving If the SEMI-AUTO mode is selected, the PMS operation will NOT
function !!
This application is possible in combination with the AUTO mode
or SEMI-AUTO mode. Installations are possible with stand alone generators or with the
Mains (extra Qc4002 Mains is then needed):
Installation with the Mains.
Operation of the generator breaker GB and Mains & Tie breaker
An optional Power Transducer is required. Automatic start/stop function with multiple gensets depending on
Automatic starting of the gen-set the load demand.

Operation of the mains breaker MB and generator breaker GB A number of Qc4002 units are being used in the power
management application, i.e. one for each mains breaker
Load control
(Qc4002 mains controller), if installed, and one for each
Stopping of the gen-set generator (Qc4002 genset controller).

2954 3390 00 13
Qc4002 control panel

All units communicate by means of an internal CANbus Parallel with 2 mains with a tie breaker (the tie breaker is optional):
connection. OPTIONAL OPTIONAL

Power management applications:


MAINS 1 DISPLAY MAINS 1A DISPLAY MAINS 1B MAINS 2 DISPLAY MAINS 2A DISPLAY MAINS 2B

Island mode application:


MAINS 3 Qc4002 Qc4002 MAINS 3 Qc4002 Qc4002
BREAKER BREAKER
MAINS MAINS MAINS MAINS
(MB1) (MB2)
DISPLAY 1 DISPLAY 2

CONSUMERS

BUSBAR DISPLAY 1 DISPLAY 2

CAN-bus TIE
BREAKER
(TB)

BUSBAR
GENERATOR Qc4002 GENERATOR Qc4002 CAN-bus
BREAKER BREAKER
(GB1) (GB2) GENERATOR Qc4002 GENERATOR Qc4002
BREAKER BREAKER
3 3 (GB1) (GB2)
3 3

DIESEL GENERATOR SET 1 DIESEL GENERATOR SET 2

DIESEL GENERATOR SET 1 DIESEL GENERATOR SET 2 ATS plant, mains unit:
Parallell to mains application: DISPLAY MAINS

MAINS
MAINS DISPLAY MAINS

3
MAINS OKAY

CONSUMERS ATS ON/OFF


Qc4002

3
DISPLAY 1 DISPLAY 2 DISPLAY 3
MAINS Qc4002
BREAKER
(MB) TIE
BREAKER
(TB)
DISPLAY 1 DISPLAY 2
CONSUMERS

BUSBAR
CAN-bus
TIE
BREAKER
(TB)
Qc4002 Qc4002 Qc4002

3 3 3

BUSBAR

CAN-bus

DIESEL GENERATOR SET 1 DIESEL GENERATOR SET 2 DIESEL GENERATOR SET 3


GENERATOR Qc4002 GENERATOR Qc4002
BREAKER BREAKER
(GB1) (GB2)
3 3

DIESEL GENERATOR SET 1 DIESEL GENERATOR SET 2

14 2954 3390 00
User manual

5 Applications details When the mains is restored within the user-defined limits for a
certain user-defined time, the gen-set will synchronise to the mains
This chapter shows the correct application configuration for the and deload the gen-set according a user defined ramp before
different use of the Qc4002. The following application disconnecting the gen-set (only if back-synchronisation feature is
configurations are possible: enabled)

Single gen-set AMF operation AUTO mode The gen-set will then go into cool down and stop.
(SEMI-AUTO mode)*
The generator is running in a system with only short simultaneous
Island mode AUTO mode
connection to other systems.
SEMI-AUTO mode
Peak shaving AUTO mode It is possible to enable/disable the back synchronisation feature.
SEMI-AUTO mode
LOAD
Fixed Power AUTO mode
SEMI-AUTO mode
Load Take Over AUTO mode G
SEMI-AUTO mode
Mains Power Export AUTO mode Qc4002
SEMI-AUTO mode
Multi gen-sets AMF operation AUTO mode
Related customer settings:
(SEMI-AUTO mode)*
Island mode AUTO mode Check that the module is in AUTO mode pushbutton on display

SEMI-AUTO mode Gen-set mode (=application) channel 6070


Peak shaving AUTO mode Cool down setting channel 6210
SEMI-AUTO mode Mains V failure channel 7060

Fixed Power AUTO mode Mains Hz failure channel 7070


SEMI-AUTO mode Back synchronisation setting of Mains channel 7080
breaker
Load Take Over AUTO mode
SEMI-AUTO mode Related customer wirings:
Mains Power Export AUTO mode
Mains sensing lines L1 / L2 / L3.
SEMI-AUTO mode
Power Management AUTO mode Wires for control and feedback of the Mains breaker.
System (SEMI-AUTO mode)*
For details on all setpoints, see the setpoint list.
( )* = the AMF and PMS operation will not function properly, when SEMI-
AUTO mode is selected! For details on the wirings, see the circuit diagram.
It is possible to use the Qc4002 for one of these purposes, or for
5.1.2 Island operation
peak shaving/fixed power/ load take over in combination with
AMF (only in AUTO mode).
In combination with SEMI-AUTO mode:
The correct configuration can be set through the Qc4002 Utility The gen-set can be started/stopped wih a local start command. The
Software or via the setup menu on the display. breaker can be closed/opened with a local command (= LOCAL
START).
From each of the above applications the module can jump into the
Test mode, by selecting Test mode via the mode button on the In combination with AUTO mode:
display. The gen-set will follow the defined Test sequences and
afterwards the gen-set will return in its previous application, The gen-set can be started/stopped with a remote start command (=
always in combination with the AUTO mode. REMOTE START).

This can be a command through a signal from the internal real time
5.1 Single running gen-set clock.

This can be a command through a binary input. When an external


5.1.1 AMF operation hard-wired switch (connected to this dedicated input) is closed, the
unit will start up and the generator breaker will be closed. When this
When the mains goes outside the user-defined voltage (over and external switch is opened again, the unit will open the generator
under) or frequency (over and under) for a certain user-defined circuit breaker and stop.
time, the mains will be disconnected and the gen-set will be started
to take over the load.

2954 3390 00 15
Qc4002 control panel

The generator is running in a system without simultaneous It is possible to enable/disable the back synchronisation feature.
connection to other systems.
LOAD
LOAD

G
G
Qc4002

Qc4002 PT

Related customer settings: Related customer settings:


Select the correct mode (Semi-auto/Auto) pushbutton MODE on Select the correct mode (Semi-auto/Auto) pushbutton MODE on
display display
Gen-set mode (=application) channel 6070 Power ramp up / ramp down channel 2610-2620
Cool down setting channel 6210 Mains imported power level channel 7000
Start command through internal real time channels 6600-6670 Daytime period channel 7010
clock
Gen-set mode (=application) channel 6070
Stop command through internal real time channels 6600-6670
Cool down setting channel 6210
clock
Back synchronisation setting of Mains channel 7080
Related customer wirings: breaker
Enable/disable AMF as 2nd application channel 7080
Remote Start switch towards the dedicated binary input
Related customer wirings:
For details on all setpoints, see the setpoint list.
Power Transducer lines
For details on the wirings, see the circuit diagram.
Wires for control and feedback of the Mains breaker
5.1.3 Peak shaving application For details on all setpoints, see the setpoint list.
In combination with AUTO mode: For details on the wirings, see the circuit diagram
The gen-set will start up when the mains imported power (measured
For more information on the Power Transducer option, please
through an optional Power Transducer PT) exceeds a user-defined
level. The gen-set will synchronise with the bus, and will take load contact Atlas Copco.
according a user-defined ramp until the user-defined allowable
mains imported power level is reached. 5.1.4 Fixed power

When the mains imported power decreases below the user-defined In combination with SEMI-AUTO mode:
mains imported power level for a user-definable time, the gen-set
will deload according a user-defined ramp and disconnect from the The gen-set will start up on a local command. The gen-set will
bus. Then the gen-set will go into cooldown. synchronise with the mains, it will connect with the bus and it will
take load according to a user-defined level and according a user-
It is possible to define two levels of max. mains imported power: defined ramp.
'day' level and 'night' level.
Stopping on a local command will deload the gen-set according a
In combination with SEMI-AUTO mode: user-defined ramp and disconnect the gen-set from the bus. Then
the gen-set will go into cooldown and stop.
The gen-set starts up once a local start command is given. The gen-
set breaker closes once the local command is given, and the In combination with AUTO mode:
synchronisation is done. The gen-set will take load only if the mains
imported power exceeds a user-defined level. The gen-set will go through the same sequences once a remote
command is given.
The gen-set breaker can be opened and the gen-set stopped with a
local command. This can be a command through a signal from the internal real time
clock.
The generator is running in a system with long simultaneous
Or this can be a command through a binary input. When an external
connection to other systems.
hard-wired switch (connected to this dedicated input) is closed, the
unit will start up and the generator breaker will be closed. When this
It is possible to enable/disable AMF as a second application when
external switch is opened again, the unit will open the generator
the gen-set is in the peak shaving application. With AMF enabled,
circuit breaker and stop.
the gen-set will always guard the mains and will act as an AMF unit
when not active as a peak shaving gen-set.

16 2954 3390 00
User manual

It is possible to enable/disable AMF as a second application when In combination with AUTO mode:
the gen-set is in fixe power application. With AMF enabled, the
The gen-set will go through the same sequences once a remote
gen-set will always guard the mains and will act as an AMF unit
command is given.
when not active as a fixed power gen-set.
This can be a command through a signal from the internal real time
It is possible to enable/disable the back synchronisation feature. clock.

The generator is running in a system with long simultaneous Or this can be a command through a binary input.
connection to other systems.
It is possible to enable/disable AMF as a second application when
LOAD the gen-set is in the Load Take Over application. With AMF
enabled, the gen-set will always guard the mains and will act as an
AMF unit when not active as a Load Take Over gen-set.
G
It is possible to enable/disable the back synchronisation feature.
Qc4002
The generator is running in a system with short simultaneous
connection to other systems.
Related customer settings:
LOAD
Select the correct mode (Semi-auto/Auto) pushbutton MODE on
display
Power ramp up / ramp down channel 2610-2620 G
Fixed Power setpoint channel 7050
Gen-set mode (=application) channel 6070 Qc4002

Cool down setting channel 6210 PT


Back synchronisation setting of Mains channel 7080
breaker
Enable/disable AMF as 2nd application channel 7080 Related customer settings:
Start command through internal real time channels 6600-6670 Select the correct mode (Semi-auto/Auto) pushbutton MODE on
clock display
Stop command through internal real time channels 6600-6670 Power ramp up / ramp down channel 2610-2620
clock Gen-set mode (=application) channel 6070
Cool down setting channel 6210
Related customer wirings:
Back synchronisation setting of Mains channel 7080
Remote Start switch towards the dedicated binary input. breaker
Enable/disable AMF as 2nd application channel 7080
Wires for control and feedback of the Mains breaker.
Start command through internal real time channels 6600-6670
For details on all setpoints, see the setpoint list. clock
Stop command through internal real time channels 6600-6670
For details on the wirings, see the circuit diagram. clock

5.1.5 Load take over Related customer wirings:


Remote Start switch towards the dedicated binary input
In combination with SEMI-AUTO mode:
Wires for control and feedback of the Mains breaker
The gen-set will start up on a local command. The gen-set will
synchronise with the mains, it will connect with the bus, and it will Wires from the optional Power Transducer
take over the load according a user-defined ramp and disconnect the
mains. To know if the load is completely taken over from the mains, For details on all setpoints, see the setpoint list.
an optional Power Transducer (PT) is necessary.
For details on the wirings, see the circuit diagram.
After a local stop command, the gen-set will synchronise again to
mains, connect the bus to mains, deload the gen-set according a For more information on the Power Transducer option, please
user-defined ramp and disconnect the gen-set from the bus. Then contact Atlas Copco.
the gen-set will go into cooldown and stop.

2954 3390 00 17
Qc4002 control panel

5.1.6 Mains power export 5.2 Multi running gen-sets

In combination with AUTO mode: 5.2.1 AMF operation


The gen-set starts as a result of a digital start command. It
The power management system (PMS) has a fully intelligent
synchronises to the mains and will start to export power to the
system which will start up all gen-sets in case of a mains failure,
mains. The amount of power exported will be kept at a fixed level
regardless of the load on the busbar (the factory).
and then stops and starts gen-sets according to the actual load and
according to each gen-set's status.
The stop command will cause the gen-set to deload and trip the
generator breaker. Afterwards, it will cool down and stop. It is possible to do this kind of intelligent load sharing between up
to 16 Qc4002 controllers.
A Power Transducer (PT) is used for indication of the power
exported from the mains. The generators are running in a system with only short
simultaneous connection to other systems. For the correct working
In combination with SEMI-AUTO mode: all the generator Qc4002 controllers need to be programmed in
The gen-set starts as a result of a local start command. It PMS - AUTO mode and the Qc4002 mains controller has to put
synchronises to the mains and will start to export power to the in AMF - AUTO mode. A complete overview on the parameters
mains. The amount of power exported will be kept at a fixed level that needs to be programmed in both controllers can be found
regardless of the load on the busbar (the factory). below.

The local stop command will cause the gen-set to deload and trip the
generator breaker. Afterwards, it will cool down and stop. G
A Power Transducer (PT) is used for indication of the power
Qc4002
exported from the mains.

PMS can
LOAD
G
Tie Mains
Breaker breaker
G Qc4002
LOAD

Qc4002
G
PT
Qc4002 Qc Mains
controller

Related customer settings:


Check that the module is in AUTO mode pushbutton on display
Gen-set mode (=application) channel 6070
Cool down setting channel 6210
Int. Communication ID channel 7531
PMS configuration channel 8020
Priority Select channel 8030
Stop Noncon. Gen-sets channel 8140
Manual priority selection channel 8080-8100
Number of ID's channel 8040-8070
Load dependent start channel 8000
Load dedendent stop channel 8010

Extra related customer settings Qc4002 Mains controller :


Mains V failure channel 7060
Mains Hz failure channel 7070
Back synchronisation setting of Mains channel 7080
breaker
Power capacity set-point channel 8193
Tie breaker channel 8190

18 2954 3390 00
User manual

NOTE :
The Qc4002 controller of the generators and the Qc4002 mains LOAD
controller are NOT the same controllers. It is not possible to mutual
exchange the 2 controllers !
G

Related customer wirings: Qc4002

Mains sensing lines L1 / L2 / L3.

Wires for control and feedback of the Mains and Tie breaker. G
PMS communication lines.
Qc4002
For more details on related customer settings, see the setpoint list.

For more details on related customer wirings, see circuit diagram. G


For more details on the PMS, see page 23. Qc4002

5.2.2 Island operation


Related customer settings:
In combination with SEMI-AUTO mode:
Select the correct mode (Semi-auto/Auto) pushbutton MODE on
Starting up and loading generators can be done through local display
commands on the LCDisplays of each unit. For each extra generator Gen-set mode (=application) channel 6070
that is started, the breaker will close once the local command is Cool down setting channel 6210
given and the synchronisation is done. Start command through internal real time channels 6600-6670
clock
In combination with AUTO mode: Stop command through internal real time channels 6600-6670
clock
Starting up and loading generators can be done through a remote
command. This can be a command through a signal from the Extra related customer settings Qc4002 Mains controller :
internal real time clock. Or this can be a command through a binary
input. Int. Communication ID channel 7531
PMS configuration channel 8020
Analogue: Priority Select channel 8030
Stop Noncon. Gen-sets channel 8140
The load sharing can be done through the analogue load sharing
lines. Manual priority selection channel 8080-8100
Number of ID's channel 8040-8070
This 'analogue' load sharing is compatible with the Qc4001 Load dependent start channel 8000
controller. Load dedendent stop channel 8010

PMS: Related customer wirings:

Via the power management system (PMS) you have a fully Remote Start switch towards the dedicated binary input
intelligent system which can determine which gen-sets to start and
PMS communication lines
stop, according to the actual load and to each gen-set's status. It is
possible to do this kind of intelligent load sharing between up to16
For more details on related customer settings, see the setpoint list.
Qc4002 controllers.
NOTE : For more details on related customer wirings, see circuit diagram.
When paralleling generators with PMS, it is no longer necessary to use the
analogue load sharing lines. This will be done through the PMS For more details on the PMS, see page 23.
communication lines.

The generators are running in a system without simultaneous


connection to other systems.

2954 3390 00 19
Qc4002 control panel

5.2.3 Peak shaving application Related customer wirings:

Via the power management system (PMS) you have a fully Mains sensing lines L1 / L2 / L3
intelligent system which will start and stop the necessary gen-set(s) Wires for control and feedback of the Mains breaker
to limit the imported mains power according the user-defined level.
PMS communication lines
It is possible to define 2 levels of max mains imported power: 'day'
level and 'night' level. For more details on related customer settings, see the setpoint list.

It is possible to do this kind of intelligent peak shaving with up to For more details on related customer wirings, see circuit diagram.
16 Qc4002 controllers.
For more details on the PMS, see page 23.
The generators are running in a system with long simultaneous
connection to other systems. 5.2.4 Fixed power

It is possible to enable/disable AMF as a second application when Via the power management system (PMS) you have a fully
the gen-sets are in this peak shaving application. intelligent system which will start up the necessary gen-set(s) when
a start signal is given, synchronise the gen-set(s) with the mains,
With AMF enabled, the gen-sets will always guard the mains and connect the gen-set(s) with the bus and load according a user-
will act as AMF units when not active as peak shaving gen-sets defined ramp to meet the user-defined fixed load.
(extra Tie breaker is needed, page 18).
When a stop signal is given, the gen-set(s) will be deloaded
It is possible to enable/disable the back synchronisation feature. according a user-defined ramp and they will be disconnected from
the bus. The gen-set(s) will go into cooldown and stop.
-

LOAD
The start and stop signals can be local commands (in combination
G with SEMI-AUTO mode), or remote commands from the binary
input or from the internal real time clock (in combination with
Qc4002 AUTO mode).
PMS can

It is possible to do this kind of intelligent fixed loading with up to


G 16 Qc4002 controllers (all equipped with this PMS option).

Qc4002 The generators are running in a system with long simultaneous


connection to other systems.

It is possible to enable/disable AMF as a second application when


G the gen-sets are in this fixed power application. With AMF
Qc4002
Mains enabled, the gen-sets will always guard the mains and will act as
controller AMF units when not active as a fixed power gen-sets (extra Tie
breaker is needed, page 18).
Related customer settings:
It is possible to enable/disable the back synchronisation feature.
Select the correct mode (Semi-auto/Auto) pushbutton MODE on
display LOAD

Power ramp up / ramp down channel 2610-2620


Mains imported power level channel 7000 G
Daytime period channel 7010
Qc4002
Gen-set mode (=application) channel 6070
Cool down setting channel 6210
PMS can

Back synchronisation setting of Mains channel 7080


breaker G
Enable/disable AMF as 2nd application channel 7080
Qc4002
Int. Communication ID channel 7531
PMS configuration channel 8020
Priority Select channel 8030
Stop Noncon. Gen-sets channel 8140 G
Manual priority selection channel 8080-8100 Mains
Qc4002 controller
Number of ID's channel 8040-8070
Load dependent start channel 8000
Load dedendent stop channel 8010

20 2954 3390 00
User manual

Related customer settings: 5.2.5 Load take over

Select the correct mode (Semi-auto/Auto) pushbutton MODE on Via the power management system (PMS) you have a fully
display intelligent system which will start the necessary gen-set(s) on a
Power ramp up / ramp down channel 2610-2620 local command or remote command, synchronise the gen-set(s) to
Fixed Power setpoint channel 7050 mains, connect to the bus, take over the load according a user
Gen-set mode (=application) channel 6070 defined ramp and disconnect mains.
Cool down setting channel 6210
Back synchronisation setting of Mains channel 7080 This intelligent system will start and stop gen-sets to meet the
breaker actual load.
Enable/disable AMF as 2nd application channel 7080
Start command through internal real time channels 6600-6670 After a local command or remote stop command, the gen-set(s) will
clock synchronise to mains, connect the bus to mains, deload the gen-
Stop command through internal real time channels 6600-6670 set(s) according a user defined ramp and disconnect the gen-set
clock from the bus. Then the gen-set(s) will go into cooldown and stop.
Int. Communication ID channel 7531
PMS configuration channel 8020 It is possible to do this kind of intelligent load take over with up to
Priority Select channel 8030 16 Qc4002 controllers (all equipped with this PMS option).
Stop Noncon. Gen-sets channel 8140
The local commands can be given when the module is in SEMI-
Running hours priority selection channel 8110
AUTO mode.
Manual priority selection channel 8080-8100
Number of ID's channel 8040-8070
The remote commands can be given when the module is in AUTO
Load dependent start channel 8000 mode. This can be through the binary input or through a signal from
Load dedendent stop channel 8010 the internal real time clock.
Related customer wirings:
The generator is running in a system with short simultaneous
Mains sensing lines L1 / L2 / L3 connection to other systems.
Remote Start switch towards the dedicated binary input It is possible to enable/disable AMF as a second application when
Wires for control and feedback of the Mains breaker the gen-sets are in this Load Take Over application. With AMF
enabled, the gen-sets will always guard the mains and will act as
PMS communication lines AMF units when not active as Load Take Over gen-sets (extra Tie
breaker is needed, page 18).
For more details on related customer settings, see the setpoint list.
It is possible to enable/disable the back synchronisation feature.
For more details on related customer wirings, see circuit diagram.
LOAD
For more details on the PMS, see page 23.
G
Qc4002
PMS can

G
Qc4002

G
Mains
Qc4002 controller

Related customer settings:

Select the correct mode (Semi-auto/Auto) pushbutton MODE on


display
Power ramp up / ramp down channel 2610-2620
Gen-set mode (=application) channel 6070
Cool down setting channel 6210

2954 3390 00 21
Qc4002 control panel

Back synchronisation setting of Mains channel 7080


LOAD
breaker
Enable/disable AMF as 2nd application channel 7080
Start command through internal real time channels 6600-6670 G
clock
Qc4002
Stop command through internal real time channels 6600-6670
clock

PMS can
Int. Communication ID channel 7531
PMS configuration channel 8020 G
Priority Select channel 8030
Stop Noncon. Gen-sets channel 8140 Qc4002
Manual priority selection channel 8080-8100
Number of ID's channel 8040-8070
Load dependent start channel 8000 G
Load dependent stop channel 8010 Mains
Qc4002 controller
Related customer wirings:
Mains sensing lines L1 / L2 / L3 Related customer settings:
Remote Start switch towards the dedicated binary input Select the correct mode (Semi-auto/Auto) pushbutton MODE on
display
Wires for control and feedback of the Mains breaker
Power ramp up / ramp down channel 2610-2620
PMS communication lines Mains Power Export setpoint channel 3080
Gen-set mode (=application) channel 6070
For more details on related customer settings, see the setpoint list. Cool down setting channel 6210
Back synchronisation setting of Mains channel 7080
For more details on related customer wirings, see circuit diagram. breaker
Enable/disable AMF as 2nd application channel 7080
For more details on the PMS, see page 23.
Start command through internal real time channels 6600-6670
clock
5.2.6 Mains power export Stop command through internal real time channels 6600-6670
clock
Via the power management system (PMS) you have a fully
Int. Communication ID channel 7531
intelligent system which will start up the necessary gen-set(s) when
PMS configuration channel 8020
a start signal is given, synchronise the gen-set(s) with the mains,
Priority Select channel 8030
connect the gen-set(s) with the bus and start to export power to the
Stop Noncon. Gen-sets channel 8140
mains. The amount of power exported will be kept at a fixed level
Running hours priority selection channel 8110
regardless of the load on the busbar (the factory).
Manual priority selection channel 8080-8100
When a stop signal is given, the gen-set(s) will be deloaded Number of ID's channel 8040-8070
according a user-defined ramp and they will be disconnected from Load dependent start channel 8000
the bus. The gen-set(s) will go into cooldown and stop. Load dedendent stop channel 8010

The start and stop signals can be local commands (in combination Related customer wirings:
with SEMI-AUTO mode), or remote commands from the binary Mains sensing lines L1 / L2 / L3
input or from the internal real time clock (in combination with
AUTO mode). Remote Start switch towards the dedicated binary input

Wires for control and feedback of the Mains breaker


It is possible to do this kind of intelligent mains power export with
up to 16 Qc4002 controllers (all equipped with this PMS option). PMS communication lines

The generators are running in a system with long simultaneous For more details on related customer settings, see the setpoint list.
connection to other systems.
For more details on related customer wirings, see circuit diagram.
It is possible to enable/disable AMF as a second application when
the gen-sets are in this mains power export application. With AMF For more details on the PMS, see page 23.
enabled, the gen-sets will always guard the mains and will act as
AMF units when not active as a mains power export gen-sets (extra
Tie breaker is needed, page 18).

It is possible to enable/disable the back synchronisation feature.

22 2954 3390 00
User manual

5.2.7 Power management system G1 & G2 & G3 are running; at 400kW (700kW - 200kW - 100kW)
=> G3 will be stopped
PMS (= Power Management System) is a system that will G1 & G2 are running; at 200kW (500kW - 200kW - 100kW) => G2
automatically start & stop generators based on the actual load will be stopped
dependency. This will be done through a PMS communication
between the different units connected. The priority on starting & stopping the generators can be chosen on
priority settings or on the amount of running hours. In manual
PMS applications are always in combination with AUTO mode. mode the start & stop sequence is determent by the chosen priority
The Qc4002 controllers from the gensets need to be programmed between the generators. The generator with the lowest priority will
as PMS in AUTO mode. When a Qc Mains controller is installed start as the latest genset and will stop as first. If running hours are
this needs to be programmed in the application that is required chosen as priority the start & stop sequence will be defined based
(AMF, LTO, Fixed power) and AUTO mode. on the actual running hours of the different generators. The lowest
By programming the parameters in AUTO mode, the
running hours will get the highest priority.
generator can start up immediately. It is
When paralleling generators with PMS, it is no longer
recommended to place the generator in SEMI-AUTO necessary to use the analogue load sharing lines. This
mode while programming all the PMS parameters ! will be done through the PMS communication lines.
In an application with PMS it is important to program correctly the Use a screened CAN communication cable with a
Start & Stop signals between the different generators because of the maximum total distance of 200 meters. Do not connect
the cable screen to the ground ! Use a 120 Ohm
following reasons:
resistor at both end controllers of the PMS as
The maximum load step needs to be programmed in the Qc4002 described in the drawings below.
controllers. This never may exceeds the power reserve of the
running generators. Otherwise the gensets will go in overload with The connections between the generators Qc4002 controllers
a sudden max. load increase before the next generator is started up (without the Qc mains controller)
and connected to the busbar.

To prevent the gensets to run in a start - stop loop. G1 G2 G3


X32 X32 X32
NOTE: 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6

A start - stop loop will result in a deload - load loop = GB open - GB close.
120ohm 120ohm
This can damage the generator breaker.
A start - stop loop can easily be avoided by assuring that the stop value is
higher than the start value. The connections for PMS between the generator and the Qc mains
controller :
The start signal is the value of the maximum required load step

The stop signal is the value when the generator should be stopped G1 G2 M
automatically. X32 X32 Qc4002
1 2 3 4 5 6 1 2 3 4 5 6 B1 B2 B3

Example :
120ohm 120ohm

Installation with 3 gensets : G1 = 300 kW; G2 = 200 kW; G3 =


200 kW
Start signal is set at 90kW (Maximum load step < 90kW)
Start signal if :

Total Power needed > (Total available power of running gensets -


setpoint start signal)

Only G1 is running; at 210kW load (300kW - 90kW) => G2 will be


started
G1 & G2 are running; at 410kW load (200kW + 300kW - 90kW) =>
G3 will be started

Stop signal is set at 100kW and priority is set as (high) G1 > G2 >
G3 (low)
Stop signal if :

Total Power needed < (Total available power of running gensets -


Power of generator with lowest priority - setpoint stop signal)

2954 3390 00 23
Qc4002 control panel

6 Standard functions & protections 6.4 Analogue controller outputs

The Qc4002 measuring system is true RMS 3-phase +/-25mA for speed governor
measurement of generator voltage, generator current, generator +/-25mA for voltage/var/cos control
frequency, mains voltage and mains frequency.

The Qc4002 module is built up with different extension cards 6.5 Load sharing between gen-sets'
that are mounted into one of the 9 different slots. Some of these analogue lines
cards are mounted as standard, and some as an option.
(Gen-set controller only)
The Qc4002 has the following control and protection functions
as standard:
6.6 Engine communication
6.1 Engine Protection Software selectable for:

The engine alarm extension card has the following configurable IVECO EDC7C1
inputs and outputs: Detroit Diesel DDEC communication
1 420 mA input for Mains Power Transducer Deutz EMR communication
2 configurable 420mA inputs Volvo EDCIII/EDCIV/EMSII
3 resistive sensor inputs for Engine Oil Pressure/Coolant Level, John Deere JDEC communication
Coolant Temperature/Alternator Temperature, Fuel Level
Scania EMS/EMSS6 communication
1 tacho input
Caterpillar C4.4/C6.6
9 binary inputs for Access Lock, Running Feedback, Engine
Failure, Emergency Stop, 2nd Parameter Set, W/L, Remote Start,
disable analogue fuel input , Static Battery Charger. 6.7 Configurable I/O extension card
13 binary inputs and 4 relay outputs
6.2 Alternator Protection
NOTE:
Over current protection, definite time characteristic
It is possible to configure binary inputs, analogue inputs and binary outputs.
Reverse power protection, definite time characteristic
Binary Inputs
Over- and under voltage (generator and busbar)
The text can be edited to a more saying name by using the USW
Over- and under frequency (generator and busbar)
Input 10 (terminal 118) can be configured as 'Sprinkler'. When
Vector jump 'Sprinkler' is selected, all alarms and fail classes are overruled. The
Df/dt (ROCOF) only alarms the gen-set will react on are 'Emergency Stop' on
terminal 117 or a 'Tacho Failure'. Also the gen-set has 7 start
Overload attempts before 'Start Failure'.
Current unbalance
Analogue Inputs
Voltage asymmetry
The text can be edited to a more saying name
Reactive power (import (excitation loss)/export)
Binary Outputs

6.3 Voltage/var/cos(phi) control The output can be configured as 'Alarm' relay

The output can be configured as 'Limit' relay


Selectable (via binary inputs or (optional) serial interface)
functions:
Constant voltage (stand-alone)
6.8 Power Management System (PMS)

Constant reactive power (parallel with mains)


6.9 Mod-bus Serial communication
Constant power factor (parallel with mains)

Reactive load sharing (parallel with other generators, island


operation)

24 2954 3390 00
User manual

7 Optional functions & protections 8 Hardware


As standard 6 slots out of 9 slots contain a dedicated extension card. The Qc4002 housing is divided into board slot positions, some of
This means that 3 slots are still free for the optional extension cards. which are standard (non-changeable) and some intended for
The following optional extension cards are available: options.

7.1 Can-open Serial communication

7.2 Profi-bus Serial communication


NOTE:
It is only possible to have one of the above options on one and the same
unit.

7.3 Analogue Transducer Output of


measured values (2x 420mA)

7.4 7 Binary Inputs

7.5 4 Relay Outputs

7.6 4 Analogue Inputs (420mA)


NOTE:
It is only possible to have one of the above options on one and the same
unit.

7.7 Ethernet - TCP/IP communication

Integrated Web Server with web pages for plant presentation.

2954 3390 00 25
Qc4002 control panel

9 Wirings

9.1 Wiring for AMF, peak shaving, fixed power, mains power export and load take over
application

This drawing gives only a rough overview on the wiring. For details please see the correct circuit diagrams of the machine.

LOAD
GENERATOR

MAINS
L1 L1
L2 S1 S2 L2
L3 S1 S2 L3
N S1 S2 N
73
74
75
76
77
78

U NEUTRAL 84
U L3 83
U L2 81
U L1 79

14
15

17
18

8
9

11
12

U L3 89
U L2 87
U L1 85
L1

L2

L3

GENERATOR

CLOSE MB
CLOSE GB
CURRENT

VOLTAGE

VOLTAGE
OPEN MB
OPEN GB

9.2 Wiring for Island and PMS mode application MAINS

This drawing gives only a rough overview on the wiring. For details please see the correct circuit diagrams of the machine.

LOAD
GENERATOR

L1 L1
L2 S1 S2 L2
L3 S1 S2 L3
N S1 S2 N
73
74
75
76
77
78

U NEUTRAL 84
U L3 83
U L2 81
U L1 79

14
15

17
18

U L3 89
U L2 87
U L1 85
L1

L2

L3
GENERATOR

CLOSE GB
CURRENT

VOLTAGE

VOLTAGE
OPEN GB

BUSBAR

26 2954 3390 00
User manual

9.3 Load sharing lines

Even though screened cable is not needed, it is recommended if the cable run is longer than 5 m between units.

37 38 39 37 38 39 37 38 39

To other
units

Load sharing cables supplied with unit.


Load share lines of up to 300 metres are commonly used, but 300 metres is not the limit.
NOTE:
When the option PMS is installed these load sharing cables are not needed. The loads are shared through the PMS communication cable.

9.4 Binary inputs

All binary inputs are 12/24 VDC.

The binary inputs use fixed signals. They do not use pulse signals.

9.5 Analogue inputs (external set-points)

The set-point inputs are passive, i.e. an external power source is needed. This can be an active output from e.g. a PLC, or a potentiometer
can be used.

9.6 Optocoupler outputs for external counter

The kWh counter (terminals 20-22) and kvarh counter (terminals 21-22) outputs are low-power outputs.

2954 3390 00 27
Qc4002 control panel

9.7 Display cable

A standard computer extension cable can be used (9-pole SUB-D male/female plugs) or a cable can be tailored:
Wires min. 0.22 mm

Max. cable length 6 m

Connect shield to plug metallic casing

9-p SUB D 9-p SUB D


male female

# #
$ $
% %
& &
' '
( (
) )
* *
+ +

Display cables are available at following lengths:


1m: 1089 9561 38
3m: 1089 9561 40
6m: 1089 9561 39

Cable types: Belden 9540, BICC H8146, Brand Rex BE57540 or equivalent.

9.8 USB cable for PC

A standard USB cable (USB/a to USB/b) is used for PC connection.


USB cable is available as 1089 9561 54.

28 2954 3390 00
User manual

10 Password levels
There are 4 different levels:
No password level

Customer password level

Service password level

Master password level

The user can scroll through the entire menu without any password.

From the moment that the user wants to change a setpoint, a


password will be required. Changing different parameters requires
different password levels. Some parameters cannot be changed by
the end-customer because of safety reasons.

Once the password has been entered, the user can change all the
accessible setpoints. Only if no actions have been taken within 3
minutes, the password entry will be deactivated, and a new
password entry will be needed.

The user can change the Customer password in channel 9116 (only
accessible via JUMP menu).

Beware: Write down the new password. If you forget it, entering
the menus will not be possible.

Service password and Master password can only be set through the
Qc4002 Utility Software.

2954 3390 00 29
Qc4002 control panel

11 Procedure for parameter setup

11.1 Parameter descriptions

In the next chapter each parameter description is structured according to the same principles. Under the parameter title heading, the detailed
parameter descriptions are illustrated and presented.

The set points are listed below in numerical order of channel number.

The default values depend on the type of gen-set. Some values are different for QAX, QAS and for QAC gen-sets. The parameter list below
shows random chosen values and might not be representative for any type of gen-set.

Below, a table indicating the parameter facts related to the individual parameter title is presented:

Menu Parameter Changeable Min. max.


number in title and settings set points
display menu indicated
indicated number in display

1000 G -P>
No. Setting Min. Max.
setting setting
1001 G -P> Set point -50.0% 0.0%
1002 G -P> Delay 0.1 s 100.0 s
1003 G -P> Relay output A Not used R3
(relay 3)
1004 G -P> Relay output B Not used R3
(relay 3)
1005 G -P> Enable OFF ON
1006 G -P> Fail class 1 5

NOTE:
Small differences due to the character of the parameters may exist between the individual tables.

11.2 Setup

At this point of the process you will have located the specific parameter description that you were looking for. Now, follow the menu
structure presented earlier in this handbook in order to set up the individual parameters. (In this overall example we have chosen to change
the set point of the parameter 1000 G -P>).
Step 1: Enter the setup menu via SETUP in the fourth display line in the entry window
Step 2: Enter the protection menu via PROT in the fourth display line in the setup menu
Step 3: Use the UP and DOWN pushbuttons to locate the selected parameter
Step 4: Enter the set point menu via SP in the fourth display line
Step 5: Enter password to change the set point
Step 6: Use the UP and DOWN pushbuttons to increase/decrease the set point setting
Step 7: Move the underscore to save and press SEL, the new set point setting has now been saved.

30 2954 3390 00
User manual

12 Parameter list
This chapter includes a complete standard parameter list.
Therefore, this part of the handbook is to be used for reference
when specific information about the individual parameters is
needed for the unit setup.

For correct values, refer to the controller.

NOTE:
The parameter lists for the available options are presented in the documents
Description of Options describing the individual options in detail.

Parameter table description

The table consists of the following possible adjustments:


Set point: The alarm set point is adjusted in the set point
menu. The setting is a percentage of the nominal
values.
Delay: The timer setting is the time that must expire from
the alarm level is reached until the alarm occurs.
Relay output A: A relay can be activated by output A.
Relay output B: A relay can be activated by output B.
Enable: The alarm can be activated or deactivated. ON
means always activated, RUN means that the
alarm has run status. This means it is activated
when the running signal is present.
Fail class: When the alarm occurs the unit will react
depending on the selected fail class.

NOTE:
Small differences due to the character of the parameters may exist between
the individual tables.

It is also possible to configure the parameters by using the PC


utility software. It will be possible to make the same configurations
as described above.

By using the PC utility software some extra functionalities are


available. For all the protections it is possible to make an automatic
acknowledgement of the alarm. Usually it is important when the
mains protections are used, as the sequences are blocked until the
alarm is acknowledged.

2954 3390 00 31
Qc4002 control panel

12.1 Protection

1000/1010 Generator reverse power (G -P>)


1000 G -P> 1

No. Setting Min. setting Max. setting


1001 G -P> 1 Set point -50.0% 0.0%
1002 G -P> 1 Delay 0.1 s 100.0 s
1003 G -P> 1 Relay output A Not used Option dependent
1004 G -P> 1 Relay output B Not used
1005 G -P> 1 Enable OFF ON
1006 G -P> 1 Fail class Alarm (1) Trip MB (6)

1010 G -P> 2

No. Setting Min. setting Max. setting


1011 G -P> 2 Set point -50.0% 0.0%
1012 G -P> 2 Delay 0.1 s 100.0 s
1013 G -P> 2 Relay output A Not used Option dependent
1014 G -P> 2 Relay output B Not used
1015 G -P> 2 Enable OFF ON
1016 G -P> 2 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator reverse power exceeds the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal power setting (parameter 6002/6012/6022/6032). It is possible to energize one or two output relays (OA
& OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1030 / 1040 / 1050 / 1060 Generator overcurrent (G I>)


1130 / 1140 Generator fast overcurrent (G I>>)
1030 G I>1

No. Setting Min. setting Max. setting


1031 G I> 1 Set point 50.0% 200.0%
1032 G I> 1 Delay 0.1 s 100.0 s
1033 G I> 1 Relay output A Not used Option dependent
1034 G I> 1 Relay output B Not used
1035 G I> 1 Enable OFF ON
1036 G I> 1 Fail class Alarm (1) Trip MB (6)

1040 G I>2

No. Setting Min. setting Max. setting


1041 G I> 2 Set point 50.0% 200.0%
1042 G I> 2 Delay 0.1 s 100.0 s
1043 G I> 2 Relay output A Not used Option dependent
1044 G I> 2 Relay output B Not used
1045 G I> 2 Enable OFF ON
1046 G I> 2 Fail class Alarm (1) Trip MB (6)

1050 G I>3

No. Setting Min. setting Max. setting


1051 G I> 3 Set point 50.0% 200.0%
1052 G I> 3 Delay 0.1 s 100.0 s
1053 G I> 3 Relay output A Not used Option dependent
1054 G I> 3 Relay output B Not used
1055 G I> 3 Enable OFF ON
1056 G I> 3 Fail class Alarm (1) Trip MB (6)

32 2954 3390 00
User manual

1060 G I> 4

No. Setting Min. setting Max. setting


1061 G I> 4 Set point 50.0% 200.0%
1062 G I> 4 Delay 0.1 s 100.0 s
1063 G I> 4 Relay output A Not used Option dependent
1064 G I> 4 Relay output B Not used
1065 G I> 4 Enable OFF ON
1066 G I> 4 Fail class Alarm (1) Trip MB (6)

1130 G I>>1

No. Setting Min. setting Max. setting


1131 G I>> 1 Set point 150.0% 350.0%
1132 G I>> 1 Delay 0.0 s 100.0 s
1133 G I>> 1 Relay output A Not used Option
1134 G I>> 1 Relay output B Not used dependent
1135 G I>> 1 Enable OFF ON
1136 G I>> 1 Fail class Alarm (1) Trip MB (6)

1140 G I>>2

No. Setting Min. setting Max. setting


1141 G I>> 2 Set point 150.0% 350.0%
1142 G I>> 2 Delay 0.0 s 100.0 s
1143 G I>> 2 Relay output A Not used Option
1144 G I>> 2 Relay output B Not used dependent
1145 G I>> 2 Enable OFF ON
1146 G I>> 2 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator current exceeds the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal current setting (parameter 6003/6013/6023/6033). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1150 /1160 Generator overvoltage (G U>)

1150 G U>1

No. Setting Min. setting Max. setting


1151 G U> 1 Set point 100.0% 120.0%
1152 G U> 1 Delay 0.1 s 100.0 s
1153 G U> 1 Relay output A Not used Option
1154 G U> 1 Relay output B Not used dependent
1155 G U> 1 Enable OFF ON
1156 G U> 1 Fail class Alarm (1) Trip MB (6)

1160 G U>2

No. Setting Min. setting Max. setting


1161 G U> 2 Set point 100.0% 120.0%
1162 G U> 2 Delay 0.1 s 100.0 s
1163 G U> 2 Relay output A Not used Option
1164 G U> 2 Relay output B Not used dependent
1165 G U> 2 Enable OFF ON
1166 G U> 2 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator voltage exceeds the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal voltage setting (parameter 6004/6014/6024/6034). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

2954 3390 00 33
Qc4002 control panel

1170 / 1180 / 1190 Generator undervoltage (G U<)


1170 G U<1

No. Setting Min. setting Max. setting


1171 G U< 1 Set point 50.0% 100.0%
1172 G U< 1 Delay 0.1 s 100.0 s
1173 G U< 1 Relay output A Not used Option
1174 G U< 1 Relay output B Not used dependent
1175 G U< 1 Enable OFF ON
1176 G U< 1 Fail class Alarm (1) Trip MB (6)

1180 G U<2

No. Setting Min. setting Max. setting


1181 G U< 2 Set point 50.0% 100.0%
1182 G U< 2 Delay 0.1 s 100.0 s
1183 G U< 2 Relay output A Not used Option
1184 G U< 2 Relay output B Not used dependent
1185 G U< 2 Enable OFF ON
1186 G U< 2 Fail class Alarm (1) Trip MB (6)

1190 G U<3

No. Setting Min. setting Max. setting


1191 G U< 3 Set point 50.0% 100.0%
1192 G U< 3 Delay 0.1 s 100.0 s
1193 G U< 3 Relay output A Not used Option
1194 G U< 3 Relay output B Not used dependent
1195 G U< 3 Enable OFF ON
1196 G U< 3 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator voltage drops below the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal voltage setting (parameter 6004/6014/6024/6034). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1200 Generator voltage trip (G voltage trip)


1200 G voltage trip

No. Setting Min. setting Max. setting


1201 G voltage trip Set point Phase-phase Phase-neutral
When Phase-Phase tripping is selected, the generator voltage alarms relate to the nominal voltage setting (parameter 6004/6014/6024/6034).
When Phase-Neutral tripping is selected, the generator voltage alarms relate to the nominal voltage setting devided by the square root of 3.

1210 / 1220 / 1230 Generator overfrequency (G f>)


1210 G f>1

No. Setting Min. setting Max. setting


1211 G f> 1 Set point 100.0% 120.0%
1212 G f> 1 Delay 0.2 s 100.0 s
1213 G f> 1 Relay output A Not used Option
1214 G f> 1 Relay output B Not used dependent
1215 G f> 1 Enable OFF ON
1216 G f> 1 Fail class Alarm (1) Trip MB (6)

34 2954 3390 00
User manual

1220 G f>2

No. Setting Min. setting Max. setting


1221 G f> 2 Set point 100.0% 120.0%
1222 G f> 2 Delay 0.2 s 100.0 s
1223 G f> 2 Relay output A Not used Option
1224 G f> 2 Relay output B Not used dependent
1225 G f> 2 Enable OFF ON
1226 G f> 2 Fail class Alarm (1) Trip MB (6)

1230 G f>3

No. Setting Min. setting Max. setting


1231 G f> 3 Set point 100.0% 120.0%
1232 G f> 3 Delay 0.2 s 100.0 s
1233 G f> 3 Relay output A Not used Option
1234 G f> 3 Relay output B Not used dependent
1235 G f> 3 Enable OFF ON
1236 G f> 3 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator frequency exceeds the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal frequency setting (parameter 6001/6011/6021/6031). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1240 / 1250 / 1260 Generator underfrequency (G f<)


1240 G f<1

No. Setting Min. setting Max. setting


1241 G f< 1 Set point 80.0% 100.0%
1242 G f< 1 Delay 0.2 s 100.0 s
1243 G f< 1 Relay output A Not used Option
1244 G f< 1 Relay output B Not used dependent
1245 G f< 1 Enable OFF ON
1246 G f< 1 Fail class Alarm (1) Trip MB (6)

1250 G f<2

No. Setting Min. setting Max. setting


1251 G f< 2 Set point 80.0% 100.0%
1252 G f< 2 Delay 0.2 s 100.0 s
1253 G f< 2 Relay output A Not used Option
1254 G f< 2 Relay output B Not used dependent
1255 G f< 2 Enable OFF ON
1256 G f< 2 Fail class Alarm (1) Trip MB (6)

1260 G f<3

No. Setting Min. setting Max. setting


1261 G f< 3 Set point 80.0% 100.0%
1262 G f< 3 Delay 0.2 s 100.0 s
1263 G f< 3 Relay output A Not used Option
1264 G f< 3 Relay output B Not used dependent
1265 G f< 3 Enable OFF ON
1266 G f< 3 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator frequency drops below the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal frequency setting (parameter 6001/6011/6021/6031). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

2954 3390 00 35
Qc4002 control panel

1270 / 1280 / 1290 Busbar/mains overvoltage (BB U>)


1270 BB U>1

No. Setting Min. setting Max. setting


1271 BB U> 1 Set point 100.0% 120.0%
1272 BB U> 1 Delay 0.10 s 99.99 s
1273 BB U> 1 Relay output A Not used Option
1274 BB U> 1 Relay output B Not used dependent
1275 BB U> 1 Enable OFF ON
1276 BB U> 1 Fail class Alarm (1) Trip MB (6)

1280 BB U>2

No. Setting Min. setting Max. setting


1281 BB U> 2 Set point 100.0% 120.0%
1282 BB U> 2 Delay 0.00 s 99.99 s
1283 BB U> 2 Relay output A Not used Option
1284 BB U> 2 Relay output B Not used dependent
1285 BB U> 2 Enable OFF ON
1286 BB U> 2 Fail class Alarm (1) Trip MB (6)

1290 BB U>3

No. Setting Min. setting Max. setting


1291 BB U> 3 Set point 100.0% 120.0%
1292 BB U> 3 Delay 0.00 s 99.99 s
1293 BB U> 3 Relay output A Not used Option
1294 BB U> 3 Relay output B Not used dependent
1295 BB U> 3 Enable OFF ON
1296 BB U> 3 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the busbar/mains voltage exceeds the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal voltage setting (parameter 6004/6014/6024/6034). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1300 / 1310 / 1320 / 1330 Busbar/mains undervoltage (BB U<)


1300 BB U<1

No. Setting Min. setting Max. setting


1301 BB U< 1 Set point 50.0% 100.0%
1302 BB U< 1 Delay 0.00 s 99.99 s
1303 BB U< 1 Relay output A Not used Option
1304 BB U< 1 Relay output B Not used dependent
1305 BB U< 1 Enable OFF ON
1306 BB U< 1 Fail class Alarm (1) Trip MB (6)

1310 BB U<2

No. Setting Min. setting Max. setting


1311 BB U< 2 Set point 50.0% 100.0%
1312 BB U< 2 Delay 0.00 s 99.99 s
1313 BB U< 2 Relay output A Not used Option
1314 BB U< 2 Relay output B Not used dependent
1315 BB U< 2 Enable OFF ON
1316 BB U< 2 Fail class Alarm (1) Trip MB (6)

36 2954 3390 00
User manual

1320 BB U<3

No. Setting Min. setting Max. setting


1321 BB U< 3 Set point 50.0% 100.0%
1322 BB U< 3 Delay 0.00 s 99.99 s
1323 BB U< 3 Relay output A Not used Option
1324 BB U< 3 Relay output B Not used dependent
1325 BB U< 3 Enable OFF ON
1326 BB U< 3 Fail class Alarm (1) Trip MB (6)

1330 BB U<4

No. Setting Min. setting Max. setting


1331 BB U< 4 Set point 50.0% 100.0%
1332 BB U< 4 Delay 0.00 s 99.99 s
1333 BB U< 4 Relay output A Not used Option
1334 BB U< 4 Relay output B Not used dependent
1335 BB U< 4 Enable OFF ON
1336 BB U< 4 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the busbar/mains voltage drops below the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal voltage setting (parameter 6004/6014/6024/6034). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1340 Busbar/mains voltage trip (BB voltage trip)


1340 BB voltage trip

No. Setting Min. setting Max. setting


1341 BB voltage trip Set point Phase-phase Phase-neutral
When Phase-Phase tripping is selected, the busbar/mains voltage alarms relate to the nominal voltage setting (parameter 6004/6014/6024/6034).
When Phase-Neutral tripping is selected, the busbar/mains voltage alarms relate to the nominal voltage setting devided by the square root of 3.

1350 / 1360 / 1370 Busbar/mains overfrequency (BB f>)


1350 BB f>1

No. Setting Min. setting Max. setting


1351 BB f> 1 Set point 100.0% 120.0%
1352 BB f> 1 Delay 0.00 s 99.99 s
1353 BB f> 1 Relay output A Not used Option
1354 BB f> 1 Relay output B Not used dependent
1355 BB f> 1 Enable OFF ON
1356 BB f> 1 Fail class Alarm (1) Trip MB (6)

1360 BB f>2

No. Setting Min. setting Max. setting


1361 BB f> 2 Set point 100.0% 120.0%
1362 BB f> 2 Delay 0.00 s 99.99 s
1363 BB f> 2 Relay output A Not used Option
1364 BB f> 2 Relay output B Not used dependent
1365 BB f> 2 Enable OFF ON
1366 BB f> 2 Fail class Alarm (1) Trip MB (6)

2954 3390 00 37
Qc4002 control panel

1370 BB f>3

No. Setting Min. setting Max. setting


1371 BB f> 3 Set point 100.0% 120.0%
1372 BB f> 3 Delay 0.00 s 99.99 s
1373 BB f> 3 Relay output A Not used Option
1374 BB f> 3 Relay output B Not used dependent
1375 BB f> 3 Enable OFF ON
1376 BB f> 3 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the busbar/mains frequency exceeds the configured level (SP) for the
configured time (DEL). The level (SP) relates to the nominal frequency setting (parameter 6001/6011/6021/6031). It is possible to energize one or two output relays
(OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1380 / 1390 / 1400 / 1410 Busbar/mains underfrequency (BB f<)


1380 BB f<1

No. Setting Min. setting Max. setting


1381 BB f< 1 Set point 80.0% 100.0%
1382 BB f< 1 Delay 0.00 s 99.99 s
1383 BB f< 1 Relay output A Not used Option
1384 BB f< 1 Relay output B Not used dependent
1385 BB f< 1 Enable OFF ON
1386 BB f< 1 Fail class Alarm (1) Trip MB (6)

1390 BB f<2

No. Setting Min. setting Max. setting


1391 BB f< 2 Set point 80.0% 100.0%
1392 BB f< 2 Delay 0.00 s 99.99 s
1393 BB f< 2 Relay output A Not used Option
1394 BB f< 2 Relay output B Not used dependent
1395 BB f< 2 Enable OFF ON
1396 BB f< 2 Fail class Alarm (1) Trip MB (6)

1400 BB f<3

No. Setting Min. setting Max. setting


1401 BB f< 3 Set point 80.0% 100.0%
1402 BB f< 3 Delay 0.00 s 99.99 s
1403 BB f< 3 Relay output A Not used Option
1404 BB f< 3 Relay output B Not used dependent
1405 BB f< 3 Enable OFF ON
1406 BB f< 3 Fail class Alarm (1) Trip MB (6)

1410 BB f<4

No. Setting Min. setting Max. setting


1411 BB f< 4 Set point 80.0% 100.0%
1412 BB f< 4 Delay 0.00 s 99.99 s
1413 BB f< 4 Relay output A Not used Option
1414 BB f< 4 Relay output B Not used dependent
1415 BB f< 4 Enable OFF ON
1416 BB f< 4 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the busbar/mains frequency drops below the configured level (SP) for
the configured time (DEL). The level (SP) relates to the nominal frequency setting (parameter 6001/6011/6021/6031). It is possible to energize one or two output
relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

38 2954 3390 00
User manual

1420 f/t (ROCOF)


1420 f/t (ROCOF)

No. Setting Min. setting Max. setting


1421 f/t (ROCOF) Set point +/- 0.1Hz/s 10.0Hz/s
1422 f/t (ROCOF) Delay 1 per 20 per
1423 f/t (ROCOF) Relay output A Not used Option
1424 f/t (ROCOF) Relay output B Not used dependent
1425 f/t (ROCOF) Enable OFF ON
1426 f/t (ROCOF) Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when a (dramatical) generator speed change exceeds the configured level
(SP) for the configured time (DEL). It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1430 Vector jump


1430 Vector jump

No. Setting Min. setting Max. setting


1431 Vector jump Set point 1.0 deg. 90.0 deg.
1432 Vector jump Relay output A Not used Option dependent
1433 Vector jump Relay output B Not used
1434 Vector jump Enable OFF ON
1435 Vector jump Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when a change in time lack of the stator magnetic field exceeds the configured
level (SP). It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1450 / 1460 / 1470 / 1480 / 1490 Generator overload (G P>)


1450 G P>1

No. Setting Min. setting Max. setting


1451 G P> 1 Set point 1.0% 200.0%
1452 G P> 1 Delay 0.1 s 100.0 s
1453 G P> 1 Relay output A Not used Option
1454 G P> 1 Relay output B Not used dependent
1455 G P> 1 Enable OFF ON
1456 G P> 1 Fail class Alarm (1) Trip MB (6)

1460 G P>2

No. Setting Min. setting Max. setting


1461 G P> 2 Set point 1.0% 200.0%
1462 G P> 2 Delay 0.1 s 100.0 s
1463 G P> 2 Relay output A Not used Option
1464 G P> 2 Relay output B Not used dependent
1465 G P> 2 Enable OFF ON
1466 G P> 2 Fail class Alarm (1) Trip MB (6)

1470 G P>3

No. Setting Min. setting Max. setting


1471 G P> 3 Set point 1.0% 200.0%
1472 G P> 3 Delay 0.1 s 100.0 s
1473 G P> 3 Relay output A Not used Option
1474 G P> 3 Relay output B Not used dependent
1475 G P> 3 Enable OFF ON
1476 G P> 3 Fail class Alarm (1) Trip MB (6)

2954 3390 00 39
Qc4002 control panel

1480 G P>4

No. Setting Min. setting Max. setting


1481 G P> 4 Set point 1.0% 200.0%
1482 G P> 4 Delay 0.1 s 100.0 s
1483 G P> 4 Relay output A Not used Option
1484 G P> 4 Relay output B Not used dependent
1485 G P> 4 Enable OFF ON
1486 G P> 4 Fail class Alarm (1) Trip MB (6)

1490 G P>5

No. Setting Min. setting Max. setting


1491 G P> 5 Set point 1.0% 200.0%
1492 G P> 5 Delay 0.1 s 100.0 s
1493 G P> 5 Relay output A Not used Option
1494 G P> 5 Relay output B Not used dependent
1495 G P> 5 Enable OFF ON
1496 G P> 5 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator power exceeds the configured level (SP) for the configured
time (DEL). The level (SP) relates to the nominal power etting (parameter 6002/6012/6022/6032). It is possible to energize one or two output relays (OA & OB) when
the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1500 Unbalance current generator (Unbalance curr.)

1500 Unbalance curr.

No. Setting Min. setting Max. setting


1501 Unbalance curr. Set point 0.0% 100.0%
1502 Unbalance curr. Delay 0.1 s 100.0 s
1503 Unbalance curr. Relay output A Not used Option
1504 Unbalance curr. Relay output B Not used dependent
1505 Unbalance curr. Enable OFF ON
1506 Unbalance curr. Fail class Alarm (1) Trip MB (6)

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the difference between the phase currents of the generator exceeds the
configured level (SP) for the configured time (DEL). The level (SP) relates to the nominal current setting (parameter 6003/6013/6023/6033). It is possible to energize
one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1510 Voltage assymetry generator (Unbalance volt.)


1510 Unbalance volt.

No. Setting Min. setting Max. setting


1511 Unbalance volt. Set point 0.0% 50.0%
1512 Unbalance volt. Delay 0.1 s 100.0 s
1513 Unbalance volt. Relay output A Not used Option
1514 Unbalance volt. Relay output B Not used dependent
1515 Unbalance volt. Enable OFF ON
1516 Unbalance volt. Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the difference between the phase-phase voltages of the generator
exceeds the configured level (SP) for the configured time (DEL). The level (SP) relates to the nominal voltage setting (parameter 6004/6014/6024/6034). It is possible
to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

40 2954 3390 00
User manual

1520 Generator reactive power import (G -Q>)


1520 G -Q>

No. Setting Min. setting Max. setting


1521 G -Q> Set point 0.0% 150.0%
1522 G -Q> Delay 0.1 s 100.0 s
1523 G -Q> Relay output A Not used Option dependent
1524 G -Q> Relay output B Not used
1525 G -Q> Enable OFF ON
1526 G -Q> Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator reactive power import exceeds the configured level (SP)
for the configured time (DEL). The level (SP) relates to the nominal power setting (parameter 6002/6012/6022/6032). It is possible to energize one or two output
relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

1530 Generator reactive power export (G Q>)


1530 G Q>

No. Setting Min. setting Max. setting


1531 G Q> Set point 0.0% 100.0%
1532 G Q> Delay 0.1 s 100.0 s
1533 G Q> Relay output A Not used Option
1534 G Q> Relay output B Not used dependent
1535 G Q> Enable OFF ON
1536 G Q> Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the generator reactive power export exceeds the configured level (SP)
for the configured time (DEL). The level (SP) relates to the nominal power setting (parameter 6002/6012/6022/6032). It is possible to energize one or two output
relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

2954 3390 00 41
Qc4002 control panel

12.2 Control

This setup menu consists of the synchronization setup and the regulation setup.

12.2.1 Synchronization

2000 Synchronization type (Sync. type)


2000 Sync. type

No. Setting First setting Second setting


2001 Sync. type Type Static sync. Dynamic sync
In dynamic synchronization, the synchronizing gen-set is running at a different speed than the generator on the busbar. This speed difference is called slip frequency.
Typically, the synchronizing gen-set is running with a positive slip frequency. This means that it is running with a higher speed than the generator on the busbar. The
objective is to avoid a reverse power trip after the synchronization. Dynamic synchronization is recommended where fast synchronization is required, and where the
incoming gen-sets are able to take load just after the breaker has been closed.
In static synchronization, the synchronizing gen-set is running very close to the same speed as the generator/mains on the busbar. The aim is to let them run at exactly
the same speed and with the phase angles between the three-phase system of the generator and the three-phase system of the busbar matching exactly. Static
synchronization is recommended where a slip frequency is not accepted, for instance if several gen-sets synchronize to a busbar with no load groups connected.

2020 Dynamic synchronization (Synchronization)


2020 Dynamic sync.

No. Setting Min. setting Max. setting


2021 Dynamic sync. fMax. 0.0Hz 0.5Hz
2022 Dynamic sync. fMin. -0.5Hz 0.5Hz
2023 Dynamic sync. UMax. 2% 10%
2024 Dynamic sync. GB 40 ms 300 ms
2025 Dynamic sync. MB 40 ms 300 ms
In this menu the maximum slip frequency (f Max), the minimum slip frequency (f Min), the maximum voltage difference between generator and busbar/mains
(U Max), the generator breaker response time (GB) and the mains breaker response time (MB) can be configured.
It is required to never have the maximum and minimum slip frequency symmetric (eg. It is NOK to have f Max = 0.2Hz and f Min = -0.2Hz) to obtain (good)
synchronizing.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.
This menu won't be shown if static synchronizing is selected in menu 2000.

2030 Static synchronization (Synchronization)

2030 Static sync.

No. Setting Min. setting Max.setting


2031 Static sync. Maximum f 0.00Hz 0.50Hz
2032 Static sync. Maximum U 2% 10%
2033 Static sync. Close window 0.1 deg. 20.0 deg.
2034 Static sync. Delay 0.1 s 99.0 s
In this menu the maximum allowed frequency difference between generator and busbar/mains (f Max), the maximum maximum voltage difference between
generator and busbar/mains (U Max) and the window where a synchronization pulse can be released (close window) can be configured.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.
This menu won't be shown if dynamic synchronizing is selected in menu 2000.

2040 Frequency synchronization PID regulator (f sync. control)


2040 f sync. control

No. Setting Min. setting Max. setting


2041 f sync. Kp 0.0 s 60.0 s
2042 f sync. Ti 0.0 s 60.0 s
2043 f sync. Td 0.0 s 2.0 s

42 2954 3390 00
User manual

In this menu the frequency synchronizing PID regulation can be configured.When dynamic synchronizing is selected, this f sync. control is used during the entire
synchronizing sequence.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2060 Phase control PID regulator (Phase control)


2060 Phase control

No. Setting Min. setting Max. setting


2061 Phase Kp 0.0 s 60.0 s
2062 Phase Ti 0.0 s 60.0 s
2063 Phase Td 0.0 s 2.0 s

In this menu the phase control PID regulation can be configured. When static synchronizing is selected, the phase control will take over from the f sync control when
the frequency deviation is so small that the phase angle can be controlled.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.
This menu won't be shown if dynamic synchronization is selected in menu 2000.

2110 Synchronization blackout (Sync. blackout)


2110 Sync. blackout

No. Setting Min. setting Max. setting


2111 Sync. blackout f max. 0.0Hz 5.0Hz
2112 Sync. blackout U max. 2% 10%
In this menu the maximum deviation from the nominal frequency (f Max) and from the nominal voltage (U Max) is defined, which allow closing of the breakers/
start of synchronization.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2120 Synchronization window (Sync Window)


2120 Sync. window

No. Setting Min. setting Max. setting


2121 Sync. window Set point 2.0% 20.0%
2122 Sync. window Delay 0.1s 2.0s
2123 Sync. window Relay output A Not used Option dependent
2124 Sync. window Relay output B Not used
2125 Sync. window Enable OFF ON

2130 Generator breaker synchronization failure (GB Sync failure)


2130 GB sync failure

No. Setting Min. setting Max. setting


2131 GB sync failure Delay 30.0 s 300.0 s
2132 GB sync failure Relay output A Not used Option dependent
2133 GB sync failure Relay output B Not used
2134 GB sync failure Enable OFF ON
2135 GB sync failure Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the synchronizing of the generator breaker takes longer then the
configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 43
Qc4002 control panel

2140 Mains breaker synchronization failure (MB Sync failure)


2140 MB sync failure

No. Setting Min. setting Max. setting


2141 MB sync failure Delay 30.0 s 300.0 s
2142 MB sync failure Relay output A Not used Option dependent
2143 MB sync failure Relay output B Not used
2144 MB sync failure Enable OFF ON
2145 MB sync failure Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the synchronizing of the mains breaker takes longer then the configured
time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2150 Phase sequence error (Phase seq error)


2150 Phase seq error

No. Setting Min. setting Max. setting


2151 Phase seq error Relay output A Not used Option dependent
2152 Phase seq error Relay output B Not used
2153 Phase seq error Fail class Alarm (1) Trip MB (6)
In this menu a failclass (FC) can be configured in case the Qc4002 senses a phase sequence error between generator and busbar/mains.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2160 Generator breaker fails to open (GB Open fail)


2160 GB open fail

No. Setting Min. setting Max. setting


2161 GB open fail Delay 2.0 s 2.0 s
2162 GB open fail Relay output A Not used Option dependent
2163 GB open fail Relay output B Not used
2164 GB open fail Enable OFF ON
2165 GB open fail Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the delay between giving a generator breaker open command and
receiving generator breaker open feedback takes longer then the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2170 Generator breaker fails to close (GB Close fail)


2170 GB close fail

No. Setting Min. setting Max. setting


2171 GB close fail Delay 2.0 s 2.0 s
2172 GB close fail Relay output A Not used Option dependent
2173 GB close fail Relay output B Not used
2174 GB close fail Enable OFF ON
2175 GB close fail Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the delay between giving a generator breaker close command and
receiving generator breaker closed feedback takes longer then the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

44 2954 3390 00
User manual

2180 Generator breaker position failure (GB Pos fail)


2180 GB pos. fail

No. Setting Min. setting Max. setting


2181 GB pos. failure Delay 1.0 s 1.0 s
2182 GB pos. failure Relay output A Not used Option dependent
2183 GB pos. failure Relay output B Not used
2184 GB pos. failure Enable OFF ON
2185 GB pos. failure Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when there is both a generator breaker open feedback as a generator breaker
closed feedback, or no generator breaker open feedback and neither a generator breaker closed feedback for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2200 Mains breaker fails to open (MB Open fail)


2200 MB open fail

No. Setting Min. setting Max. setting


2201 MB open fail Delay 2.0 s 2.0 s
2202 MB open fail Relay output A Not used Option dependent
2203 MB open fail Relay output B Not used
2204 MB open fail Enable OFF ON
2205 MB open fail Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the delay between giving a mains breaker open command and receiving
mains breaker open feedback takes longer then the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2210 Mains breaker fails to close (MB Close fail)


2210 MB close fail

No. Setting Min. setting Max. setting


2211 MB close fail Delay 2.0 s 2.0 s
2212 MB close fail Relay output A Not used Option dependent
2213 MB close fail Relay output B Not used
2214 MB close fail Enable OFF ON
2215 MB close fail Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the delay between giving a mains breaker close command and receiving
mains breaker closed feedback takes longer then the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2220 Mains breaker position failure (MB Pos fail)


2220 MB pos. fail

No. Setting Min. setting Max. setting


2221 MB pos. fail Delay 1.0 s 1.0 s
2222 MB pos. fail Relay output A Not used Option dependent
2223 MB pos. fail Relay output B Not used
2224 MB pos. fail Enable OFF ON
2225 MB pos. fail Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when there is both a mains breaker open feedback as a mains breaker closed
feedback, or no mains breaker open feedback and neither a mains breaker closed feedback for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 45
Qc4002 control panel

2240 Separate synchronization relay (Sep Sync Relay)


2240 Sep. sync. relay

No. Setting Min. setting Max. setting


2241 Sep. sync. relay GB Not used Option dependent
2242 Sep. sync. relay MB Not used
When the Qc4002 gives the synchronising command, then the relays on terminal 17/18/19 (generator breaker) and terminal 11/12/13 (mains breaker) will activate,
and the breaker must close when this relay output is activated. This default function can be modified using a digital input and extra relay outputs depending on the
required function. The relay selection is made in the menu 2400, and the input is selected in the input settings in PARUS.

2250 Close before excitation (Close bef. exc.)


2250 Close bef. exc.

No. Setting Min. setting Max. setting


2251 Close bef. exc. Set point 0 RPM 4000 RPM
2252 Close bef. exc. Timer 0.0 s 999.0 s
2253 Close bef. exc. Relay output A Not used Option dependent
2254 Close bef. exc. Enable OFF
It is possible to close the breaker before the engine is started. This function is called close before excitation.
The close before start function can be used, if the load requires a soft start. This can be the case when the gen-sets connect to a transformer.
Note:
This function can only be used when a magnetic pick up is used.

2260 Breaker sequence (Breaker seq.)


2260 Breaker seq.

No. Setting Min. setting Max. setting


2261 Breaker seq. Break Close GB Close GB+TB
2262 Breaker seq. Delay 0.0 s 999.0 s
2263 Breaker seq. RpmOK 0 RPM 4000 RPM
The GB close before start function can be used in three applications:
Qc4002 single gen-set plant.
Qc4002 power management plant - no tie breaker present.
Qc4002 power management plant - tie breaker present.
In one of the applications a tie breaker is present, and it must be adjusted in the menu 2261 whether only the generator breaker must be closed or both the generator
breaker and also the tie breaker.

2270 Close before excitation failure (Close bef. exc. fail)


2270 Cl.bef.exc.fail

No. Setting Min. setting Max. setting


2271 Cl.bef.exc.fail Delay 0.0 s 999.0 s
2272 Cl.bef.exc.fail Relay output A Not used Option dependent
2273 Cl.bef.exc.fail Relay output B Not used
2274 Cl.bef.exc.fail Enable OFF ON
2275 Cl.bef.exc.fail Fail class Alarm (1) Trip MB (6)
If the starting of the gen-set does not succeed, then the alarm menu 2270 Excitation failure will occur, and the selected fail class will be executed.

46 2954 3390 00
User manual

12.2.2 Regulation

2510 Frequency control PID regulator (f control)


2510 f control

No. Setting Min. setting Max. setting


2511 f control Kp 0.0 s 60.0 s
2512 f control Ti 0.0 s 60.0 s
2513 f control Td 0.0 s 2.0 s
In this menu the frequency control PID regulation can be configured.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2530 Power control PID regulator (P control)


2530 P control

No. Setting Min. setting Max. setting


2531 P control Kp 0.0 s 60.0 s
2532 P control Ti 0.0 s 60.0 s
2533 P control Td 0.0 s 2.0 s
In this menu the power control PID regulation can be configured. The P control will be active if the genset is running parallel to another genset or to mains.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2540 Power loadshare CONTROL PID regulator (P loadsh. control)


2540 P load sh. ctrl

No. Setting Min. setting Max. setting


2541 P load sh. ctrl f Kp 0.00 s 60.00 s
2542 P load sh. ctrl f Ti 0.00 s 60.00 s
2543 P load sh. ctrl f Td 0.00 s 2.00 s
2544 P load sh. ctrl P weight 0.0% 100.0%

In this menu the power control PID regulation while loadsharing can be configured.
The P loadshare control will be active if the genset is running parallel to another genset and using the analogue loadshare lines.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2550 Analogue governor regulator output offset (Analogue GOV)


2550 Analogue GOV

No. Setting Min. setting Max. setting


2551 Analogue GOV Offset 0% 100%

This is the output value of the regulator output where the regulation will start.
It is ideal that this value equals the regulator output value when running at nominal frequency.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 47
Qc4002 control panel

2560 Analogue governor regulation failure (GOV reg. fail)


2560 GOV reg. fail

No. Setting Min. setting Max. setting


2561 GOV reg. fail Deadband 1.0% 100.0%
2562 GOV reg. fail Delay 10.0 s 300.0 s
2563 GOV reg. fail Relay output A Not used Option dependent
2564 GOV reg. fail Relay output B Not used

2610 Power ramp up (Power ramp up)


2610 Power ramp up

No. Setting Min. setting Max. setting


2611 Power ramp up Speed 1.0 %/s 20.0 %/s
2612 Power ramp up Delay point 1% 100%
2613 Power ramp up Delay time 0.0 s 9900 s

2620 power ramp down (power ramp down)


2620 Power ramp down

No. Setting Min. setting Max. setting


2621 Power ramp down Speed 0.1%/s 20.0%/s
2622 Power ramp down Breaker open point 1% 20%

2630 Deload error (Deload error)


2630 Deload error

No. Setting Min. setting Max. setting


2631 Deload error Delay 0.0 s 60.0 s
2632 Deload error Output A Not used Option dependent
2633 Deload error Output B Not used
2634 Deload error Enable OFF ON
2635 Deload error Fail class Alarm (1) Trip MB (6)

2640 Voltage control PID regulator (U control)


2640 U control

No. Setting Min. setting Max. setting


2641 U control Kp 0.0 s 60.0 s
2642 U control Ti 0.0 s 60.0 s
2643 U control Td 0.0 s 2.0 s
In this menu the voltage control PID regulation can be configured.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu

48 2954 3390 00
User manual

2650 Voltage control PID regulator (U control)


2650 Q control

No. Setting Min. setting Max. setting


2651 Q control Kp 0.0 s 60.0 s
2652 Q control Ti 0.0 s 60.0 s
2653 Q control Td 0.0 s 2.0 s
In this menu the reactive power control PID regulation can be configured.
The Q control will be active if the genset is running parallel to another genset or to mains.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2660 Reactive power loadshare control PID regulator (Q loadsh. control)


2660 Q load sh. ctrl

No. Setting Min. setting Max. setting


2661 Q load sh. ctrl U Kp 0.00 60.00
2662 Q load sh. ctrl U Ti 0.00 s 60.00 s
2663 Q load sh. ctrl U Td 0.00 s 60.00 s
2664 Q load sh. ctrl Q weight 0.0% 100.0%
In this menu the reactive power control PID regulation while loadsharing can be configured.
The Q loadshare control will be active if the genset is running parallel to another genset and using the analogue loadshare lines.
Kp: the gain for the proportional part.
Ti: the integral action time for the integral part.
Td: the differential action time for the differential part.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2670 Analogue AVR regulator output offset (Analogue AVR)


2670 Analogue AVR offset

No. Setting Min. setting Max. setting


2671 Analogue AVR Offset 0% 100%
This is the output value of the regulator output where the regulation will start.
It is ideal that this value equals the regulator output value when running at nominal voltage.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2680 Analogue AVR regulation failure (AVR reg. fail)


2680 AVR reg. fail

No. Setting Min. setting Max. setting


2681 AVR reg. fail Deadband 1.0% 100%
2682 AVR reg. fail Delay 10.0 s 300.0 s
2683 AVR reg. fail Relay output A Not used Option dependent
2684 AVR reg. fail Relay output B Not used

2740 Regulation delay (Delay reg.)


2740 Delay reg.

No. Setting Min. setting Max. setting


2741 Delay reg. Delay 0s 9900 s
2742 Delay reg. Output A Not used Option dependent
2743 Delay reg. Output B Not used
2744 Delay reg. Enable OFF ON

2954 3390 00 49
Qc4002 control panel

2760 Overlap

No. Setting Min. setting Max. setting


2761 Overlap Enable OFF ON
2762 Overlap Delay 0.10 s 99.90 s
If this menu is enabled (ENA), the timer (DEL) will be the maximum time that generator and mains will be parallel.
Power ramp-up and power ramp down will take place as configured in 2610 and 2620, but if the overlap timer has expired one of the breakers will be opened (MB
in case of power ramp up, GB in case of power ramp down).

2780 Regulator output type (Reg. output)


2780 Reg. output

No. Setting 1st setting 2nd setting 3rd setting


2781 Reg. output GOV Relay Analogue EIC
2782 Reg. output AVR Relay Analogue -

2900 Manual droop frequency regulation (f - Regulation)


2900 f - Regulation

No. Setting 1st setting 2nd setting 3rd setting


2901 f - Regulation Type Internal External External
active passive

No. Setting Min. setting Max. setting


2902 f - Regulation Droop 0.0% 20.0%
2903 f - Regulation EA- 80.0% 110.0%
2904 f - Regulation EA+ 90.0% 130.0%

2900 Manual droop voltage regulation (U - Regulation)


2910 U - Regulation

No. Setting 1st setting 2nd setting 3rd setting


2911 U - Regulation Type Internal External External
active passive

No. Setting Min. setting Max. setting


2912 U - Regulation Droop 0.0% 20.0%
2913 U - Regulation EA- 80.0% 110.0%
2914 U - Regulation EA+ 90.0% 130.0%

50 2954 3390 00
User manual

12.3 Input/output

This menu consists of parameters for configuration of the inputs and outputs.

12.3.1 Binary input setup

3000 / 3010 / 3020 / 3030 / 3040 / 3130 / 3140 / 3150 / 3160 / 3170 / 3180 / 3190 / 3200 / 3210 / 3220 /
3230 / 3240 / 3250 / 3430 / 3440 / 3450 / 3460 / 3470 / 3480 Digital input *** (Dig. input ***)
3**0 Dig. input ***

No. Setting Min. setting Max. setting


3**1 Dig. input *** Delay 0.0 s 100.0 s
3**2 Dig. input *** Relay output A Not used Option dependent
3**3 Dig. input *** Relay output B Not used
3**4 Dig. input *** Enable OFF ON
3**5 Dig. input *** Fail class Alarm (1) Trip MB (6)
3**6 Dig. input *** High Alamr N/O N/C
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the digital input senses a situation different from what is configured in
the high alarm (N/X) for the configured time (DEL).
High alarm On = N/O = alarm when the switch connected to the input is closed.
High alarm Off = N/C = alarm when the switch connected to the input is opened.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

3400 / 3410 / 3420 Multi-input configured as digital input (Dig. Input)


3400 Dig. Input

No. Setting Min. setting Max. setting


3401 Dig. Input Wirebreak OFF ON
3402 Dig. Input Delay 0.0 s 100.0 s
3403 Dig. Input Relay output A Not used Option dependent
3404 Dig. Input Relay output B Not used
3405 Dig. Input Enable OFF ON
3406 Dig. Input Failclass Alarm (1) Trip MB (6)
This menu is applicable, and will be shown, if multi-input 102 is configured to be a binary input.

3410 Dig. Input

No. Setting Min. setting Max. setting


3411 Dig. Input Wirebreak OFF ON
3412 Dig. Input Delay 0.0 s 100.0 s
3413 Dig. Input Relay output A Not used Option dependent
3414 Dig. Input Relay output B Not used
3415 Dig. Input Enable OFF ON
3416 Dig. Input Failclass Alarm (1) Trip MB (6)
This menu is applicable, and will be shown, if multi-input 105 is configured to be a binary input.

2954 3390 00 51
Qc4002 control panel

3420 Dig. Input

No. Setting Min. setting Max. setting


3421 Dig. Input Wirebreak OFF ON
3422 Dig. Input Delay 0.0 s 100.0 s
3423 Dig. Input Relay output A Not used Option dependent
3424 Dig. Input Relay output B Not used
3425 Dig. Input Enable OFF ON
3426 Dig. Input Failclass Alarm (1) Trip MB (6)
This menu is applicable, and will be shown, if multi-input 108 is configured to be a binary input.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the digital input senses an alarm situation for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to configure if it's a high
alarm or not (N/X), to make this alarm auto-acknowledging and/or to define conditions when this alarm should be inhibited.
High alarm On = N/O = alarm when the switch connected to the input is closed.
High alarm Off = N/C = alarm when the switch connected to the input is opened.

3490 Emergency stop (EMERGENCY Stop)


3490 Emergency stop

No. Setting Min. setting Max. setting


3491 Emergency stop Delay 0.0 s 100.0 s
3492 Emergency stop Relay output A Not used Option dependent
3493 Emergency stop Relay output B Not used
3494 Emergency stop Enable OFF ON
3495 Emergency stop Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the measured voltage at terminal 118 is not equal to the supply voltage
for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

52 2954 3390 00
User manual

12.3.2 Analogue input setup

4120 / 4130 / 4250 / 4260 / 4380 / 4390 Multi-input configured as 420mA input (420mA ***)
41*0 4-20mA 102.*

No. Setting Min. setting Max. setting


41*1 4-20mA 102.* Set point 4mA 20mA
41*2 4-20mA 102.* Delay 0.0 s 600.0 s
41*3 4-20mA 102.* Relay output A Not used Option dependent
41*4 4-20mA 102.* Relay output B Not used
41*5 4-20mA 102.* Enable OFF ON
41*6 4-20mA 102.* Fail class Alarm (1) Trip MB (6)
41*7 4-20mA 102.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 102 is configured to be a 420mA input.

42*0 4-20mA 105.*

No. Setting Min. setting Max. setting


42*1 4-20mA 105.* Set point 4mA 20mA
42*2 4-20mA 105.* Delay 0.0 s 600.0 s
42*3 4-20mA 105.* Relay output A Not used Option dependent
42*4 4-20mA 105.* Relay output B Not used
42*5 4-20mA 105.* Enable OFF ON
42*6 4-20mA 105.* Fail class Alarm (1) Trip MB (6)
42*7 4-20mA 105.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 105 is configured to be a 420mA input.

43*0 4-20mA 108.*

No. Setting Min. setting Max. setting


43*1 4-20mA 108.* Set point 4mA 20mA
43*2 4-20mA 108.* Delay 0.0 s 600.0 s
43*3 4-20mA 108.* Relay output A Not used Option dependent
43*4 4-20mA 108.* Relay output B Not used
43*5 4-20mA 108.* Enable OFF ON
43*6 4-20mA 108.* Fail class Alarm (1) Trip MB (6
43*7 4-20mA 108.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 108 is configured to be a 420mA input.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the 420mA input exceeds or doesn't reach (depending of what is
configured in the high alarm setting) the configured level (SP) for the configured time (DEL).
High alarm On = alarm when the 420mA value exceeds the configured level (SP).
High alarm Off = alarm when the 420mA value goes below the configured level (SP).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited

4140 / 4150 / 4270 / 4280 / 4400 / 4410 Multi-input configured as VDC input (VDC ***)
41*0 V DC 102.*

No. Setting Min. setting Max. setting


41*1 V DC 102.* Set point 0.0V DC 40.0V DC
41*2 V DC 102.* Delay 0.2 s 999.0 s
41*3 V DC 102.* Relay output A Not used Option dependent
41*4 V DC 102.* Relay output B Not used
41*5 V DC 102.* Enable OFF ON
41*6 V DC 102.* Fail class Alarm (1) Trip MB (6)
41*7 V DC 102.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 102 is configured to be a VDC input.

2954 3390 00 53
Qc4002 control panel

42*0 V DC 105.*

No. Setting Min. setting Max. setting


42*1 V DC 105.* Set point 0.0V DC 40.0V DC
42*2 V DC 105.* Delay 0.0 s 600.0 s
42*3 V DC 105.* Relay output A Not used Option dependent
42*4 V DC 105.* Relay output B Not used
42*5 V DC 105.* Enable OFF ON
42*6 V DC 105.* Fail class Alarm (1) Trip MB (6)
42*7 V DC 105.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 105 is configured to be a VDC input.

44*0 V DC 108.*

No. Setting Min. setting Max. setting


44*1 V DC 108.* Set point 0.0V DC 40.0V DC
44*2 V DC 108.* Delay 0.0 s 600.0 s
44*3 V DC 108.* Relay output A Not used Option dependent
44*4 V DC 108.* Relay output B Not used
44*5 V DC 108.* Enable OFF ON
44*6 V DC 108.* Fail class Alarm (1) Trip MB (6)
44*7 V DC 108.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 108 is configured to be a VDC input.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the VDC input exceeds or doesn't reach (depending of what is configured
in the high alarm setting) the configured level (SP) for the configured time (DEL).
High alarm On = alarm when the VDC value exceeds the configured level (SP).
High alarm Off = alarm when the VDC value goes below the configured level (SP).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

4160 / 4170 / 4290 / 4300 / 4420 / 4430 Multi-input configured as PT input (PT ***)
41*0 PT 102.*

No. Setting Min. setting Max. setting


41*1 PT 102.* Set point -49 482
41*2 PT 102.* Delay 0.0 s 999.0 s
41*3 PT 102.* Relay output A Not used Option dependent
41*4 PT 102.* Relay output B Not used
41*5 PT 102.* Enable OFF ON
41*6 PT 102.* Fail class Alarm (1) Trip MB (6)
41*7 PT 102.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 102 is configured to be a PT100 or a PT1000 input.

4**0 PT 105.*

No. Setting Min. setting Max. setting


4**1 PT 105.* Set point -40 250
4**2 PT 105.* Delay 0.0 s 600.0 s
4**3 PT 105.* Relay output A Not used Option dependent
4**4 PT 105.* Relay output B Not used
4**5 PT 105.* Enable OFF ON
4**6 PT 105.* Fail class Alarm (1) Trip MB (6)
4**7 PT 105.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 105 is configured to be a PT100 or a PT1000 input.

54 2954 3390 00
User manual

44*0 PT 108.*

No. Setting Min. setting Max. setting


44*1 PT 108.* Set point -40 250
44*2 PT 108.* Delay 0.0 s 600.0 s
44*3 PT 108.* Relay output A Not used Option dependent
44*4 PT 108.* Relay output B Not used
44*5 PT 108.* Enable OFF ON
44*6 PT 108.* Fail class Alarm (1 Trip MB (6)
44*7 PT 108.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 108 is configured to be a PT100 or a PT1000 input.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the PT input exceeds or doesn't reach (depending of what is configured
in the high alarm setting) the configured level (SP) for the configured time (DEL).
High alarm On = alarm when the measured value exceeds the configured level (SP).
High alarm Off = alarm when the measured value goes below the configured level (SP).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

4180 / 4190 / 4310 / 4320 / 4440 / 4450 Multi-input configured as VDO oil pressure input (VDO oil ***)
41*0 VDO oil 102.*

No. Setting Min. setting Max. setting


41*1 VDO oil 102.* Set point 0.0 bar 10.0 bar
41*2 VDO oil 102.* Delay 0.0 s 990.0 s
41*3 VDO oil 102.* Relay output A Not used Option dependent
41*4 VDO oil 102.* Relay output B Not used
41*5 VDO oil 102.* Enable OFF ON
41*6 VDO oil 102.* Fail class Alarm (1) Trip MB (6)
41*7 VDO oil 102.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 102 is configured to be a VDO oil pressure input.

43*0 VDO oil 105.*

No. Setting Min. setting Max. setting


43*1 VDO oil 105.* Set point 0.0 bar 10.0 bar
43*2 VDO oil 105.* Delay 0.0 s 600.0 s
43*3 VDO oil 105.* Relay output A Not used Option dependent
43*4 VDO oil 105.* Relay output B Not used
43*5 VDO oil 105.* Enable OFF ON
43*6 VDO oil 105.* Fail class Alarm (1) Trip MB (6)
43*7 VDO oil 105.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 105 is configured to be a VDO oil pressure input.

44*0 VDO oil 108.*

No. Setting Min. setting Max. setting


44*1 VDO oil 108.* Set point 0.0 bar 10.0 bar
44*2 VDO oil 108.* Delay 0.0 s 600.0 s
44*3 VDO oil 108.* Relay output A Not used Option dependent
44*4 VDO oil 108.* Relay output B Not used
44*5 VDO oil 108.* Enable OFF ON
44*6 VDO oil 108.* Fail class Alarm (1) Trip MB (6)
44*7 VDO oil 108.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 108 is configured to be a VDO oil pressure input.

2954 3390 00 55
Qc4002 control panel

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the VDO input exceeds or doesn't reach (depending of what is
configured in the high alarm setting) the configured level (SP) for the configured time (DEL).
High alarm On = alarm when the measured value exceeds the configured level (SP).
High alarm Off = alarm when the measured value goes below the configured level (SP).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

4200 / 4210 / 4330 / 4340 / 4460 / 4470 Multi-input configured as VDO water temperature input (VDO
water ***)
42*0 VDO water 102.*

No. Setting Min. setting Max. setting


42*1 VDO water 102.* Set point 40 C 150 C
42*2 VDO water 102.* Delay 0.0 s 990.0 s
42*3 VDO water 102.* Relay output A Not used Option dependent
42*4 VDO water 102.* Relay output B Not used
42*5 VDO water 102.* Enable OFF ON
42*6 VDO water 102.* Fail class Alarm (1) Trip MB (6)
42*7 VDO water 102.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 102 is configured to be a VDO coolant temperature input.

43*0 VDO water 105.*

No. Setting Min. setting Max. setting


43*1 VDO water 105* Set point 40 150
43*2 VDO water 105* Delay 0.0 s 600.0 s
43*3 VDO water 105* Relay output A Not used Option dependent
43*4 VDO water 105* Relay output B Not used
43*5 VDO water 105* Enable OFF ON
43*6 VDO water 105* Fail class Alarm (1) Trip MB (6)
43*7 VDO water 105.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 105 is configured to be a VDO coolant temperature input.

44*0 VDO water 108.*

No. Setting Min. setting Max. setting


44*1 VDO water 108.* Set point 40 150
44*2 VDO water 108.* Delay 0.0 s 600.0 s
44*3 VDO water 108.* Relay output A Not used Option dependent
44*4 VDO water 108.* Relay output B Not used
44*5 VDO water 108.* Enable OFF ON
44*6 VDO water 108.* Fail class Alarm (1) Trip MB (6)
44*7 VDO water 108.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 108 is configured to be a VDO coolant temperature input.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the VDO input exceeds or doesn't reach (depending of what is
configured in the high alarm setting) the configured level (SP) for the configured time (DEL).
High alarm On = alarm when the measured value exceeds the configured level (SP).
High alarm Off = alarm when the measured value goes below the configured level (SP).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

56 2954 3390 00
User manual

4220 / 4230 / 4350 / 4360 / 4480 / 4490 Multi-input configured as VDO fuel level unit (VDO fuel ***)
42*0 VDO fuel 102.*

No. Setting Min. setting Max. setting


42*1 VDO fuel 102.* Set point 0% 100%
42*2 VDO fuel 102.* Delay 0.0 s 990.0 s
42*3 VDO fuel 102.* Relay output A Not used Option dependent
42*4 VDO fuel 102.* Relay output B Not used
42*5 VDO fuel 102.* Enable OFF ON
42*6 VDO fuel 102.* Fail class Alarm (1) Trip MB (6)
42*7 VDO fuel 102.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 102 is configured to be a VDO fuel level input.

43*0 VDO fuel 105.*

No. Setting Min. setting Max. setting


43*1 VDO fuel 105.* Set point 0% 100%
43*2 VDO fuel 105.* Delay 0.0 s 600.0 s
43*3 VDO fuel 105.* Relay output A Not used Option dependent
43*4 VDO fuel 105.* Relay output B Not used
43*5 VDO fuel 105.* Enable OFF ON
43*6 VDO fuel 105.* Fail class Alarm (1) Trip MB (6)
43*7 VDO fuel 105.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 105 is configured to be a VDO fuel level input.

44*0 VDO fuel 108.*

No. Setting Min. setting Max. setting


44*1 VDO fuel 108* Set point 0% 100%
44*2 VDO fuel 108* Delay 0.0 s 600.0 s
44*3 VDO fuel 108* Relay output A Not used Option dependent
44*4 VDO fuel 108* Relay output B Not used
44*5 VDO fuel 108* Enable OFF ON
44*6 VDO fuel 108* Fail class Alarm (1) Trip MB (6)
44*7 VDO fuel 108.* High Alarm OFF ON
These menu's are applicable, and will be shown, if multi-input 108 is configured to be a VDO fuel level input.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the VDO input exceeds or doesn't reach (depending of what is
configured in the high alarm setting) the configured level (SP) for the configured time (DEL).
High alarm On = alarm when the measured value exceeds the configured level (SP).
High alarm Off = alarm when the measured value goes below the configured level (SP).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

4240 / 4370 / 4500 Multi-input wire fail protection (W. fail ***)
4240 W. fail 102

No. Setting Min. setting Max. setting


4241 W. fail 102 Relay output A Not used Option dependent
4242 W. fail 102 Relay output B Not used
4243 W. fail 102 Enable OFF ON
4244 W. fail 102 Fail class Alarm (1) Trip MB (6)
This menu is applicable for input 102.

2954 3390 00 57
Qc4002 control panel

4370 W. fail 105

No. Setting Min. setting Max. setting


4371 W. fail 105 Relay output A Not used Option dependent
4372 W. fail 105 Relay output B Not used
4373 W. fail 105 Enable OFF ON
4374 W. fail 105 Fail class Alarm (1) Trip MB (6)
This menu is applicable for input 105.

4500 W. fail 108

No. Setting Min. setting Max. setting


4501 W. fail 108 Relay output A Not used Option dependent
4502 W. fail 108 Relay output B Not used
4503 W. fail 108 Enable OFF ON
4504 W. fail 108 Fail class Alarm (1) Trip MB (6)
This menu is applicable for input 108.

If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when a wirebreak or a shortcircuit is sensed at the multi-input.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4510 / 4520 Overspeed (Overspeed)


4510 Overspeed 1

No. Setting Min. setting Max. setting


4511 Overspeed 1 Set point 100% 150%
4512 Overspeed 1 Delay 0.0 s 100.0 s
4513 Overspeed 1 Relay output A Not used Option dependent
4514 Overspeed 1 Relay output B Not used
4515 Overspeed 1 Enable OFF ON
4516 Overspeed 1 Fail class Alarm (1) Trip MB (6)

4520 Overspeed 2

No. Setting Min. setting Max. setting


4521 Overspeed 2 Set point 100% 150%
4522 Overspeed 2 Delay 0.0 s 100.0 s
4523 Overspeed 2 Relay output A Not used Option dependent
4524 Overspeed 2 Relay output B Not used
4525 Overspeed 2 Enable OFF ON
4526 Overspeed 2 Fail class Alarm (1) Trip MB (6
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the engine speed exceeds the configured level (SP) for the configured
time (DEL).
The level (SP) relates to the nominal rpm setting (parameter 6005/6015/6025/6035).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

4530 CRANK FAILURE (Crank failure)


4530 Crank failure

No. Setting Min. setting Max. setting


4531 Crank failure Set point 1 rpm 4000 rpm 50 rpm
4532 Crank failure Delay 0.0 s 20.0 s
4533 Crank failure Relay output A Not used Option dependent
4534 Crank failure Relay output B Not used
4535 Crank failure Enable OFF ON
4536 Crank failure Fail class Alarm (1) Trip MB (6)

58 2954 3390 00
User manual

If the engine speed doesn't reach the configured level (SP) after the configured time (DEL), this alarm will be raised.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.
This menu is only active if an MPU is used as primary running feedback.

4540 Running feedback failure (Run feedb. fail.)


4540 Run feedb. fail

No. Setting Min. setting Max. setting


4541 Run feedb. fail Delay 0.0 s 20.0 s
4542 Run feedb. fail Relay output A Not used Option dependent
4543 Run feedb. fail Relay output B Not used
4544 Run feedb. fail Enable OFF ON
4545 Run feedb. fail Fail class Alarm (1) Trip MB (6)
If there is running feedback detected on the frequency, but the primary running feedback has not detected running, this alarm will be raised.
The delay (DEL) starts when there is frequency running detection.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4550 MPU wirebreak (MPU wirebreak


4550 MPU wirebreak

No. Setting Min. setting Max. setting


4551 MPU wirebreak Relay output A Not used Option dependent
4552 MPU wirebreak Relay output B Not used
4553 MPU wirebreak Enable OFF ON
4554 MPU wirebreak Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA) and there is no running feedback detected from the MPU while the machine is running, the Qc4002 will act as configured in the
failclass (FC).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4560 Hz/V failure (Hz/V failure)


4560 Hz/V failure

No. Setting Min. setting Max. setting


4561 Hz/V failure Delay 1.0 s 99.0 s
4562 Hz/V failure Relay output A Not used Option dependent
4563 Hz/V failure Relay output B Not used
4564 Hz/V failure Enable OFF ON
4565 Hz/V failure Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA) and frequency and voltage are not within the limits set in parameters 2111 & 2112 when the delay (DEL) has expired, the Qc4002
will act as configured in the failclass (FC). The delay (DEL) starts when there is running feedback.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4570 Start failure (Start failure)


4570 Start failure

No. Setting Min. setting Max. setting


4571 Start failure Relay output A Not used Option dependent
4572 Start failure Relay output B Not used
4573 Start failure Fail class Alarm (1) Trip MB (6)
If the generator hasn't started after the number of start attempts (parameter 6190), the Qc4002 will act as configured in the failclass (FC).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 59
Qc4002 control panel

4580 Stop failure (Stop failure)


4580 Stop failure

No. Setting Min. setting Max. setting


4581 Stop failure Delay 10.0 s 120.0 s
4582 Stop failure Relay output A Not used Option dependent
4583 Stop failure Relay output B Not used
4584 Stop failure Enable OFF ON
4585 Stop failure Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA) and there is still running feedback when the delay (DEL) after a stop has expired, the Qc4002 will act as configured in the failclass
(FC).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4960 Battery undervoltage at terminal 1 (U< aux. Term. 1)


4960 U< aux. term. 1

No. Setting Min. setting Max. setting


4961 U< aux. term. 1 Set point 8.0 V 32.0 V
4962 U< aux. term. 1 Delay 0.0 s 999.0 s
4963 U< aux. term. 1 Relay output A Not used Option dependent
4964 U< aux. term. 1 Relay output B Not used
4965 U< aux. term. 1 Enable OFF ON
4966 U< aux. term. 1 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the measured battery voltage at terminal 1 doesn't reach the configured
level (SP) for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4970 Battery overvoltage at terminal 1 (U> aux. Term. 1)


4970 U> aux. term. 1

No. Setting Min. setting Max. setting


4971 U> aux. term. 1 Set point 12.0 V 36.0 V
4972 U> aux. term. 1 Delay 0.0 s 999.0 s
4973 U> aux. term. 1 Relay output A Not used Option dependent
4974 U> aux. term. 1 Relay output B Not used
4975 U> aux. term. 1 Enable OFF ON
4976 U> aux. term. 1 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the measured battery voltage at terminal 1 exceeds the configured level
(SP) for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

4980 Battery undervoltage at terminal 98 (U< aux. Term. 98)


4980 U< aux. term.98

No. Setting Min. setting Max. setting


4981 U< aux. term.98 Set point 8.0 V 32.0 V
4982 U< aux. term.98 Delay 0.0 s 999.0 s
4983 U< aux. term.98 Relay output A Not used Option dependent
4984 U< aux. term.98 Relay output B Not used
4985 U< aux. term.98 Enable OFF ON
4986 U< aux. term.98 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the measured battery voltage at terminal 98 doesn't reach the configured
level (SP) for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

60 2954 3390 00
User manual

4990 Battery overvoltage at terminal 98 (U> aux. Term. 98)


4990 U> aux. term.98

No. Setting Min. setting Max. setting


4991 U> aux. term.98 Set point 12.0 V 36.0 V
4992 U> aux. term.98 Delay 0.0 s 999.0 s
4993 U> aux. term.98 Relay output A Not used Option dependent
4994 U> aux. term.98 Relay output B Not used
4995 U> aux. term.98 Enable OFF ON
4996 U> aux. term.98 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the measured battery voltage at terminal 98 exceeds the configured
level (SP) for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

12.3.3 Output setup

5000 / 5010 / 5020 / 5030 / 5040 / 5050 / 5060 / 5110 / 5120 / 5130 / 5140 Output relay ** (Relay **)
5**0 Relay **

No. Setting First/min. setting Second/max. setting Third setting


5**1 Relay 05 Function Alarm Limit Horn
5**2 Relay 05 OFF delay 0.0 s 999.9 s -
In this menu it is possible to set the function (FUNC) of the output relay.
If set as Alarm Relay, then the alarm will be shown at the display and the relay will be energized as long as the alarm is active.
If set as Limit Relay, then the alarm won't be shown when the relay is energized (active alarm), and the relay will automatically de-energize when the Off-Delay
(DEL) has expired. The Off-Delay starts counting at the moment the activating parameter has returned to a to normal value. If set as Horn Relay, the relay will be
energized as long as configured in parameter 6130.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

5780 / 5790 Analogue output ** limits (AOUT ** Limits)


5780 AOut 66 limits

No. Setting Min. setting Max. setting


5781 AOut 66 limits Min. 0mA 10mA
5782 AOut 66 limits Max. 10mA 25mA
This menu is used for the speed governing (to EIC) analogue output (AOUT66).

5790 AOut 71 limits

No. Setting Min. setting Max. setting


5791 AOut 71 limits Min. 0mA 10mA
5792 AOut 71 limits Max. 10mA 25mA
This menu is used for the voltage governing (to AVR) analogue output (AOUT71).

These menu's are used to define the minimum and maximum regulator output current.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 61
Qc4002 control panel

5820 / 5830 / 5840 / 5850 / 5860 / 5870 / 5880 / 5890 / 5900 / 5910 / 5920 / 5930 / 5940 / 5950 ** Output
(** output)
These menu's could be used to configure analogue outputs 66 and 71 to control according to the measured P, Q, S, PF, f, U, I, Ubb, fbb, multi-input 102, multi-input
105, multi-input 108, total consumed P and total available P values.
Since in most cases analogue outputs 66 and 71 are used for speed and voltage regulation, this feature cannot be used.

5**0 ** output *

No. Setting Min. setting Max. setting


5**1 ** output * Output A Not used Option dependent
5**2 ** output * Output B Not used
5**3 ** output * Type 0-20mA 4-20mA
5**4 ** output * Max. value *** ***
5**5 ** output * Min. value *** ***
Analogue Output is used to configure which analogue output to use (66, 71 or disabled).
Type is used to configure 0-20mA or 4-20mA.
Max. is the measured value to equal 20mA output.
Min. is the measured value to equal 4mA (or 0mA) output.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

5980 / 5990 Governor/AVR output (Goverenor / AVR Output)


5980 Governor output

No. Setting 1st setting 2nd setting 3rd setting


5981 Governor output Output A Disabled AO 66 AO 71
This menu is used for the speed governing (to EIC) analogue output (AOUT66).

5990 AVR output

No. Setting 1st setting 2nd setting 3rd setting


5991 AVR output Output A Disabled AO 66 AO 71
This menu is used for the voltage governing (to AVR) analogue output (AOUT71).

When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

62 2954 3390 00
User manual

12.4 System

The menu includes parameters for the system setup.

12.4.1 General setup

6000 / 6010 / 6020 / 6030 Nominal settings * (Nom. Settings *)


These menu's are used to configure the machine's nominal settings.
For dual/triple voltage/frequency machines, up to 4 groups of nominal settings can be configured.
It are these values which are used to calculate eg. over-/undervoltage/-frequency, overcurrent/-load/-speed,

6000 Nom. settings

No. Setting Min. setting Max. setting


6001 Nom. settings Frequency 48.0Hz 62.0Hz
6002 Nom. settings Power 10kW 20000kW
6003 Nom. settings Current 0A 9000A
6004 Nom. settings Voltage 100V 25000V
6005 Nom. settings Rpm 100 rpm 4000 rpm
6006 Nom. settings Set 1 4

6010 Nom. settings 2

No. Setting Min. setting Max. setting


6011 Nom. settings 2 Frequency 48.0Hz 62.0Hz
6012 Nom. settings 2 Power 10kW 20000kW
6013 Nom. settings 2 Current 0A 9000A
6014 Nom. settings 2 Voltage 100V 25000V
6015 Nom. settings 2 Rpm 100 rpm 4000 rpm

60*0 Nom. settings *

No. Setting Min. setting Max. setting


60*1 Nom. settings * Frequency 48.0Hz 62.0Hz
60*2 Nom. settings * Power 10kW 20000kW
60*3 Nom. settings * Current 0A 9000A
60*4 Nom. settings * Voltage 100V 25000V
60*5 Nom. settings * Rpm 100 rpm 4000 rpm
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6040 Generator transformer ratios (G transformer)


These menu's are used to configure the machine's voltage and current transformer ratio's.
If voltage transformers are used, make sure that there is no primary-secondary phase shift.

6040 G transformer

No. Setting Min. setting Max. setting


6041 G transformer U primary 100V 25000V
6042 G transformer U secondary 100V 690V
6043 G transformer I primary 5A 9000A
6044 G transformer I secondary 1A 5A
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6050 Busbar/Mains transformer ratio (BB transformer)


These menu's are used to configure the mains/busbar voltage transformer ratio.
If voltage transformers are used, make sure that there is no primary-secondary phase shift.

6050 BB settings

No. Setting Min. setting Max. setting


6051 BB settings U primary 100V 25000V
6052 BB settings U secondary 100V 690V
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 63
Qc4002 control panel

6070 Generator mode (Genset Mode)


This menu is used to change the generator's application mode.

6070 Gen-set mode

No. Setting Setting


6071 Gen-set mode Type Island operation
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6080 Language (Language)


6080 Language

No. Setting Setting


6081 Language Type English Qc
English will be the default English texts.
English Qc will be English with correct texts for the I/O's.
Other languages will have the correct texts for the I/O's.

When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.
By means of PARUS it is also possible to modify translated texts (all, except the 'English').

6090 Date and time (internal clock)

No. Setting Min. setting Max. setting


6091 Date and time Year 2001 2100
6092 Date and time Month 1 12
6093 Date and time Day 1 31
6094 Date and time Weekday 1 7
6095 Date and time Hour 0 23
6096 Date and time Minute 0 59

6100 Counters (Counters)


6100 Counters

No. Setting Min. setting Max. setting


6101 Counters Abs. run hours 0 hrs 999 hrs
6102 Counters Abs. th. run hours 0 th. hrs 99 th. hrs
6103 Counters GB operations 0 20000
6104 Counters MB operations 0 20000
6105 Counters kWh reset OFF ON
6106 Counters Start attempts 0 20000
Absolute Run Hours: Offset adjustment of the total running hours counter.
Abs. Th. Run Hours: Offset adjustment of the total running thousands hours counter.
GB Operations: Offset of the generator breaker close commands.
MB Operations: Offset of the mains breaker close commands.
kWh Reset: Resets the kWh counter.
Start Attempts: Offset adjustment of the total amount of start attempts.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

64 2954 3390 00
User manual

6110 / 6120 Service timer * (Service Timer *)


61*0 Service timer *

No. Setting Min. setting Max. setting


61*1 Service timer * Enable OFF ON
61*2 Service timer * Running hours 0 hrs 9000 hrs
61*3 Service timer * Days 1 days 1000 days
61*4 Service timer * Fail class Alarm (1) Trip MB (6)
61*5 Service timer * Relay output A Not used Option dependent
61*6 Service timer * Reset OFF ON

Run Hours (RUN): Number of running hours to activate the alarm (FC).
Days (DAY): If the running hours (RUN) are not reached before this number of days, the alarm (FC) will be activated.
Failclass (FC): Action @ alarm.
Output A: Relay to be activated in case of alarm.
Enable: Enable/disable the alarm function.
Reset: Resets the service timer.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6130 Alarm horn (Alarm Horn)


6130 Alarm horn

No. Setting Min. setting Max. setting


6131 Alarm horn Delay 0.0 s 990.0 s
This timer (DEL) is used to configure how long the Horn relay outputs stay energized.
If this timer is set to 0s., then the Horn relay stays energized as long as the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6160 Run status (Run status)


6160 Run status

No. Setting Min. setting Max. setting


6161 Run status Delay 0.0 s 300.0 s
6162 Run status Relay output A Not used Option
6163 Run status Relay output B Not used dependent
6164 Run status Enable OFF ON
6165 Run status Fail class Alarm (1) Trip MB (6)
The delay (DEL) of this menu is used at RUN inhibited alarms.
This delay starts when running feedback is sensed, and then the delay will give eg. oilpressure, voltage, frequency time to come to an OK level before the RUN
inhibited alarms become active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6170 Running detection (Run detection)


6170 Running detect.

No. Setting Min. setting Max. setting


6171 Number of teeth Teeth 0 teeth 500 teeth
6172 Run detect type Type Binary input
MPU input
Frequency
Engine communication
6173 Running detect. Running rpm 0 rpm 4000 rpm
6174 Remove starter Remove starter 1 rpm 2000 rpm
Number of Teeth: Only used if an MPU is connected to the Qc4002.
Run. detect type: Here the primary source for running detection is configured.
Run. detection: When the rpm is above this setpoint, the machine is considered to be running (in case of MPU or EIC).
Remove starter: At this rpm, the starter will be disengaged (in case of MPU or EIC).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 65
Qc4002 control panel

6180 Starter (Starter)


6180 Starter

No. Setting Min. setting Max. setting


6181 Starter Start prepare 0.0 s 600.0 s
6182 Starter Ext. prepare 0.0 s 600.0 s
6183 Starter Start ON time 1.0 s 30.0 s
6184 Starter Start OFF time 1.0 s 99.0 s
Start prepare (PRE): Preheat time.
Extended start prepare (EXT): Time that preheating continues during cranking (if cranking stops, also preheat will stop).
Start ON time: Maximum crank time.
Start OFF time: Recovery time between two start attempts.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6190 Start attempts (Start attempts)


6190 Start attempts

No. Setting Min. setting Max. setting


6191 Start attempts Set point 1 10
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6210 Stop (Stop)


6210 Stop

No. Setting Min. setting Max. setting


6211 STOP Cooling down 0.0 s 990.0 s
6212 STOP Extended stop 1.0 s 99.0 s
Cooldown (COOL): Is the time the engine will keep on running between a stop command (and opening the generator breaker if closed) and the actual
stopping of the engine.
Extended stop time (EXT): Is the time when the generator is blocked to start (between actual stopping of the engine and the next possible start command).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6220 Hz/V OK (Hz/V OK)


6220 Hz/V OK

No. Setting Min. setting Max. setting


6221 Hz/V OK Delay 1.0 s 99.0 s
This is how long the frequency and the voltage need to be inside the limits (configured in 2111 & 2112) before the GB can be closed.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6230 GB control (GB control)


6230 GB control

No. Setting Min. setting Max. setting


6231 GB control Close delay tGBC 0.0 s 30.0 s
6232 GB control Load time 0.0 s 30.0 s
GB close delay: This is the time in which the Qc4002 expects feedback from a breaker action.
GB load time: This is the time which the breaker spring gets to load. After the breaker has been opened, it cannot be closed again until this timer has elapsed.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

66 2954 3390 00
User manual

6260 Power derate (Power derate)


6260 Power derate

No. Setting Min. setting Max. setting


6261 Power derate Input Multi input 102
Multi input 105
Multi input 108
M-logic
EIC
6262 Power derate Start derate 0 20000
6263 Power derate Derate slope 0.1%/U 100.0%/U
6264 Power derate Proportional OFF ON
6265 Power derate Enable OFF ON
6266 Power derate Derate limit 0.0% 100.0%
Input: Here the source for the temperature is defined.
Start Derate @: From this temperature derating will start.
Derate Slope: Defines how much will be derated per C
Enable: Enables/disables the power derate function
Derate Limit: This is the lowest derate level
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6270 Stop coil wire fail

No. Setting Min. setting Max. setting


6271 Stop coil w. fail Relay output A Not used Option dependent
6272 Stop coil w. fail Relay output B Not used
6273 Stop coil w. fail Enable OFF ON
6274 Stop coil w. fail Fail class Alarm (1) Trip MB (6)

6280 Internal communication failure (Int. comm. fail.)


6280 Int. comm. fail

No. Setting Min. setting Max. setting


6281 Int. comm. fail Relay output A Not used Option dependent
6282 Int. comm. fail Relay output B Not used
6283 Int. comm. fail Enable OFF ON
6284 Int. comm. fail Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when there is no communication between the different processors inside
the Qc4002.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6290 Idle running (Idle running)


Since our EIC's are not prepared for the idle run, this function cannot be used.

6320 Engine heater (Engine heater)


6320 Engine heater

No. Setting Min. setting Max. setting


6321 Engine heater Set point 20 deg. 250 deg.
6322 Engine heater Relay output Not used Option dependent
6323 Engine heater Input type Multi input 102
Multi input 105
Multi input 108
EIC
6324 Engine heater Hysteresis 1 deg. 70 deg.
6325 Engine heater Enable OFF ON
If this menu is enabled (ENA), the Qc4002 will energize the configured output (OA) when the measured temperature (via TYP) goes below the setpoint (SP).
The hysteresis to switch off again is configured in the hysteresis setpoint (HYS).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 67
Qc4002 control panel

6330 Engine heater alarm (Engine heater 1)


6330 Engine heater 1

No. Setting Min. setting Max. setting


6331 Engine heater 1 Set point 10 deg. 250 deg.
6332 Engine heater 1 Delay 1.0 s 300.0 s
6333 Engine heater 1 Relay output A Not used Option dependent
6334 Engine heater 1 Relay output B Not used
6335 Engine heater 1 Enable OFF ON
6336 Engine heater 1 Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the engine temperature drops below the configured level (SP) for the
configured time (DEL), when the engine heater in 6320 is enabled and active.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

6380 Loadshare output level (Loadshare out)

6380 Load share output

No. Setting Min. setting Max. setting


6381 Load share out Set point 1.0 V 5.0 V

Here the voltage level of the loadsharing lines, when the generator is supplying nominal power can be configured.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.
This menu is only available when menu 6390 is set to 'adjustable'.

6390 Loadshare type (Loadshare type)


6390 Load share type

No. Setting Min. setting Max. setting


6391 Load share type Type Adjustable Selco T4800
Here the voltage level of the loadsharing lines can be fixed at 5VDC, or set to adjustable. The exact voltage level then needs to be set in 6380.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6400 Master clock (Master clock)


This functionality can be used if there is a consumer in the load which works based on the zero-crossings.

6400 Master clock

No. Setting Min. setting Max. setting


6401 Master clock Start hour 0h 23h
6402 Master clock Stop hour 0h 23h
6403 Master clock Difference 1s 999 s
6404 Master clock Set point 0.1Hz 1.0Hz
6405 Master clock Enable OFF ON

Start Hour (STA): Compensation starts at this hour.


Stop Hour (STO): Compensation stops at this hour.
Difference (DIFF): The setpoint in seconds that initiates the compensation.
Compensation (COMP): Frequency difference when the compensation is initiated.
Enable (ENA): Enables the function.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

68 2954 3390 00
User manual

6410 Battery test (Battery test)


6410 Battery test

No. Setting Min. setting Max. setting


6411 Battery test Set point 8.0V DC 32.0V DC
6412 Battery test Delay 1s 300 s
6413 Battery test Input type Power supply
Multi input 102
Multi input 105
Multi input 108
6414 Battery test Relay output A Not used Option dependent
6415 Battery test Enable OFF ON
6416 Battery test Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the engine will be cranked without firing for the configured time (DEL), and the Qc4002 will act as configured in the failclass (FC)
if the battery voltage (measured from (TYPE)) drops below the configured level (SP).
It is possible to energize an output relays (OA) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6420 Automatic battery test (Auto batt. test)


6420 Auto batt. test

No. Setting Min. setting Max. setting


6421 Auto batt. test Enable OFF ON
6422 Auto batt. test Day Monday (1) Sunday (7)
6423 Auto batt. test Hours 0h 23 h
6424 Auto batt. test Week 1 52
6425 Auto batt. test Relay output Start relay Option dependent
If this menu is enabled (ENA), the Qc4002 will automatically perform a battery test (as configured in 6410), every so many weeks as configured in (WEEK), at
the weekday configured in (DAY), at the time configured in (HRS).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6430 Batt. asymmetry

No. Setting Min. setting Max. setting


6431 Batt. asymmetry Input type 1 Power supply (1) Multi input 108 (4)
6432 Batt. asymmetry Reference 1 Power supply (1) Multi input 108 (4)
6434 Batt. asymmetry Input type 2 Power supply (1) Multi input 108 (4)
6435 Batt. asymmetry Reference 2 Power supply (1) Multi input 108 (4)

6440 Battery asym. 1

No. Setting Min. setting Max. setting


6441 Battery asym. 1 Set point 0.1V 15.0V
6442 Battery asym. 1 Delay 0.0 s 10.0 s
6443 Battery asym. 1 Relay output A Not used Option dependent
6444 Battery asym. 1 Relay output B Not used
6445 Battery asym. 1 Enable OFF ON

6450 Battery asym. 2

No. Setting Min. setting Max. setting


6451 Battery asym. 2 Set point 0.1V 15.0V
6452 Battery asym. 2 Delay 0.0 s 10.0 s
6453 Battery asym. 2 Relay output A Not used Option dependent
6454 Battery asym. 2 Relay output B Not used
6455 Battery asym. 2 Enable OFF ON

2954 3390 00 69
Qc4002 control panel

6460 Maximum ventilation (Max. ventilation)


6460 Max. ventilation

No. Setting Min. setting Max. setting


6461 Max. ventilation Set point 20 deg. 250 deg.
6462 Max. ventilation Relay output A Not used Option dependent
6463 Max. ventilation Hysteresis 1 deg. 70 deg.
6464 Max. ventilation Enable OFF ON
If this menu is enabled (ENA), the Qc4002 will active the output relay configured in (OA) if the measured value (measuring source defined in 6320) exceeds the
configured setpoint (SP). The output relay will be de-energized again if the temperature has dropped as much as the configured hysteresis value (HYS).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6470 / 6480 Maximum ventilation alarm * (Max. vent. *)


64*0 Max. vent. *

No. Setting Min. setting Max. setting


64*1 Max. vent. * Set point 20 deg. 250 deg.
64*2 Max. vent. * Delay 0.0 s 60.0 s
64*3 Max. vent. * Relay output A Not used Option dependent
64*4 Max. vent. * Relay output B Not used
64*5 Max. vent. * Enable OFF ON
64*6 Max. vent. * Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the measured temperature (see 6460) exceeds the configured level (SP)
for the configured time (DEL) when 6460 is enabled and active.
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

6490 Summer/winter time (Sum/Win time)


6490 Sum/Win time

No. Setting Min. setting Max. setting


6491 Sum/Win time Enable OFF ON
This function makes the Qc4002 automatically adjust its clock according to summer or winter time.
This function follows the EU summer/winter time changes.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6500 Block switchboard error (Blk. swbd error)


6500 Blk. swbd error

No. Setting Min. setting Max. setting


6501 Blk. swbd error Delay 0.0 s 999.0 s
6502 Blk. swbd error Parallel OFF ON
6503 Blk. swbd error Relay output A Not used Option dependent
6504 Blk. swbd error Relay output B Not used
6505 Blk. swbd error Enable OFF ON
6506 Blk. swbd error Fail class Alarm (1) Trip MB (6)
The Qc4002 will block the start sequence when the generator is not running, and act as configured in the failclass (FC) when the digital input which is configured
as 'switchboard error input' becomes high for the configured time (DEL).
Parallel (PAR) 'On': All start sequences are blocked.
Parallel (PAR) 'Off': Only AMF start sequence is blocked.
It is possible to energize one or two output relays (OA & OB) when the alarm is enabled (ENA) and active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

70 2954 3390 00
User manual

6510 Stop switchboard error(Stp. swbd error)


6510 Stp. swbd error

No. Setting Min. setting Max. setting


6511 Stp. swbd error Delay 0.0 s 999.0 s
6512 Stp. swbd error Relay output A Not used Option dependent
6513 Stp. swbd error Relay output B Not used
6514 Stp. swbd error Enable OFF ON
6515 Stp. swbd error Fail class Alarm (1) Trip MB (6)
The Qc4002 will stop the generator when it is running in Auto, and act as configured in the failclass (FC) when the digital input which is configured as 'switchboard
error input' becomes high for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is enabled (ENA) and active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu, to make this alarm auto-
acknowledging and/or to define conditions when this alarm should be inhibited.

6540 Not in Auto (Not in auto)


6540 Not in auto

No. Setting Min. setting Max. setting


6541 Not in auto Delay 10.0 s 900.0 s
6542 Not in auto Relay output A Not used Option dependent
6543 Not in auto Relay output B Not used
6544 Not in auto Enable OFF ON
6545 Not in auto Fail class Alarm (1) Trip MB (6)
If this menu is enabled (ENA), the Qc4002 will act as configured in the failclass (FC) when the Qc4002 is not in Auto for the configured time (DEL).
It is possible to energize one or two output relays (OA & OB) when the alarm is active.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6550 Fuel pump logic (Fuel pump logic)


6550 Fuel pump logic

No. Setting Min. setting Max. setting


6551 Fuel pump logic Set point 1 0% 100%
6552 Fuel pump logic Set point 2 0% 100%
6553 Fuel pump logic Delay 0.1 s 300.0 s
6554 Fuel pump logic Relay output A Not used Option dependent
6555 Fuel pump logic Input type Multi input 102
Multi input 105
Multi input 108
6556 Fuel pump logic Fail class Alarm (1) Trip MB (6)
If the fuel level is below setpoint 1 (S1), the output relay configured in (OA) will be energized unit the fuel level reaches setpoint 2 (S2).
If the fuel didn't rise for 2% within the time configured in the fill check delay (DEL), the Qc4002 will act as configured in the failclass (FC).
The measuring input (TYP) is the input where the fuel level is measured.
Enabling/disabling of this functionality can only be done via the PARUS.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

6600 / 6610 / 6620 / 6630 / 6640 / 6650 / 6660 / 6670 Start/stop command timer * (Start/Stop Cmd *)
66*0 Start/Stop Cmd *

No. Setting Min. setting Max. setting


66*1 Start/Stop Cmd * Enable OFF ON
66*2 Start/Stop Cmd * Type STOP START
66*3 Start/Stop Cmd * Day Monday (1) Mo-Tu-We-Th-Fr-Sa-
Su (11)
66*4 Start/Stop Cmd * Hour 0.0 h 23.0 h
66*5 Start/Stop Cmd * Minute 0.0 59.0
In these menu it is possible to enable (EN) a generator start or stop command (TYPE) at the configured days (DAY) on the configured time (HOUR & MIN).
For this functionality, the unit has to be in Auto.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 71
Qc4002 control panel

12.4.2 Mains setup

7000 Mains Power (Mains Power)


7000 Mains power

No. Setting Min. setting Max. setting


7001 Mains power Day -20000kW 20000kW
7002 Mains power Night -20000kW 20000kW
7003 Mains power Transducer range max. 0kW 20000kW
7004 Mains power Transducer range min. -20000kW 0kW
This menu is used for Peak Shave applications.
The Day (DAY) setting is the allowed mains power during day hours.
The Night (NIGHT) setting is the allowed mains power during night hours.
Day/night periods are configured in 7010.
Transducer range min. equals 4mA at MI102 (needs to be configured as 4-20mA).
Transducer range max. equals 20mA at MI102 (needs to be configured as 4-20mA).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7010 Daytime period (Daytime period)


7010 Daytime period

No. Setting Min. setting Max. setting


7011 Daytime period Start hour 0h 23 h
7012 Daytime period Start minute 0 min 59 min
7013 Daytime period Stop hour 0h 23 h
7014 Daytime period Stop minute 0 min 59 min
In this menu the start (STAH & STAM) and stop (STOH & STOM) of the daytime (hours and minutes) can to be configured.
The period outside the daytime is then the nighttime.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7020 Start generator (Start generator)


7020 Start generator

No. Setting Min. setting Max. setting


7021 Start generator Set point 5% 100%
7022 Start generator Delay 0.0 s 990.0 s
7023 Start generator Minimum load 0% 100%
If mains power has exceeded the setpoint (SP) for the configured time (DEL), then the generator will start (depending of the selected application mode) and take at
least the load which is configured in (LOAD).
The setpoint refers to the settings defined in 7000.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7030 Stop generator (Stop generator)


7030 Stop generator

No. Setting Min. setting Max. setting


7031 Stop generator Set point 0% 80%
7032 Stop generator Delay 0.0 s 990.0 s
If mains power goes below the setpoint (SP) for the configured time (DEL), then the generator will stop (depending of the selected application mode).
The setpoint refers to the settings defined in 7000.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

72 2954 3390 00
User manual

7040 Test (Test)


7040 Test

No. Setting Min. setting Max. setting


7041 Test Set point 1% 100%
7042 Test Test time 0.5 min 999.0 min
7043 Test Return mode Semi-auto Auto
7044 Test Test type Simple
Load
Full
This menu is used to run a test cyclus with the generator.
The setpoint (SP) setting defines how much power the generator must produce (in % of the generator's nominal power setting) when in parallel to the mains.
The timer (DEL) setting defines how long the test cyclus should last.
The return mode (RETURN) parameter defines to which mode the Qc4002 needs to return after finishing the test cyclus.
The type (TYPE) parameter defines which kind of test run is required:
- simple test: will only start the gen-set and run it at nominal frequency with the generator breaker open. The test will run until the timer expires.
- load test: will start the gen-set and run it at nominal frequency, synchronise the generator breaker and produce the power typed in the set point in menu
7041. The test will run until the timer expires. To run the load test it is required that 'Sync to Mains' is enabled in menu 7084.
- full test: will start the gen-set and run it at nominal frequency, synchronise the generator breaker and transfer the load to the generator before opening
the mains breaker. When the test timer expires, the mains breaker will be synchronised and the load is transferred back to the mains before the
generator breaker is opened and the generator is stopped. To run the full test it is required that 'Sync to Mains' is enabled in menu 7084.
Test mode cannot be used if the gen-set is in island operation.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7050 Fixed Power Setpoints (Fixed Power Set)


7050 Fixed power test

No. Setting Min. setting Max. setting


7051 Fixed power set Power set point 0% 100%
7052 Fixed power set Power factor 0.6 1.0
When running in fixed power mode, the Qc4002 governor and AVR regulators will control the generator to meet the setpoints configured in the P and PF parameters
of this menu.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7060 Mains voltage failure (U mains failure)


7060 U mains failure

No. Setting Min. setting Max. setting


7061 U mains failure Fail. delay 1.0 s 990.0 s
7062 U mains failure Mains OK delay 10 s 9900 s
7063 U mains failure U< 80% 100%
7064 U mains failure U> 100% 120%
7065 U mains failure Mains fail. control Start eng. + open MB Start eng.
In this menu, the healthy mains voltage parameters can be configured.
With U< (LOW) the low voltage limit can be defined (in % of the generator's nominal voltage).
With U> (HIGH) the high voltage limit can be defined (in % of the generator's nominal voltage).
The fail delay (FAIL) is used to define for how long mains voltage must be outside the limits before the generator will be started.
The OK delay (OK) defines how long mains voltage must be inside the limits again before the load will be shifted to mains again.
Mains fail control (MC) defines if at a mains fail (valid for both U fail as f fail) the mains breaker will open when the generator is started (Start + Open MB) or when
the generator is ready to take over (Start).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 73
Qc4002 control panel

7070 Mains frequency failure (f mains failure)


7070 f mains failure

No. Setting Min. setting Max. setting


7071 f mains failure Fail. delay 1.0 s 990.0 s
7072 f mains failure Mains OK delay 10 s 9900 s
7073 f mains failure f< 80.0% 100.0%
7074 f mains failure f> 100.0% 120.0%
In this menu, the healthy mains frequency parameters can be configured.
With f< (LOW) the low frequency limit can be defined (in % of the generator's nominal freq.).
With f> (HIGH) the high frequency limit can be defined (in % of the generator's nominal freq.).
The fail delay (FAIL) is used to define for how long mains frequency must be outside the limits before the generator will be started.
The OK delay (OK) defines how long mains frequency must be inside the limits again before the load will be shifted to mains again.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7080 Mains breaker control (MB control)


7080 MB control

No. Setting Min. setting Max. setting


7081 MB control Mode shift OFF ON
7082 MB control MB close delay tMBC 0.0 s 30.0 s
7083 MB control Back sync. OFF ON
7084 MB control Sync. to mains OFF ON
7085 MB control Breaker type MB No breaker
7086 MB control MB Load time 0.0 s 30.0 s
With mode shift (SHT) it is possible to activate AMF as second mode. When enabled and operating in Auto, mains will be supervised for failures.
The MB close delay (DEL) is the time in which the Qc4002 expects feedback from a breaker action.
If backsync (BS) is enabled, there will be synchronisation when returning from generator to mains.
If sync to mains (SM) is enabled, it is possible to sync to mains.
The breaker type (TP) can be:
- mains breaker
- no breaker
- ATS
The MB load time (DEL) is the time which the breaker spring gets to load. After the breaker has been opened, it cannot be closed again until this timer has elapsed.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

12.4.3 Communication setup

7500 Communication control (Comm. control)


7500 Comm. control

No. Setting Min. setting Max. setting


7501 Comm. control Power OFF ON
7502 Comm. control Frequency OFF ON
7503 Comm. control Voltage OFF ON
7504 Comm. control PF OFF ON
7505 Comm. control Reactive power OFF ON
Selecting communication control ON (over Modbus) will overrule external and internal settings.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

74 2954 3390 00
User manual

7510 External communication (Ext. comm.)


7510 Ext. comm.

No. Setting Min. setting Max. setting


7511 Ext. comm. ID 1 247
7512 Ext. comm. Speed 9600Baud 19200Baud
7513 Ext. comm. Mode RTU ASCII
The mode ASCII is used for modem communication (ASCII: 7 data bit. RTU: 8 data bit).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7520 External communication error (Ext. comm. error)


7520 Ext. comm. error

No. Setting Min. setting Max. setting


7521 Ext. comm. error Timer 1.0 s 100.0 s
7522 Ext. comm. error Output A Not used Option dependent
7523 Ext. comm. error Output B Not used
7524 Ext. comm. error Enable OFF ON
7525 Ext. comm. error Failclass Alarm (1) Trip MB (6)
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7530 Internal PMS communications (Int. comm.)


7530 Int. comm.

No. Setting Min. setting Max. setting


7531 Int. comm. ID 1 16
7532 Int. comm. Fail mode Manual Semi-auto No mode change
7533 Int. comm. FC missing all units Alarm (1) Trip MB (6)
7534 Int. comm. FC fatal CAN error Alarm (1) Trip MB (6)
7535 Int. comm. FC any DG missing Alarm (1) Trip MB (6)
7536 Int. comm. FC any mains Alarm (1) Trip MB (6)
missing

This menu is used for the PMS Can communication.


The ID of the generator in the PMS system can be configured, as well as how the PMS systme will react to several error cases.
In case of a PMS failure, the generator will go to fail mode.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7540 CAN interface 1 (CAN I/F 1)


7540 CAN I/F 1

No. Setting Min. setting Max. setting


7541 CAN I/F 1 Type OFF PM comm.

In this menu, the Can interface 1 has been assigned for communication with the engine electronics.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7550 CAN interface 2 (CAN I/F 2)


7550 CAN I/F 2

No. Setting Min. setting Max. setting


7551 CAN I/F 2 Type OFF PM comm.
In this menu, the Can interface 2 has been assigned for PMS communication.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 75
Qc4002 control panel

7560 Engine interface (Engine I/F)


7560 Engine I/F

No. Setting Min. setting Max. setting


7561 Engine I/F Type OFF
DDEC
EMR
JDEC
Iveco
Perkins
Caterpillar
Volvo Penta EMS
Volvo Penta EMS 2
Scania EMS
Scania EMS S6
In this menu, the Engine Can interface has been configured to communicate with Deutz EMR / Volvo EDC4 engine electronics systems.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7570 Engine interface communication error (El comm. error)


7570 EI comm. error

No. Setting Min. setting Max. setting


7571 EI comm. error Timer 0.0 s 100.0 s
7572 EI comm. error Output A Not used Option dependent
7573 EI comm. error Output B Not used
7574 EI comm. error Enable OFF ON
7575 EI comm. error Failclass Warning Trip MB

When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7580 Engine controller warning (ElC warning)


7580 EIC warning

No. Setting Min. setting Max. setting


7581 EIC warning Timer 0.0 s 100.0 s
7582 EIC warning Output A Not used Option dependent
7583 EIC warning Output B Not used
7584 EIC warning Enable OFF ON
7585 EIC warning Failclass Warning Trip MB

With this menu it is poosible to activate an action if a general EIC warning is transmitted over CANbus
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7590 Engine controller shutdown (ElC shutdown)


7590 EIC shutdown

No. Setting Min. setting Max. setting


7591 EIC shutdown Timer 0.0 s 100.0 s
7592 EIC shutdown Output A Not used Option dependent
7593 EIC shutdown Output B Not used
7594 EIC shutdown Enable OFF ON
7595 EIC shutdown Failclass Warning Trip MB

With this menu it is poosible to activate an action if a general EIC shutdown is transmitted over CANbus
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

76 2954 3390 00
User manual

7600 Engine controller overspeed (ElC overspeed)


7600 EIC overspeed

No. Setting Min. setting Max. setting


7601 EIC overspeed Setpoint 0 rpm 2000 rpm
7602 EIC overspeed Timer 0.0 s 100.0 s
7603 EIC overspeed Output A Not used Option dependent
7604 EIC overspeed Output B Not used
7605 EIC overspeed Enable OFF ON
7606 EIC overspeed Failclass Alarm Trip MB

This menu can be used to define an alarm based on the CANbus rpm.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7610 / 7620 Engine controller coolant temperature 1 & 2 (ElC coolant T1 & T2)
7610 EIC coolant T1

No. Setting Min. setting Max. setting


7611 EIC coolant T1 Setpoint -40 deg. 210 deg.
7612 EIC coolant T1 Timer 0.0 s 100.0 s
7613 EIC coolant T1 Output A Not used Option dependent
7614 EIC coolant T1 Output B Not used
7615 EIC coolant T1 Enable OFF ON
7616 EIC coolant T1 Failclass Alarm Trip MB

7620 EIC coolant T2

No. Setting Min. setting Max. setting


7621 EIC coolant T2 Setpoint -40 deg. 210 deg.
7622 EIC coolant T2 Timer 0.0 s 100.0 s
7623 EIC coolant T2 Output A Not used Option dependent
7624 EIC coolant T2 Output B Not used
7625 EIC coolant T2 Enable OFF ON
7626 EIC coolant T2 Failclass Alarm Trip MB

These menu's can be used to define alarms based on the CANbus coolant temperature.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

7630 / 7640 Engine controller oil pressure 1 & 2 (ElC oil press. 1 & 2)
7630 EIC oil press. 1

No. Setting Min. setting Max. setting


7631 EIC oil press. 1 Setpoint 0.0 bar 10.0 bar
7632 EIC oil press. 1 Timer 0.0 s 100.0 s
7633 EIC oil press. 1 Output A Not used Option dependent
7634 EIC oil press. 1 Output B Not used
7635 EIC oil press. 1 Enable OFF ON
7636 EIC oil press. 1 Failclass Alarm Trip MB

7640 EIC oil press. 2

No. Setting Min. setting Max. setting


7641 EIC oil press. 2 Setpoint 0.0 bar 10.0 bar
7642 EIC oil press. 2 Timer 0.0 s 100.0 s
7643 EIC oil press. 2 Output A Not used Option dependent
7644 EIC oil press. 2 Output B Not used
7645 EIC oil press. 2 Enable OFF ON
7646 EIC oil press. 2 Failclass Alarm Trip MB

These menu's can be used to define alarms based on the CANbus coolant temperature.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 77
Qc4002 control panel

12.5 Power management setup

8000 PMS Load dependent start (Load dep. start)


8000 Load dep. start

No. Setting Min. setting Max. setting


8001 Load dep. start Set point 0 kW 20000 kW
8002 Load dep. start Timer 0.0 s 990.0 s
8003 Load dep. start Minimum load 0 kW 20000 kW
If the power reserve of the running machines connected to the bus doesn't reach the setpoint (SP) anymore for the configured time (DEL), the next priority machine
will be started and connected to the bus.
If possible, the generator will take at least the configured minimum load (LOAD).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8010 PMS Load dependent stop (Load dep. stop)


8010 Load dep. stop

No. Setting Min. setting Max. setting


8011 Load dep. stop Set point 0 kW 20000 kW
8012 Load dep. stop Timer 5.0 s 990.0 s
If the power reserve of the running machines connected to the bus, minus the nominal power of the connected machine with lowest priority, exceeds the setpoint (SP)
for the configured time (DEL), the lowest priority connected machine will be stopped.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8020 PMS Configuration (PMS config.)


8020 PMS config.

No. Setting Min. setting Max. setting


8021 PM config. DGs available 1 16
8022 PM config. Mains available No mains Single mains Multiple mains
8023 PM config. PMS active OFF ON
8024 PM config. Start/stop Remote Local Timer
8025 PM config. Command unit OFF ON
In DG's available (DG) it's necessary to configure the total amount of generators in the PMS system.
In mains available (MA) can be configured if there is a mains (with Qc4002 Mains controller) in the PMS system.
The PMS can be activated in (PA).
In Start/Stop, it needs to be configured if the PMS system will be started Local, Remote or by means of the timer commands.
If (CU) is enabled, then this controller can be used to transmit certain parameters throughout the PMS system (always one is enables as command unit).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8030 PMS Priority select (Priority select)


8030 Priority select

No. Setting Min. setting Max. setting


8031 Priority select Priority Manual Running hours Fuel optimisation
8032 Priority select Multistart set 1 1 16 -
8033 Priority select Minimum running 1 16 -
set 1
8034 Priority select Multistart OFF ON -
configuration
8035 Priority select Multistart set 2 1 16 -
8036 Priority select Minimum running 1 16 -
set 2
The multi-start function can be adjusted to operate with two different settings. These settings consist of set points for how many gen-sets to start and the minimum
number of running gen-sets.
It is possible to switch between the settings using M-Logic or in the menu 8034.
The numbers to start (menu 8032/8035) can be selected depending on the number of DG's available (menu 8021). The load depending start and stop function will be
active, as soon as the generator breakers are closed or, if a tie breaker is installed, as soon as the tie breaker is closed. It is possible to adjust the number of gen-sets,
or an auto calculation can be selected.
If it is needed to delay the load dependent start and stop function, it can be done through the M-logic function.

78 2954 3390 00
User manual

The multi starting function can be combined with the setting of a minimum number of running gen-sets (menu 8033/8036). This means that the load dependent stop
function is disregarded when only the specific number of gen-sets is running.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8040 / 8050 / 8060 / 8070 PMS Number of IDs (Number of IDs)


80*0 Number of IDs

No. Setting Min. setting Max. setting


80*1 Number of IDs ID1 OFF ON
80*2 Number of IDs ID2 OFF ON
80*3 Number of IDs ID3 OFF ON
80*4 Number of IDs ID4 OFF ON
80*5 Number of IDs ID5 OFF ON
80*6 Number of IDs ID6 OFF ON

This menu is used to enable/disable ID's in the PMS system.


If more then 6 DG's are in the system, then more of these menu's will be appearing.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8080 / 8090 / 8100 PMS Priority setting (Priority)


8**0 Priority

No. Setting Min. setting Max. setting


8**1 Priority P1 1 16
8**2 Priority P2 1 16
8**3 Priority P3 1 16
8**4 Priority P4 1 16
8**5 Priority P5 1 16
8**6 Priority Tx OFF ON

This menu is used to set the manual priority of the ID's.


After setting all priorities, Tx needs to be enabled to transmit all priority parameters throughout the PMS system.
If more then 5 DG's are in the system, more of these menu's will be appearing.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8110 PMS Running hours priority (Running hours)


8110 Running hours

No. Setting Min. setting Max. setting


8111 Running hours Priority adjustment 1 hrs 20000 hrs
8112 Running hours Type Absolute run hours Relative run hours
8113 Running hours Reset relative counter OFF ON

The purpose of the priority selection based on running hours is to let all the gen-sets have the same or nearly the same amount of running hours.
Every time the adjusted period in menu 8111 is reached, a new order of priority is determined, and the gen-sets with first priorities will be started (if not already
running), and the gen-sets with the last priorities will stop.
There are two possibilities for operating the priority routine based on the running hours: Absolute or relative. The selection between the absolute and relative routine
defines whether the offset adjustment of the running hours is taken into consideration in the priority calculation.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8120 Ground relay (Ground relay)


8120 Ground relay

No. Setting Min. setting Max. setting


8121 Ground relay Output A Not used Option
8122 Ground relay Output B Not used dependent
8123 Ground relay Enable OFF ON
The purpose of this function is to always let the star point of only one gen-set be connected to ground during island mode operation. The reason for this is to avoid
circulating currents between the generators.
The Qc4002 which has the lowest ID and where the generator breaker is closed will close its ground relay. Should this gen-set stop, it will open its ground relay
when the generator breaker opens, and the ground relay of the generator which now has the lowest ID closes its ground relay instead.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

2954 3390 00 79
Qc4002 control panel

8140 Stop of not connected generators (Stop noncon. DG)


8140 Stop non-con. DG

No. Setting Min. setting Max. setting


8141 Stop non-con. DG Timer 10.0 s 600.0 s

If peak shaving is selected and the imported power increases above the start set point, the gen-set(s) will start. If the load now drops below the start set point, it will
remain disconnected from the busbar but will not stop, because the imported power is higher than the stop set point.
This function will make sure that the gen-sets stop after the adjusted time.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8170 PMS Fuel optimization priority (Fuel optimize)


8170 Fuel optimize

No. Setting Min. setting Max. setting


8171 Fuel optimize Setpoint 30% 100%
8172 Fuel optimize Swap setpoint 50 kW 20000 kW
8173 Fuel optimize Timer 0.0 s 999.0 s
8174 Fuel optimize Hours 1h 20000 h
8175 Fuel optimize Enable OFF ON

The setpoint (PCT) is the % of the nominal power which gives the best fuel economy.
The swap setpoint (SWP) is the improvement in nominal power which must be obtained for the configured time (DEL) before fuel optimising will be initiated.
The hours setpoint (HOUR) is the maximum allowed difference in running hours, if this function is enabled (ENA).
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

8220 / 8230 / 8240 / 8250 / 8260 PMS Available power* (Avail. power*)
82*0 Avail. power*

No. Setting Min. setting Max. setting


82*1 Avail. power* Set point 10 kW 20000 kW
82*2 Avail. power* Timer 1.0 s 999.9 s
82*3 Avail. power* Output A Not used Option dependent
82*4 Avail. power* Output B Not used
82*5 Avail. power* Enable OFF ON

This function is used to activate a relay when a specific amount of power is available. The purpose of this function is to be able to connect load groups when the gen-
sets of the emergency power plant are running.
In each of the gen-sets, 5 levels can be adjusted (menus 8220 - 8260):
These set points can activate a relay when the specific amount of available power is reached. The relay output can be used for connecting load groups when sufficient
power is available. The relays will activate when the available power is higher than the set point, but be aware that when the load groups are being connected, then
the available power will decrease and the relay(s) deactivate again, if the available power is below the set point. So it is necessary to make an external holding circuit.
It is possible to adjust different levels of available power in all gen-sets. This gives the possibility to use several load groups if this is necessary.
When connected with PARUS, it is also possible to configure the requested password level to be allowed to do modifications in this menu.

80 2954 3390 00
User manual

12.6 Jump menus

A number of menus can only be entered using the jump menu.

9000 Software version

Information about the actual software downloaded to the unit. Please check this before contacting Atlas Copco regarding service and support
matters.

9020 Service port

The service port can be set up to use the ASCII communication. The ASCII communication is used when the utility software is connected
through a modem.

Selection 0 must be used for cable connection between the Qc4002 and the PC.
Selection 1 must be used for modem connection between the Qc4002 and the PC.

9100 Qc4002 mains selection


9100 Application

No. Setting Min. setting Max. setting


9100 Application Application 0 (generator) 1 (mains)

911X User password

No. Setting Min. setting Max. setting


9116 User password Setting 0 32000
9117 Service password YYYYY setting 0 32000
9118 Master password XXXXX setting 0 32000

9120 Service menu

This menu is used in service situations. In the alarm selection you can see all the alarm timers and their remaining time if they are counting.
The input and output selections show the present status of the inputs and outputs. E.g. mode inputs, relay outputs and load sharing lines.
No. Setting Description
9121 Service menu Timers Shows remaining alarm delay time
9122 Service menu Digital inputs Shows digital input status
9123 Service menu Digital outputs Shows digital output status
9124 Service menu Miscellaneous Shows miscellaneous information

9130 Single phase/split phase/three phase


This menu is used to choose between the different AC measurement systems.
No. Setting Description
9131 Mode Mode 0 = Three phase system
1 = Split phase system
2 = Single phase system

9140 Angle comp. BB/G


No. Setting Min. setting Max. setting
9140 Angle comp. BB/G Degrees -45.0 +45.0

If the transformer has an angle displacement then synchronising can ONLY be used with Yy1, Dy1, Yd1, Yy11, Dy11 and
Yd11 transformers. (+/-30 deg. phase shift).

The factory setting is 0 degrees and it has to remain at that value except when one of the six mentioned transformers is
installed between the generator and the mains/busbar measurements.

2954 3390 00 81
Qc4002 control panel

Any error in this setting will cause a false closing of the breaker! Therefore it is essential to make a check of the angular
precision before allowing the Qc4002 to perform a real breaker closing.

82 2954 3390 00
User manual

13 Technical specifications
Accuracy: Analogue inputs:
Class 1.0 -10...+10V DC:
Impedance: 100kW
Fast overcurrent:
Not galvanically separated
3% of 350%*In
0(4)...20mA:
Analogue outputs: Impedance: 50kW
Class 1 according to total range Not galvanically separated
To IEC 688
RPM (MPU):
Operating temperature: 2...70V AC
CE: -25...70C 10...10000Hz, 250...3000W
UL: -25...50C
Multi inputs:
Climate: 0(4)...20mA:
Class HSE, to DIN 40040 0-20mA, +/- 1%
Not galvanically separated
Meas. voltage:
Binary:
100-690V AC +/-20%
Max. resistance for ON detection: 100W
Consumption: Not galvanically separated
Max. 0.25VA/phase PT100/1000:
-40...250C, +/-1%
Meas. current:
Not galvanically separated
-/1 or -/5A AC
To IEC 751 and EN60751
Consumption: VDO:
Max. 0.3VA/phase 0...1700W, +/-2%
Not galvanically separated
Current overload:
V DC:
4 x In continuously
0...40V DC, +/-1%
20 x In, 10 sec. (max. 75A)
Not galvanically separated
80 x In, 1 sec. (max. 300A)
Relay outputs:
Meas. frequency:
Electrical rating: 250V AC/30V DC, 5A
30...70Hz
Thermal rating @ 50C: 2A: Continuously
Auxiliary supply (terminals 1 and 2): Thermal rating @ 50C: 4A: tON = 5 sec., tOFF = 15 sec. (unit
12/24 V DC (8...36V continuously, 6V 1 sec.) status output: 1A)
Max. 11W consumption
Open collector outputs:
Auxiliary supply (terminals 98 and 99): Supply: 8...36V DC, max. 10mA
12/24 V DC (8...36V continuously, 6V 1 sec.) Analogue outputs: 0(4)...20mA and +/-25mA
Max. 5W consumption Galvanically separated
Active output (internal supply)
Binary inputs:
Load max. 500W
Optocoupler, bi-directional
Update rate: Transducer output: 250 ms
ON: 8...36V DC
Update rate: Regulator output: 1000 ms
Impedance: 4.7kW
OFF: <2V DC Load sharing lines:
-5...0...+5V DC
Impedance: 23.5 kW

2954 3390 00 83
Qc4002 control panel

Galv. separation: Mounting:


Between AC voltage, AC current and other I/Os: DIN-rail mount or base mount with 6 screws
3250V AC, 50Hz, 1 min.
Safety:
Between analogue outputs and other I/Os:
To EN 61010-1, installation category (overvoltage category)
500V DC, 1 min. III, 600V, pollution degree 2
Between binary input groups and other I/Os: EMC/CE: To EN 61000-6-1/2/3/4
500V DC, 1 min. SS4631503 (PL4) and IEC 255-3
Response times: Material:
Reverse power: 150 ms All plastic materials are selfextinguishing according to UL94
Overcurrent: 200 ms (V1)
Fast overcurrent: 40 ms
Plug connections:
Over-/undervoltage: 150 ms
AC current: 4.0 mm multi stranded
Over-/underfrequency: 300 ms
Other: 1.5 mm and 2.5 mm multi stranded
df/dt (ROCOF): 75 ms
Vector jump: 20 ms Display:
Overload: 200 ms 9-pole Sub-D female
Current unbalance: 200 ms
Service port:
Voltage unbalance: 200 ms
USB A-B
React. power import/export: 200 ms
Overspeed: 400 ms Protection:
Digital inputs: 250 ms Unit: IP20
Emergency stop: 200 ms Display: IP52 (IP54 with gasket)
Multi inputs: 800 ms
To IEC 529 and EN 60529
Wire failure: 600 ms
Approvals: CE, UL 508

84 2954 3390 00
User manual

14 Dimensions

115.0 (4.528)
165.0 (6.496)

144.0 (5.669)
230.0 (9.055) 120.0 (4.724)

OK
115.0 (4.528)

220.0 (9.055)
20.0 (0.787)

2954 3390 00 85
www.atlascopco.com
Printed in Belgium 07/2008 - 2954 3390 00

Das könnte Ihnen auch gefallen