World Energy, Absorption Machines Features

World Energy Absorption Machine


provide the best solution for CHP and CCHP application by utilizing waste heat World Energy Absorption Machine family is an excellent solution for maximizing an energy efficiency at
more efficiently. Industrial application as well as Commercial application.

No CFC’s and Environmentally safe EXHAUST-ENERGY RECOVERY RELIABILITY & EASY MAINTENANCE
Exhaust Gas Driven Absorption Machine produces both of Hermetically-designed refrigerant and solution pumps
Cost-Effective Direct Cooling & Heating (Exhaust Gas Driven Type) cooling & heating directly from exhaust gas from which are only moving parts provide reliability and they are
reciprocating engine or gas turbine without additional heat field serviceable through pumps isolation valves. Also
Low Noise & Low Vibration operation recovery systems. And Hot water Driven type Machine marine-type water box cover on both of the absorber and
Precise & Optimized Control by Microprocessor-based Controller produces cooling from engine jacket water or the other hot condenser allows easy tube-cleaning and water-box-
water. Specially, in Double-lift type Machine, hot water inspection.
Saving of Initial Investment energy can be utilized by 55oC.
And factory performance test, which is provided as an
High Reliability COST-EFFECTIVE COOLING AND HEATING optional basis, ensure the performance and function of
World Energy’s Exhaust Gas Driven Absorption Machine is chiller before shipment.
designed to have double-effect cycle providing more
Table of contents efficient usage of the same energy input. The Machine
operates with the waste energy from exhaust gas and
Single-Effect Double-Lift Hot Water Driven Type generates cooling and heating energy. Cooling operation
Performance Data 14~15 produces chilled water, while heating operation produces
Features 3 Foundation 16 hot water up to 60oC (140oF) as a standard and 79oC (175oF)
Control System 4 Thermal Insulation 17 as an option. Utilizing exhaust gas, full load cooling
Absorption Cycle 5~7 Single-Effect Hot Water Driven Type operation results in a Machine COP (coefficient of
Performance Data 18~19 performance) of 1.3 at standard ARI operating conditions.
Double-Effect Exhaust Gas Driven Type

03 /
Performance Data 8~9 Foundation 20 EXCELLENT PART LOAD PERFORMANCE
Foundation 10 Thermal Insulation 21 Microprocessor-based control system allows stable, part
Installation 11 Piping Diagram 22 load operation at cooling water temperatures as low as 18oC

Feature
Thermal Insulation 12 Cooling Water Quality Control 22 (64 oF) without a cooling water bypass. For maximum
Start-up Sequence 13 Wiring Diagrams 23 efficiency, a variable frequency drive pump automatically UNIFORM DISTRIBUTION OF REFRIGERANT & SOLUTION
maintains optimum solution flow to Low-Temp Generator The refrigerant and solution distribution system in
and also High-Temp Generator during whole operation. evaporator and absorber is performed based on gravity and
siphon phenomenon. This gravitational dropping distribution
SIMPLE CONNECTION system adopts stainless steel tray and allows uniform
Unit-mounted electrical items are factory-wired to the solution spray and continuous heat transfer. Different from
chiller microprocessor control panel. Only a single-point nozzle spray type of distribution system, this system
electrical connection to the chiller from the building’s eliminates an external pump to spray the solutions with
electrical service is required. A transformer, mounted in the nozzles and prevents nozzles from clogging.
chiller control panel, provides secondary, single-phase
power for the machine controls. ANTI-CRYSTALLIZATION CONTROLS PROPER SOLUTION
CONCENTRATION
LOW NOISE & VIBRATION Solution concentration is limited in several ways to avoid
The overall sound level of the machine is 65dBA from both crystallization and over-dilution, providing dependable,
1meter distance from the machine. This allows the trouble-free operation. The concentration control system
machines to be installed near occupies spaces or in areas automatically monitors the refrigerant water level in the
with strict sound requirements. Low vibration levels also evaporator in conjunction with the solution temperature
make it possible to install the chiller on upper floors without returning to the absorber.
Double-Effect Exhaust Gas Driven Type Single-Effect Double-Lift Hot Water Driven Type Single-Effect Hot Water Driven Type
special consideration for vibration dampening systems.
The Machine also incorporates a simple, passive method of
First Issued on September 2007 PRECISE & OPTIMIZED OPERATION control to correct any crystallization that would typically
Second Issued on February 2008 Factory mounted, wired and tested microprocessor-based start to occur on the shell side of the low temperature
controller monitors and controls the machine operation solution heat exchanger under abnormal conditions.
World Energy Co., Ltd. (Design & Manufacturing) continuously and automatically. A touch screen display
identifies operational status and fault indication. All RELIABLE PURGE SYSTEM
477-4 Dokjeong-Ri, Jangan-Myeon, Hwaseong-Si, Kyeonggi-Do, Korea
components meet internally acceptable codes like UL or CE Non-condensable gases are periodically exhausted from the
http://www.worldenergy.co.kr or KS or the equivalents. storage tank by a simple procedure performed while the
During the start-up sequence, the controller initiates a self- machine is running. Evacuation is performed by a unit-
Promore International Ltd. (Sales Representative) diagnostic system check to verify that all sensors are in mounted vacuum pump that is connected to the purge
5th Floor Hana Building, 996-14 Daechai-Dong, Gangnam-Gu, Seoul, Korea range. Remote start/stop switch and a key-locked control evacuation valve.
chp promoreintl.com panel door protects against unauthorized access.

We reserve the right to modify, change or discontinue the data or design without prior notice World Energy Co.
Control System Absorption Cycle
World Energy Absorption Machine Double-Effect Exhaust Gas Driven Machine
Microprocessor-based Unit Controller is factory mounted, wired and tested to ensure a protection of Cooling Cycle (Cooling Mode)
the Machine and efficient capacity control. The program logic provides proper Start/Stop of the The double-effect, exhaust-gas driven absorption machine generator where it is heated and re-concentrated to a
Machine and also enables a communication interface with others. consists of an evaporator, absorber, condenser, high- strong solution by the high temperature water vapor
temperature and low-temperature generators, solution released from the solution in the high-temperature
Component Test and Diagnostic Check Low Chilled Water Temperature Alarm heat exchangers, refrigerant and solution pumps , purge generator. Since the low-stage generator acts as the
Touch Screen Interface for Status Display, Set-point Low Cooling Water Temperature Alarm system, controls and accessories. During the cooling mode, condenser for the high-stage generator, the heat energy
Control, and System Configuration Low Chilled Water Flow Alarm the machine operates at the condition that under vacuum, first applied in the high-stage generator is used again in the
Primary and Secondary Status Messages water boils at a low temperature. Under typical operating low-stage generator, thus reducing the heat input by
Individual Start/Stop Schedules for Local Mode Overrides approximately 45% as compared to an absorption chiller
conditions, this occurs at approximately 4.4oC (40oF), thereby
Recall of Up to 999 Alarm and Alert Messages with Hot Water High Temperature (Low Temp. Hot Water with a single-stage of re-concentration. The water vapor
cooling the chilled water that circulates through the
Diagnostic Help Driven type only) released in the shell side of the low-stage generator, in
evaporator tubes. A refrigerant pump is used to spray the
Extensive Diagnostic and Service Capabilities Generator Solution High Temperature addition to the now condensed water vapor from the tube
refrigerant(water) over the evaporator tubes to improve
Advanced Crystallization Protection High Concentration side of the low-stage generator, enters the condenser to be
heat transfer.
Safety Cutouts cooled and returned to a liquid state. The refrigerant water
Temperature Sensor Faults To make the cooling process continuous, the refrigerant then returns to the evaporator to begin a new cycle.
Solution Pump Motor Overload/High Temperature Leaving Chilled Water Temperature
Refrigerant Pump Motor Overload/High Temperature (water) vapor must be removed as it is produced. To
Cooling Water Temperature Entering Absorber accomplish this, a lithium bromide solution (which has a To remove heat from the machine, cooling water from a
Low Chilled Water Temperature Cutout Refrigerant Condensate Temperature from Condenser
Low Refrigerant Temperature Cutout high affinity for water) is used to absorb the water vapor. As cooling tower is first circulated through the tubes of the
Refrigerant Evaporating Temperature this process continues, the lithium bromide becomes absorber to remove the heat of vaporization. The water is
Low Cooling Temperature Cutout Strong Solution Temperature Leaving Generator
Low Chilled Water Flow Cutout diluted, reducing its absorption capacity. A solution pump then circulated through the tubes of the condenser. The re-
Entering Hot Water Temperature (Low Temp. Hot Water then transfers this diluted solution to the generators where concentrated (strong) solution from the low-stage generator
Low Cooling Water Flow Cutout (Option) Driven type only)
Generator High Temperature Cutout it is re-concentrated in two stages (double-effect) to boil off flows back to the absorber to begin a new cycle.
Exhaust Gas Temperature Cutout (Exhaust Gas Driven the previously absorbed water. A variable frequency drive For efficiency purposes, the medium concentration solution
Hot Water High Temperature Cutout (Low Temp. Hot type only)
04 /

05 / Absorption Cycle
Water Driven type only) on the solution pump automatically maintains optimum from the high-stage generator is passed through the high-
High Temperature Generator High Pressure Cutout solution flow to the generators at all operating conditions temperature solution heat exchanger to pre-heat the diluted
Capacity Control (weak) solution, while pre-cooling the medium
(Exhaust Gas Driven type only) for maximum efficiency. The diluted solution is pumped to
Leaving Chilled Water Control concentration solution. The re-concentrated (strong)
Control System of World Energy Absorption Machine

High Temperature Generator Low Level Cutout (Exhaust the high-temperature generator where it is heated and re-
Running Travel Limit (Control Valve Opening Limit) solution from the low-stage generator is passed through the
Gas Driven type only) concentrated to a medium concentration solution by the
Exhaust Gas Leak Cutout (Exhaust Gas Driven type only) exhaust heat from the gas turbine or reciprocating engine low-temperature solution heat exchanger to pre-heat/pre-
Indications exhaust gas. The medium concentration solution from the cool the solution before being returned to the absorber.
Protective Limits Chiller Operating Status Message high-temperature generator flows to the low-temperature
Strong Solution Leaving High Temperature Generator Absorption Cycle State Points
Alarm Dilution Cycle
Low Temp.
Hot Water High Temperature Alarm (Low Temp. Hot Power-On Condenser Generator
Water Driven type only) Alarm
Refrigerant Pump Overload/High Temperature Alarm Safety Shutdown Message Cooling Water
Outlet
Solution Pump Motor Overload/High Temperature Alarm Run Hours
Low Refrigerant Temperature Alarm Control Valve Position

Exhaust Gas
Outlet

Chilled Water
Outlet
Change
Valve
(close) Bypass

Chilled Water Evaporator Absorber Change


Inlet Valve Exhaust Gas
(close) Inlet

High Temp. M
Generator
Diverter Valve

Cooling Water
Inlet

Microprocessor Touch Screen Control Panel Refrigerant Solution Low Temp. High Temp.
Pump Pump Heat Exchanger Heat Exchanger

World Energy Co. World Energy Co.


Absorption Cycle Absorption Cycle
Double-Effect Exhaust Gas Driven Machine Single-Effect Double-Lift Hot Water Driven Machine
Heating Cycle (Heating Mode) Cooling Cycle
During the heating mode, the cycle follows a different vapor This condensed water then flows to the absorber section Double Lift Hot water driven absorption chiller has main The intermediated solution in 2nd generator is heated up by
flow path than that undertaken for cooling and does not use where it mixes with the concentrated solution returning cycle and aux. cycle driving hot water and the refrigerant vapor is generated.
the typical absorption process. In addition, the absorber- from the high-temperature generator. The diluted solution The chilled water is cooled down in evaporator and the The vaporized refrigerant from 2nd generator is absorbed
condenser cooling water circuit is drained and thus not is then pumped back to the high-temperature generator to vaporized refrigerant is absorbed into concentrated solution into absorbent solution in aux. absorber and it becomes aux.
operated, since all heat rejection from the machine is repeat the vapor generation phase for the heating function. which is coming from 2nd generator. The concentrated diluted solution. The aux. diluted solution is delivered to
designed to take place through the evaporator (now the Quick changeover from cooling to heating is accomplished solution becomes diluted solution and the heat is absorbed aux. generator through aux. heat exchanger, and the
heating bundle) in a classic two-pipe system that utilizes by switching the positions of two hand valves, draining the into cooling water. The diluted solution in absorber flows to solution is heated up by driving hot water return from 2nd
only the evaporator nozzles. absorber-condenser water circuit and putting the machine 1st generator through low temp. heat exchanger and high generator and becomes aux. concentrated solution. The
High temperature water vapor produced in the high- into heating mode by changing the position of a switch in the temp. heat exchanger, and 95oC of driving hot water heats aux. concentrated solution is delivered to aux. absorber
temperature generator section is passed directly to the control panel. up the diluted solution and refrigerant vapor is generated. through aux. heat exchanger. The refrigerant vapors which
evaporator via the absorber where it condenses and The hot water temperatures is 60oC (140oF) as a standard The absorbent solution in 1st generator becomes are generated 1st generator and aux. generator are
transfers its heat to the water circulating through the without additional components and 79oC (175oF) as an option intermediate solution and it flows to 2nd generator through condensed in condenser and then flow into evaporator, and
evaporator tubes. with the additional heat exchanger. high temp. heat exchanger. the heat in condenser is absorbed by cooling water.
Hot water temperature at 60oC (140oF)
Low Temp.
Condenser Generator

Cooling Water
Outlet

Exhaust Gas
06 /

07 /
Outlet

Chilled Water Cooling water


Outlet Outlet
Change
Absorption Cycle

Absorption Cycle
Valve Condenser
(open) Bypass
2nd Generator Aux. Absorber
Chilled Water Evaporator Absorber Change
Inlet Valve Exhaust Gas
(open) Inlet

High Temp. M
Generator Concentrated Solution Aux. Diluted
Diverter Valve
Pump Solution Pump Hot water
Cooling Water Outlet
Inlet
Aux. Generator
Refrigerant Solution Low Temp. High Temp.
Pump Pump Heat Exchanger Heat Exchanger Chilled water
Outlet Aux. Concent rated
Aux. Heat
Exchanger Solution Pump

Hot water temperature at 79oC (175oF)


Low Temp. Change Valve
Condenser Hot water Outlet
Generator (close)
Chilled water Hot water
Cooling Water Evaporator Absorber
Hot water Inlet Inlet Inlet
Outlet

1st Generator
Change Valve
(close)

Exhaust Gas Refrigerant


Outlet Cooling water Diluted Solution
Inlet Intermediate Solution
Concent rated Solution
Aux. Intermediate Solution
Aux. Concent rated Solution
Chilled Water
Intermediate Solution Chilled water
Outlet
Bypass
Refrigerant Diluted Solution Low Temp. High Temp. Cooling water
Pump Pump Heat Exchanger Heat Exchanger Pump
Hot water
Chilled Water Absorber
Evaporator Exhaust Gas
Inlet
Inlet

High Temp. M Concent rated Solution Chilled water


Change Valve Generator
Diverter Valve
Refrigerant
(close) Diluted Solution Aux. Intermediate Solution Cooling water
Cooling Water Intermediate Solution Aux. Concent rated Solution Hot water
Inlet

Refrigerant Solution Low Temp. High Temp.


Pump Pump Heat Exchanger Heat Exchanger

World Energy Co. World Energy Co.


Double-Effect Exhaust Gas Driven Absorption Machine CHP Series
100 ~ 1,500 Tons

PERFORMANCE DATA
Double-Effect Exhaust Gas Driven Type (100~360RT) Double-Effect Exhaust Gas Driven Type (400~1500RT)

Model CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP CHP
Unit 040 045 050 056 063 070 080 090 100 1100 120 130 140 150
010 012 015 018 021 024 028 032 036
usRT 100 120 150 180 210 240 280 320 360 400 450 500 560 630 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500
Cooling Capacity
kW 351 422 527 633 738 844 984 1,125 1,265 1,406 1,582 1,757 1,968 2,214 2,460 2,812 3,163 3,515 3,866 4,218 4,569 4,921 5,272
Temp. C
o
12 / 7 12 / 7
Chilled Flow rate ton/h 60.5 72.6 90.7 109 127 145 169 194 218 242 272 302 339 381 423 484 544 605 665 726 786 847 907
Water P. Drop mAq 4.8 5.1 6.6 7.0 6.4 6.3 4.6 4.5 5.0 5.1 4.4 3.9 3.6 5.0 6.6 4.7 6.4 8.5 7.2 9.2 11.5 8.3 10.2
Connection mm 100 125 150 150 200 250 300 350
Temp. C
o
32 / 37.5 32 / 37.5
Cooling Flow rate m3/h 100 120 150 180 210 240 280 320 360 400 450 500 560 630 700 800 900 1000 1100 1200 1300 1400 1500
Water P. Drop mAq 11.1 11.3 11.5 11.8 11.8 12.1 11.2 10.7 11.1 10.8 10.7 10.8 7.7 10.6 14.0 8.7 11.8 15.6 3.0 3.8 4.8 4.0 4.9
Connection mm 125 150 200 200 250 300 350 400
Mcal/h 283 340 425 510 595 680 793 906 1019 1133 1274 1416 1586 1784 1982 2266 2549 2832 3115 3398 3682 3965 4248
Heating Capacity
kW 329 395 494 592 691 790 922 1053 1185 1317 1481 1646 1843 2074 2304 2633 2962 3291 3621 3950 4279 4608 4937
Temp. C
o
55.3 / 60 55.3 / 60
08 / Double-Effect Exhaust Gas Driven Type (Performance Data)

09 / Double-Effect Exhaust Gas Driven Type (Performance Data)


Hot Flow rate ton/h 60.5 72.6 90.7 109 127 145 169 194 218 242 272 302 339 381 423 484 544 605 665 726 786 847 907
Water P. Drop mAq 4.8 5.1 6.6 7.0 6.4 6.3 4.6 4.5 5.0 5.1 4.4 3.9 3.6 5.0 6.6 4.7 6.4 8.5 7.2 9.2 11.5 8.3 10.2
Connection mm 100 125 150 150 200 250 300 350
Flow rate kg/sec 0.88 1.05 1.32 1.58 1.84 2.11 2.46 2.81 3.16 3.51 3.95 4.39 4.92 5.53 6.15 7.03 7.91 8.78 9.66 10.54 11.42 12.30 13.18
Cooling C
o
450 / 165 450 / 165
Temp.
Heating C
o
450 / 125 450 / 125
Exhaust
Pressure Drop mmAq 77 82 79 92 97 113 129 131 123 131 133 134 143 133 146 155 153 176 213 221 212 206 184
Gas
Inlet Conn. mm*mm 908*394 908*472 908*589 908*667 908*706 908*745 908*823 908*901 1362*706 1362*745 1362*823 1362*901 1362*994 1362*1129 1362*1219 1362*1204 1362*1354 1362*1404 1362*1404 1362*1504 1362*1654 1362*1804 1362*2054
Outlet Conn mm 400 500 600 600 750 1000
Diverter Valve mm 400 500 600 600 750 1000
Power source 3 400V (50Hz) 3 400V (50Hz)
Abs. Pump kW(A) 2.0 (5.7) 2.4 (6.1) 3.4 (9.0) 3.4 (9.0) 5.5 (14.3) 7.5 (21.9)
Ref. Pump kW(A) 0.3 (1.5) 0.4 (1.6) 0.4 (1.6) 1.5 (3.8)
Electric
Purge Pump kW(A) 0.4 (1.4) 0.4 (1.4) 0.75(2.2)
Control Panel KVA 0.2 (0.5) 0.2 (0.5)
Amp.(400Vac) A 9.1 9.5 9.6 12.5 12.5 17.8 20.0 28.4
Lenght (L) mm 2,597 3,680 3,686 4,744 4,776 4,776 4,954 4,998 5,540 6,038 5,460 5,958 6,483 6,293 6,818 7,318 6,974 7,475
Size Width (W) mm 1,662 1,740 1,857 1,935 2,150 2,189 2,267 2,375 2,270 2,309 2,491 2,569 2,934 3,069 3,159 3,330 3,480 3,530 4,348 4,448 4,598 4,932 5,182
Height (H) mm 2,090 2,254 2,420 2,420 2,633 2,962 3,380 3,500 3,700
Rigging Ton 5.0 5.3 6.4 6.8 7.9 8.5 9.8 10.3 12.8 13.2 15.7 16.5 21.2 23.1 24.6 31.0 33.6 35.6 41.1 43.4 46.4 50.2 54.1
Weight
Operation Ton 5.4 5.8 7.0 7.4 8.6 9.3 10.7 11.3 14.0 14.6 17.2 18.1 23.7 25.8 27.5 34.8 37.6 39.9 46.2 48.8 52.1 56.5 60.8

Note Note
1. Working pressure of each water side is based on 1.0MPa (150pisg) 1. Working pressure of each water side is based on 1.0MPa (150pisg)
2. Lowest outlet temperature of chilled water is 5oC and 18oC for cooling water. 2. Lowest outlet temperature of chilled water is 5oC and 18oC for cooling water.
3. Controllable cooling capacity range shall be 25~100% as a standard condition and 0~100% as an option. 3. Controllable cooling capacity range shall be 25~100% as a standard condition and 0~100% as an option.
4. Each water flow can be adjusted within 50 ~120%. 4. Each water flow can be adjusted within 50 ~120%.
5. Fouling factor 0.0001 m2.h.oC/Kcal for Absorber and Condenser, 0.0001 m2.h.oC/Kcal for Evaporator and Generator. 5. Fouling factor 0.0001 m2.h.oC/Kcal for Absorber and Condenser, 0.0001 m2.h.oC/Kcal for Evaporator and Generator.
6. 79oC of hot-water temperature is possible as an option. 6. 79oC of hot-water temperature is possible as an option.

World Energy Co. World Energy Co.


Double-Effect Exhaust Gas Driven Absorption Machine CHP Series
100 ~ 1,500 Tons

FOUNDATION SYSTEM PIPINGS


K/2 A Exhaust Gas Cooling
Bypass Air Fuel Tower
Air Handling Unit Expansion Tank
I

Anchor Bolt Supply water


H

Nut Engine
Steel Plate
Diverter Air vent
AV
Welding Machine Feet Valve
F F P T
Absorber, Evaporator, Condenser Drain line
& Low Temperature Generator Shell Assembly

B
Exhaust gas Bleed off
Exhaust gas Outlet
Inlet

Cooling water Outlet


Chilled / Hot Thermostat
Flow meter water Pump Pressure gauge
(1st) P
F P T Chilled water Outlet Temperature Gauge

E
T
J/2 Chilled / Hot Damper valve
Example of Abchoring water Pump P T
Chilled water Inlet Bypass valve
J (2nd)
Cooling water Inlet Strainer
K Bypass valve
Valve
D
G G
Note Foundation Cooling
Drain Ditch
1. Drain ditch should be prepared around foundation. High Temperature ABSORPTION CHILLER water

50
Generator Assemply Pump
2. Horizontal level of foundaton surface should be
10 / Double-Effect Exhaust Gas Driven Type (Foundation)

11 /
P T
maintained less than 1mm per 1m. Supply Header Return Header
3. indicates the location of anchor bolts.
(Anchor bolt, nut and steel plates are not supplied) 1) All external equipment out of dotted line is scope of DIVERTER VALVE & EXHAUST GAS DUCT

Double-Effect Exhaust Gas Driven Type (Installation)


customer’s.
C 2) Refer to outline drawing and specification data sheet for For Diverter Valve;
the external dimensions of the machine, the location & the 1) Install the diverter valve at the exhaust gas duct end of
A B C D E H I J K F G diameter of water pipe connection and the dimensions & gas turbine or reciprocating engine and level the diverter
Model (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (ton) (ton) the size of Exhaust gas line connections. valve horizontally by using the level gauge.
CHP010 400 236 2.0 0.7 3) The locations of chilled water pumps, cooling water 2) Install the transient duct between high-stage generator
1,941
CHP012 500 225 2.1 0.8 pumps and expansion tanks shall be determined in and diverter valve.
700 1,000 100 200
CHP015 600 234 2.5 1.0 consideration of the hydrostatic head of pumps and the 3) Connect the wiring in accordance with wiring diagram of
2,961 height of building. And the Machine shall not be subject to the manufacturer.
CHP018 700 223 2.6 1.1
150 350 a pressure higher than the designed pressure at any
CHP021 1,060 700 278 3.1 1.2 Bypass
2,936 water header.
CHP024 700 298 3.4 1.3 Exhaust
890 4) For cooling water quality control, it is recommended to
CHP028 1,130 800 287 3.9 1.4 install cooling water bleed-off device on the inlet pipe line
3,956 105 205 Exhaust
CHP032 900 306 4.1 1.5 of cooling towers.
Gas
CHP036 700 279 5.1 1.9 5) Around 10 meshes of strainers are recommended to be Exhaust
1,150 installed in the cooling water line. Duct
CHP040 700 299 5.3 2.0 Diverter
3,906 990 6) For the maintenance and the inspection of the Machine, Valve
CHP045 800 352 6.2 2.4 the following equipment shall be installed on each chilled
1,370 105 205 Actuator
CHP050 900 341 200 400 6.4 2.6 water and cooling water inlet/outlet lines as well as stop Vertical
Duct
CHP056 3,856 1,000 445 8.8 3.0 valve.
CHP063 4,398 1,150 1,600 1,100 463 9.6 3.3 Thermometers and pressure gauges shall be installed at High Stage
chilled and cooling water inlet/outlet. Generator
CHP070 4,896 1,200 458 10.3 3.5
Air relief valves shall be installed on each chilled and
CHP080 4,348 1,200 486 12.4 4.9
cooling water lines at higher points than each water
CHP090 4,846 1,210 2,400 1,400 461 13.4 5.4 headers.
CHP100 5,371 1,400 486 105 205 14.4 5.6 Drain valves shall be installed at the lowest position For Exhaust Gas Duct;
CHP110 4,896 1,400 1,171 17.3 5.8 between the stop valves of chilled and cooling water and 1) Sharp bend and restrictions should be avoided to allow
300 500 the Machine and the drain valve shall be piped to the drain
CHP120 5,421 1,290 1,500 1,171 18.3 6.1 smooth gas flow.
5,921 1,700 1,146 6.6
ditch. 2) The exhaust gas duct outlet should be arranged to
CHP130 2,500 19.4
7) There shall be a sufficient clearance for access to the prevent the rain water from entering into the machine
CHP140 5,371 1,800 1,131 21.1 7.1 absorber, evaporator, condenser, and generator to
1,500 and the drain connection should be provided to remove
CHP150 5,871 2,100 1,106 22.4 8.0 facilitate inspection and cleaning work. the condensate from the exhaust gas outlet side.

World Energy Co. World Energy Co.


¡Æ ¡
¡Æ
¡Æ

Double-Effect Exhaust Gas Driven Absorption Machine CHP Series


¡Æ
¡Æ

¡Æ
¡Æ

100 ~ 1,500 Tons

THERMAL INSULATION START-UP SEQUENCE


Start No
Request

Verify All sensors No Sensor Fault /


in range
Prestart Alerts
In Prestart safties

Yes

Start Chilled Cooling 79 deg C Heating


Mode
Water Pump

60 deg C Heating

Start Water
Verify Timer A B
No
12 /

13 /
Double-Effect Exhaust Gas Driven Type (Thermal Insulation)

Double-Effect Exhaust Gas Driven Type (Start-up Sequence )


Verify Chilled No Verify timer Yes Chilled Water
HOT Surface Cold Surface elapsed
Water Flow Fault
High Temp. Evaporator (with Water Box)
Low Temp. Generator (with Water Box) Inlet & Outlet Pipes
Heat Exchanger (with Pipe) Yes

Hot Surface (m2) Cold Surface (m2)


Model
75mm 50mm 25mm 40mm 20mm Start 3 min
Start-Stop Condition Yes Monitor for
CHP010 7.9 2.8 3.5 4.0 0.3 Refrigerant Pump
Start-Stop
CHP012 8.5 2.8 3.5 4.0 0.3 Delay Timer
CHP015 9.2 3.8 4.8 5.4 0.3
CHP018 9.7 3.8 4.8 5.4 0.3 No No
CHP021 10.1 4.0 5.8 6.1 0.4
CHP024 10.4 4.0 5.8 6.1 0.4 Start Cooling
CHP028 10.9 5.1 6.3 7.4 0.5 Water Pump Ref Pump
CHP032 11.4 5.1 6.3 7.6 0.5
Timer elapsed
CHP036 17.6 6.0 7.1 8.2 0.5
CHP040 18.0 6.0 7.1 8.2 0.5
CHP045 18.8 6.7 7.7 9.8 0.5 Start Water
Verify Timer
CHP050 19.5 6.7 7.7 9.8 0.5 Yes
CHP056 21.3 7.5 7.9 13.5 0.6 No
CHP063 22.6 8.3 8.9 15.0 0.7
CHP070 23.4 9.2 9.5 16.0 0.7 Start Refrigerant
CHP080 23.9 10.5 11.0 17.0 1.1 Pump
Verify Cooling No Water timer Yes Cooling Water
CHP090 25.3 11.5 11.4 18.5 1.2
Water Flow Elapsed Fault
CHP100 25.8 13.0 11.8 20.0 1.2
CHP110 27.0 15.5 13.7 22.5 1.4
CHP120 28.0 16.8 14.0 11.1 1.4 Yes
CHP130 29.4 18.2 14.3 11.7 1.4
Start Machine Running
CHP140 30.9 18.1 14.6 13.3 1.5 Start Tower Solution
CHP150 33.3 19.6 15.1 13.8 1.5 Control Pump

World Energy Co. World Energy Co.


Single-Effect Double-Lift Hot Water Driven Absorption Machine 2AB Series
75 ~ 975 Tons

PERFORMANCE DATA
Single-Effect Double-Lift Hot Water Driven Type (75~240RT) Single-Effect Double-Lift Hot Water Driven Type (270~975RT)
2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB 2AB
Model Unit
075 090 110 135 155 180 210 240 270 300 340 375 420 470 525 600 675 750 825 900 975

kW 264 316 387 474 545 633 738 844 949 1054 1,195 1,318 1,476 1,652 1,845 2,110 2,373 2,637 2,901 3,165 3,428
Cooling Capacity
usRT 75 90 110 135 155 180 210 240 270 300 340 375 420 470 525 600 675 750 825 900 975

Temp. o
C 13 / 8 13 / 8

Chilled Flow rate m /h 3


45.4 54.5 66.6 81.7 93.8 109 127 145 163 182 206 227 254 284 316 363 408 454 499 545 590
Water P. Drop mH2O 6.4 6.8 9.6 10.5 9.0 9.6 9.7 9.5 10.2 10.5 9.1 9.7 7.4 10.2 4.5 3.3 4.4 5.9 5.0 6.4 8.0

Connection mm 80 100 125 150 200 250 300

Temp. o
C 31 / 36.5 31 / 36.5

Cooling Flow rate m3/h 107 128 156 192 240 256 298 341 384 426 476 533 597 668 746 853 959 1066 1172 1279 1386
Water P. Drop mH2O 13.4 13.9 11.3 12.2 14.0 12.9 13.2 12.8 12.5 12.4 12.2 12.6 9.9 13.6 10.0 14.1 10.4 13.7 10.7 13.6 17.0
14 /

15 /
Connection mm 125 150 200 250 300 350 400
Temp. o
C 95 / 55 95 / 55
Single-Effect Double-Lift Hot Water Driven Type (Performance Data)

Single-Effect Double-Lift Hot Water Driven Type (Performance Data)


Flow rate m /h 3
8.9 10.7 13.1 16.0 18.4 21.4 24.9 28.5 32.0 35.6 39.8 44.5 49.8 55.8 62.3 71.2 80.1 89.0 97.9 107.0 116.0

Hot Pressure Shell mH2O 5.7 6.1 4.3 4.9 5.0 5.3 6.0 6.4 5.6 5.8 6.0 6.1 4.2 5.6 4.5 2.9 3.8 4.9 4.0 5.0 6.2
Water Drop Control Valve mH2O 2.4 3.4 5.1 2.9 3.8 5.1 2.8 3.7 4.6 2.3 2.8 3.5 1.7 2.2 2.7 3.6 4.5 2.1 2.6 3.1 3.6
Connection mm 65 80 100 125

Control Valve mm 40 50 65 65 80 100 125


Power source - 3 400, 50Hz 3 400, 50Hz
Abs. Pumps kW(A) 4.5 (14.4) 4.7 (14.63) 7.3 (23.5A) 8.2 (28.7A) 13.3 (44.7A)
Ref. Pump kW(A) 0.3 (1.5A) 0.4 (1.6A) 0.4 (1.6A) 1.5 (3.8A)
Electric
Purge Pump kW(A) 0.4 (1.4A) 0.4 (1.4A) 0.75(2.2)
Control Panel kW(A) 0.2 (0.5A) 0.2 (0.5A)

Total Amps. A 17.8 17.9 18.1 27.0 32.2 50.4 51.2


Lenght (L) mm 2,635 3,680 3,693 4,738 4,852 4,856 4,933 5,475 5,973 5,618 6,116 6,641 6,300 6,825 7,325
Size Width (W) mm 1,736 1,989 2,230 2,337 2,625 2,815 3,005

Height (H) mm 2,293 2,427 2,566 2,963 3,262 4,050 4,200


Rigging ton 4.4 4.6 5.7 6.0 7.2 7.5 8.8 9.2 11.3 11.8 13.5 14.0 19.0 20.7 22.2 26.7 28.7 30.7 36.4 38.4 40.8
Weight
Operation ton 5.1 5.3 6.6 7.0 8.4 8.9 10.4 10.9 13.4 14.1 16.2 16.9 23.0 25.0 26.9 31.6 34.0 36.3 43.1 45.5 48.3

Note Note
1. Working pressure of chilled/cooling water circuits are based on 1.0Mpa (150pisg) and 1.6MPa (230pisg) for driving 1. Working pressure of chilled/cooling water circuits are based on 1.0MPa (150pisg) and 1.6MPa (230pisg) for driving
hot water circuit. hot water circuit.
2. Standard flow rate of chilled water per usRT is 0.6048m3/h, 1.42m3/h for cooling water and 0.1187ton/h for hot water. 2. Standard flow rate of chilled water per usRT is 0.6048m3/h, 1.42m3/h for cooling water and 0.1187ton/h for hot water.
3. Fouling factor 0.0001 m2.h.oC/Kcal for Absorber and Condenser, 0.0001 m2.h.oC/Kcal for Evaporator and Generator. 3. Fouling factor 0.0001 m2.h.oC/Kcal for Absorber and Condenser, 0.0001 m2.h.oC/Kcal for Evaporator and Generator.

World Energy Co. World Energy Co.


Single-Effect Double-Lift Hot Water Driven Absorption Machine 2AB Series
75 ~ 975 Tons

FOUNDATION THERMAL INSULATION


D Anchor Bolt
Nut
E Steel Plate

Welding Machine Feet

F 2'nd
Generator Aux.
Condenser
Absorber

Aux.
Generator

Evaporator Absorber

G
1'st
Generator

B
C
H

Example of Abchoring

Foundation HOT Surface Cold Surface


Drain Ditch
1st Generator (with Water Box) Evaporator (with Water Box)
0

50
2nd, Aux. Generator (with water Box) Inlet & Outlet Pipes of Refrigerant Pump
I & Heat Exchanger Body (with Pipes)
16 /

17 /
0 A
Note
1. Drain ditch should be prepared around foundation. 3. indicates the location of anchor bolts.
Single-Effect Double-Lift Hot Water Driven Type (Foundation)

Single-Effect Double-Lift Hot Water Driven Type (Thermal Insulation)


2. Horizontal level of foundation surface should be (Anchor bolts, nuts and steel plates are not supplied)
maintained less than 1mm per 1m.

A B C D E F G H I Hot Surface (m2) Cold Surface (m2)


Model Model
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) 50mm 25mm 19mm 10mm
2AB075 2AB075 3.1 7.3 4.0 0.3
1,941 205
2AB090 2AB090 3.1 7.3 4.0 0.3
1,343 1,543 325 125 1,178 738 520
2AB110 2AB110 3.1 9.8 5.4 0.3
2,961 205
2AB135 2AB135 3.1 9.8 5.4 0.3
2AB155 2AB155 3.6 11.5 6.1 0.4
2,936 205
2AB180 2AB180 3.6 11.5 6.1 0.4
1,528 1,728 350 150 1,363 873 600
2AB210 2AB210 3.6 14.3 7.4 0.5
3,956 205
2AB240 2AB240 3.6 14.3 7.6 0.5
2AB270 2AB270 4.8 16.0 8.2 0.5
1,696 1,896 1,531 991 650 205
2AB300 2AB300 4.8 16.0 8.2 0.5
3,906 400 200
2AB340 2AB340 5.7 18.7 9.8 0.5
1,786 1,986 1,621 1,051 690 205
2AB375 2AB375 5.7 18.7 9.8 0.5
2AB420 3,856 2AB420 6.6 21.7 13.5 0.6
2AB470 4,398 1,973 2,173 450 250 1,808 1,198 750 205 2AB470 6.6 23.6 15.0 0.7
2AB525 4,896 2AB525 6.6 25.4 16.0 0.7
2AB600 4,348 2AB600 7.8 28.4 16.3 1.2
2AB675 4,846 2,136 2,336 500 300 1,926 1,286 800 205 2AB675 7.8 30.3 17.8 1.2
2AB750 5,371 2AB750 7.8 32.1 19.4 1.2
2AB825 4,826 2AB825 8.5 35.1 19.5 1.3
2AB900 5,351 2,366 2,566 500 500 2,156 1,416 860 205 2AB900 8.5 37.0 21.2 1.3
2AB975 5,851 2AB975 8.5 38.8 25.7 1.3

World Energy Co. World Energy Co.


Single-Effect Hot Water Driven Absorption Machine HWAR Series
30 ~ 975 Tons

PERFORMANCE DATA
Single-Effect Hot Water Driven Type (30~180RT) Single-Effect Hot Water Driven Type (210~975RT)

HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR- HWAR-
Model Unit
L030 L040 L050 L060 L075 L090 L110 L135 L155 L180 L210 L240 L270 L300 L340 L375 L420 L470 L525 L600 L675 L750 L825 L900 L975
kW 105 141 175 211 264 316 387 474 545 633 738 844 949 1,054 1,195 1,318 1,476 1,652 1,845 2,110 2,373 2,637 2,901 3,165 3,428
Cooling Capacity
usRT 30 40 50 60 75 90 110 135 155 180 210 240 270 300 340 375 420 470 525 600 675 750 825 900 975
Temp. o
C 13 / 8 13 / 8
Chilled Flow rate m /h 3
18.1 24.2 30.2 36.3 45.4 54.5 66.6 81.7 93.8 109 127 145 163 182 206 227 254 284 316 363 408 454 499 545 590
Water P. Drop mH2O 4.9 5.1 9.7 10.6 10.4 11.0 9.6 10.6 9.6 9.7 9.8 9.6 10.3 10.6 9.4 9.8 7.5 10.3 4.6 3.4 4.6 6.1 4.0 5.2 6.4
Connection mm 65 80 100 125 125 150 200 250 300
Temp. o
C 31 / 36.5 31 / 36.5
Cooling Flow rate m /h 3
39.6 52.8 66.1 79.3 99 119 145 178 205 238 277 317 357 396 449 495 555 621 693 792 891 990 1,090 1,189 1,288
Water P. Drop mH2O 6.3 6.6 12.6 14.0 10.9 7.2 10.8 11.6 11.3 11.9 11.0 10.5 10.9 10.6 10.7 10.7 6.2 8.5 11.4 7.2 9.7 12.7 10.9 13.9 17.3
Connection mm 100 125 150 200 250 300 350 400
Temp. o
C 95 / 80 95 / 80
18 /

19 /
Flow rate ton/h 8.4 11.2 14 16.8 21.0 25.2 30.8 37.8 43.4 50.4 58.8 67.2 75.6 84.0 95.2 105 118 132 147 168 189 210 231 252 273
Hot Pressure Shell mH2O 0.8 1.1 1.9 2.2 1.5 1.6 0.7 0.8 0.9 1.0 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.2 3.0 1.8 2.5 3.3 2.6 3.3 4.1
Single-Effect Hot Water Driven Type (Performance Data)

Single-Effect Hot Water Driven Type (Performance Data)


Water Drop Control Valve mH2O 2.1 3.8 2.2 3.2 5 7.1 4.3 2.5 3.3 4.5 2.4 3.2 4.0 5.0 2.4 3.0 3.7 4.7 2.6 3.4 4.3 5.3 1.9 2.3 2.7
Connection mm 50 65 80 100 100 125 150 200
Control Valve mm 40 50 65 80 100 100 125 150 200
Power source - 3 400, 50Hz 3 400, 50Hz
Abs. Pumps kW(A) 1.2(3.3A) 1.5 (4.5A) 2.0 (5.8A) 2.4 (6.9A) 2.4 (6.9A) 3.0 (9.5A) 4.5 (15.4A)
Ref. Pump kW(A) 0.2 (1.2A) 0.3 (1.5A) 0.4 (1.6A) 0.4 (1.6A) 1.5(3.8A)
Electric
Purge Pump kW(A) 0.4 (1.4A) 0.4 (1.4A) 0.75(2.2)
Control Panel kW(A) 0.2 (0.5A) 0.2 (0.5A)
Total Amps. A 6.3 7.9 9.2 10.4 10.4 13.0 15.2 21.9
Lenght (L) mm 2,091 2,591 2,597 3,680 3,686 4,744 4,776 4,880 4,998 5,540 6,038 5.644 6,142 6,667 6,293 6,818 7,318
Size Width (W) mm 1,168 1,294 1,419 1,419 1,545 1,625 1,830 2,209 2,379
Height (H) mm 1,981 2,255 2,389 2,389 2,540 2,838 3,222 3,600 4,000
Rigging ton 2.1 2.2 2.6 2.7 3.6 3.7 4.6 4.8 5.5 5.8 6.8 7.1 8.8 9.2 10.5 10.9 14.7 16.0 17.2 19.3 21.6 23.9 26.2 28.5 30.8
Weight
Operation ton 2.3 2.5 2.9 3.1 4.1 4.2 5.2 5.5 6.4 6.8 7.9 8.4 10.4 10.9 12.5 13.1 17.8 19.4 20.8 23.3 26.1 29.0 31.8 34.6 37.5

Note Note
1. Working pressure of chilled/cooling water circuits are based on 1.0MPa (150pisg) and 1.6MPa (230pisg) for driving 1. Working pressure of chilled/cooling water circuits are based on 1.0MPa (150pisg) and 1.6Mpa (230pisg) for driving
hot water circuit. hot water circuit.
2. Standard flow rate of chilled water per usRT is 0.6048m3/h, 1.321m3/h for cooling water and 0.280ton/h for hot water. 2. Standard flow rate of chilled water per usRT is 0.6048m3/h, 1.321m3/h for cooling water and 0.280ton/h for hot water.
3. Fouling factor 0.0001 m2.h.oC/Kcal for Absorber and Condenser, 0.0001 m2.h.oC/Kcal for Evaporator and Generator. 3. Fouling factor 0.0001 m2.h.oC/Kcal for Absorber and Condenser, 0.0001 m2.h.oC/Kcal for Evaporator and Generator.
4. High temperature (100 ~ 150 degree C) Hot Water Driving type is available as additional model. Followings are the standard 4. High temperature (100 ~ 150 degree C) Hot Water Driving type is available as additional model. Followings are the standard
capacity range and the standard operational condition for the model selection; capacity range and the standard operational condition for the model selection;
- Cooling capacity range as Standard model : 100 ~ 1300RT - Cooling capacity range as Standard model : 100 ~ 1300RT
- Hot water Inlet / Outlet temperature : 138 / 108 degree C - Hot water Inlet / Outlet temperature : 138 / 108 degree C
- Chilled water Inlet / Outlet temperature : 12 / 7 degree C - Chilled water Inlet / Outlet temperature : 12 / 7 degree C
- Cooling water Inlet / Outlet temperature : 32 / 39 degree C - Cooling water Inlet / Outlet temperature : 32 / 39 degree C

World Energy Co. World Energy Co.


Single-Effect Hot Water Driven Absorption Machine HWAR Series
30~ 975 Tons

FOUNDATION Anchor Bolt


THERMAL INSULATION
A Nut
Steel Plate

B Welding Machine Feet


C
D
Condenser

Generator

Evapo
Absorber rator

Example of Abchoring
0
F Foundation
G Drain Ditch

50
HOT Surface Cold Surface
H

L
J
I

Generator (with water Box) Evaporator (with Water Box)


20 /

21 /
Note Heat Exchanger Body (with Pipes) Inlet & Outlet Pipes of Refrigerant Pump
1. Drain ditch should be prepared around foundation. 3. indicates the location of anchor bolts.
2. Horizontal level of foundation surface should be (Anchor bolts, nuts and steel plates are not supplied)
Single-Effect Hot Water Driven Type (Foundation)

Single-Effect Hot Water Driven Type (Thermal Insulation)


maintained less than 1mm per 1m.

A B C D F G H I J K L Hot Surface (m2) Cold Surface (m2)


Model Model
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) 50mm 25mm 19mm 10mm
HWAR-L030 HWAR-L030 2.3 1.4 3.3 0.2
1,158 1,321 1,484
HWAR-L040 HWAR-L040 2.3 1.4 3.3 0.2
125 1,000 850 800 50 200 163 163
HWAR-L050 HWAR-L050 2.7 1.6 3.9 0.3
1,758 1,921 2,084
HWAR-L060 HWAR-L060 2.7 1.6 3.9 0.3
HWAR-L075 HWAR-L075 2.8 1.5 4.0 0.3
1,778 1,941 2,104
HWAR-L090 HWAR-L090 2.8 1.5 4.0 0.3
125 900 800 700 100 200 163 163
HWAR-L110 HWAR-L110 3.8 1.7 5.4 0.3
2,798 2,961 3,124
HWAR-L135 HWAR-L135 3.8 2.1 5.4 0.3
HWAR-L155 HWAR-L155 4.0 2.4 6.1 0.4
2,761 2,936 3,111
HWAR-L180 HWAR-L180 4.0 2.4 6.1 0.4
150 1,095 995 890 175 175
HWAR-L210 HWAR-L210 5.1 3.0 7.4 0.5
3,781 3,956 4,131
HWAR-L240 HWAR-L240 5.2 3.2 7.6 0.5
HWAR-L270 HWAR-L270 6.0 3.5 8.2 0.5
HWAR-L300 HWAR-L300 6.0 3.5 8.2 0.5
200 1,195 1,095 990 200 200 3,706 3,906 4,106
HWAR-L340 HWAR-L340 6.7 3.6 9.8 0.5
HWAR-L375 HWAR-L375 6.7 3.7 9.8 0.5
HWAR-L420 105 205 3,631 3,856 4,081 HWAR-L420 7.5 4.6 13.5 0.6
HWAR-L470 250 1,355 1,255 1,150 225 225 4,273 4,398 4,523 HWAR-L470 8.3 5.0 15.0 0.7
HWAR-L525 4,771 4,896 5,021 HWAR-L525 9.2 5.3 16.0 0.7
HWAR-L600 4,098 4,348 4,598 HWAR-L600 12.5 5.5 16.3 1.2
HWAR-L675 1,415 1,315 1,210 4,596 4,846 5,096 HWAR-L675 13.5 5.7 17.8 1.2
HWAR-L750 5,121 5,371 5,621 HWAR-L750 14.6 6.0 19.4 1.2
300 250 250
HWAR-L825 4,676 4,826 4,976 HWAR-L825 14.9 6.6 19.5 1.3
HWAR-L900 1,495 1,395 1,290 5,201 5,351 5,501 HWAR-L900 16.0 7.0 21.2 1.3
HWAR-L975 5,701 5,851 6,001 HWAR-L975 17.0 7.4 25.7 1.3

World Energy Co. World Energy Co.


Installation Wiring Diagrams

Piping Diagram Cooling tower M


Double-Effect Exhaust Gas Driven Type
TB1 TB4 TB3 TB6
Thermostat Supply water
Bleed off
P Pressure gauge

Air handling unit


T Temperature Gauge
Drain line
R S T GND 705 706 707 708 246 247 273 272 R2 S2 GND 219 221 400 401 403 404 406 407 500 501 502 503 504 505 506 507 508 509
Valve

Expansion tank Drain Valve

Air Vent
(+) (-) (-) (+)

52CH

52CO
AX1
Absorption chiller

COOLING WATER PUMP


Cooling water

COOLING WATER PUMP


P T

CHILLED WATER PUMP

CHILLED WATER PUMP


Chilled / Hot Outlet
DIVERTER VALVE ASS'Y TERMINAL BOX

COOLING TOWER FAN


REMOTE S TART/STOP
Flow meter G2

F
water
Pump(1st)
P T
Chilled water
Outlet
AA
A
Hot water P T
Hot Water Diff. Pressure
Control Valve 3 PHASE
Outlet
GA
Hot water Outlet
POWER
Chilled / Hot P T E Hot water control valve

ALARM SIGNAL
A

START SIGNAL
water
Pump(2nd) Chilled water

RUN SIGNAL

RUN SIGNAL

RUN SIGNAL
G1 Hot water P T

INTER LOCK

INTER LOCK
Inlet Inlet Hot water Inlet
Bypass valve 705 706 707 708 246 247 273 272 R2 S2 GND 219 221

Cooling
water
(+) (-) (-) (+)
pump
Cooling water Inlet P T

BLACK

TO USER'S MCC
Supply header Return header

FROM USER'S MCC


NOTE#2

GRAY

PINK

RED
1) All external equipment out of dotted line is scope of 7) Around 10 meshes of strainers are recommended to be

AIR SEAL B LOWER CH ASSIS GROUND


customer’s. installed in the cooling water line.
22 /

23 /
AIR SEAL B LOWER
DIVE RTER VALVE POSITION
ACTUATOR FULL C LOSE

CONTROL SIGNAL (4~20mA)

FEEDBACK SIGNAL (0~10V)


DIVE RTER VALVE ACT UATOR

DIVE RTER VALVE ACT UATOR


CONTACT

CONTACT

POWER (115V)

POWER (24V)
2) Refer to outline drawing and specification data sheet for 8) For the maintenance and the inspection of the Machine,

ACTUATOR FULL OPEN


the external dimensions of the machine, the location & the following equipment shall be installed on each chilled
the diameter of water pipe connection and etc. water and cooling water inlet/outlet lines as well as stop
Single-Effect Hot Water Driven Type (Piping Diagram / Cooling Water Quality Control)

Single-Effect Hot Water Driven Type (Wiring Diagrams)


3) Driving hot water must be maintained as design valve.
temperature. Thermometers and pressure gauges shall be installed
4) It is strongly recommended to install stop valves at hot at chilled and cooling water inlet/outlet. Note
water inlet and outlet pipe. Air relief valves shall be installed on each chilled and is field wiring at the site after
5) The locations of chilled water pumps, cooling water cooling water lines at higher points than each water completion of chiller installation
pumps and expansion tanks shall be determined in header.
consideration of the hydrostatic head of pumps and the Drain valves shall be installed at the lowest position
height of building. And the Machine shall not be subject to between the stop valves of chilled and cooling water and
a pressure higher than the designed pressure at any the Machine and the drain valve shall be piped to the
water header. drain ditch.
6) For cooling water quality control, it is recommended to
install cooling water bleed-off device on the inlet pipe line
8) There shall be a sufficient clearance for access to the
absorber, evaporator, condenser, and generator to
Hot Water Driven Type
of cooling towers. facilitate inspection and cleaning work. TB1 TB4 TB6

Cooling Water Quality Control R S T GND 246 247 GND 272 273 400 401 403 404 406 407 500 501 502 503 504 505 506 507 508 509

The cooling water which is recycled by cooling tower is Therefore, it is recommended to control the water quality;
exposed into atmosphere and polluted as it is vaporized. If the following table shows guideline for cooling water and

52CH

52CO
AX1
the cooling water gets polluted, it develops corrosion and make-up water. The tube cleaning method and interval
also scale inside the tubes and Absorption Machine depends on each water quality.

FEEDBACK SIGNAL (4~20mADC)


HOT WATER CONTROL 3 WAY VALVE

HOT WATER CONTROL 3 WAY VALVE


OUTLET SIGNAL (0~10 VAC)

COOLING WATER PUMP

COOLING WATER PUMP


CHILLED WATER PUMP

CHILLED WATER PUMP

COOLING TOWER FAN


performance drops.

REMOTE S TART/STOP
3 PHASE
Tendency POWER
Items Cooling Water Make-up Water

ALARM SIGNAL
Corrosion Scale

START SIGNAL

RUN SIGNAL

RUN SIGNAL

RUN SIGNAL
INTER LOCK

INTER LOCK
PH (25°C) 6.5 ~ 8.0 6.5 ~ 8.0
Conductivity (25°C, s/cm) Max. 800 Max. 200
Chloride ion CI (mg / cI / ) Max. 200 Max. 50
Standard Sulfuric acid ion SO42-(mg CaCo3 / ) Max. 200 Max. 50
Alkalinity pH4.8 (mg CaCo3 / ) Max. 100 Max. 50
Total hardness (mg CaCO3 / ) Max. 200 Max. 50 FROM USER'S MCC TO USER'S MCC
Iron Fe (25°C) Max. 1.0 Max. 0.3

Reference
Sulfides S2- ion (ms S2-/ ) No trace No trace Note
Ammonium ion NH4+ (mg NH4+/ ) Max. 1.0 Max. 0.2 is field wiring at the site after
HOT WATER 3 WAY VALVE
Silica SiO (mg SiO2 / ) Max. 50 Max. 30 completion of chiller installation
CONTROL

World Energy Co. World Energy Co.