: 56 :

15.2. The order of the display should be as follows :


15.2.1. Mode I :
1) LCD check.
2) Meter serial number.
3) Real time and date.
4) Voltage sequence.
5) Phase Association.
6) Instantaneous Voltage and signed currents phase wise.
7) Instantaneous frequency.
8) Signed Instantaneous KW.
9) Instantaneous KVA.
10) Signed Instantaneous KVAR (with Lead / Lag)
11) Instantaneous PF (with lead/Lag ).
12) Cumulative import active energy and all TOD active energy
13) Cumulative import reactive energy (lag) 24 hours register
14) Cumulative import reactive energy (lead) 24 hours register
15) Cumulative import apparent energy 24 hours register
16) Average Power factor import for current billing period.
17) Import KVA MD with all TOD for the current billing period.
18) Cumulative Import KVA MD
19) Cumulative export active energy and all TOD active energy.
20) Cumulative export reactive energy (lag) 24 hours register
21) Cumulative export reactive energy (lead) 24 hours register
22) Cumulative export apparent energy 24 hours register
23) Average Power factor export for current billing period.
24) Export KVA MD with all TOD for the current billing period.
25) Cumulative Export KVA MD
26) Last block average frequency (Import & Export)
27) Net kVArh High.
28) Net kVArh Low.
29) Nature of present tamper with date & time.
30) Total number of tamper counts.
31) Reset count.

Note:
1. The above 31 parameters with current readings available in the BCS., end during
downloading.
2. Net Reactive Energy Resisters reset to zero during MD Reset.
15.2.2. Mode II :

1) Reset (Previous month) import/export active energy with all TOD readings.
2) Reset import/export reactive energy lag
3) Reset import/export reactive energy (lead)
4) Reset import/export apparent energy
5) Reset import/export power factor.
6) Reset import/export KVA MD with all TOD reading.
7) Cumulative kVArh High.
8) Cumulative kVArh Low.
9) Cumulative programming count.
10) Voltage failure count.
11) Current failure count
12) Voltage unbalance count
13) Current unbalance count
: 57 :

15.2.3. Mode III : (Test mode display)


1) High Resolution total kWh Import.
2) High Resolution total kVArh Import Lag.
3) High Resolution total kVArh Import Lead.
4) High Resolution total kVAh Import.
5) Rising Demand Import kVA with elapsed time (simultaneously displayed)
6) High Resolution total kWh Export.
7) High Resolution total kVArh Export Lag.
8) High Resolution total kVArh Export Lead.
9) High Resolution total kVAh Export.
10)Rising Demand Export kVA with elapsed time (simultaneously displayed)
11)Average Frequency for 15 minutes present integration period.

All energy parameters shall have resolution of 6 decimal places.

ABT BILLING DATA:

Following parameters shall be stored in non volatile memory automatically as ABT DATA.

1. Average frequency for each successive 15 min block .

2. Cumulative kWh at each midnight in seven digits including two


decimal.

3. Cumulative kVArh for Voltage HIGH condition (>103%) at each


midnight in seven digits including two decimal.

4. Cumulative kVArh for Voltage LOW condition (<97%) at each


midnight in seven digits including two decimal.

Note: Net Reactive Energy HIGH ={(Export Lag + Import Lead) (Import Lag
+ Export Lead)}

Net Reactive Energy LOW ={(Import Lag + Export Lead) (Export Lag
+ Import Lead)}

15.3. THE DISPLAY OF THE ABOVE PARAMETERS SHOULD APPEAR IN THE SAME
ORDER AS INDICATED ABOVE.