Sie sind auf Seite 1von 6

776 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO.

2, MAY 2004

Quasi-Coupled Three-Phase Radial Load Flow


Esther Romero Ramos, Antonio Gmez Expsito, and Gabriel lvarez Cordero

AbstractIgnoring mutual coupling in three-phase load-flow anced networks demands for as fast as possible load-flow sub-
computations saves a lot of computational effort but provides routines.
inaccurate results for many applications. In this paper, the effect As discussed in [23], most voltage and current imbalance is
of mutual coupling is taken into account through equivalent
branch voltage sources or bus current injections. This simple idea due to unbalanced loading, the network asymmetry being much
allows accurate enough solutions to be obtained, while much of less important. Partly because of this, ignoring mutual coupling
the computational saving associated with decoupled load flows and running three separate single-phase load flows usually pro-
is retained. Experiments on several unbalanced networks are vides satisfactory results. This strategy is, however, unaccept-
reported showing the performance of the proposed idea when able when exact solutions are sought.
applied to distribution load flows based on the forward/backward
tree sweeps. In this paper, a methodology is presented from which sev-
eral phase-decoupled distribution load-flow schemes can be de-
Index TermsDistribution networks, three-phase load flow, un- veloped. The basic idea lies in modeling the effect of mutual
balanced loads.
coupling as branch voltage sources or additional bus injections,
rather than neglecting it. This makes phase decoupling compat-
I. INTRODUCTION ible with accurate results but still much less expensive than full
three-phase computations.
B OTH at operational and planning stages, the load-flow
tool constitutes the cornerstone of many important ap-
plications. Efficient and reliable load-flow solutions, such as
The paper is organized as follows. Section II briefly reviews
electrical models associated with distribution feeders and the
the NewtonRaphson [1] and the fast decoupled load flow two major categories of load-flow methods. Section III presents
[2], have been widely used in transmission systems. It has the proposed idea and discusses possible ways of applying it
long been known, however, that these techniques may present to existing load flows. Finally, test results are provided in Sec-
convergence problems when applied to certain distribution net- tion IV.
works, owing to their distinctive features (higher ratios,
radial or weakly meshed topology, high ratio of long-to-short II. BACKGROUND
line reactance for lines incident to the same bus). Distribution systems consist of unbalanced three-phase
Consequently, load-flow techniques specially designed for feeders from which two- and single-phase laterals are usually
distribution networks have been developed. References [3][15] tapped off. In this situation, one-line equivalent models do not
constitute examples of such load-flow methods intended for ra- constitute accurate representations.
dial networks. Most of them take full advantage of the radial The impedances for overhead and underground lines can be
topology to save computation time. Some of these techniques calculated in a very accurate form using Carsons equations.
are also suitable for weakly meshed cases [4][9], [12][15], Carsons original equations can be reduced to a much simpler
and/or voltage-dependent loads [4], [5], [9], [10], [12][14]. and easy to use form, known as modified Carsons equations,
Most published methods are suitable to perform three-phase with no significant loss of accuracy [24]. When modified
simulations. This is of interest particularly in the U.S., where Carsons equations are used, a 4 4 primitive impedance
many single-phase laterals and service transformers exist, but matrix results for an overhead four-wire grounded-wye line
also in those cases where balanced networks feed significantly section. In the same way, for an underground grounded-wye
unbalanced loads. In addition to the increased data and model line segment consisting of three concentric neutral cables, a
complexity, three-phase load flows involve much more com- 6 6 matrix will result [24].
putational effort than three single-phase load flows. This com- For most applications, the primitive impedance matrix needs
putational effort becomes critical when the load flow is run to be reduced to a 3 3 phase-frame matrix consisting of the
many times, as happens, for instance, in service restoration [16], self- and mutual-equivalent impedances for the three phases (see
feeder reconfiguration [17], [18], phase balancing [19], [20], Fig. 1). A standard method to do that is the Krons reduction
volt/var control [21], optimal location of capacitors [22], etc. [25]. In this case, the assumption is made that the line has a
The application of such complex optimization tools to unbal- multigrounded neutral. So, the final form of the Krons reduc-
tion technique allows relating bus voltages with branch currents
by means of the following equation:
Manuscript received June 12, 2003.
E. R. Ramos and A. G. Expsito are with the Electrical Engineering De-
partment, University of Sevilla, Sevilla 41092, Spain (e-mail: eromero@us.es;
age@us.es).
G. . Cordero is with REE, Madrid, Spain (e-mail: galvarez@ree.es).
(1)
Digital Object Identifier 10.1109/TPWRS.2003.821624

0885-8950/04$20.00 2004 IEEE


RAMOS et al.: QUASI-COUPLED THREE-PHASE RADIAL LOAD FLOW 777

Fig. 1. Three-phase branch section between buses i and j .

The above coupled model constitutes the building block


of any computational method that simultaneously analyzes Fig. 2. Modeling of branch coupling by a voltage source.
the three phases and their interactions (mutual coupling).
Broadly speaking, there are two kinds of three-phase load-flow
techniques, namely
1) methods formally applying the NewtonRaphson itera-
tive scheme which, at each iteration, solves a system of
the form

(2)

Usually, but not necessarily, comprises the bus


voltage corrections in polar coordinates and repre-
sents some form of the power [26] or current mismatches
[9], [27];
2) methods taking advantage of the radial structure to avoid
explicitly storing and factorizing any matrix. A back-
ward sweep first estimates branch currents (or powers)
followed by a forward-voltage-updating procedure that
applies (1) [3], [15].
Among the main benefits of three-phase analysis, by far the Fig. 3. Voltage-source to current-source transformation followed by
largest in terms of general accuracy is representation of un- current-source shift.
balanced loading and configuration. However, some models of
electrical behavior used in distribution planning and operation are the additional voltage drops originated by the mutual cou-
neglect mutual coupling by assuming all off-diagonal terms in pling. These voltage sources , in series
(1) as zero with the impedances , are represented in Fig. 2.
It can be shown that every voltage source in series with
the impedance is equivalent to a pair of equal but opposite
(3)
current sources, one entering node and the other leaving node
, whose value is
In this approach (see [23]), a one-line load-flow algorithm is
used to compute voltages and currents on each of the three (5)
phases individually, as if the other two did not exist. This greatly
reduces complexity of data and computation, but introduces no- Fig. 3 represents, for phase , the circuit transformations sug-
ticeable inaccuracies, particularly when representing rural dis- gested above.
tribution systems. Notice that, at a nonterminal node, the total current injection
due to mutual coupling will be the contribution of outcoming
III. PROPOSED METHODOLOGY branches minus that of the incoming branch. Fig. 4 illustrates
this idea for a 3-branch system (only one phase is shown).
Equation (1) can be rewritten as follows:
An improvement to the conventional decoupled approach de-
scribed in the previous section can be achieved by using the
ideas presented above. Depending on the load-flow technique
adopted, two different schemes can be considered.
(4) 1) Methods explicitly solving an equation system. In terms
where of phases, rather than buses, the block structure of (2) is

(6)
778 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 2, MAY 2004

Fig. 5. The 10-node system three-phase diagram.

Fig. 4. Current injections accounting for mutual coupling for a 3-branch


system.

The procedure presented in this section allows writing (6)


as

(7)

where the right-hand side vector has been modified to ac-


count for the mutual network terms, that is, the equiva-
lent bus current injections (note that, in [14], off-diag-
onal blocks are simply ignored). Two possibilities arise to Fig. 6. The 25-node system three-phase diagram.
solve (7), namely: 1) The current mismatch vector is si-
multaneously computed for the three-phases; 2) The cur-
rent mismatch vector is sequentially computed for each
phase and the respective equation is solved. As the so-
lution of each phase benefits from previously updated
bus voltages, better convergence rates are expected for
the second approach (the number of iterations could be
even smaller than that of the three-phase conventional
solution).
This category of solution methods is currently being
investigated and will not be further pursued in this paper.
Note, however, that, if convergence does not significantly
deteriorate, large computational savings are expected as
a consequence of three 2N 2N equation systems, com-
prising 12N nonzero elements each, being solved, instead Fig. 7. The 1007-node system single-phase diagram.
of a 6N 6N system containing 108N nonzero elements.
2) Methods exploiting the radial structure. In this case, The key idea consists of starting with a certain
there is no need to perform the voltage-source to cur- number of fully decoupled forward sweeps. Then,
rent-source transformation. The backward sweep first a single exactly coupled forward sweep is carried
estimates branch currents as usual, while three arrange- out, followed by the required number of approx-
ments are possible for the forward sweep: imately coupled forward sweeps to achieve con-
Fully decoupled: (3) is solved so that no mutual vergence. If the exact forward sweep is performed
coupling is taken into account. too late, then extra iterations may be required. If it
Exactly coupled: Voltages are updated by means of is applied from the very beginning, then the values
(1). Branch voltage sources, , are saved for may not be accurate enough.
future use. Since the forward sweeps resort to the respective
Approximately coupled: (4) is applied. Instead of re- 3 3 branch impedance matrix to update the
computing the terms , they are retrieved from next bus voltages, without actually building the
a previous iteration. whole network Jacobian, the computational saving
RAMOS et al.: QUASI-COUPLED THREE-PHASE RADIAL LOAD FLOW 779

TABLE I
NUMBER OF ITERATIONS, COMPUTATIONAL EFFICIENCY, AND RELATIVE ERRORS

TABLE II
LARGEST COMPONENT OF THE POWER MISMATCH VECTOR
FOR THE 1007-BUS SYSTEM

TABLE III
LARGEST COMPONENT OF THE POWER MISMATCH VECTOR
FOR THE 13-BUS SYSTEM

Fig. 8. Voltage magnitude profile along the lateral leading to the terminal bus
1028 (phase b) for the 1007-bus system.

(a) only the first forward sweep is fully decoupled;


(b) the first two forward sweeps are fully decoupled.
Results corresponding to the following unbalanced systems
will be reported:
A 8.66-kV, 10-node system whose three-phase diagram
is shown in Fig. 5 (both the electrical data and the exact
solution are included in the Appendix). While the three-
phase branch sections of this system are symmetrically
Fig. 9. Voltage magnitude profile along the lateral leading to the terminal bus coupled, all bus loads are quite unbalanced. In addition,
675 (phase b) for the 13-bus system.
large voltage drops are expected, particularly at phase
which feeds a total load of 450 kW.
attained by the adopted solution may be not so
A 13-node system downloaded from [28]. This IEEE
dramatic as in 1).
test system comprises several load types and a regulating
transformer. As we have not developed a fully featured
IV. TEST RESULTS commercial code, its tap settings have been assigned their
In this section, scheme 2) described above, based on a com- converged values. Also, branch shunt susceptances are
bination of different forward/backward sweeps, will be tested ignored which, according to [24], provides virtually exact
and compared with both an exact three-phase load flow [15] and results.
its fully decoupled counterpart. Two versions of the proposed A 4.16-kV, 25-node system reported in [4] (see the three-
methodology will be applied: phase diagram in Fig. 6). This network comprises unsym-
780 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 2, MAY 2004

TABLE IV
NUMBER OF ITERATIONS, COMPUTATIONAL EFFICIENCY AND RELATIVE ERRORS FOR THE 1007-BUS SYSTEM AND DIFFERENT LOAD FACTORS

metrical branch sections but the loading level is not as high TABLE V
as in the previous cases. LOADS (kW AND kVAR) FOR THE 10-NODE SYSTEM
A 13.8-kV, 1007-node real system whose one-line dia-
gram is shown in Fig. 7.
Table I collects the most important figures obtained when
solving the above networks on a 933-MHz, 128-Mb PC. For the
exact method, both the number of iterations and absolute execu-
tion times are provided. For the approximate methods, from left
to right, the number of iterations, relative computational saving
and largest voltage magnitude error are given. Relative compu-
tational saving, defined as

3) Version (b) of the proposed scheme takes more time than


version (a), because of the extra iteration required for con-
refers to the whole iterative process. Percentages shown are vergence in all tested cases.
the average of several runs, as individual execution times are Table IV expands, for the 1007-bus system, the data presented
slightly different under Windows. The convergence threshold is in Table I by increasing each bus load proportionally. Apart from
for all experiments reported in Table I. the larger number of iterations, the above comments still apply.
Figs. 8 and 9 represent the voltage magnitude profile along A noteworthy difference arises for the last two cases, where ver-
the lateral and phase leading to largest errors, for the 1007-bus sion (b) of the proposed methodology takes less iterations and
and 13-bus systems, respectively. It can be observed in Fig. 8 provides more accurate results than version (a). This suggests
that, because of the coupling, voltage magnitudes start to rise that computation of voltage sources modeling branch coupling
from a given bus to the lateral end. This effect is neglected by should be delayed under stressed conditions until better branch
the fully decoupled method, which explains the resulting larger currents are available.
errors.
Tables II and III present, for the same two systems, the largest
component of the power mismatch vector at the end of each V. CONCLUSIONS
iteration. These two systems constitute extreme cases, both from A well-known approach to approximately computing
the point of view of convergence rate and imbalance. Note that three-phase load flows is based on ignoring the mutual cou-
convergence rate for the 13-bus network is nearly lineal. pling among phases so that three separate single-phase load
From the results presented above, the following conclusions flows can be run. However, the results provided by this proce-
can be reached. dure may not be accurate enough in certain circumstances.
1) The proposed quasicoupled methodology is about two or- This paper further explores the possibilities for a phase-de-
ders of magnitude more accurate than the fully decoupled coupled methodology to be applied to unbalanced distribution
approach. Voltage magnitude errors are abnormally large networks without losing accuracy. With this goal in mind, a pro-
for the 13-bus system, also requiring more iterations to cedure is proposed by which the mutual terms are accounted for
achieve convergence. by adding equivalent current injections to each bus or inserting
2) About 40% computational saving can be obtained with voltage sources in series with each branch. Bus current injec-
version (a) of the proposed methodology, compared to the tions are more appropriate when NewtonRaphson-based load
50% reduction achieved by the fully decoupled algorithm, flows are employed, while branch voltage sources are preferable
which cannot guarantee accurate enough results. These when forward/backward sweeps are adopted.
figures do not apply to the 13-bus system, constituting Finally, several results are provided so as to numerically as-
probably one of the hardest test cases for any load-flow sess the accuracy and efficiency of the approximately coupled
algorithm. methodology discussed in the paper.
RAMOS et al.: QUASI-COUPLED THREE-PHASE RADIAL LOAD FLOW 781

TABLE VI [14] W.-M. Lin, Y.-S. Su, H.-C. Chin, and J.-H. Teng, Three-phase unbal-
SELF AND MUTUAL IMPEDANCES (
) FOR THE 10-NODE SYSTEM anced distribution power flow solutions with minimum data prepara-
tion, IEEE Trans. Power Syst., vol. 14, pp. 11781183, Aug. 1999.
[15] C. S. Cheng and D. Sjirmohammadi, A three-phase power flow method
for real-time distribution system analysis, IEEE Trans. Power Syst., vol.
10, pp. 671679, May 1995.
[16] K. N. Miu et al., Fast service restoration of large-scale distribution sys-
tems with priority customers and constraints, IEEE Trans. Power Syst.,
vol. 13, pp. 789795, Aug. 1998.
[17] A. B. Morton and I. M. Y. Mareels, An efficient-brute force solution
to the network reconfiguration problem, IEEE Trans. Power Delivery,
vol. 15, pp. 9961000, July 2000.
TABLE VII [18] V. Borozan, D. Rajicic, and R. Ackovski, Minimum loss reconfigu-
EXACT SOLUTION FOR THE 10-NODE SYSTEM ration of unabalanced distribution networks, IEEE Trans. Power De-
livery, vol. 12, pp. 435442, Jan. 1997.
[19] J. Zhu, G. Bibro, and M.-Y. Chow, Phase balancing using simulated
annealing, IEEE Trans. Power Delivery, vol. 14, pp. 15081513, Nov.
1999.
[20] T. H. Chen and J. T. Cherng, Optimal phase arrangement of distribution
transformers connected to a primary feeder for system unbalance im-
provement and loss reduction using a genetic algorithm, IEEE Trans.
Power Syst., vol. 15, pp. 9941000, Aug. 2000.
[21] M. E. Baran and M.-Y. Hsu, Volt/Var control at distribution systems,
IEEE Trans. Power Syst. , vol. 14, pp. 312318, Feb. 1999.
[22] M. T. Bishop and R. E. Lee, Distribution system line loss reduction
trough enhanced capacitor location techniques, IEEE Trans. Power
Syst., vol. PS-1, pp. 190197, Apr. 1986.
[23] H. L. Willis, Power Distribution Planning: Reference Book. New
York: Marcel Dekker, 1997.
[24] W. H. Kersting, Distribution System Modeling and Analysis. Boca
APPENDIX Raton, FL: CRC Press, 2002.
[25] G. Kron, Tensorial analysis of integrated transmission systems, Part I,
See Tables VVII. the six basic reference frames, AIEE Trans., vol. 71, 1952.
[26] H. L. Nguyen, NewtonRaphson method in complex form, IEEE
Trans. Power Syst., vol. 12, pp. 13551359, Aug. 1997.
REFERENCES [27] A. G.A. Gmez Expsito and E. R.E. Romero Ramos, Augmented
[1] W. F. Tinney and C. E. Hart, Power flow solution by Newtons method, rectangular load flow model, IEEE Trans. Power Syst., vol. 17, pp.
IEEE Trans. Power App. Syst., vol. PAS-86, pp. 14491460, 1967. 271276, May 2002.
[2] B. Stott and O. Alsac, Fast decoupled load-flow, IEEE Trans. Power [28]. [Online]. Available: http://ewh.ieee.org/soc/pes/dsacom/testfeeders.html
App. Syst., vol. PAS-93, pp. 859869, 1974.
[3] W. H. Kersting, A method to teach the design and operation of distri-
bution system, IEEE Trans. Power App. Syst., vol. 103, no. PAS-7, pp.
19451952, July 1984.
[4] S. K. Goswami and S. K. Basu, Direct solution of distribution systems, Esther Romero Ramos was born in Spain in 1967. She received the electrical
Proc. Inst. Electr. Eng. C, vol. 138, Jan. 1991. engineering and Dr.Eng. degrees in 1992 and 1999, respectively, from the Uni-
[5] T.-H. Chen et al., Distribution system power flow analysisa rigid versity of Sevilla, Sevilla, Spain.
approach, IEEE Trans. Power Delivery, vol. 6, pp. 11461152, July From 1992 to 1993, she was with Sainco, Sevilla, Spain. Since 1993, she
1991. has been with the Department of Electrical Engineering, University of Sevilla,
[6] D. Shirmohammadi, H. W. Hong, A. Semlyen, and G. X. Luo, A com- Sevilla, Spain, where she is currently an Associate Professor. She is interested
pensation-based power flow method for weakly meshed distribution and in state estimation, load-flow problems, and analysis and control of distribution
transmission networks, IEEE Trans. Power Syst., vol. 3, pp. 753762, systems.
May 1988.
[7] G. X. Luo and A. Semlyen, Efficient load flow for large weakly meshed
networks, IEEE Trans. Power Syst., vol. 5, pp. 13091316, Nov. 1990.
[8] D. Rajicic, R. Ackovski, and R. Taleski, Voltage correction power
flow, IEEE Trans. Power Delivery, vol. 9, pp. 10561062, Apr. 1994. Antonio Gmez Expsito was born in Spain in 1957. He received the electrical
[9] P. A. N. Garca, J. L. R. Pereira Jr., S. Carneiro, V. M. da Costa, and N. engineering and Dr.Eng. degrees from the University of Sevilla, Sevilla, Spain.
Martins, Three-phase power flow calculations using the current injec- Since 1982, he has been with the Department of Electrical Engineering, Uni-
tion method, IEEE Trans. Power Syst., vol. 15, pp. 508514, May 2000. versity of Sevilla, where he is currently a Professor and Head of the Department.
[10] R. G. Cspedes, New method for the analysis of distribution networks, His primary areas of interest are sparse matrices, load flow, reactive power op-
IEEE Trans. Power Delivery, vol. 5, pp. 391396, Jan. 1990. timization, state estimation, and computer relaying.
[11] A. G.A. Gmez Expsito and E. R.E. Romero Ramos, Reliable load
flow technique for radial distribution networks, IEEE Trans. Power
Syst., vol. 14, pp. 10631069, Aug. 1999.
[12] E. R.E. Romero Ramos and A. G.A. Gmez Expsito, A general-pur-
pose load flow technique for balanced distribution networks, in Gabriel lvarez Cordero was born in Spain in 1969. He received the electrical
IASTED Conf., Marbella, Spain, Sept. 2000. engineering degree in 1998 from the Univeristy of Sevilla, Sevilla, Spain.
[13] R. D. Zimmerman and H. D. Chiang, Fast decoupled power flow un- From 1998 to 2000, he was with Isotrol, Sevilla, Spain, and from 2000 to
balanced for radial distribution systems, IEEE Trans. Power Syst., vol. 2003, he was with Norcontrol, Madrid, Spain. Since 2003, he has been with
10, pp. 20452052, Nov. 1995. REE, Madrid, Spain. He is interested in three-phase load-flow problems.

Das könnte Ihnen auch gefallen