Beruflich Dokumente
Kultur Dokumente
Outlines
1
20/09/2017
Generation System
13.8 kV 15.6 kV
Transmission System
132 kV 500 kV
Distribution System
11 kV 66 kV
Panelboard
Feeding
240/415V
Harmonic Loads
2
20/09/2017
Source: Siemens
3
20/09/2017
4
Simple High Low Favorable
structure reliability losses and
of supply flexible
expansion
options
4
20/09/2017
10
5
20/09/2017
11
Sub-transmission Line
(66kV or 33kV) Distribution
Substation
Primary Secondary
Substation Substation 3 Phase
Consumers
11kV Feeder (415V)
Industrial
Consumer
12
6
20/09/2017
14
7
20/09/2017
16
8
20/09/2017
17
Voltage Criteria
Steady-State Voltage Fluctuation (Normal Condition):
Voltage level % variation
415 V and 240 V -10% & +5%
6.6 kV, 11 kV, 22 kV,33 kV +/- 5%
132 kV and 275 kV -5% & +10
18
9
20/09/2017
Low Voltage:
Single-phase, two-wire, 240V, up to 12 kVA maximum
demand
Three-phase, four-wire, 415V, up to 45 kVA maximum
demand
Three-phase, four-wire, C.T. metered, 415V, up to
1,000 kVA maximum demand
19
20
10
20/09/2017
Frequency Criteria
The supply frequency is 50 Hz 1%
21
22
11
20/09/2017
23
24
12
20/09/2017
25
26
13
20/09/2017
CB4 CB5
Distribution Distribution
Substation 2 Substation 3
CB3 CB6
A
CB2 CB1 Distribution
Substation 1
27
28
14
20/09/2017
29
30
15
20/09/2017
31
32
16
20/09/2017
33
34
17
20/09/2017
Radial System
In this system, the LV distribution lines radiate out from
the distribution substation.
Radial Line 1
LV CB Switch-cum
Fuse Units
11 kV Line
220 kVA 11 Radial Line 2
kV/415V
35
36
18
20/09/2017
Looped System
In this case, the reliability of supply is better than in the
radial system. In the case of fault on one line, the load
can be fed from the other by connecting switch S.
415/240 V
CB
S
11 kV Line
220 kVA 11
kV/415V
415/240 V
38
19
20/09/2017
T1 T2 T3 Fuse
39
20
20/09/2017
41
42
21
20/09/2017
43
44
22
20/09/2017
45
46
23
20/09/2017
47
Cooling
3 N 15 12 0.7 17.1 17.1
tower 1 fan
Cooling
3 S 15 12 0.7 17.1 -
tower 2 fan
Heater 3 N 5 - - - 5 5
24
20/09/2017
50
25
20/09/2017
51
TASK
Decide the proper supply voltage from local utility
52
26
20/09/2017
53
Delta at primary
Free of 3rd harmonics of the magnetising currents and
any possible homopolar current are free to circulate
through the sides of the delta, without flowing into the
network; thus, the magnetic fluxes remain sinusoidal
at the secondary.
In case of unbalanced loads at the secondary
winding, the reaction current absorbed by the primary
flows only through the corresponding winding (as
shown in the figure) without affecting the other two.
54
27
20/09/2017
55
56
28
20/09/2017
57
58
29
20/09/2017
59
60
30
20/09/2017
TASK
Design a simple power system (one-line diagram)
61
62
31
20/09/2017
63
64
32
20/09/2017
65
Infinite source
FLA = ?
What is %Z?
1000 kVA
ISCmax = ?
11kV 415 V
kVASC = ?
%Z = 5%
kVASC = ?
66
33
20/09/2017
500 MVASC
MVASC(TX) = ?
1000 kVA MVASC(SEC) = ?
11kV 415 V ISCmax = ?
%Z = 5%
kVASC = ?
67
FLA = ?
1000 kVA ISCmax = ?
11kV 415 V kVASC = ?
%Z = 5.0%
kVASC = ? Is the given size (1000
kVA) suitable to serve
the motor load?
68
34