Phoenix Controls temperature and humidity sensors provide a stable, secure environment for those facilities that need it the
most, such as hospitals, cleanrooms, and laboratory animal facilities. These sensors also simplify room balancing by
eliminating the need for a certified person to accompany the balancer during the commissioning process.
PTS300 Temperature Sensor with Display, PCS300 CombinationSensor with PHS300 Humidity Sensor
Override and Setpoint Setpoint Display Override
Phoenix Controls PTS300 is a room temperature sensor. The PTS300-OS, PTS300-DOP and PTS300-DOS have both override
and setpoint. The PTS300-DOS features a large LCD display, slider setpoint adjustment, and pushbutton override. The PTS300-
DOP features a large LCD display, pushbutton setpoint adjustment, and pushbutton override.
The PHS300 room sensor is available as a humidity transmitter only without display.
Phoenix Controls PCS300 is a multiple output transmitter for temperature and humidity with setpoint capability and occupied/
unoccupied override switching. The large easy-to-read display is ideal for cross room viewing and membrane pushbuttons are
designed for easy operation and cleaning.
A fully featured unit can have three active channel outputs, override, and a passive sensor output. All ranges are factory set, however
each temperature and humidity sensor channel has a local offset adjust for fine tuning. The display can be locally customized to the
customers preference.
TABLE OF CONTENTS
Specifications ................................................... 2
Ordering Guide................................................ 3
Valid Catalog Numbers .................................... 4
Features and Applications................................. 6
Dimensions ...................................................... 7
Maintenance .................................................... 8
Troubleshooting ............................................... 8
Output Tables ................................................ 10
75 Discovery Way Acton, MA 01720 Tel (978) 795-1285 Fax (978) 795-1111 www.phoenixcontrols.com
2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15 MKT-0165 MPC-2190 TEMPERATURE AND HUMIDITY SENSORS 1 OF 12
SPECIFICATIONS
Combination
Temperature Humidity
Supply Voltage 9 to 40 Vdc (LCD only) Not Used 15 to 35 Vdc 10 to 35 Vdc 10 to 35 Vdc
(current or
NOTE: Use of PVC350-HW is voltage output)
required for LON applications
Operating Temperature Range 32 to 122F -40 to 212F 32 to 122F -22 to 158F -22 to 158F
(0 to 50C) (-40 to 100C) (0 to 50C) (-30 to 70C) (-30 to 70C)
2 OF 12 TEMPERATURE AND HUMIDITY SENSORS MKT-0165 MPC-2190 2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15
ORDERING GUIDE
PHS 300 - P
PTS 300 - P - N - 1
PTS 300 - Q - D O S - 3
PCS 305 - Z - D H O P 8 - 2
FAMILY
PTS300 PHS300 PHS220 PCS320 PCS310 PCS305 PCS300 PCS220 SENSOR TYPE
PTS300 PHS300 PHS220 PCS320 PCS310 PCS305 PCS300 PCS220 SENSOR LOCATION
- - - - - - D = Duct
- - - - - - O = Outside
- - - - - P = Room, Phoenix enclosure: white
- - - - - Q = Room, Phoenix enclosure: simulated stainless steel
- - - - - Z = Room, Stat3 enclosure
PVC 350 HW
PRODUCT FAMILY
PVC = Phoenix Voltage Converter
UNIT TYPE
350 = 350 mA maximum load
RECTIFICATION
HW = Half-wave
2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15 MKT-0165 MPC-2190 TEMPERATURE AND HUMIDITY SENSORS 3 OF 12
VALID CATALOG NUMBERS
Catalog Number without Catalog Number with 1 Point Temperature Catalog Number with 3 Point Temperature and/
Calibration Certificate and/or Humidity Calibration Certificate or Humidity Calibration Certificate
PHX-TEMP-SENSOR
PHX-HUMID-SENSOR
PHX-COMBO-SENSOR
4 OF 12 TEMPERATURE AND HUMIDITY SENSORS MKT-0165 MPC-2190 2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15
Catalog Number without Catalog Number with 1 Point Temperature Catalog Number with 3 Point Temperature and/
Calibration Certificate and/or Humidity Calibration Certificate or Humidity Calibration Certificate
PCS305-Z-DHOP7 PCS305-Z-DHOP7-2 PCS305-Z-DHOP7-7
2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15 MKT-0165 MPC-2190 TEMPERATURE AND HUMIDITY SENSORS 5 OF 12
FEATURES AND APPLICATIONS
Temperature Sensors
Room Sensors
Phoenix Controls offers four types of room-mounted temperature sensors. Each sensor incorporates a 10 k thermistor that has an
accuracy of 0.36 F (0.2 C).
These options are available on room-mounted sensors:
The Phoenix enclosure can be used in wipe-down applications.
An LCD display is optional and offers readings to the tenth degree.
An override switch can be incorporated that allows the user to temporarily override the temperature setpoint.
Temperature setpoint adjustment is available in either a pushbutton or slider configuration.
Pushbutton operation allows the user to see a change in the setpoint on the display.
A setpoint slider offers a warm/cool scale and its setting is not indicated on the display.
Duct Sensors
Duct sensor information can be found in the PTS102 Temperature Sensor (Ducts) Product Data Sheet (MKT-0235).
6 OF 12 TEMPERATURE AND HUMIDITY SENSORS MKT-0165 MPC-2190 2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15
DIMENSIONS
Temperature Sensors
PTS300-X sensor only PTS300-X-OS with setpoint slider and PTS300-X-DOP with display, pushbutton
override setpoint, and override
Humidity Sensors
PCS300-X and PHS300-X sensor only PCS300-X-DOS with display, setpoint slider and PCS305-Z-DOP; PCS310-Z-DOP;
override and PCS320-Z-DOP with display, pushbutton
temperature setpoint, and override
NOTE: X = "P" Phoenix enclosure in white or "Q" Phoenix enclosure with simulated stainless steel overlay.
2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15 MKT-0165 MPC-2190 TEMPERATURE AND HUMIDITY SENSORS 7 OF 12
Outside Sensors Duct Sensors
(Humidity and Combination only) (Humidity and Combination only)
Duct Sensor information can be found in the PTS102 Temperature
Sensors Product Data Sheet (MKT-0235)
4.50 in.
(114.3 mm) 4.50 in.
(114.3 mm)
MAINTENANCE
Phoenix Controls sensors require no ongoing preventative maintenance. Once the field engineer has completed the field setup,
these units will provide years of continuous operation.
TROUBLESHOOTING
Temperature Sensors
Room Sensors
The controller reports a higher than A. Confirm that the input is set up correctly in the front-end software.
actual temperature
B. Verify that the wires are not physically shorted.
C. Check wiring for proper termination.
D. Verify that the sensor output is correct.
E. Verify that the sensor output is correct from (J2) pin 1 to pin 2.
F. Determine whether the sensor that is exposed to an external source is different from the
room environment (conduit draft).
The controller reports a lower than A. Confirm that the input is set up correctly in the front-end software.
actual temperature B. Verify that the thermistor is not physically open.
C. Check wiring for proper termination.
D. Verify that the sensor output is correct.
E. Verify that the sensor output is correct from (J2) pin 1 to pin 2.
F. Determine whether the sensor that is exposed to an external source is different from the
room environment (conduit draft).
The setpoint is not working correctly A. Verify that the setpoint output is correct from (J2) pin 5 to pin 6.
B. Verify that J4 and J5 are set up correctly.
C. Check wiring for proper termination.
The override is not working correctly A. Verify that the output from (J2) pin 3 to pin 4 is less than 50 ohms when S1 is used.
B. Check wiring for proper termination.
8 OF 12 TEMPERATURE AND HUMIDITY SENSORS MKT-0165 MPC-2190 2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15
TROUBLESHOOTING (CONTINUED)
The unit will not operate; the display is A. Check power supply/controller voltage supply.
not working. B. Disconnect sensor and check power wires for +15 to +24 Vdc power to the sensor.
The humidity reading is maximum 20 A. Make sure the sensor is installed properly and is not shorted.
mA or 5 Vdc or 100%. B. Quick Check:
Remove sensor. The readings should change toward 0%.
The humidity reading is minimum 4 mA A. Verify that the humidity sensor is installed.
or 0 Vdc or 0%.
B. Quick Check:
Short the sensor terminal block with a wire. The readings should change toward 100%.
The display will not toggle between Check Toggle Rate Adjustment pot on the back of the sensor, and make sure the adjustment is
temperature and humidity. correct according to the diagram below.
Settings:
Markings:
10-second cycle
10
3 20
T H Temperature only
The controller reports a higher than A. Confirm that the input is set up correctly in the front-end software.
actual temperature B. Verify that the wires are not physically shorted or open.
C. Check wiring for proper termination.
D. Disconnect wires and measure sensor resistance with an Ohm meter.
E. Verify that the sensor output is correct (see note below).
The controller reports a lower than A. Confirm that the input is set up correctly in the front-end software.
actual temperature B. Verify that the thermistor is not physically open or shorted.
C. Check wiring for proper termination.
D. Disconnect wires and measure sensor resistance with an Ohm meter.
E. Verify that the sensor output is correct (see note below).
NOTE: Measure the temperature at the sensors location using an accurate temperature standard. Disconnect the sensor wires and measure
the temperature sensors resistance with an Ohm meter. Compare the temperature sensors resistance to the Thermistor Output Table on page
10. If the measured resistance is different from the temperature table by more than 5%, call the Phoenix Controls Product Support Center.
2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15 MKT-0165 MPC-2190 TEMPERATURE AND HUMIDITY SENSORS 9 OF 12
OUTPUT TABLES
10 OF 12 TEMPERATURE AND HUMIDITY SENSORS MKT-0165 MPC-2190 2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15
F C Ohms F C Ohms F C Ohms
31 -0.56 33,599 107 41.67 4,981 183 83.89 1,109
%RH mA 5V %RH mA 5V
0 4.00 0.00 50 12.00 2.50
2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15 MKT-0165 MPC-2190 TEMPERATURE AND HUMIDITY SENSORS 11 OF 12
%RH mA 5V %RH mA 5V
39 10.24 1.95 89 18.24 4.45
12 OF 12 TEMPERATURE AND HUMIDITY SENSORS MKT-0165 MPC-2190 2002 Phoenix Controls. Specifications subject to change without notice. Rev. 8/15