Beruflich Dokumente
Kultur Dokumente
Users Manual
ACS800-307 and ACS800-507
Cabinet-installed Diode Supply Units (DSU)
ACS800 Multidrive Manuals
Users Manual
3AFE68279364 Rev C EN
EFFECTIVE: 01.09.2005
Table of Contents
Table of Contents
Hardware description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Overview of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single-line circuit diagram of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Layout view of the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Single-line circuit diagram of the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
One-module (size D4), six-pulse DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Two-module, six-pulse DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
One-module, twelve-pulse DSU / Two-module, twelve-pulse DSU . . . . . . . . . . . . . . . . . . . . . . 20
Three-module, twelve-pulse DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Single-line circuit diagrams of DSU modules D3 and D4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DSU module layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Block diagram: communications and measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Connections between the boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Diode Supply Main Board DSMB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Diode Supply Accessory Board DSAB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Diode Supply Connector Board DSCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Diode Supply System Board DSSB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Terminal blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Entering Settings and Diagnostics Mode of the panel, and reading and setting values . . . . 26
Digital input and relay output terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table of Contents
6
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Input power connection, cabinet-installed unit equipped with input fuses . . . . . . . . . . . . . . . . . . . 36
Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Six-pulse connection, two DSU modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Twelve-pulse connection, two DSU modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Connecting the input power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Input power connection, cabinet-instelled unit with no input fuses . . . . . . . . . . . . . . . . . . . . . . . . . 39
Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Six-pulse connection, two DSU modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Twelve-pulse connection, two DSU modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Connecting the input power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Use of the dual-cable screw lug connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Removal of the dual-cable screw lug connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Control connections to a cabinet-installed unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Connecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Start-up
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Installation check-list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Basic checks with no voltage connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Connecting voltage to input terminals and auxiliary circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Starting DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Checks with DSU started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
On-load checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Checking the cleanliness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cleaning the heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Replacing the air filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Checking the input power connections and DSU quick connector . . . . . . . . . . . . . . . . . . . . . . . . . 50
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Changing the fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table of Contents
7
Fault Tracing
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Status, fault and warning LEDs on module cover and on the external control board (DSSB) . . . . 53
Table of Contents
8
Table of Contents
9
Compatibility
The manual is compatible with the cabinet-installed Diode Supply Units ACS800-307
and ACS800-507. Some chapters are also valid for the ACS800-304 and
ACS800-704 diode supply modules.
Safety instructions
Follow all safety instructions delivered with the drive.
Read the complete safety instructions before you install, commission, use or
service the drive. The complete safety instructions are given in ACS800
Multidrive Safety Instructions [3AFE64760432 (English)].
Read the software function specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are
given in the section describing the related user-adjustable parameters.
Read task specific safety instructions before starting the task. See the section
describing the task.
Reader
The reader of the manual is expected to know the standard electrical wiring
practices, electronic components, and electrical schematic symbols.
Contents
How the Diode Supply Unit works
Hardware description
Electrical installation
Start-up
Maintenance
Fault Tracing
ACS800-307 and ACS800-507 technical data
ACS800-304 and ACS800-704 technical data
Example circuit diagrams
Other documents
User documentation of a multidrive delivery contains technical drawings and a set of
manuals. Technical drawings are tailor-made for each delivery. The composition of
the manual set depends on the composition of the drive.
The manuals are listed below. The codes refer to the original English manuals.
Manual Included in
ACS800-307 and ACS800-507 Cabinet-installed Diode Supply Unit Users delivery which
Manual includes the
corresponding
ACS800-207 Cabinet-installed IGBT Supply Unit Users Manual supply module
(3AFE 68233810)
etc.
Operation principle
The DSU is a half-controlled thyristor-diode rectifier. It rectifies three phase AC
current to direct current for the intermediate DC link of the drive. The intermediate
DC link is further supplying the inverter that runs the motor. There might be one
inverter only (single drive) or several inverters (multi drive) connected to the
intermediate circuit. The figure below shows the main circuit diagram of the diode-
thyristor rectifier.
+
V11 V13 V15 V21 V23 V25
iu
U1.1
V1.1
uvs
W1.1
Uc
U1.2
V1.2
W1.2
Thyristors (V11, V13, V15, V21, V23, V25) connect the AC line terminals in cyclic
sequence to the upper DC busbar (+). Diodes (V12, V14, V16, V22, V24, V26)
connect the AC terminals in cyclic sequence to the lower DC busbar (-). In the
normal steady-state operation with continuous current, each thyristor and diode
carries the current for a 120 period.
There are two control modes for the upper leg thyristor firing: the charging mode and
the normal mode. The charging mode is in operation a short period after the power
switch on: While the intermediate circuit capacitors located in the inverter module(s)
are charged, the thyristor firing angle is controlled from 270 to 0 degrees. In the
normal mode, the thyristor firing angle is 0 degrees: The thyristors operate as
diodes.
Six-pulse connection
Supply transformer DSU module
U1.1
V1.1
W1.1
U1.2
V1.2
W1.2
Twelve-pulse connection*
Supply transformer DSU module
W1.2
Shorter than power If DC voltage does not drop remarkably: DSU restarts rectifying
loss ride-through time - Diode bridge stays in normal operating mode. automatically.
- DSU keeps internal contactors energised.
Longer than power DSU stops and opens the main contactors. Operation continues
loss ride-through time only after manual
reset and restart.
Delay setting range is 0 to 40 seconds. For instructions on the setting, see chapter
Hardware description, page 26.
START
Is earth current
function active? 1) No
Yes
Is earth current
No above wake up level? 2)
Yes
Is fault trip
selection ON for the No
earth current function?
3)
Yes
DSU trips to a fault, illuminates DSU continues operation and DSU does not monitor earth
earth fault LED and energizes energizes relay output (earth current.
relay output (earth current current warning).
fault).
1) Function is inactive when the wake up level is set to NONE. See page 26.
2) See page 26 for setting/checking the wake up level of the earth current function.
3) See page 26 for the fault trip selection (ON = fault trip, OFF = warning).
Hardware description
Hardware description
16
B Incoming cubicle
See Layout view of the supply unit on page 18.
D Inverter cubicles:
See ACS800-107 Hardware Manual (3AFE68233453 [English])
Cubicle widths
A 600 mm
B 400, 500 or 600 mm (with switch-disconnector)
Drive with two-module, 600 or 1000 mm (with air circuit breaker)
six-pulse DSU C 400 mm (one module)
A B C D 600 mm (two modules)
Hardware description
17
M M
M M
M M
3~ 3~ 230/115 VAC
+24 VDC
400 VAC
230/115 VAC
Ground fault supervision Note: This diagram represents a drive with two
Voltage display of DSSB D4 DSU supply and two R8i inverters and two
brake chopper/resistor units (optional). No input
Motor fan supply (optional)
fuses or main switches/breakers are shown here.
Hardware description
18
9 9
5 5
4 4
10 10
6
6
3 3
Hardware description
19
B 7 C 10
6
Symbols refer to
descriptions given on Control circuitry
page 18. GE
ER N
EM
I
CY
DSSB
0 S
n A
2 STOP board 5
B C
U<
6 7 10
Supply
transformer 1
8
9
n
DC supply
3 for inverters
10
Symbols refer to
descriptions given on Control circuitry
page 18. GE
ER N
EM
I
CY
DSSB
0 S
2 n
STOP board 5 A
Hardware description
20
B C 10
7
9
1 n
DC supply
Supply for inverters
transformer
Symbols refer to
descriptions given on Control circuitry 10
page 18. 2
GE
ER N
EM
I
CY
0 S
DSSB n
STOP board 5 A
B U< C 10
6
7
8
9 n
B U< DC supply
for inverters
Supply
transformer
1 n
Symbols refer to
descriptions given on Control circuitry
page 18. GE
ER N
2
EM
I
CY
DSSB
0 S
n
STOP board 5 A
Hardware description
21
Q1 Q1
(optional) (optional)
K1 K1, K2
(optional) (optional)
L1 L1, L2
F1, F2 F1 - F4
Device Explanation
C1 Quick connector
F1 - F4 DC fuses
L1, L2 Chokes
M1 Fan
Q1 Switch-disconnector
Hardware description
22
AC 1
n
Q1
Aux. voltage
DSCB Aux. voltage DSSB-01
K1, K2 DSAB Fan failure
Over temp. failure
Over temp. warning
Ready
Current meas.
Supply phase missing
DC-fuse failure
Disconnector open
Disconnector closed
DSMB Contactors closed
Phase currents (6)
Charging Enable
Reset
Contactor control
DC
Hardware description
23
DSSB
DSAB
X500 X400
DSCB
X301
X304 X300
DSMB
-02
-01
X100
=
~
M
~
Fan motor
Hardware description
24
Display unit
Actual value display
Ready LED
On DSSB board
Auxiliary switches on cabinet
door, wired to DSSB
Operating switch (standard in
cabinet-installed units)
Fault reset button (standard in
cabinet-installed DSU)
Hardware description
25
Terminal blocks
X500 Ribbon cable to DSCB board via module quick connector
Hardware description
26
Entering Settings and Diagnostics Mode of the panel, and reading and setting values
Setting power loss ride- Switching fault trip on/off for Activating earth current func-
through time 1) earth current function 2) tion and setting wake-up
level 2)
Continues
Display
Mode
+
on next
page
Enter
Settings and autoexit (20 s.)
Diagn.
Mode
Set time in sec. (up and Select ON or OFF (down Select: NONE, 1, 2,
autoexit (20 s.) down keys) key) [A] (up and down keys)
Display
Mode
+ +
autoexit (2 s.)
autoexit (2s.)
+
Press up key
Display
Mode
Press down key
autoexit (2s.)
Direction of display change
Display
Mode
Setting accepted
1) For more information, see chapter How the Diode Supply Unit
works.
2) For more information, see chapter How the Diode Supply Unit
works.
Hardware description
27
continues
from previous Display
Mode
page
exit
+ +
Display Display
Mode Mode
Read status code (deci-
mal value) 5)
LED on
Earth cur- No. of
LED off rent value 6) modules 7)
3) No. of modules. DSSB needs the value for scaling the current output signal
connected to current meters on cabinet door (optional equipment).
4) After replacing a damaged contactor, reset the contactor fault information stored
onto the control board.
5) Consult ABB representative for information on codes.
6) Earth current peak value that the DSSB board monitors constantly when the
earth current function is active. VAC phase
balance
7) Number of parallel modules. DSSB board detects this automatically. Note: No.
[%] 8)
of modules must be given separately for the current output signal scaling.
8) 7599% = normal operation allowed, < 75% = DSU trips on a fault.
+ exit
Display
Mode
Hardware description
28
S11 S11
1 DSSB board terminals
1 3 ST
0 X10 Local digital inputs
1 START 0 -> 1: DSU closes main contactors and starts rectifying.
2 4
Note: Local ON input must be switched on.
1
0
1 2 ON 1: DSU is rectifying.1) 0: DSU stops rectifying and opens
START
contactors.
3
14
X2
0
1
6 +24 V +24 VDC
separate terminal block to which the user connections are to be made. See the
circuit diagrams delivered with the unit.
Hardware description
29
X4
1 -24V -24 VDC
2 +24V +24 VDC
3 Ground Ground
X8 Emergency stop input
1 EM +24V 0: Emergency stop
2 EM -24V 0: Emergency stop
Hardware description
30
Basic code
Digit no. Name Alternatives Description
5 380500 V
7 380690 V
Option codes
This is a common list for the ACS800 supply units. Not all options are available/used
for the Diode Supply Unit (ACS800-307or -507).
Heading Code Description
Input A012 Supply frequency 50 Hz
A013 Supply frequency 60 Hz
Degree of B052 IP21, UL type 1, NEMA 1
protection
B053 IP22, UL type 1, NEMA 1
B054 IP42, UL type 1, NEMA 1
B055 IP54, UL type 12, NEMA12
Construction C121 Marine construction
C128 Cooling air through bottom
C129 UL listed components
C130 Connection to air outlet duct
Filters E202 EMC/RFI filter for 1. environment, restricted distribution.
TN (grounded) power system.
E210 EMC/RFI filter for 2nd environment.
TN/IT (grounded/ungrounded) power system.
Line options F250 Line contactor
F253 Load break switch (OETL)
Hardware description
31
Hardware description
32
Hardware description
33
Basic code
Digit no. Name Alternatives Description
Option codes
Heading Code Description
Line options F250 Line contactor(s) inside
0F253 No load break switch(es) inside
Example
ACS800-704-0910-7+F250 means:
6/12-pulse supply module, frame D4
910 kVA apparent power rating (690 V)
380690 V nominal voltage
Supply module is equipped with load break switches (no selection +0F253 exists)
and main contactors.
Hardware description
34
Hardware description
35
Electrical installation
Electrical installation
36
Connection diagrams
Six-pulse connection, two DSU modules in parallel
PE PE
*) 1L1
L1 Switching,
1L2
L2 breaking,
1L3 disconnecting
L3
and grounding
**) devices ***)
Incoming cubicle
***)
Notes:
For details, see the delivery specific circuit diagrams. (Included in every delivery.) For cable selection
instructions, see ACS800 Multidrive, Planning the Electrical Installation (3AFE64783742 [English]).
*)
Fuses are not required if the input power line is constructed of busbars that withstand the transformer short
circuit current.
**)
The cable lead-through details (number and size of holes), and cable connection details (number and
dimensions of busbars, tightening torque) are given in chapter ACS800-307 and ACS800-507 technical data,
page 59.
***)
There are no contactors inside the DSU module(s) when the incoming cubicle is equipped with an air circuit
breaker.
Electrical installation
37
PE PE
*) 1L1 Switching, breaking,
disconnecting and
1L2
grounding devices
1L3
2L1
***)
Switching, breaking,
2L2 disconnecting and
2L3 grounding devices
**)
Incoming cubicle
***)
Notes:
For details, see the delivery specific circuit diagrams. (Included in every delivery.) For cable selection
instructions, see ACS800 Multidrive, Planning the Electrical Installation (3AFE64783742 [English]).
*)
Fuses are not required if the input power line is constructed of busbars that withstand the transformer
short circuit current.
**)
No bridging (connecting 1L1 to 2L1, 1L2 to 2L2, and 1L3 to 2L3) is allowed!
There are two separate incoming cubicles one for terminals 1L1, 1L2 and 1L3, the other for 2L1, 2L2
and 2L3 if a) the unit is equipped with air circuit breakers, b) the drive is UL listed, or c) the incoming
cubicle is designed for a busbar connection.
The cable lead-through details (number and size of holes), and cable connection details (number and
dimensions of busbars, tightening torque) are given in chapter ACS800-307 and ACS800-507 technical
data, page 59.
***)
There are no contactors inside the modules when the incoming cubicle is equipped with air circuit
breakers.
Electrical installation
38
Release the handle and open the input fuse cubicle door.
Remove the shrouds that protect the input power busbars and cable lead-through.
Electrical installation
39
Connection diagrams
Six-pulse connection, two DSU modules in parallel
PE
U1.1
V1.1
W1.1
U1.2
***)
V1.2
W1.2
L1
*) **)
L2 PE
L3
U1.1
V1.1
W1.1
U1.2
***)
V1.2
W1.2
*)
Notes:
For details, see the delivery specific circuit diagrams. (Included in every delivery.)
No parallel input power cables are shown here. The recommended cable types and numbers per each
basic DSU module type are given in chapter ACS800-304 and ACS800-704 technical data, page 63.
*)
Fuses for protecting the recommended input cables and DSU modules are given in chapter
ACS800-304 and ACS800-704 technical data, page 63.
**)
The cable connection details (number and dimensions of busbars, tightening torque) are given in
ACS800-304 and ACS800-704 technical data, page 64.
***)
Contactors are optional.
Electrical installation
40
PE
U1.1
V1.1
W1.1
***)
U1.2
V1.2
L1
L2 W1.2
L3
*) **)
L1 PE
L2
L3
U1.1
V1.1
W1.1
***)
U1.2
V1.2
W1.2
**)
*)
Notes:
For details, see the delivery specific circuit diagrams. (Included in every delivery.)
It is also possible to connect all input power terminals of module 1 to the transformer Y-output and
module 2 to the transformer D-output. However, note that then the two bridges inside a single module
do not form a twelve-pulse connection any more. This means that the benefits of the twelve-pulse
connection are not available during a temporary operation with only one module (e.g. during
maintenance of the other module).
No parallel input power cables are shown here. The recommended cable types and numbers per each
basic DSU module type are given in chapter ACS800-304 and ACS800-704 technical data, page 63.
*)
Fuses for protecting the recommended input cables and DSU modules are given in chapter
ACS800-304 and ACS800-704 technical data, page 63.
**)
The cable connection details (number and dimensions of busbars, tightening torque) are given in
ACS800-304 and ACS800-704 technical data, page 64.
***)
Contactors are optional.
Electrical installation
41
3 3
3
2
Lead the cables into the inside of the cabinet and connect as follows:
Twist the cable shields to bundles and connect to cabinet PE (ground)
busbar. Connect the separate ground conductors/cables to cabinet PE 1
(ground) busbar.
Connect the phase conductors to the input power terminals (U1.1 ). For
tightening torques, see chapter ACS800-304 and ACS800-704 technical
data, page 66.
(1) Depending on the cable size, use cable lugs or dual-cable screw lug con-
nectors. See chapter ACS800-304 and ACS800-704 technical data, page 64.
For installation details, see Use of the dual-cable screw lug connector below.
WARNING! Make sure to refit the transparent plastic insulators onto the termi-
nals.
(2) Recommendation: 360 grounding of
the cable shield at the lead-through
suppresses interference.
2
Grommet (in IP54
units only)
Electrical installation
42
1
2
3
Electrical installation
43
Disconnect the supply (rectifier) unit and auxiliary circuit from power-line.
Release the door handle and open the door of the control and I/O cubicle.
Remove the two locking screws at the edge of the swing-out frame and open the frame.
Run the cables into the inside of the cabinet through the grommets provided.
Top entry units only: If several cables need to be run through one grommet, use Loctite 5221 (cat. no.
25551) under the grommet to seal the cable entry.
Side view
Strain relief EMI conductive
cushions
Electrical installation
44
If the outer surface of a cable shield is non-conductive, turn the shield inside out as shown below and
apply copper foil to keep the shielding continuous. Do not cut the grounding wire (if present).
Copper foil
Grounding wire
On top entry units, sort the cables so that the thinnest and thickest cables are at opposite ends of the
opening.
Top view
Run the cables to the swing-out frame as shown below. Wherever possible, use the existing cable trunking
(1) in the cabinet. Use sleeving wherever the cables are laid against sharp edges. Leave some slack in the
cable at the hinge (2) to allow the frame to open fully. Tie the cables to the braces (3) to provide strain
relief.
3
1
Electrical installation
45
Cut the cables to suitable length. Strip the cables and conductors.
Twist the cable shields into bundles and connect them to the ground terminal nearest to the terminal block.
Keep the unshielded portion of the cables as short as possible.
Connect the conductors to appropriate terminals (see chapter Hardware description, page 28 and the
circuit diagrams delivered with the unit).
Electrical installation
46
Electrical installation
47
Start-up
Start-up procedure
Action Additional information
Installation check-list
WARNING! Ensure that the disconnector of the supply transformer is
locked to open position, i.e. no voltage is, or cannot be connected to drive
inadvertently. Check also by measuring that there is no voltage
connected.
Check that the mechanical and electrical installation of the drive is
inspected and OK.
Ensure that the surroundings and inside of the cabinet are free from dust After the start, the cooling air fans
and loose objects like cable trimmings and other waste left from the may suck nearby loose objects into
installation. the unit. This might cause failure and
damage the unit.
Basic checks with no voltage connected
If the cabinet-installed DSU is equipped with an air circuit breaker, check Optional device. See the delivery
the current trip limits of the breaker (preset at the factory). specific circuit diagrams.
General rule
Ensure the selectivity condition is fulfilled i.e. the breaker trips at a lower
current than the protection device of the supplying network, and that the
limit is high enough not to cause unnecessary trips during the
intermediate DC circuit load peak at start.
Long term current limit
Rule of thumb: Set to the rated AC current of the module.
Peak current limit
Rule of thumb: Set to a value 3-4 times the rated AC current of the
module.
If earth (ground) fault supervision is required, tune the monitoring function See chapter Hardware description,
by setting the current trip level. page 26.
Note: Inactivate the internal earth (ground) fault detection in an IT (ungrounded)
power system.
Note: If the drive is equipped with a separate insulation monitoring device, do not
activate the DSU function but tune the insulation monitoring device after the DSU
is started.
Check the settings of the relays and breakers/switches of the auxiliary Optional devices. See delivery
circuits. specific circuit diagrams.
Disconnect the unfinished or unchecked 230/115 VAC cables that lead
from the terminal blocks to the outside of the equipment.
Start-up
48
Close the main contactors (or breaker) and start the DSU: Turn the three-
position operating switch on the cabinet door from 0 to START position for
2 s.
Checks with DSU started
Check the correct operation of the emergency-stop circuits. Optional device. See delivery specific
circuit diagrams.
Activate and check the operation of the power loss ride-through function. See chapter How the Diode Supply
(Only if automatic restart is required/allowed after a short power supply Unit works, page 13.
break.)
Check the tuning of the insulation monitoring device. Optional device. See delivery specific
Manuals by Bender (manufacturer): IRDH265 manual (code: TGH1249 en), IRDH275/ circuit diagrams and the manual
IRDH275B manual (code: THG1361en.) delivered with the monitoring device.
On-load checks
Check that the DSU cooling fan rotates freely in the right direction. The fan should rotate noiselessly in
the direction the arrow on the fan
cover points to.
Check the correct operation of the current meters. Optional device. See delivery specific
circuit diagrams.
Start-up
49
Maintenance
Maintenance intervals
If installed in an appropriate environment, the unit requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Every 3 years Quick connector check See Checking the input power
and cleaning connections and DSU quick connector
on page 50.
Every 6 years Cooling fan change See Changing the fan on page 51.
Maintenance
50
WARNING! Read and follow the instructions given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)]. Ignoring the instructions can cause physical
injury or death, or damage to the equipment.
WARNING! Read and follow the instructions given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)]. Ignoring the instructions can cause physical
injury or death, or damage to the equipment.
WARNING! Read and follow the instructions given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)]. Ignoring the instructions can cause physical
injury or death, or damage to the equipment.
Remove the module from cabinet. See chapter Electrical installation, page 41.
Check the tightening torques of the input power terminals. See chapter
ACS800-304 and ACS800-704 technical data, page 66.
Clean all contact surfaces of the quick connector and apply some antioxidant joint
compound on them.
Replace the module.
Maintenance
51
Fan
The life span of the cooling fan is about 60 000 hours. The actual life span depends
on the running time and load of the fan, ambient temperature and dust
concentration.
Replacement fans are available from ABB. Do not use other than ABB specified
spare parts.
WARNING! Read and follow the instructions given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)]. Ignoring the instructions can cause physical
injury or death, or damage to the equipment.
Maintenance
52
WARNING! Read and follow the instructions given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)]. Ignoring the instructions can cause physical
injury or death, or damage to the equipment.
Extract the module to be serviced from cabinet. Follow the directions given in
chapter Electrical installation, page 41.
Fasten the air baffle plate (provided with the unit) to the top module guide to block
the airflow through the empty module bay.
Readjust the current output signal scaling of the DSSB board if meters are
connected. See chapter Hardware description, page 26.
Reconnect the module after service in reverse order.
Maintenance
53
Fault Tracing
Status, fault and warning LEDs on module cover and on the external
control board (DSSB)
D C F u s , 0 e 0 , 0m F ,0 m m
0 ma m i l m u r e P o w e r
F a n F , a 0 0 i l mu rm e F a n F u ll S p e e d
,0 m m
O v e r T e m p F , 0a 0 i l m u m r e O v e rT e m p W a r n in g
P h a s e L 1 .1 M i, 0 s 0 s m i n m g P h a s e L 1 .2 M is s in g
P h a s e L 2 .1 M is s in g P h a s e L 2 .2 M is s in g
,0 m m
,0 m m
,1 3 m m
P h a s e L 3 .1 M is s in g P h a s e L 3 .2 M is s in g
C o d e : 6 x 4 x 6 x 9 x 4 x x8 x 8 x 3
, 0 0 ,m 0 m m m
Fault Tracing
54
Note: A fault indication LED starts blinking after the fault is detected. If the input power is cut off, the
LED on the DSSB board turns off. The DSU module LED keeps blinking until the back-up battery
discharges. Battery discharge time is about five minutes.
Fault Tracing
55
Ratings
Type Module type Frame No overload Light overload use Heavy-duty use
Icontmax Icontmax Imax SN Pcontmax In PN Ihd Phd
A (AC) A (DC) A (DC) kVA kW (DC) A (DC) kW A (DC) kW
UN = 400 V (Range 380 - 415 V)
6-PULSE DIODE (DSU)
ACS800-307-0200-3 ACS800-304-0320-7 D3 286 350 462 198 183 335 175 280 147
ACS800-307-0280-3 ACS800-304-0450-7 D3 408 500 700 283 262 480 251 400 210
ACS800-307-0400-3 ACS800-704-0640-7 D4 571 700 924 396 367 670 351 560 293
ACS800-307-0570-3 ACS800-704-0910-7 D4 816 1000 1400 566 524 960 503 800 419
ACS800-307-0790-3 ACS800-704-0640-7 2xD4 1143 1400 1848 792 733 1340 702 1120 587
ACS800-307-1050-3 ACS800-704-0910-7 2xD4 1518 1860 2604 1052 974 1790 938 1490 780
ACS800-307-1580-3 ACS800-704-0910-7 3xD4 2278 2790 3906 1578 1461 2685 1406 2230 1168
ACS800-307-2100-3 ACS800-704-0910-7 4xD4 3037 3720 5208 2104 1949 3580 1875 2980 1561
ACS800-307-2630-3 ACS800-704-0910-7 5xD4 3796 4650 6510 2630 2436 4475 2344 3720 1949
12-PULSE DIODE (DSU)
ACS800-507-0400-3 ACS800-704-0640-7 D4 571 700 924 396 367 670 351 560 293
ACS800-507-0570-3 ACS800-704-0910-7 D4 816 1000 1400 566 524 960 503 800 419
ACS800-507-0790-3 ACS800-704-0640-7 2xD4 1143 1400 1848 792 733 1340 702 1120 587
ACS800-507-1050-3 ACS800-704-0910-7 2xD4 1518 1860 2604 1052 974 1790 938 1490 780
ACS800-507-1580-3 ACS800-704-0910-7 3xD4 2278 2790 3906 1578 1461 2685 1406 2230 1168
ACS800-507-2100-3 ACS800-704-0910-7 4xD4 3037 3720 5208 2104 1949 3580 1875 2980 1561
ACS800-507-2630-3 ACS800-704-0910-7 5xD4 3796 4650 6510 2630 2436 4475 2344 3720 1949
UN = 500 V (Range 380 - 500 V)
6-PULSE DIODE (DSU)
ACS800-307-0250-5 ACS800-304-0320-7 D3 286 350 462 247 229 335 219 280 183
ACS800-307-0350-5 ACS800-304-0450-7 D3 408 500 700 353 327 480 314 400 262
ACS800-307-0490-5 ACS800-704-0640-7 D4 571 700 924 495 458 670 439 560 367
ACS800-307-0710-5 ACS800-704-0910-7 D4 816 1000 1400 707 655 960 629 800 524
ACS800-307-0990-5 ACS800-704-0640-7 2xD4 1143 1400 1848 990 917 1340 877 1120 733
ACS800-307-1310-5 ACS800-704-0910-7 2xD4 1518 1860 2604 1315 1218 1790 1172 1490 976
ACS800-307-1970-5 ACS800-704-0910-7 3xD4 2278 2790 3906 1972 1827 2685 1758 2230 1460
ACS800-307-2630-5 ACS800-704-0910-7 4xD4 3037 3720 5208 2630 2436 3580 2344 2980 1951
ACS800-307-3290-5 ACS800-704-0910-7 5xD4 3796 4650 6510 3287 3045 4475 2930 3720 2436
12-PULSE DIODE (DSU)
ACS800-507-0490-5 ACS800-704-0640-7 D4 571 700 924 495 458 670 439 560 367
ACS800-507-0710-5 ACS800-704-0910-7 D4 816 1000 1400 707 655 960 629 800 524
ACS800-507-0990-5 ACS800-704-0640-7 2xD4 1143 1400 1848 990 917 1340 877 1120 733
ACS800-507-1310-5 ACS800-704-0910-7 2xD4 1518 1860 2604 1315 1218 1790 1172 1490 976
ACS800-507-1970-5 ACS800-704-0910-7 3xD4 2278 2790 3906 1972 1827 2685 1758 2230 1460
ACS800-507-2630-5 ACS800-704-0910-7 4xD4 3037 3720 5208 2630 2436 3580 2344 2980 1951
ACS800-507-3290-5 ACS800-704-0910-7 5xD4 3796 4650 6510 3287 3045 4475 2930 3720 2436
Type Module type Frame No overload Light overload use Heavy-duty use
Icontmax Icontmax Imax SN Pcontmax In PN Ihd Phd
A (AC) A (DC) A (DC) kVA kW (DC) A (DC) kW A (DC) kW
UN = 690 V (Range 525 - 690 V)
6-PULSE DIODE (DSU)
ACS800-307-0340-7 ACS800-304-0320-7 D3 286 350 462 341 316 335 303 280 253
ACS800-307-0490-7 ACS800-304-0450-7 D3 408 500 700 488 452 480 434 400 361
ACS800-307-0680-7 ACS800-704-0640-7 D4 571 700 924 683 632 670 605 560 506
ACS800-307-0980-7 ACS800-704-0910-7 D4 816 1000 1400 976 904 960 867 800 723
ACS800-307-1370-7 ACS800-704-0640-7 2xD4 1143 1400 1848 1366 1265 1340 1211 1120 1012
ACS800-307-1810-7 ACS800-704-0910-7 2xD4 1518 1860 2604 1815 1681 1790 1617 1490 1346
ACS800-307-2720-7 ACS800-704-0910-7 3xD4 2278 2790 3906 2722 2521 2685 2426 2230 2015
ACS800-307-3630-7 ACS800-704-0910-7 4xD4 3037 3720 5208 3629 3361 3580 3235 2980 2693
ACS800-307-4540-7 ACS800-704-0910-7 5xD4 3796 4650 6510 4537 4202 4475 4043 3720 3361
12-PULSE DIODE (DSU)
ACS800-507-0680-7 ACS800-704-0640-7 D4 571 700 924 683 632 670 605 560 506
ACS800-507-0980-7 ACS800-704-0910-7 D4 816 1000 1400 976 904 960 867 800 723
ACS800-507-1370-7 ACS800-704-0640-7 2xD4 1143 1400 1848 1366 1265 1340 1211 1120 1012
ACS800-507-1810-7 ACS800-704-0910-7 2xD4 1518 1860 2604 1815 1681 1790 1617 1490 1346
ACS800-507-2720-7 ACS800-704-0910-7 3xD4 2278 2790 3906 2722 2521 2685 2426 2230 2015
ACS800-507-3630-7 ACS800-704-0910-7 4xD4 3037 3720 5208 3629 3361 3580 3235 2980 2693
ACS800-507-4540-7 ACS800-704-0910-7 5xD4 3796 4650 6510 4537 4202 4475 4043 3720 3361
00184674.XLS / Rev E
Nominal ratings
Icont.max continuous rms input (AC) or output (DC) current. No overload capability at 40C.
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by module temperature.
Pcont.max nominal output power
Light overload use (10% overload capability) ratings
IN continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN output power in light overload use
Heavy-duty use (50% overload capability) ratings
Ihd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd output power in heavy duty-use
Type Height Width 4 Width 5 Width 6 Width 7 Depth 1 Depth 2 Weight Noise Heat loss Air flow
mm mm mm mm mm mm mm kg dB kW m3/h
ACS800-507-3630-7 2130 2400 3000 300 - 600 730 1900 59.0 20 2880
ACS800-507-4540-7 2130 3200 300+300 - 600 730 2170 60.0 25 3600
00184674.XLS / Rev E
Height For IP22 and IP42 cubicles. IP54: 2315 mm, IP54R: 2051 mm
Width 1 3 Widths for the previous generation design (no longer in production)
Width 4 With load switch (OETL), cable entry from below
Width 5 With air circuit breaker, cable entry from below
Width 6 Additional width due to cable entry from above
Width 7 Additional width due to EMC line filter (1st Environment)
Depth 1 Air inlet through grating on front door
Depth 2 Air inlet through cabinet bottom (additional bottom extension on back) and/or cable entry from top
Weight With switch-disconnector
13 [0.51] 40 [1.57]
M12 70 Nm n 60 mm
2)
() (50 lb.ft) (n 2.36)
50 [1.97]
1)
n = 9 for units with one or two parallel diode supply modules, n = 18 for units with three to four parallel
modules, n = 27 for units with five parallel modules
2) No. of input busbars in six-pulse unit:
Other data
The following subsections in chapter ACS800-304 and ACS800-704 technical data
are also valid for the ACS800-307 and ACS800-507.
Input cable and AC fuses
Internal DC fuses
Dimensions, noise, losses, inductance, and air flow
Input power connection
Efficiency
Degree of Protection
Ambient conditions
Cooling
Materials
Standards
Markings
Ratings
Diode Supply Unit Consists of module Nominal ratings Light overload use Heavy-duty use
type frame Icontmax Icontmax Imax SN Pcontmax In PN Ihd Phd
A [AC] A [DC] A [DC] [kVA] [kW] [ADC] [kW] [ADC] [kW]
400 V / 6-pulse Diode Supply Unit
ACS800-304-0320-7 ACS800-304-0320-7 D3 286 350 462 198 183 335 175 280 147
ACS800-304-0450-7 ACS800-304-0450-7 D3 408 500 700 283 262 480 251 400 210
ACS800-704-0640-7 ACS800-704-0640-7 D4 571 700 924 396 367 670 351 560 293
ACS800-704-0910-7 ACS800-704-0910-7 D4 816 1000 1400 566 524 960 503 800 419
ACS800-704-1370-7 ACS800-704-0640-7 2D4 1143 1400 1848 792 733 1340 702 1120 587
ACS800-704-1810-7 ACS800-704-0910-7 2D4 1518 1860 2604 1052 974 1790 938 1490 780
ACS800-704-2720-7 ACS800-704-0910-7 3D4 2278 2790 3906 1578 1461 2685 1406 2230 1168
ACS800-704-3630-7 ACS800-704-0910-7 4D4 3037 3720 5208 2104 1949 3580 1875 2980 1561
ACS800-704-4540-7 ACS800-704-0910-7 5D4 3796 4650 6510 2630 2436 4475 2344 3720 1949
400 V / 12-pulse Diode Supply Unit
ACS800-704-0640-7 ACS800-704-0640-7 D4 571 700 924 396 367 670 351 560 293
ACS800-704-0910-7 ACS800-704-0910-7 D4 816 1000 1400 566 524 960 503 800 419
ACS800-704-1370-7 ACS800-704-0640-7 2D4 1143 1400 1848 792 733 1340 702 1120 587
ACS800-704-1810-7 ACS800-704-0910-7 2D4 1518 1860 2604 1052 974 1790 938 1490 780
ACS800-704-2720-7 ACS800-704-0910-7 3D4 2278 2790 3906 1578 1461 2685 1406 2230 1168
ACS800-704-3630-7 ACS800-704-0910-7 4D4 3037 3720 5208 2104 1949 3580 1875 2980 1561
ACS800-704-4540-7 ACS800-704-0910-7 5D4 3796 4650 6510 2630 2436 4475 2344 3720 1949
380...500 / 6-pulse Diode Supply Unit
ACS800-304-0320-7 ACS800-304-0320-7 D3 286 350 462 247 229 335 219 280 183
ACS800-304-0450-7 ACS800-304-0450-7 D3 408 500 700 353 327 480 314 400 262
ACS800-704-0640-7 ACS800-704-0640-7 D4 571 700 924 495 458 670 439 560 367
ACS800-704-0910-7 ACS800-704-0910-7 D4 816 1000 1400 707 655 960 629 800 524
ACS800-704-1370-7 ACS800-704-0640-7 2D4 1143 1400 1848 990 917 1340 877 1120 733
ACS800-704-1810-7 ACS800-704-0910-7 2D4 1518 1860 2604 1315 1218 1790 1172 1490 976
ACS800-704-2720-7 ACS800-704-0910-7 3D4 2278 2790 3906 1972 1827 2685 1758 2230 1460
ACS800-704-3630-7 ACS800-704-0910-7 4D4 3037 3720 5208 2630 2436 3580 2344 2980 1951
ACS800-704-4540-7 ACS800-704-0910-7 5D4 3796 4650 6510 3287 3045 4475 2930 3720 2436
380...500 V / 12-pulse Diode Supply Unit
ACS800-704-0640-7 ACS800-704-0640-7 D4 571 700 924 495 458 670 439 560 367
ACS800-704-0910-7 ACS800-704-0910-7 D4 816 1000 1400 707 655 960 629 800 524
ACS800-704-1370-7 ACS800-704-0640-7 2D4 1143 1400 1848 990 917 1340 877 1120 733
ACS800-704-1810-7 ACS800-704-0910-7 2D4 1518 1860 2604 1315 1218 1790 1172 1490 976
ACS800-704-2720-7 ACS800-704-0910-7 3D4 2278 2790 3906 1972 1827 2685 1758 2230 1460
ACS800-704-3630-7 ACS800-704-0910-7 4D4 3037 3720 5208 2630 2436 3580 2344 2980 1951
ACS800-704-4540-7 ACS800-704-0910-7 5D4 3796 4650 6510 3287 3045 4475 2930 3720 2436
525...690 V / 6-pulse Diode Supply Unit
ACS800-704-0320-7 ACS800-304-0320-7 D3 286 350 462 341 316 335 303 280 253
ACS800-304-0450-7 ACS800-304-0450-7 D3 408 500 700 488 452 480 434 400 361
ACS800-704-0640-7 ACS800-704-0640-7 D4 571 700 924 683 632 670 605 560 506
ACS800-704-0910-7 ACS800-704-0910-7 D4 816 1000 1400 976 904 960 867 800 723
ACS800-704-1370-7 ACS800-704-0640-7 2D4 1143 1400 1848 1366 1265 1340 1211 1120 1012
ACS800-704-1810-7 ACS800-704-0910-7 2D4 1518 1860 2604 1815 1681 1790 1617 1490 1346
ACS800-704-2720-7 ACS800-704-0910-7 3D4 2278 2790 3906 2722 2521 2685 2426 2230 2015
ACS800-704-3630-7 ACS800-704-0910-7 4D4 3037 3720 5208 3629 3361 3580 3235 2980 2693
ACS800-704-4540-7 ACS800-704-0910-7 5D4 3796 4650 6510 4537 4202 4475 4043 3720 3361
Diode Supply Unit Consists of module Nominal ratings Light overload use Heavy-duty use
type frame Icontmax Icontmax Imax SN Pcontmax In PN Ihd Phd
A [AC] A [DC] A [DC] [kVA] [kW] [ADC] [kW] [ADC] [kW]
525...690 V / 12-pulse Diode Supply Unit
ACS800-704-0640-7 ACS800-704-0640-7 D4 571 700 924 683 632 670 605 560 506
ACS800-704-0910-7 ACS800-704-0910-7 D4 816 1000 1400 976 904 960 867 800 723
ACS800-704-1370-7 ACS800-704-0640-7 2D4 1143 1400 1848 1366 1265 1340 1211 1120 1012
ACS800-704-1810-7 ACS800-704-0910-7 2D4 1518 1860 2604 1815 1681 1790 1617 1490 1346
ACS800-704-2720-7 ACS800-704-0910-7 3D4 2278 2790 3906 2722 2521 2685 2426 2230 2015
ACS800-704-3630-7 ACS800-704-0910-7 4D4 3037 3720 5208 3629 3361 3580 3235 2980 2693
ACS800-704-4540-7 ACS800-704-0910-7 5D4 3796 4650 6510 4537 4202 4475 4043 3720 3361
00184674.xls / A
Nominal ratings
Icont.max continuous rms input (AC) or output (DC) current. No overload capability at 40C.
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by module temperature.
Pcont.max nominal output power
Light-overload use (10% overload capability) ratings
IN continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN output power in light overload use
Heavy-duty use (50% overload capability) ratings
Ihd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd output power in heavy duty-use
aR fuse
Screw fuse 1740M4417 (700 A, 690 VAC) by Bussman. (This fuse type is always
used in the cabinet-installed DSU.)
gG and T fuses
Module type AC-fuses 1) IEC Cabling USA Cabling Cabling Arrangement
IEC (gG) UL (T) Copper Aluminium Copper
[A] [A] [mm2] [mm2] [AWG]
UN = 400 V (Range 380415 V)
6-PULSE DSU
DSU frame D3
ACS800-304-0320-7 400 500 2(370+35) 2(3120+41Cu) 2(33/0)
ACS800-304-0450-7 500 600 2(3120+70) 2(3185+57Cu) 2(3300 MCM) U1.1
ACS800-704-0640-7 400 500 22(370+35) 22(3120+41Cu) 22(33/0)
V1.1
ACS800-704-0910-7 500 600 22(3120+70) 22(3185+57Cu) 22(3300 MCM)
W1.1
12-PULSE DSU
ACS800-704-0640-7 400 500 22(370+35) 22(3120+41Cu) 22(33/0) PE
ACS800-704-0910-7 500 600 22(3120+70) 22(3185+57Cu) 22(3300 MCM)
U1.2
UN = 500 V (Range 380500 V)
6-PULSE DSU V1.2
ACS800-304-0320-7 400 500 2(370+35) 2(3120+41Cu) 2(33/0) W1.2
ACS800-304-0450-7 500 600 2(3120+70) 2(3185+57Cu) 2(3300 MCM)
ACS800-704-0640-7 400 500 22(370+35) 22(3120+41Cu) 22(33/0)
ACS800-704-0910-7 500 600 22(3120+70) 22(3185+57Cu) 22(3300 MCM)
12-PULSE DSU DSU frame D4
ACS800-704-0640-7 400 500 22(370+35) 22(3120+41Cu) 22(33/0)
ACS800-704-0910-7 500 600 22(3120+70) 22(3185+57Cu) 22(3300 MCM) U1.1
UN = 690 V (Range 525690 V) V1.1
6-PULSE DSU W1.1
ACS800-304-0320-7 400 500 2(370+35) 2(3120+41Cu) 2(33/0)
ACS800-304-0450-7 500 600 2(3120+70) 2(3185+57Cu) 2(3300 MCM) PE
ACS800-704-0640-7 400 500 22(370+35) 22(3120+41Cu) 22(33/0) U1.2
ACS800-704-0910-7 500 600 22(3120+70) 22(3185+57Cu) 22(3300 MCM)
V1.2
12-PULSE DSU
ACS800-704-0640-7 400 500 22(370+35) 22(3120+41Cu) 22(33/0) W1.2
ACS800-704-0910-7 500 600 22(3120+70) 22(3185+57Cu) 22(3300 MCM)
00158760.xls / Rev B
1) Use one fuse per each input terminal of the DSU module (i.e. six fuses per D4 module, three fuses per D3 module).
Internal DC fuses
All DSU modules: Bussmann screw fuse, 170M 4417, 700 A / 690 V, 1BN/50
Degree of Plain module: IP20, Cabinet: IP20, IP21, IP22, IP42 or IP54
Protection
Ambient conditions
The unit is to be used in a heated indoor controlled environment.
Operation Storage Transportation
Altitude above sea level 01000 m - -
10002000: 2.5% derating - -
for every 100 m
Max. 4000 m ASL
Temperature 0+50C -40+70C -40+70C
+40+50C derating 1% /
1C above 40C
Relative humidity 595%, no condensation 595% 595%
allowed
Vibration (IEC 60068-2-6) 1058 Hz, 0.075 mm
displacement amplitude
58150 Hz 10 m/s2
Vibration (Marine 313.8 Hz 1.0 mm
Classification) displacement amplitude
13.8100 Hz / m/s2
Shock (IEC-60068-2-6) Not allowed max. 100 m/s2 18 ms max. 100 m/s2 18 ms
Free fall (IEC-60068-2-6) Not allowed 25 mm 25 mm
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
(0.7 to 1.05 atmospheres) (0.7 to 1.05 atmospheres) (0.6 to 1.05 atmospheres)
Contamination (IEC-721-3-3) Class 3C2 - chemical gases Class 1C2 - chemical gases Class 2C2 - chemical gases
Class 3S2 - solid particles Class 1S2 - solid particles Class 2S2 - solid particles
Cooling
Method Centrifugal fan, speed controlled according to cooling element temperature
Max. 190 l/s, noise < 65 dB
Free space See dimensional drawings
Air flow See type specific figures
Net air inlet / module 0.117 m2
Net air outlet / module 0.065 m2
Recommended IP22/42 filter AIR TEX G-150 by Luftfilter
material
Materials
Module enclosure 2 mm sheet steel
Flat busbars Tin plated copper or aluminium
Fire safety of materials Insulating materials & non-metallic items: Mostly self-extinctive
(IEC-332-1)
Package Plywood. Bands PP or steel.
Disposal According to the general ABB drives specification
Standards
See ACS800 Multidrive and ACS800 Multidrive Modules Planning the Electrical Installation [3AFE64783742 (English)].
Markings
See ACS800 Multidrive and ACS800 Multidrive Modules Planning the Electrical Installation [3AFE64783742 (English)].
ABB Oy
AC Drives
P.O. Box 184
FIN-00381 HELSINKI
FINLAND
Telephone +358 10 22 11
Fax +358 10 22 22681
Internet http://www.abb.com