Beruflich Dokumente
Kultur Dokumente
1
Contents
General Hardware Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Hardware Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PLC Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Memory Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Memory Backup Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
The I/O Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
The J1 and J2 Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring External Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PLC Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Comm Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
A120 I/O Expansion Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fixed Analog I/O in the 612 Models . . . . . . . . . . . . . . . . . . . . . . . . . 10
Base Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Optional Hardware Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Partial Sampling of Available A120 I/O Modules . . . . . . . . . . . . . . . 17
Fixed I/O Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
115 VAC Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
230 VAC Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
24 VDC Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
User-selectable High-speed Counter/interrupt Inputs . . . . . . . . . . 29
Dedicated High-speed Interrupt Inputs . . . . . . . . . . . . . . . . . . . . . . . 31
Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Triac Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
24 VDC (FET) Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Installing the Optional Battery or Battery Capacitor . . . . . . . . . . . . . . . 48
Serial I/O Expansion Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Terminating the Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
A120 I/O Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Calculating Power Requirements in an A120 I/O
Expansion System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
A120 I/O Expansion Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Connecting the PLC to a Programming Panel . . . . . . . . . . . . . . . . . . . . 56
RS-232 Cable Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
RS-232 Cable Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
16 (24 VDC) in
12 relay out
110CPU61200 24 VDC 4 analog in
2 analog out
16 (115 VAC) in
110CPU51201 115 VAC 8 triac out
4 relay out
16 (230 VAC) in
110CPU51202 230 VAC 8 triac out
4 relay out
16 (24 VDC) in
110CPU51203 24 VDC
12 (24 VDC) FET out
16 (24 VDC) in
110CPU61203 24 VDC 12 (24 VDC) FET out
4 analog in
2 analog out
16 (24 VDC) in
110CPU61204 24 VDC 12 relay out
4 analog in
2 analog out
Battery cover
Captive screw for the output terminal block Captive screw for the output terminal block
Terminal block for fixed discrete outputs
* The 612 PLC has an additional set of terminal blocks for analog I/O (see page 11).
3
2
N 4
3
5
24 RET 4
The labels for the power source termi-
nal connections are in red lettering.
5
Note Add a wire loop between
the pins labeled JUMPER.
Model 11051201 PLCs use a
115 VAC external power source,
wired like this:
L
2
115 VAC
N
4
The display panel on the front of the To reference the physical I/O point to an
Micro PLCs uses light-emitting diodes LED number in the display, refer to the
(LEDs) to indicate the health and status field wiring diagrams presented in this
of the units CPU, battery, communica- book.
tion ports, and fixed I/O points. The
column of LEDs on the right side of the If the run LED on the right is flashing in
unit indicates PLC status: conjunction with any of the input LEDs,
an error has been detected. The pat-
PLC Status LEDs tern of the input LED flashes indicates
LED Function the nature of the error. The person pro-
gramming the PLC can refer to the
power ok A green LED turned ON when internal
power is OK Modicon Micro Ladder Logic Manual
ready An amber LED that is ON when the PLC
(890 USE 146 00) for a description of
has passed its power-up diagnostics, system crash codes.
and remains ON as long as the PLC is
healthy
The additional connectors for analog in- comm ports. The illustration on the fol-
put and output channels are located on lowing page shows the pin positions.
the bottom of the unit to the left of the
21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Agency Approvals
All models are F.M. Class I, Div. 2 approved (except for the 61204 which is
pending), and are designed to meet VDE 0160 standards
The following models are UL 508 Listed for Industrial Control Equipment and
CSA 142 Certified for process control equipment:
110CPU51200
110CPU51201
110CPU51202
110CPU61200
110CPU61203
110CPU61204
The 110CPU51203 is CSA Certified, with UL pending
CE Compliance
Conformal Coating
25-pin
Premade for PC-XTs 110XCA20400
Wire-it-yourself (male) 110XCA20401
Wire-it-yourself (female) 110XCA20402
For more details and a complete listing of all current A120 I/O modules, see
Modicon A120 Series I/O Modules User Guide, 890USE10900 formerly
GM-A984-IOS.
24 VDC 24 VDC
24 V 24 V
22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
User-selectable
counter or Dedicated Group B Group A
interrupt interrupts Cnt/int com 24 VDC Inputs 24 VDC Inputs
Modicon 110CPU51200
110CPU61200
110CPU61204
Group D common
Group C common
Group D Group C
Relay Outputs Relay Outputs Isolated Relay Outputs
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
3 A Fuses
L L L L L L L L L L L L
12 11 10 9 8 7 6 5 4 3 2 1
Out Out Out Out Out Out Out Out Out Out Out Out
12 11 10 9 8 7 6 5 4B 3B 2B 1B
Note Fast-blow fuses are recommended for input and output protection.
24 V 24 V
22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
User-selectable
counter or Dedicated Group B Group A
interrupt interrupts Cnt/int com 24 VDC Inputs 24 VDC Inputs
Modicon 110CPU51200
110CPU61200
110CPU61204
Group D common
Group C common
Group D Group C
Relay Outputs Relay Outputs Isolated Relay Outputs
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
3 A Fuses
24 V common L L L L L L L L L L L L
12 11 10 9 8 7 6 5 4 3 2 1
24 VDC
Out Out Out Out Out Out Out Out Out Out Out Out 24 V common
12 11 10 9 8 7 6 5 4B 3B 2B 1B
Note Fast-blow fuses are recommended for input and output protection.
Note To reduce the risk that electrical noise from field I/O devices will
effect Micro operation, we recommend that a separate 24 VDC power
source be used for the field I/O. A dual power-source configuration can
also be beneficial in preventing a failure in a single field device from
shutting down power to the PLC.
Note The wiring for the analog I/O of the 612s is shown in the simpli-
fied schematics on pages 40 (for the inputs) and 42 (for the outputs).
AC Hot AC Hot
AC Neutral In In In In In In In In
.16A Fuse 16 15 14 13 12 11 10 9 AC Neutral
Group A common
Group B common
Cnt/ Int In In In In In In In In
Int 1 8 7 6 5 4 3 2 1
.16A Fuse
22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
115V
Modicon 110CPU51201
Group B common
Group B hot
Group A common
Group A hot
Isolated
Relay Outputs Triac Group B Triac Group A
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L L L L L L L L L L L
Relay Neutral 12 11 10 9 8 7 6 5 4 3 2 1
Out Out Out Out Out Out Out Out
12A 11A 10A 9A 8 7 6 5Out Out Out Out
4 3 2 1
* The 24 V power supply from pins 19 and 20 in the top block provide up to 150 mA at 24 V.
Note Fast-blow fuses are recommended for input and output protection.
AC Hot
AC Hot
AC Neutral
In In In In In In In In AC Neutral
.16 A Recommended 16 15 14 13 12 11 10 9
Group A common
Group B common
Cnt/ Int In In In In In In In In
int 1 8 7 6 5 4 3 2 1 .16A Fuse
230V
22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
User-selectable
counter or Dedicated Group B Group A
interupt Interrupt +24 V out 230 VAC Inputs 230 VAC Inputs
+24 V ref
Group B common
Group B Hot
Group A common
Group A Hot
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L L L L L L L L L L L
Relay Neutral 12 11 10 9 8 7 6 5 4 3 2 1
Out Out Out Out Out Out Out Out Out Out Out Out
12A 11A 10A 9A 8 7 6 5 4 3 2 1
Group B Hot
Note: Fast-blow fuses are recommended for input and output protection
22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Modicon 110CPU51203
110CPU61203
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L L L L L L L L L L L
12 11 10 9 8 7 6 5 4 3 2 1
12 11 10 9 8 7 6 5 4 3 2 1
Out Out Out Out Out Out Out Out Out Out Out Out
Note Fast-blow fuses are recommended for input and output protection.
24 V Common 24 V Common
.16 A Cnt/ Int Int .16 A
+24 V int 2 1 Group B common Group A common +24 V
In In In In In In In In In In In In In In In In
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Modicon 110CPU51203
110CPU61203
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L L L L L L L L L L L
12 11 10 9 8 7 6 5 4 3 2 1
12 11 10 9 8 7 6 5 4 3 2 1
Out Out Out Out Out Out Out Out Out Out Out Out
Note Fast-blow fuses are recommended for input and output protection.
Note To reduce the risk that electrical noise from field I/O devices will
effect Micro operation, we recommend that a separate 24 VDC power
source be used for the field I/O. A dual power-source configuration can
also be beneficial in preventing a failure in a single field device from
shutting down power to the PLC.
Note The wiring for the analog I/O of the 110CPU61203 is shown in
the simplified schematics on pages 40 (for the inputs) and 42 (for the
outputs).
Field Logic
side side
VCC
Isolation
Method Opto-coupler
Channel-to-bus 1780 VAC, 2 kV DC
Group-to-group 1780 VAC, 2 kV DC
Addressing 16 discrete bits in
1 register in
Maximum wire length 100 m
Wire size 20 AWG
Response time
ONOFF 25 ... 30 ms
OFFON 25 ... 30 ms
Field Logic
side side
VCC
Isolation
Method Opto-coupler
Channel-to-bus 1780 VAC, 2500 VDC
Group-to-group 1780 VAC, 2500 VDC
Maximum wire length 100 m
Wire size 14 AWG
Response time
ONOFF 25 ... 30 ms
OFFON 25 ... 30 ms
25 V
20 V
INPUT VOLTAGE
15 V
10 V
+5 V
0 mA 1 mA 2 mA 3 mA 4 mA 5 mA 6 mA 7 mA 8 mA 9 mA 10 mA 11 mA
+5 V
Minimum
INPUT VOLTAGE
10 V
Typical
15 V
20 V
Maximum
25 V
30 V
0 mA 1 mA 2 mA 3 mA 4 mA 5 mA 6 mA 7 mA 8 mA 9 mA 10 mA 11 mA
Field Logic
side side
Isolation
Method Opto-coupler
Channel-to-bus 1780 VAC, 2500 VDC
Group-to-group 1780 VAC, 2500 VDC
Response time
ONOFF 2 ms
OFFON 2 ms
Maximum wire length 100 m
Wire size 14 AWG
20 V
INPUT VOLTAGE
15 V
10 V
+5 V
0 mA 2 mA 4 mA 6 mA 8 mA 10 mA 12 mA 14 mA
Field Logic
side side
Interrupt/counter
5V
Com
Isolation
Method Opto-coupler
Channel-to-bus 500 VDC
Group-to-group 500 VDC
Addressing 1 register in
Maximum cable length 50 m
Response time
OFFON 10 ... 20 ms
ONOFF 10 ... 20 ms
Required cable type Shielded twisted pair, for noise immunity
Wire size 20 AWG
Up-counter positive edge trigger
Maximum counter rate 5 kHz
Pulse duration > 100 ms
Interrupt voltage level To assure reliable system operation,
interrupt voltage must be brought from OFF
to ON and maintained ON for 350 ms
minimumany pulse duration < 20 ms is
filtered
Isolation
Method Opto-coupler
Channel-to-bus 500 VDC
Maximum cable length 50 m
Required cable type Shielded twisted pair, for noise immunity
Wire size 20 AWG
Interrupt voltage level To assure reliable system operation, interrupt
voltage must be brought from OFF to ON and
maintained ON for 350 ms minimumany
pulse duration < 50 ms is filtered
5000
4000
3000
2000
1000
120 VAC Resistive
500
400
OPERATION (x 10 )
300
3
200
100
50
120 VAC cos = 0.7
20
0.1 0.2 0.3 0.5 1 2 3 4 5
Logic Field
side 5V side
Isolation
Channel-to-bus 1780 VAC, 2500 VDC
Group-to-group 1780 VAC, 2500 VDC
Mechanical operating cycles 20,000,000
Surge withstand capability 4 kV
Response times
ONOFF 10 ms
OFFON 10 ms
Maximum wire length 100 m
Wire size
One wire 14 AWG
Two wires 20 AWG
Using Relay Outputs with Inductive
Loads
The mechanical relay outputs in Micro controllers must be provided with additional
protection when connected to an inductive load. Properly suppressing inductive
loads reduces radiated noise and prolongs the life of the relay contacts. The follow-
ing three figures provide examples of how to suppress various inductive loads.
OUTPUT Inductive
AC Load
* *
50 W
0.47 mf 115 AC
SOURCE
COMMON
*Minimum voltage rating of 200 VAC.
50 W
0.47 mf 230 AC
SOURCE
COMMON
*Minimum voltage rating of 400 VAC.
OUTPUT Inductive
DC Load
Clamping Diode* +
24VDC
SOURCE
--
COMMON
*Diode must be a minimum of 2A, continuous, and greater than two times the maximum rated load voltage.
2.0
RMS current/ point
All points on with same load
Measured with PLC mounted in normal upright position.
1.0
AMPS
.75
.5
0 10 20 30 40 50 60
AMBIENT TEMPERATURE
DEGREE C
Logic Live
side Field
side
Load
Varistor 280 VAC
Group Common
Isolation
Method Opto-coupler
Channel-to-bus 1780 VAC, 2500 VDC
Group-to-group 1780 VAC, 2500 VDC
Response times
ONOFF 8 ms
OFFON 8 ms
Maximum wire length 100 m
Wire size
One wire 14 AWG
Two wires 20 AWG
1.0
.5
0 12 24 36 45 48 60
AMBIENT TEMPERATURE
DEGREE C
Field
side
+24 V Power IN
Logic side
VCC
To Load
+24 REF
Isolation
Channel-to-bus 1780 VAC, 2500 VDC
Group-to-group 500 VAC
Response times
ONOFF 1 ms
OFFON 1 ms
Maximum wire length 100 m
Wire size 14 AWG
Electrical Characteristics
Input channels
Number 4
Types Current inputs, 20 mA full scale
Voltage inputs, 10 V full scale
Input ranges +10 V, 0 ... 10 V, 4 ... 20 mA
Input filter Single-pole low-pass,
--3 dB frequency of 10 Hz (+20%)
Input resistance
Current mode 250 W (+0.1%)
Voltage mode > 20 MW
Input protection
Differential 50 VDC maximum
Channel-to-channel 30 VDC maximum
Over current 25 mA maximum
Common mode range 25 VDC channel-to-channel
Group Isolation 1000 VAC RMS, 1 min. maximum
(Analog inputs are isolated from analog outputs,
input power, discrete I/O, and communication
ports.)
Wire size
1 wire 12 AWG
2 wires 14 AWG
Conversion
Type Sigma Delta
Resolution 16 bits for +10 V
15 bits for 0 ... 10 V
1314 bits for 4 ... 20 mA
Update time 55 ms/channel if scanned > 55ms;
otherwise, 4 times the scan rate.
Differential nonlinearity No missing codes
Repeatability +3 counts
Jumper Field
Connections
Input 1 (+)
Current 10
Input Analog
Sense 1
11 250 W .1% MUX DC DC
4 ... 20 mA Input 1 (--)
12
Input 2 (+)
13 ADC
Sense 2 CPU
14
Input 2 (--)
15
Input 3 (+) V REF
16
Voltage Sense 3
Input 17
Input 3 (--)
18
Input 4 (+)
19
Sense 4
20
Input 4 (--)
21
Isolation
barrier
Note:
To reduce the possibility of erroneous readings if one or more device wires become
disconnected, it is recommended that the appropriate input and sense lines be
jumpered as shown in the above illustration.
Electrical Characteristics
Output channels
Number 2
Types Current outputs
Voltage outputs
Group Isolation 1000 VAC RMS (60 Hz), 1 min. maximum
(Analog outputs are isolated from analog inputs,
input power, discrete I/O, and communication
ports.)
1000 VDC, 1 min. maximum
Current range 4 ... 20 mA
Loop supply voltage
Maximum 30 V
Minimum 12 V
Vloop -- 7 V
= Max. R
Max loop resistance .02
Voltage range 0 ... 10 V
Output loads 10 mA maximum
.1 mF maximum
1 kW minimum
Conversion
Resolution 12 bits
Linearity errors +.05% maximum
Differential nonlinearity Guaranteed monotonic
Update time 10 ms/channel
Note Additional separate 24 VDC supplies for I/O are not required be-
cause these circuits are isolated internally. Separate supplies may be
used and can improve system performance by avoiding the interference
caused by poor power supply regulation and load transients.
Note Twisted shielded pair cable is recommended. Terminate shields
to channel return to reduce power supply switching noise.
Field
Connections
0 ... 10V
1
2 ZL
3
DC DC 4 ZL
5
D/A
6 4 ... 20 mA +
7 24V
250W
.1% 8 --
V REF
9
CPU
D/A
Isolation
barrier
250W
.1%
56.00 mm
(2.20 in)
base +
terminal
141.5 mm blocks
(5.57 in)
123.5 mm
158.75 mm 132.375 mm (4.86 in) PLC
(6.25 in) (5.21 in) base
9.125 mm
(0.359 in) 17.75 mm
(.698 in)
76 mm
(3 in)
158.75 mm
(6.25 in)
4b
158.75 mm
6.25 in
158.75 mm
6.25 in
130 mm
Input air temp < 60 degrees C 5.07 in
--
Termination 120 W
RS-485 port
Data rate on the link 125 kbyte (+ ) 110XCA10100
Yconnector
Encoding scheme NRZ
The RJ11 cable plugs directly into the 110XCA10100 Y-connector Pinouts
RS-485 ports on the two units at the
RJ11 Plug for the RS485 Port
head and tail ends of the link. All the
1 2 3 4 5 6
other units on the link use a
(110XCA10100) RJ11 Y-connector.
The 110 XCA 101 00 Y-connector
RJ11 plug 1 2 3 4 5 6 1 2 3 4 5 6
RJ11 Jack for the Cable RJ11 Jack for the Cable
RJ11 jacks
Pin 1 = chassis ground
Pin 2 = TXHi
37.3 mm Pin 3 = TXLo
(1.47 in)
A120 I/O
tie point
Ribbon cable
connector
Rack 1 Rack 2
Rack 1 Rack 2
PLC PLC
A A
Rack 1 Rack 1
BXT 201 BXT 201
DTA 201 DTA 201 DTA 201
B B
A A
Rack 1 Rack 1
Rack 2 Rack 2
BXT 201 BXT 201
DTA 201 DTA 201 DTA 201
B B
Note The rack numbers in a stacked layout are determined by the way the
rack on the right side of the lower level is connected via BXT 201 cable to the
PLC or to rack 1 above.
A A
B B
A
A
Rack 1 Rack 1
Rack 2 BXT 202 Rack 2 BXT 202
DTA 201 DTA 201 DTA 201
B B
pin 1 1* 1 DCD
TXD 3 2 RXD
pin 9 RXD 4 3 TXD
DSR 2 4 DTR
GND 5 5 GND
RTS 6 8 CTS
9 RI
chassis 8 case of
ground the connector
50.8 mm
(2 in)
pin 1
110XCA20400
25-pin Female Adapter Micro PC-XT Pinouts
RJ45 Connector 25-pin D-shell
pin 1 1* 1
RXD 4 2 TXD
TXD 3 3 RXD
CTS 7 4 RTS
RTS 6 5 CTS
6 DSR
8 DCD
DSR 2 20 DTR
4--40 jack
screws RJ45 jack chassis 8 1 chassis
(8x8) ground ground
39.6 mm
(1.56 in) pin 1
P
parent/child concept
with 512/612, 4
with 512/612 serial I/O, 49
R
relay output specifications, 32
S
specifications
base unit, 13
fixed I/O, 18
T
triac output specifcations, 35