MANUAL
SmartDGA
Confidential Information
The material contained herein consists of information that is the property of LumaSense
Technologies, Inc. and intended solely for use by the purchaser of the equipment described in this
manual. All specifications are subject to change without notice. Changes are made periodically to
the information in this publication, and these changes will be incorporated in new editions.
LumaSense Technologies, Inc. prohibits the duplication of any portion of this manual or the use
thereof for any purpose other than the operation or maintenance of the equipment described in
this manual, without the express written permission of LumaSense Technologies.
Copyright
LumaSense Technologies 2016. All rights reserved.
Trademarks
SmartDGA, SmartDGA Guide, SmartDGA Gauge, SmartDGA Guard, SmartDGA EZHub, LumaSMART
iCore, DGA Viewer, SmartDGA Diagnostics Software, and LumaSMART are trademarks of LumaSense
Technologies, Inc. All other trademarks are trademarks, registered trademarks, and/or service marks
of their respective holders.
Service Centers
LumaSense Technologies, Inc. LumaSense Technologies GmbH
North America Other Than North America
Sales & Service Sales & Support
Santa Clara, CA Frankfurt, Germany
Ph: +1 800 631 0176 Ph: +49 (0) 69 97373 0
Ph: +1 408 727 1600 Fax: +49 (0) 69 97373 167
Fax: +1 408 727 1677
E-mail info@LumaSenseinc.com
support@LumaSenseinc.com
eusupport@LumaSenseinc.com
Website http://www.LumaSenseinc.com
Part No 515-0012-01
Revision A
July 2016
Contents
1 General........................................................................................................................... 7
1.1 Information about this Manual ............................................................................ 7
1.2 Legend ................................................................................................................... 7
1.3 Limit of Liability and Warranty ............................................................................ 7
6 Plumbing ...................................................................................................................... 20
6.1 Transformer Valves ............................................................................................. 20
6.1.1 Drain Valve ........................................................................................................ 20
6.1.2 Fill Valve ............................................................................................................ 20
6.1.3 Ancillary Valves.................................................................................................. 20
6.2 SmartDGA Valve Kits........................................................................................... 21
6.2.1 Single Valve Kit (VA-1) ...................................................................................... 21
6.2.2 Dual Valve Kit (VA-2)......................................................................................... 21
6.2.3 Inline Valve Kit (VA-0) ....................................................................................... 22
6.2.4 Optional Extra Valve with Tee .......................................................................... 22
8 Tubing .......................................................................................................................... 29
11 Communications.......................................................................................................... 39
11.1.1 RS845 Connection.............................................................................................. 40
11.1.2 Ethernet Connection ......................................................................................... 40
11.1.3 Data Communications ....................................................................................... 42
Index .................................................................................................................................. 75
1.2 Legend
Note: Indicates tips and useful information in this manual. All notes should be read to
effectively operate the instrument.
If LumaSense Technologies will be performing the installation of your SmartDGA system, you will be
required to verify that you have completed all the necessary pre-installation tasks as explained in
this manual before an installation can be scheduled. Mark the checkbox next to each of the tasks
listed below that you have completed and then sign and submit a copy of this page to your RSM.
Task Description Done N/A
Identified an appropriate mounting location and transformer valve(s) for connecting the SmartDGA
Instrument(s)
If necessary, appropriate reducers and/or adapters have been installed on the transformer valves
Appropriate valve kit(s) has been chosen for mounting/connecting each SmartDGA Instrument(s)
If using an Inline (VA-0) valve kit, installed any necessary hardware (such as Unistrut) for supporting
the mounting plate
If using a Dual Valve (VA-2) or Inline (VA-0) valve kit, appropriate length of stainless steel or flexible
tubing is ready on-site
If necessary, a stainless steel tee and extra valve has been installed on the drain valve
If using a NEMA 4X enclosure, all communication and relay cables are ran to it using conduit
If not using a NEMA 4X enclosure, power is ran to the EZHub location using conduit
If not using a NEMA 4X enclosure, power is ran to the iCore location using conduit
If necessary or desired, an outage has been scheduled and approved for the installation date
All necessary tools for the installation (not provided by LumaSense) are ready on-site
I confirm that this pre-installation manual has been reviewed and understood in its entirety and
that all necessary site preparation tasks have been completed (as marked above) in order for
LumaSense Technologies to proceed with the installation of our SmartDGA System.
Note: The LumaSMART iCoreTM is not required to operate the SmartDGA system.
Note: The installation of any sunshade(s) must be done by the customer after the
installation of the SmartDGA system.
Instrument Specifications
Enclosure Rating IP 55
Green - Normal
Sunlight visible indicators for condition Yellow - Caution
codes
Blue - Warning
Red - Alarm
Note: Indicators normally flash on for 5 seconds,
Red/Blue - System Status Error
off for 15 seconds
Green/Yellow - Loss of Communication
Environment
TM TM
SmartDGA Instrument SmartDGA EZHub LumaSMART iCore
Storage Humidity
1 99% RH 1 99% RH 1 99% RH
(non-condensing)
Dimensions
20.9 x 8.6 dia. 10.3 x 5.7 x 6 8.7 x 7.4 x 6.6
(L x H x D)
Optional Communications IEC61850 Edition 2, DNP3 IEEE Std 1815-2013, ModBus RTU V1.02,
(Modbus available with PC, others available with iCore) ModBus TCP/IP 1.0b protocols for up to 3 EZHubs
Relay Contact Ratings Single phase alarm relays (8 A, 250 VAC; 5 A, 30 VDC)
Outage needed
if < 4m from an
energy source
Caution: Never sample oil directly from the LTC to the SmartDGA Instrument.
A side stream of oil is connected from the LTC tank to the Filmax filtration unit.
The SmartDGA Instrument will then sample the filtered oil from the FIlmax filtration unit.
Fill Valve
Ancillary Valve
Drain Valve
Note: This valve should never be used to sample oil from the transformer because there
is no guarantee that oil will always be at this position.
Note: This kit is only compatible if the drain valve is a ball, gate, or plug valve.
Note: This mounting approach has inherent limitations and risks and should only be used
when the VA-0 and VA-2 options are not viable.
Drain Valve
Fill Valve
Drain Valve
Plug
Tee
Note: If the thread type for the drain valve is greater than 2 NPT, please contact
LumaSense for additional options (such as an adapter plate or fire hose adapter).
LumaSense offers two types of reducers, but they must be ordered separately:
2 to 1 NPT Reducer (LumaSense PN 90-2382)
1.5 to 1 NPT Reducer (LumaSense PN 90-2381)
LumaSense offers two types of reducers, but they must be ordered separately:
2 to 1 NPT Reducer (PN 90-2382)
1.5 to 1 NPT Reducer (PN 90-2381)
Note: If the thread type for the drain valve is greater than 2 NPT, please contact
LumaSense for additional options (such as an adapter plate, fire hose adapter, etc.).
LumaSense also offers a Swagelok adapter (PN SS-600-1-16) that will thread into a female 1 NPT
reducer and accept 3/8 tubing, but it must be ordered separately.
7.3.3 Distance between the Drain Valve and Return Valve
To ensure proper oil flow and pressure, the following distance requirements from the drain valve to
the return valve must be met.
Vertical distance from the drain valve to the return valve 3 to 20 (0.91 m to 6.1 m)
Piping distance from the drain valve to the return valve < 32.8 (10.0 m)
Example of connection to the Filmax Example of the connections on the Filmax filtration
filtration unit with stainless steel tubing. unit before connecting to the SmartDGA instrument.
When mounting with the VA-2 or VA-0 valve kits, 3/8 stainless steel tubing should be used for
connecting the SmartDGA instruments to valves on the transformer or LTC filtration unit.
Rubber pipe clamp needs to be used to secure the stainless steel tubing and you should never have
more than four (4) right angles for each connection from the DGA instrument to the valve.
Alternatively, flexible tubing can also be used.
Warning: Do not cross the top of the tank when routing tubing.
Note: Stainless steel tubing is not available from nor provided by LumaSense for
installation. Ensure you have enough tubing on-hand prior to installation.
Example of stainless steel tubing Example of stainless steel Example of stainless steel
installed and bent using tubing installed and bent tubing installed and bent
right angles. without using right angles. using various angles.
5.00
(127 mm)
5.00
(127 mm)
Caution: If mounting the EZHub in a NEMA 4X enclosure, keep in mind that direct
sunlight can cause temperatures to reach above the maximum rated ambient
temperature of 55 C, in which case it is recommended that you install a separate
sunshade over the NEMA 4X enclosure after installing the SmartDGA monitoring system.
A shaded installation location is recommended.
Note: If you will be mounting the EZHub unit in a NEMA 4x enclosure, you will need to
mount the enclosure on a wall, Unistrut stand, or Unistrut H-frame prior to installation.
Note: If you will be mounting the EZHub unit in a substation control building or a
transformer control cabinet, you will need to mount the EZHub unit prior to installation.
EZHub mounted in NEMA 4X EZHub mounted in NEMA 4X EZHub mounted in control cabinet
enclosure on a wall enclosure on a Unistrut Stand near the transformer
Note: The communication cable provided will be unterminated on one end so that it can
be fed through conduit (if desired), cut to length, and then terminated (with two
provided Phoenix connectors). Any conduit needs to be laid down prior to installation.
Note: LumaSense provides connectors but does not supply a power cable for the EZHub.
Caution: The mounting position and location chosen for the iCore should ensure that the
vents on the top of the iCore box will not be blocked during normal operation. Blocked
vents could cause the iCore to overheat.
Caution: Direct sunlight will cause heating of the enclosure and may cause overheating
beyond the temperature rating of the iCore.
6.58
(167.13 mm)
5.58
141.73 mm
10.07
(255.78 mm)
5.74
(145.80 mm)
5.25
(133.35 mm)
9.4
(238.76 mm)
Note: LumaSense provides connectors but does not supply a power cable for the iCore.
Data stored in the EZHub can be viewed using the DGA Viewer software installed on an external PC
or the LumaSmart iCore connected via RS485 or Ethernet connection. The USB connection is for
uploading and downloading functions (such as downloading data or uploading a new version of
firmware). Depending on your needs protocols may also be used for communications.
Example of an EZHub unit and iCore Example of all the EZHub connections for
controller connected to an Ethernet switch. power and communications.
Note: If using an Ethernet Switch for multiple EZHubs connected to the iCore, you will
need one port for the iCore, one port for the network, and one port for each EZHub.
Note: If fiber optical cables are needed, the all-weather fiber optic should be used with a
rugged jacket. In addition, the fiber optic cables need to be routed into the trench or if
outside, the cables need to be protected with black PVC pipe or flexible conduit.
Note: We do not support the 32 bits system and other wireless connection beside DeltaX.
All SCADA/DCS, PLC systems should communicate via iCore with DGA viewer installed.
Note: The protocols must be updated to the latest version(s) in order to be compatible
with the EZHub.
NEMA 4X enclosure is
attached to Unistrut
mounted on the side of
the Filmax filtration unit
NEMA 4X enclosure is
mounted to the same
Unistrut H-frame as the
SmartDGA Instruments
Unistrut H-frame is
supported by two stand
bases attached to concrete
13.1 Installation
Installation can be done by LumaSense Technologies or a certified contractor.
Ensure you have all the necessary parts and tools on hand prior to installing your SmartDGA system.
4 HOLES
3/4" Diameter
6
4 1/4"
Item Description
1 ENCLOSURE,MODIFIED,NEM-4,DGA
8 LABEL,SERIAL NUMBER,LUXTRON
9 ASSY,OPTION,NEMA-4,DWG,DGA
13 FOAM,SENSOR
15 BAG,4 x 6,RESEALABLE,4MIL
17 WASHER,#10,FLAT,STAINLESS STEEL
18 WASHER,10-32,SPLIT,SS
Note: The LumaSMART iCore is optional and is not required for the SmartDGA system.
Note: The LumaSMART iCore is optional and is not required for the SmartDGA system.
A
I
Ancillary Valves 20
iCore 71, 72
iCore Dimensions 35
C Inline Valve Kit (VA-0) 22
Certifications 15 Installation Services 49
Clearance 23
Commissioning Services 50 M
Communications 39
Minimum Clearances 23
Communications Cable 32
Mounting Clearance 23
Criteria
Mounting Examples 43
Dual Valve Mounting (VA-2) 25
Mounting for the EZHub 31
LTC 17
Mounting for the iCore 35
LTC Inline Mounting (VA-0) 27
Mounting for the SmartDGA Instrument 23
Single Valve Mounting (VA-1) 24
Mounting Plate 26, 27
Transformer 17
Transformer Inline Mounting (VA-0) 26
Tubing 29 N
NEMA 4 56, 58, 60
D NEMA 4X Enclosure 10, 32, 35, 46, 54, 57
NPT Reducer 24, 25
Data Communications 42
Drain Valve 20
Drawings and Diagrams 53 P
Dual Valve Kit (VA-2) 21
Plumbing 20
Power for External Computer 37
E Power for the EZHub 33
Power for the iCore 37
Ethernet 72, 73
Pre-Installation Tasks 8
Ethernet Connection 36, 40
Extra Tee (optional) 22
Extra Valve (optional) 22 R
EZHub 32, 65, 73
Required Tools 51
EZHub Dimensions 31
RS485 71
RS485 Connection 36
F RS845 Connection 40
Fill Valve 20
S
G Single Valve Kit (VA-1) 21
SmartDGA Dimensions 23
Gas Pathways 73
SmartDGA Instrument Dimensions 53
Gauge 9
SmartDGA Valve Kits 21
Guard 9
Specifications
Guide 9
Certifications 15
Environment 13