Pre-fault:
Healthy voltages and load current
Fault: fault voltages and currents.
ABB AB, 2007
SOTF
IED 670 Directional Measurement is based on memory voltage, to ensure correct
directional detection even at close-in faults, where the level of faulty voltages is too
low to ensure a correct measurement of the phase angles (directionality).
SOTF
Switch onto fault must also know that the Circuit Breaker is going to be closed. This
is done by an external signal (Close Command to CB) or by Automatic Dead Line
Detection.
DeadLine
Detection
ABB AB, 2007
SOTF
Information that Circuit Breaker is going to be closed can be done by an external
signal (Close Command to CB).
When CB is going to be closed SOTF opens one time-window of 1s. If during this
window a non-directional fault (ZM02-STND) is detected THEN SOTF-TRIP signal is
issued.
ABB AB, 2007
SOTF
Information that Circuit Breaker is going to be closed can be done by built-in dead line
detection.
When Dead Line Detection signal goes from 1 to 0, one time-window of 1s (default
value) is opened. If during this window a fault is detected (UI Level algorithm) THEN
SOTF-TRIP signal is issued.
ABB AB, 2007
SOTF
Time delay: to avoid that too fast auxiliary Normally Closed CB contacts enable SOTF before
the tripped protection function (and also ZM02-STND) resets with consequence the A/R
attempt is blocked by SOTF.
ABB AB, 2007