PRECISION PLASTIC INDUSTRIES PVT LTD.

TEST REPORT IS : 3419

Size: 25mm Dp Junction Box 1/2/3/4 Way Date: 08/04/2017


Batch No : 171471
DETAILS OF
NO. OBSERVATION REMARKS
TEST
Visual
Examination
1. Smooth Finish Confirms
& Construction
Cl. 5
Marking Spout Type J Box, Logo Precision India ISI
2. Confirms
Cl. 2 Logo 25mm
Dimension Test All accessories are checked with 25 mm OD
3. Confirms
Cl. 6 conduit as per IS:9537 Part 3
Resistance to Heat Cl. 10 Required
Cut a sample of suitable Specification
size Sample & support are
placed in even at 600 C for The diameter of
4. 2 hrs and a force of 2 Kgs. impression should 1.5mm 1.6mm 1.4mm
Applied with steel ball of not be more than
5mm diameter upto 1 2mm.
hour. Then diameter of
impression is measured.
Resistance to Impact Cl.
16
The filling is held against a
The sample shall not
solid wall birck of
5. show damage or No Cracks
concrete. The test
cracks to naked eye.
apparatus is so arranged
and a hammer with 1Nm
id applied.
Moisture Absorption Cl.
12
One sample is kept in oven
The increase in
at 600 C for 24 hrs. Then
weight of sample
cooled to ambient
6. corresponding to Less than 1%
temperature. Dry weight is
moisture absorbed
noted then immersed in
shall not exceed 1%.
water for 24 hrs. and once
again after drying weight
is noted.
Test for Chemical Action
Cl. 13
a) Acid solution 330 ml
There should not be
of HCL diluted to 1 No No
7. any sign of
ltr. detoriation detoriation
deterioration.
b) Alkaline solution 80
gms of NaOH diluted
to 1 ltr period 1 week.
Copper Test Cl. 14
There shall be no
Copper strip of 25mm
evidence of
8. width wound 3 turns on No formation of copper salts
formation of Copper
specimen and kept in oven
salts on specimens.
at 1200 C for 7 hrs.
The OD shall not
Resistance to Oil Cl. 15
differ from original
One specimen kept in oil Less than2%. No penetration
9. OD by more than
bath at 600 C for 48 hrs. of oil
5%. There should be
and then cooled to 270 C.
no penetration of oil.
Resistance to Burning Cl.
11
The flame should
One sample is damped to No No No
10. die out in less than
the stand and brought in flame flame flame
30 seconds.
contact with Burner for 1
minute.
Dielectric Strength Cl.
17.2
Al entries except one are
plugged and filled with
sphenoidal metal and the
There should be no
11. sample is kept in a No break down
break down.
container filled with
sphenoidal metal and
2500V AC is applied
between the terminals for
15 mins.
Insulation Resistance Cl.
17.3
With same arrangement as The insulation
12. above a 500V DC is resistance should be 380 M
applied between the more than 100M.
terminals at 600 C for 1
minute.

Production: 3000 pcs


Approved By