Beruflich Dokumente
Kultur Dokumente
SOLENOID VALVES
2-Way Solenoid Valves 201-216
3-Way Solenoid Valves 301-310
4-Way Solenoid Valves 401-406
Manual Reset Valves 501-502
Electrical Latch & Release Type Valves 505-506
lntrins~cSafe Valve Operators 507-508
212 Pulse & P~lotValves 509-512
212 Way Washing Machine Valves 513
212 Way Fuel Oil Valve 513
212 Dual Coil, High & Low Flow Solenoid Valves 514 -
312 Dual Coil, Redundant Control Valves 514
212 Way External Pilot Solenoid Valves 515
- - - - - - - - - - - - - -
Direct Acting1
PortsIPositions Function Pilot Return Pilot
solenoidlair spring
6 o
6 .chlorine.
,,NEOPRENE: U s e d on alcohols, m i l d a c i d s , w a t e r , air, a c e t o n e ,
a m m o n i a , a r g o n g a s and o t h e r g a s e s ; A l s o in u s e o f refrigeration
TEFLON: G o o d a s a s e a t i n g material for l a r g e s i z e valves. A l s o
g o o d a s d i s c material for u s e o n c o r r o s i v e fluid w h e r e all synthetic
r u b b e r fail. S o m e l e a k a g e i s e x p e c t e d w h e n u s e d o n g a s ; a l s o s o m e
s y s t e m and c r y o g e n i c s y s t e m . slight l e a k a g e will b e e x p e r i e n c e d w h e n u s e d o n liquids.
I
Acetic Acid
I Qualifying Service
information
Pure Liquid (glacial) not as
1 Materials of Construction
and 0rderi"g Information
Stainless steel normally
I
Benzene-Bensol
1 Qualifying Service
Information
Coal-tar solvent or additiveto
I Materials of Construction
and Ordering Information
Standard cataloguevalves
I !
CH3COOH corrosive as diluted. closed valves except with CsHs motor fuels. Attacks most except Viton disc and gasket;
ethylene propylene elastomers. add suffix "V" to catalogue
elastomers. Add suffix "E" number.
to catalogue number.
Butane One of the principal LPgases. Special construction required.
Acetone Flammable solvent. Not Standard catalogue valves CH
,, Used as fuel for household and Use suffix 'V" to catalogue No.
CH3COCH3 corrosive to most metals. except with etylene other industrial purposes. Also a
propylene elastomers.Add refrigerant and a propellant in
suffix " E to catalogue , aerosol cans.
Number. Teflon or metal
seated valves also used. Carbon Dioxide Used in industrial refrigeration, , For gas pressures below 7 Bar
(Gas or Liquid) refrigeration of foods and use standardvalves with
Acetylene
HC = CH
Colorless gas. Highly
flammable. Used in welding and
Standard catalogue
aluminium, brass, Steel or
COP carbonatedbeverages. Also, as a
fire extinguisher and inert - BunaUN"discs.
cutting equipment. If moisture is stainless steel valves, and atmosphere in welding equipment. Above 7 Bar use specially
present Copper.Silver and alloys specify aluminium shading designed valve forthis service.
containingmore than 66% copper coil. Group iI C Coil (Only 118" available)
are not suitable. enclosure necessary.
Carbon
Air, Lubricated Mostsources of air carry Standard resilient seated valves except with Teflon or
lubricationfrom pumps and other cataloguevalves. Viton discs. Add suffix 'T"
equipment. Others are directly
lubricatedin lines.
in well ventilated areas.
Toluene One of the coal-tar solvents. Standard cataloguevalves Water, A purilied Water, sometimes called Stainless steel valves except
(Toluol) Used in aviationand high octane except with Viton disc and Distilledor deionizedwater, neutral and free with ethylene propylene
CHJCBHS gasolines. Alsoa solvent for gasket; add suffix "V" to Deionized from contaminants. elastomers. Add suffix " E
paints, coatings, resins etc. It is a catalogue number. tocatalogue number.Tellon
flammable liquid. and metal seated valves also
used.
Trichloro- Common degreasing solvent.
ethylene non-combustible,but very toxic. valves if dry, except use Standard resilientseated
CHCI :CCI 2 Requires adequate ventilation. Viton elastomers add suffix catalogue valves. However,
"V" tocatalogue number. If areatedwater which is slightly
moisture is present, use acidic will cause seat erosion
stainlesssteel. Metal andTeflon by process known as
seated valves also used. dezincification.Stainless steel
or plastic valves should then
Turpentine Solvent or thinner lor paints, Standardresilientseated be selected.
varnishes and lacquers. Also a catalogue valves.
rubber solvent and reclaiming Water, High When handling water to, generally Special designs for car wash
agent. The liquid is volatile. Pressure above 500 psi erosion and water applications, etc. Consult
fruits, orplants, such as Ground seated valves. 9ZC this change of state in
Nut oils, cottonseedoils, etc. unlikely.
Vinegar A dilute impure solutionof Stainless steel valves except Water, Sea Difficult to handledueto Use appropriate ball valve
ac6tic acid. with V i t ~ n e l a ~ t ~ mAdd
er~. Brine Brackish galvanic corrosion. with Rotary Actuators &
suffix 'V" to catalogue number. AVCON air pilot valve.
Water. Boiler Commonlytreated water with Standardstainless steel
Feed inhibitorsto avoid corrosion of catalogue valves.
boiler tubes.
.. . .
Cross Sectional Views of AVCON Solenoid Valves
mater~alselection
t 212 Way Pilot Diaphragm I 2/2 Way Pilot Piston, I
Je must be treated ,
There are a num-
such as tempera-
and concentration !
:an change a satls- ,
g ~ntoa Falr (F) or
U) l ~ s t ~ n g
7
gravlty air 1
ited 1 bar absolute
c gravlty water = 1
FIG RA FIG 3R
'1 412 Way Pilot Poppet Single Solenoid 1 412 Way Pilot Poppet Double Solenoid 1
412 Way Spool Type Single Solenoid
PRIN(:
Solenoi
1
1
1. Mag
stati~
1 stair
3 coil
FIG. 9 A FIG 9 B
1 conr
field
net,
mag
pull
coil
-
412 Way Spool Type Double Solenoid
ERGISED
3
dow~
sagt
2 Bod1
forgi
syntl
11 asse
, mon
? Soleno~
'
i
I b~oadc
A) Dlre~
B) Inter
FIG 1 0 A FIG 1 0 B I hrag
& 2E
C) Inter
Type
I 7B, E
D) Man1
E) Eleci
Type
TYPE
HOW'
$ The Sol
.ate,
.For exa
can be
i 2/2 Dil
corpora
closes t
3 or norm
1 these v
o r.~. f ~ sc e
2/2 Pi1
These :
less anc
- 4-
I are in T\
A) Main
closc
Qs) PI~o
or nc
Manufactured bv:
orific
AVCON' CONTROLS PVT. LTD. ates
23/24, New Nandu lndustr~alEstate, Mahakali Caves Road,
Andheri (East), Bombay-400 093. Tel No 6349134,6345489.
Tlx. No 011-79044, ACPL IN, Tele Fax 022-632 5851, GRAM. MOTORVALVE, Bombay-93.
110-5-88
I
3 AVCON SOLENOID VALVES
ENGINEERING INFORMATION
AND DATA
I
Solenoid Valve. On energisation - action reverses.
TYPE OF SOLENOID' VALVES AND These valves are also again available in dual coil
HOW VALVE WORKS: execution.
The Solenoid Valves have 21314-ports and are desig-
nated by number of main port and number of positions. 412-Way - Spool and Sleeve Type Valves :
For example - 212, 312, 412, 413. The Solenoid Valves (refer fig.9)
Class of insulation Ambient and fluid temp. rise Temp. due to El. supply Allowable max. temp. rise
"C "C including ambient.
F 75 80 155%
H 100 80 lab%
TABLE 2
TYPE OF COILS (SQUARE SERIES)
TABLE 3
TYPE OF COILS (ROUND SERIES)
Co~l
code no. lnsulat~onclass Power ratlng
AC DC
P5
5000
F
ForH
10
10
10
10
1 THE MINI
Normal
P 75 For H 22 30 gree cel
times, w
r
Most of the AVCON valves are supplied with Class 'F' coils. Whenever valve application is for higher fluid temperature ble amb
or higher ambient temperature, use of Class 'H' insulated coil is recommended. Consult AVCON Factory for advice. bient ter
termine:
TABLE 4 maximu~
COIL ENCLOSURES (AVAILABLE) AND CODE NOS: 1 undercc
I fluid terr
AVCON General' Waterproof Protection 'Flameproof Group IIA. Flameproof Group IIC.
Magnetic Purpose Class IP-55. IP-56, llB as per IS 2148, as per IS2148,
construction Protection IP-65. IP-67 as per Waterproof upto IP-67, Waterproof upto IP-67 can be F
Ref. No. IP-20as per IS 2147, Dustproof as per IS 2147. Dustproof as per IS 2147, Dustproof Sales.
IS2147 as per IS 4012 and Dust as per IS 4012 and Dust as per IS 4012. Dust
Tight as per IS4013 Tight as per IS4013 Tightas per IS 4013
(1) (2) (3) (4)
M-30 M30 - -
M45-1 (SQ.L RD.) M45-1(SQ. L RD.) WP-M45-1-IP-67 FLP-M45-1-IIB FLP-M45 -110 .
M45-6(SQ. L RD.) M45-6 (SQ. L RD.) WP-M45-6-IP-67 FLP-M45-6-llB FLP-M45-llB The Lette
M50 (SO. 8 RD.) M-50 (SQ. L RD.) WP-M50-IP-67 FLP-M5O-IIB FLP-M5O.-IIB i -The firs
5000 5000 5000-WP-67 5000-FLP-llB 5000-FLP-llC objects
P5 P5 P5-WP-67 P5-FLP-IIB -
Standard)
NOTES:
1. Approx. confirming to NEMA 1 & 2.
2. Approx. confirming to NEMA 3. 3R. 35. 4. 4X. 5.
3. Approx. confirming to NEMA 4. 7C. 7D. NEC 500 Class I Div 2. Group C & D.
4. Approx. confirming to NEMA 4, 7. 9. E. F;G. Class 1. Div. II. Group A & B. Class II. Div. II, Group E. F, G.
SOLENOID VALVE
CONSTRUCTIONS:
Internal parts which are in contact with the fluid are magnetic construction, can be used for D.C. with cer-
made out of Brass or series 300 and 400 Stainless tain restrictions, but NOT viceversa. AVCON core
steel. Shading ring is fixed as per requirement of fluid. tubes are one piece design and are welded to station-
However, standard shading ring is made out of cop- ery magnet at the top by micro plasma Tig welding
per. No shading ring is provided in D.C. design. A.C. process. This makes sound joint.
MINIMUM OPERATING SPECIAL SUFFIXES USED
PRESSURE DIFFERENTIAL: FOR FEATURES:
Minimum operating pressure differentialis-which requires Refer to Table on pagel07.ln order to facilitate produc-
,.to open the valve and keep it open: Direct Acting and tion engineering and indication to simplify supply
Semi-lift type diaphragm or piston valves, do nor re- code, AVCON uses various suffixes to the valve
quire minimum pressure differential. 2-Way Pilot Oper- catalogue numbers. Useof suffixes is limited to certain
ated Valves with piston or diaphragm, will start closing conditions. Many a times, depend on application en-
below indicated minimum pressure differential. 3- gineering.
Way, and CWay, Pilot Operated Valves, minimum
pressure differential is to be measured between the SEISMIC CAPABILITY:
inlet and exhaust ports. The indicated minimum pres- Number of valves from AVCON range are tested and
sure differential figures must be maintained through- are capable of withstanding Seismic vibration test.
out the operations to ensure complete change over This capability ensures that AVCON Solenoid Valves
from one ~ositionto other. can operate during and following a simulated ear-
thquake. The testing applies with IEEE standard (IEEE
MAXlMLlM OPERATING PRESSLIRE recommended practices for seismic qualifications of
DIFFERENTIAL: Class IE equipment for Nuclear Power Generating Sta-
Maximum operating pressure differential is - a diffe- tions.) For specific seismic test data on particular
rential pressure between the inlet and outlet sides of valve, Consult AVCON Sales.
the valve,against which solenoid can safely operate.
For practical purpose - working pressure mentioned RESPONSE TIME:
in the leaflet is considered to be maximum operating Response time from fully closed to fully open position
pressure differential. or vice-versa, is depending on valve size, operating
mode, electrical characteristics, fluid, pressure, temp-
SAFE WORKING PRESSURE: erature, pressure drop and many other factors. Indica-
Many a times regarded as caie body pressure, to tive response time for A.C. Valve on air service can be
which the valve can be safely subjected to, without generalised as under:
causing damage to the valve. Safe working pressure Direct Acting Small .............................5 to 20 ms
for any valve can be three to five times of maximum Valves
operating pressure differential. Direct Acting Large
Valves ......................................... 20 to 50 ms.
'TEMPERATURE LIMITA'I'IONS: Internal Pilot Operated and
THE MINIMUM & MAXIMUM AMBIENT TEMPERATURE semi-lift valves, small
Normal limitation for minimum temperature is 'O'de- diaphragm type valves .....................15 to 18 ms.
gree centigrade, where moisture is present. Many a Large diaphragm
times, where moisture is not a factor minimum tolera- type valves ..................................... 50 to 100 ms
ble ambient temperature can be -5C. Maximum am- Small Piston type
bient temperature is listed in Table 1 , which also de- valves .................... .... ................ 50 to 125 ms
termines safe limitations for coil insulation. The Large piston type
maximum operating temperatures is determined valves ........................................... I 0 0 to 200 msecs.
under continuous energised conditions with maximum DC valves will increase the operating time approxi-
fluid temperature existing in the valve. Under certain mately 50% over indicative A.C. valve timings. In case,
conditions, maximum ambient temperature limitation where response time is critical, Consult AVCON with
can be extended upto 100C. Please Consult AVCON complete details; perhaps response time can be im-
Sales. proved to meet special application conditions.
I
i I
! STANDARD OF PROTECTION FOR ELECTRICAL HOUSINGS
,
;
ASPERIS2147of1962
The Letters IP (degree of protection) followed by 2 f~gurese.g. IP 54
I
1
:j -The first figure shows the standard of protection of the energised parts and internal moving parts against penetration by foreign
objects
-The second figure shows the standard of protection against penetration by liquids.
IP 1st Figure Abridged definition 2nd figure Abridged definition IP 1st Figure Abridged definition 2nd figure Abridged definition
I I I I
IP 0 Noprotect~on 0 No protection IP 4 Protection against solid 4 Protection against
bod~es0 greater than cascading water
1 mm
I I
IP 1 Protection against 1 Protection against 5 Protection against
solid bodies 0 vertical drops water jets
greater than 50 mm of water
I Protection against
drops of water
u~to 15'anale from
Dust sealed completely Protection against
sea water or simllar
Protected against
IIPI
3
I
effects of immersion
Can be operated
under water
I
NOMOGRAPHS (Kv FLOW CHARTS) j 1. A s t
rate
eg
FLOW CHART STEAM
The rate of flow of a flutd or gas through the valve or system 1s 2 If th
Qm = 22 the
determined by uslng data of system pressure, pressure dlfferentlal,
klnd of flu~d,vlscoslty, temperature and effectlve area of the orlflce 4,
Where = Q = Flow rate ln ~ ~ / h r
All these cr~ter~a, except effectlve area, and pressure drop are 9,
Qv = Volume of flow at standard cond~t~ons
~ndependentof the valve construction Both effectwe area and 16)
Qm = Mass flow In Kglhr
pressure drop can be speclfled by means of flow factor (Kv) A p = Pressure drop ~nbar 3 The
The flow factor expresses the relatlonshlp between the flow and Ps = Supply pressure ~nBar absolute (Ps + 1) Cor
pressure drop The Kv factor IS standard according to VDENDI 21 73 To = Amblent Temperature = 293K 4 If th
and IS deflned as flow In M3/hr of water at 5C to 30C, passlng Tl = Fluld temperature = 273 + t ("C) "K wat
through a valve, wlth pressure drop of 1 bar d = Speclflc Mass relatlve to water or
to alr (for gaseous medla)
Wlth the followlng formula the actual flow for any condltlon can be
calculated The dlmenslons of Kv values can be transposed
by means. of followlng factors
LIQUIDS
Q = Kv \
IF M3/hr (eq-1)
Kv (Umln)
Kv (M3/hr)
Cv (Galllmln)
= 16 7 x Kv (Wlhr)
= 0 06 x Kv (UMln)
= 0 07 x Kv (UMln) (In USA)
I Table
Kv = Q \IT
d (denslty)
(eq-1A)
Kv (UMln)
CV
Kv ((ln
~ USGPM)
~/hr) = 1
= 14 3 x Cv (GalllM~n)
Kv16
(M3/hr)
x Cv ( x~0USGPM)
n86
(In USA)
Q
Kv = (where A P < 0.5 P,-07 P1) (eq-2A)
512 x / m
Kv = ild
512 X P l
(where A P > 0.7P1) , (eq-2A)
To finc
the tat
I To finc
found
For flol
i EXAM
Specif
! Inlet PI
i Requlr
/ Solutio
, Note:
:\ minim(
may el
gases
j media
oy;sl; valve,
drop.
CRotes EXAMPLES:
: 1. As the flow rate is directly proportional to the Kv value, other flow Specified : flow rate 5 m3/hr Solution: under the column
rates can be calculated from the table by multiplying factors: water : A P 0.4 bar A P = 0.4 bar find 5 m3/hr.
e.g. given Kv value 0.01; read on table behind Kv = 1 and Required : Kv value Read Kv= 8 in the extreme
multiply the flow rates by 0.01. left hand column.
2. If the pressure drop is beyond the specifications of the table use 'Pecified : rate0.05 m31hr
: the following factors: AP5bar
Requlred : Kvvalue
4 x A P : multiply the flow rates from the table by 2
9 x A P : multiply the flow rates from the table by 3
16 x A P : multiply the flow rates from the table by 4
3. The table is valid for all fluids with a viscosity upto 65 cStokes.
-
Solution : the flow rate is beyond the table 1, multiply the flow
rate by 100 (100 x 0.05) = 5m3/hr) under the
column A P = 5 bar find 5 m3/hr. Read Kv value is
between 2 and 2.5. Divide the result b y 100.
Consult Avcon if viscosity exceeds 65 cStokes. Required Kv value is between 0.02 and 0.025.
, 4. If the given specific gravity is greater than the specific gravity of
--
water, multiply the flow rates of the table with
The flow rates specified in this table are normalized values of 2 WAY VALVES, STEAM SERVICE:
Kv = 1, for air of 20C only.
To find the actual flow for a given Kv, multiply the values, General description: Rugged forged brass Gunmetal and stainless
found from the table, by the specified Kv value. steel body valves for heavy duty steam service.
To find the actual Kv value for a given flow rate, divide the val- Applications: These dependable valves are used in laundry, dry
ues, found from the table, by the specified flow rate. cleaning, steam irons, steam atomization, sterilizers etc. I
For flow rate on steam, refer to Steam-section, Table 4. I
Installation: Valves of bulletin (2000 B)should be mounted with
EXAMPLE: solenoid vertical and upright.
i
Specified: Flow rate 4 M3/hr gas,lnlet pressure 10 bar, A P 3 Valve sizing: To find the actual flow rate for steam, the following
bar. Required Kv value. formula is used:
Solution: Find the flow of rate (for a Kv = 1) in the intersection
of the pressure drop column ( A P) at 3 bar and thecolumn P-
supply (Ps) at 10 bar. Read 138 m3/hr (Kv = 1). To find the ac-
tual Kv divide the specified flow rate (4 m3/hr) by the value
found for a Kv = 1 For explanation and further information on flow dafa, refer to
Actual Kv = -
138
= 0.029 Table-4. To facilitate quick selection of a valve for a given
dflow rate, the table specifies flow rate as a function of
pressure drop for a number of Kv values.
TABLE4 FLOW RATE FOR STEAM.
The flow rates specified in this table are normalized values EXAMPLE: Specified: Steam inlet pressure 10 bar, steam
for Kv = 1. temperature 180"C, allowable A P 0.5 bar, Kv value 5.6. Required:
To find the actual flow for a given Kv, multiply the values, actual steam flow.
found from the table, by the specified Kv value. Solution: Refer to table, find the flow (for a Kv = 1) in the intersection
To find the actual Kv value for a given flow rate, divide the of the pressure drop column ( A P ) at 0.5 bar and the column
(?-supply Ps) at 10 bar. Read 52 ~ ~ / hMultiplyr. this value by the
values, found from the table, by the specified flow rate.
specified Kv value to find the weight of steam: 52 x 5.6 = 291 kglhr.
Manufactured bv:
Kilometers 1
PRESSURE CONVERSIONS
ORIFICE SIZES
Common catalogue ORIFICE sizes and IS0 equivalents in mm.
TORQUE CONVERSIONS
inches mrn inches mm
K~logramForce 3 1 (0.0469)
~ 1.19 'Il6 (0.4375)
Obtain Inch Pounds
11.11
NewtonMeters Meters Foot Pounds
'Il6 (0.0625) 1.59 1', (0.5000) 12.70
kpm 5/M (0.0781) 1.98 5/8 (0.6250) 15.88
Newton Meters 1
-
0.1020
-
0.7376
-
8.851
3/32 (0.0937) 2.38 111q6(0.6875) 17.46
1', (0.1250) 3.18 314 (0.7500) 19.05
Kilogram ForceMeters 9.807 1 7.233 86.80 'I3, (0.1562) 1 (1.OOOO)
3.97 25.40
Foot Pounds 1.356 0 1383 1 12.00 ll/M (0.1719) 4.37 1118(1.1250) 28.58
Inch Pounds 0.1130 0.01152 0.08333 1 31,6 (01875) 4.76 1'1, (1.2500) 31.75
'132 (0.2187) 5.55 1'12 (1.50CO) 38.10
'Iq (0.2500) 6.35 13/4 (17500) 44.45
1'3, (0.2812) 7.14 2(2.0000) 50.80
5116 (0.3125) 7.94 3(3.0000) 1 76.20
Manufactured by:
SPECIFICATIONS
Sizes : 3 rnrn (118")to 15 rnm (112")
End connections : Standard - BSP, Optional
- NPT
Construction -body : Standard -Brass forged,
bar stock
: Optional -Stainless steel
casted, bar stock.
: Standard - Nitrile (Buna'N')
Optional - Neoprene,
Viton, others,
Differential pressure : 0 to 40 bar
Temperature of fluid : -5C to 80" C
7 Coil voltage : Standard - 230-volts,
50 Hz. A.C.
Optional -Any standard
A.C.1D.C.
voltage range.
Coil insulation : Ambient upto 75C ,
and temperature Class 'F' insulated
upto 155C
Class 'H' insulated
upto 180C
Coil rating : Continuousl rated
Enclosure 6
: Standard - eneral
Purpose IP-20 Sales ~ o i n t : Most versatile and
Optional - Weatherproof reliable valve for
upto IP-67, millions of trouble
Flameproof upto FLPTIB free operations.
-IIc. Applications : Furnaces, boilers, textile
Fluids : Air, water, gas, vacuum machinery, water
light and heavy oil, treatment plant,
corrosive fluids, etc. ash handling,
Optional features : Manual override, sugar machinery
mounting bracket. and others.
SPECIFICATIONS TABLE
2.2 WAY NORMALLY CLOSED
I CONSTRUCTION REF.: 2
*
CONSTRUCTION REF.:4
DIMENSIONS
Note:
Technical specification details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON
Manufactured by:
SPECIFICATIONS
Sizes : 3 mm (118") to 35 mm (1 l/2")
\ ,
SPECIFICATIONS TABLE
2/2 WAY NORMALLY CLOSED
DIMENSIONS
Note:
Technical specifications details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON
./ '.,
u.
Manufactured by
AVCON CONTROLS PVT. LTD.
23/24, New Nandu lndustr~alEstate, Mahakal~Caves Road,
Andher~(East), Bombay-400 093 Tel No 6349134,6345489
Tlx No 01 1-79044, ACPL IN, Tele Fax 022-632 5851, GRAM MOTORVALVE, Bombay-93
~ A - ~ - RR3 R
C, 212 Way Semi Pilot DATA SHEET
9230 A
Diaphragm Type Solenoid Valves 9230 D
NORMALLY CLOSED, ENERGISED TO OPEN. I
SPECIFICATIONS
Sizes : 10 mm (318") to 50 mm (2")
End connections : Standard -ESP, Optional
- NPT
Construction - body : Standard -Brass forged,
: Optional Stainless steel
casted
Diaphragm - seat : Standard - Nitrile (Buna'N')
Optional - Neoprene,
Viton
Differential pressure : 0 to 2 bar for 9230A and
0 to 6 bar for 9230D valves
Temperature of flu~d : -5" C to 80C
'--I Co~lvoltage : Standard - 230-volts,
50 Hz. A.C.
L-.- Optional -An standard
A.&D.c.
voltage range.
Coil insulation : Ambient upto 75O C
and temperature Class 'F' insulated
upto -155" C
Class 'H' insulated
upto 180" C
Coil rating : Continuously rated Sales point : High volume flow,
Enclosure : Standard -General low pressure application -
Purpose IP-20, Only normally closed
Optional -Weatherproof design available.
upto IP-67, Applications : Gas burning equipments,
Flameproof upto FLPIIB autoclaves, Oil centrifuge
-IIC. plants, Vacuum plants,
Fluids : Air, water, gas, vacuum Pump seal water
light oil, application, low pressure
water circulation system,
corrosive fluids, etc. solar heating system
Optional features : Manual override, Gas generator and other.
mounting bracket.
SPECIFICATIONS TABLE
212 WAY NORMALY CLOSED
PowerConsumption8Watt Rating
Class
Coil Type AC DC - of Protection
VA VA Insulation
Inrush Holding Watts.
M.45.1 (SQ. 8 RD.) 36 18 10 F GPNP IP.67
M.45.6 (SQ 8 RD.) 60 30 16.7 F GPNP IP.67
M.50 fSQ. 8 RD) 41 GPNP lp.67
80
- F
20 - -
500C 36 18 10 F.H GPNP IP.55 15.2148Group IIA. 110 upto IP 67
M.45 FLP I1BlIIC.1 36 18 10 F.H
IS.2148. Group. IA. IIA, IIB, IIC
M.45 FLP I1BlllC.6 60 30 16.7 F,H uplolP67
M.50 FLP 11B/IlC 80 41 20 F
P.5. 36 18 10 F GPNP IP 67
CONSTR. REF.: 79
Note:
Technical specification details & dimensions are subject to change without prior notice.
Dimensions in the table are. approximale subject to final confirmation by AVCON
Manufactured bv:
@ AVCON' CONTROLS PVT. LTD.
23/24, New Nandu Industrial Estate,.Mahakali Caves Road,
Andheri (East). Bombay-400 093. Tel. No. 6349134. 6345489.
Tlx. No. 01 1-79044, ACPL IN, Tele. Fax. 022-632 5851, GRAM: MOTORVALVE, Bombay-93.
206-5-88 R2
,?
/'
212 Way Pilot Operated DATA SHEET
9100 F
Diaphragm Type Solenoid Valves 9120 F
NORMALLY CLOSED, ENERGISED TO OPEN,
NORMALLY OPEN, ENERGISED TO CLOSE.
SPECIFICATIONS
Sizes : 6 mm (114") to 75 mm (3")
End connections : Standard - BSP,
Optional - NPT
Construction - body : Upto 50 mm (2") Brass
foraed and above in
_~r&z~casted.
Optional - Upto 30 MM
(1 1/4") in S.S. 304 casted.
Diaphragm - seat : standard - Nitrile (Buna'N')
Optional - Neoprene, Viton
and others.
Differential pressure :0,5tolObar .
Temperature of fluid ~-5"Ct0120"C
Coil voltage : Standard - 230-volts,
'
-L, 50 Hz. A.C.
Optional -Any standard
A.C.1D.C.
voltage range.
Coil insulation : Ambient upto 75" C
and temperature Class 'F' insulated
upto 155" C
Class 'H' insulated
upto 180" C Optional features : Manual override,
Coil rating : Continuously rated mounting bracket.
Enclosure : Standard - General Sales point : Most reliable, maintenance
Purpose IP-20, free, on-off valve
Optional -Weatherproof In our range.
upto IP-67, Applicat~on : Chemical, textile, cement
Flameproof upto FLP I[B machinery, combustion
- IIC . equipment, air dryer,
Fluids : Air, water, Qas,l i ~ hoil,
t cleaning equipment and others.
heavy oil, CorrosGe NOT SUITABLE
fluid, etc. FOR STEAM DUTY.
SPECIFICATIONS TABLE
4
.c.,
/2/2
,,
'
WAY NORMALLY CLOSED
I
7
Cod T v ~ e
VA
Power Consumpt~on& Walt Ratlng
AC
VA
DC
Class
01
Insulation
I Protect~on
CONSTR. 1 60 CONSTR. .
REF.: w . : i i P
Note:
Technical specifications details & dirnenslons are subject to change without prior notice
Dimensions in the table are approximate subject to final conflrrnation by AVCON
0
Manufactured by
AVCON CONTROLS PVT. LTD.
23/24, New Nandu lr~dustrlalEstate, Mahakall Caves Road,
Andher~(East) Bombay-400 093 Tel No 6349134, 6345489
Tlx No 01 1-79044 ACPL IN, Tele Fax 022-632 5851, GRAM MOTORVALVE, Bombay-93
208- 5-88 R2
3 212 Way Pilot Operated Piston Type DATA SHEET
9100 H
High Pressure Solenoid Valves 9120 H
NORMALLY CLOSED, ENERGISED TO OPEN,
NORMALLY OPEN, ENERGISED TO CLOSE.
SPECIFICATIONS
Sizes \ ,
I .
D~fferent~al
pressure
Temperature of flu~d
Cod voltage
2 to 30 bar
-5C to 120C
Standard - 230-volts,
50 Hz. A.C..
Optional -Any standard
A.C.1D.C.
voltage range.
Coil insulation Ambient upto 75C
and temperature Class 'F' insulated
upto 155" C
' Class 'H' insulated
upto 180" C
Coil rating : Continuously rated
Enclosure : Standard -General Sales point Highly reliable, compact,
Purpose IP-20, . .. maintenance free valve,
Optional -Weatherproof suitable for thousands
upto IP-67, of operations.
Flameproof upto FLPDB Applications Chemical, textile,
-IIC . petrochemical, water
Fluids : Air, water, light hydraulic oil, treatment, ash handling
hot water, corrosive system, combustion
medium, etc. eaui~mentetc.
Optional features : Manual override, NOTSUITABLE FOR STEAM
mounting bracket. DUTY APPLICATION.
!
0 SPECIFICATIONS TABLE
2/2 WAY NORMALLY CLOSED
CONSTR. REF.: 10
CONSTR. REF.: 1
DIMENSIONS
Pipe Pipe
Catalogue Size Constr. A Weight Catalogue Size Constr. A Weight
Number kgs. Number kgs.
(inch) 1 (inch)
9100H 10 318 9 86 16 127 57 1.700 19120H 10 318 13 86 16 148 57 1.950
Note:
Technical specifications details &.dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON
Manufactured by:
@ AVCON-CONTROLS PVT. LTD.
23/24. New Nandu Industrial Estate. Mahakali Caves Road,
Andheri (East). Bombay-400 093. Tel. No. 6349134. 6345489.
Tlx. No..011-79044, ACPL IN, Tele. Fax. 022-632 5851, GRAM. MOTORVALVE,Bombay-93
'3212 Way Pilot Operated DATA SHEET
9160 K
Diaphragm Type Solenoid Valves 9162 K
NORMALLY CLOSED, ENERGISED 'TO OPEN,
NORMALLY OPEN, ENERGISED TO CLOSE
SPECIFICATIONS
Sizes : 25 mm (1") to 100 mm (4")
End connections : Standard Flanged to ASA
150 RF.
optional - Other standards
Construction - body : Standard -Cast lron with
stainless steel seat,
Optional -Cast Steel
I -seat : Standard - Nitrile (Buna'N')
Optional -Neoprene, Viton
and others.
Differential pressure : 0.6 to 10 bar
Temperature of fluid : -5" C to 80C
: Standard - 230-volts,
50 Hz. A.C.
Optional -Any standard
A.C.1D.C.
voltage range.
Cotl ~nsulation : Ambient upto 75" C
and temperature Class 'F' insulated
upto 155" C
Class 'H' insulated
upto 180" C
Coil rat~ng : Continuousl rated
Enclosure : standard - 6eneral
Purpose IP-20,
1
O~tional- WeatherDr00f
upto IP-67,
Flameproof upto FLP IIB
-EC. Applications : Textile processing
Fluids : ~ i rgas,
, light oil, machinery, Sugar
Optional features : Manual override, machinery, silo fluidisation
Sales point : Flanged valve body in or wherever depeqdable
1 On-off type control is
I Cast lron materia1,reliable
and build around modular required. NOT SUITABLE
concept. FOR STEAM DUTY.
t SPECIFICATIONS TABLE
i
i 212 WAY NORMALLY CLOSED
d
I
e
1
1 212 WAY NORMALLY OPEN
DIMENSIONS
Note:
Technical spec~ficat~ondetails & dimensions are subject to change without prior notice
Dimensions in the table are approximate subject to final confirmation by AVCON
Manufactured by.
@ AVCON CONTROLS PVT. LTD.
23/24, New Nandu Industrial Estate, Mahakali Caves Road,
Andheri (East), Bombay-400 093. Tel. No. 6349134, 6345489.
Tlx. No. 01 1-79044, ACPL IN, Tele. Fax. 022-632 5851, GRAM: MOTORVALVE, Bombay-93.
: 3
-
212 Way Pilot Operated DATA SHEET
9160 P
Piston Type Solenoid Valves 9162 P
NORMALLY CLOSED, ENERGISED TO OPEN,
NORMALLY OPEN, ENERGISED TO CLOSE.
SPECIFICATIONS
1:
11
Sizes : 25 mrn (1") to 150 mm ( 6 )
End connections : Standard -Flanged
to ASA 150
O~tional-Other standard
flanges.
Construction - body : Standard - Cast Iron
Optional -Cast steel
-Piston : Brass bar stock or bronze
-seat : Teflon
Differential pressure : 2to25 bar -
Temperature of fluid :-5"Cto120"C
Coil voltage : Standard - 230-volts,
50 Hz. A.C.
Optional -Any standard
A.C.1D.C.
voltage range.
Coil insulation : Ambient upto 75" C
and temperature Class 'F' insulated
'upto 155" C
Class 'H' insulated
upto 180" C
Coil rating : Continuousl rated
Enclosure : standard - zeneral Sales point : Reliable and maintenance
Purpose IP-20, free, on-off valve in
Optional - Weatherproof Cast Iron -Cast Steel body
U D ~ OIP-67. with flanges.
~ i a m e ~ r oupto
o f FLPI[B Applications : Furnaces, boilers, textile
-TIC. machinery,treatment
Fluids : Air,gas, light oil, plant, ash handling plant,
Optional features : Manual override, sugar machinery plant, etc.
SPECIFICATIONS TABLE
212 WAY NORMALLY CLOSED