Indoor HT panel consisting of 13 Nos VCB's ( Incoming-3Nos , Bus Coupler-2 Nos,Outgoing 08 Nos)

11KV, 3 Phase, 50Hz, 800 Amps capacity, Indoor type ,Repturing capacity of 350MVA, over load and
earth fault protection, ammeter, Voltmeter, frequency meter along with bus riser to extend the bus bar
chamber of existing VCB to match with other VCB as per IEC 62271-100/200 with SCADA compatability
with existing protocol and including one bus riser panel for connection with existing HT copper bus bar
of 800 Amps along with all accessories including numerical over current and earth fault protection relays
complete all as specified and directed

(A) 11 KV Incomer Panel : Supply , installation, testing and commissioning of 11KV 800A, 18.4KA
incoming VCB consisting of

(a) Continues high conductivity electrolytic copper bus bar, Raychem insulated for full-voltage, phase
identification made at the end by coloured tape, bus bar shall be mounted on integral seal off bushing
and interconnection with electrolytic grade copper with joints silver plated.

(b) Circuit breaker shall be mounted on a withdrawable Truck which shall be horizontally draw out from
service position to isolated position.

(c) Motorised Spring Charged Mechanism.

(d) Cast Resin Current Transformer, 11 KV, 1000/500/5+5A, 15 VA, CI 5P10,CI0.5-3 Nos

(e) Cast Resin Three phase Potential Transformer 11 KV/1.732/110V/ 1.732, 100VA, CI 1.0 03 Nos with
desired capacity PT Fuses. (f) Accessories like local remote selector switch. Breaker Control
Switch (TNC), space, Heater with Thermostat, DC & AC Control Ckt through MCB, Indicating LED lamps
for R Y B Phases, Spring Charged, DC Supply Healthy, Breaker ON/OFF, Breaker in service , Test,
Disconnected position.

(g) Multi function meter Parameters: VLL, VLN, A, HZ, W, VA, VAR, PF (Total & Phasewise), Wh, Vah,
VARh inductive and capacitive), Load hours, ON hours and interruptions, with OLD register, % of THD for
current and Voltage, K factor, High Low values of VLL, A, HZ, W, VA, VAr, PF, neutral current display, % of
unbalance V&A for all phases. Accuracy Class : 0.2 Display: LED/LCD Mounting : Flush 1 No. L&T
(ER300N) / Elmeasure (EN8400LM) / Conzerv (EM 3360)

(h) 1 No of Feeder Protection Relay 50/51 (3 phase overcurrent), 50/51 N (Earth overcurrent), 67 P (3
phase directional overcurrent), 67 N (Earth fault overcurrent), 37 (3 Phase undercurrent), 46 (Negative
phase sequence overcurrent), 59 N (Residual over voltage), 32 (Directional power protection
(Under/Over active/reactive power)), 81U/O (Under/over frequency), 49 (Thermal overload), 79
(Autoreclose),50 BF (Circuit breaker failure detection), Cold load pick up, Inrush blocking, Relay will be
Modbus Protocol :-

(i) Numerical relay should be of bay control and protection unit type having built in protection,
measurement, bay control and monitoring features
(ii) Numerical relay shall have graphical LCD display with support single line diagram (MIMIC). Local
measurement, event and alarm views through its display.

(iii) The relay shall be of nature IEC 61850 designs thus offering optimal connection interface on the
61850-8-1 standard with KEMA Certificate level a for @ 61850 compliance and GOOSE communication.

(iv) The GOOSE signal performance has to be in accordance with type IA and fulfil the requirements of
class P1. Three transfer time of GOOSE interlock shall be less than 10 m sec (GOOSE performance class
P1 message type 1A).

(v) The number of binary inputs shall not be less than fifteen (15).

(j) High speed master trip relay - 01 No (k) Trip circuit supervision relay - 01 No (l) 800 Amps VCB, CT
Ratio : 200-100/5-5A

(k) Trip circuit supervision relay - 01 No eqv in ABB/Siemens/AREVA.


(l) PT fuse failure relay - 01 No eqv in ABB/Siemens/ AREVA

(m) Anti pumping relay (VAA 11) eqv in ABB or Siemens - 1 set

(n) Air insulated rear end bottom entry cable box suitable for termination of XLPE cables.

(o) panel must have additional features

(i) continuous rated closing/tripping coils

(ii) Spring charging handle

(iii) Fully internal arc tested for 40KA for 1 sec.

(iv) Manual closing/tripping of the VCB with compartment door closed

(v) Short time rating for 3 seconds as per IEC 62271-100

(vi) Mechanical endurance test - M2

(p) Breaker shall be provided with the following features : (i) Auxiliary switch 6 NO + 6 NC contacts
mounted on the draw out portion of the switchgear.

(ii) position cell switch with 3 NO + 1NC Contact one each for test position and service position.
(B) 11KV Bus Coupler Panel : Supply , installation, testing and commissioning of Bus coupler 11KV
18.4KAfor 3 sec HT Vaccum Circuit Breaker for incoming confirming to the IEC 62271-200.

(a) 800Amps Continues high conductivity eletrolytic copper bus bar, Raychem insulated for full voltage,
phase identification made at the end by coloured tape, bus bar shall be mounted on integral seal off
bushing and interconnection with electrolytic grade copper with joints silver plated.
(b) Circuit braker shall be mounted on a withdrawable truck which shall be horizontally draw out from
service position to isolated position with ease and model of HWX of SCHNEIDER or eqv in
Siemens/ABB/BHEL.

(c) motorised spring charged mechanism

(d) accessories like local remote selector switch, breaker control switch (TNC), space, heater with
thermostat, DC & AC control ckt through MCB, indicating LED lamps for R Y B Phases, spring charged, DC
supply healthy, breaker ON/OFF, breaker in service, test disconnected position
(e) master trip relay (VAJH 13) - 01 No eqv in ABB/Siemens

(f) Anti pumping relay (VAA 11) eqv in ABB or Siemens - 01 Set

(g) DC supervision relay (VAA 21) - 1 Set eqv in ABB or Siemens

(h) Air insulated rear end bottom entry cable box suitable for termination of XLPE cables.

(j) Panel must have additional features

(i) Continuous rated closing/tripping coils

(ii) fully internal arc tested for 40KA for 1 sec

(iii) Manual closing/tripping of the CB with compartment door closed

(iv) Short time rating for 3 seconds as per IEC 62271-100 (v) mechanical endurance test -M2

(k) Breaker shall be provided with following features : - (i) Auxiliary switch 6NO + 6NC contacts mounted
on the draw out portion of the switchgear.

(ii) Postion Cell switch with 3 NO + 1NC Contact one each for test position and service position.
(C) 11KV Outgoing Panel : Supply , installation, testing and commissioning of outgoing 11KV 800A,
18.4KA for 3 Sec HT Vaccum circuit breaker for incomer confirming to IEC 62271 - 200.

(a) 800 Amps Continuous bus bar material shall be of high conductivity eletrolytic copper only. All bus
bars shall be insulated with heat shrinkable Raychem sleeves and joints shall be covered with bitumen
compound followed by HT tape. Phase identification shall be made at the end by colored tape. Bus
bars shall be mounted on integral seal of bushing. All interconnection shall be of electrolytic grade
copper only with joints silver plated.

(b) Circuit braker shall be mounted on a withdrawable truck which shall be horizontally draw out from
service position to isolated position. with ease and model of HWX of AREVA or eqv in Siemens/ABB
(c) motorised spring charged mechanism

(d) Cast resing current transformer 11KV, 400-200/5+5A, 15VA, CI 5P 10, C10,5-3 Nos
(e) accessories like local remote selector switch, breaker control switch (TNC), space, heater with
thermostat, DC & AC control ckt through MCB, indicating LED lamps for R Y B Phases, spring charged, DC
supply healthy, breaker ON/OFF, breaker in service, test disconnected position

(f) Multi function meter, Digital type (Displaying A, V, PF, Hz, KVA, KW, KVAR, KWh, KVARh etc class 0.5
with Rs. 485 port for communication in IEC 61850 .

(g) 800 Amps VCB CT Ration 200-100/5-5A

(h) earthing truck for 11KV

(j) Bus side earthing truck - 1 No and cable side earthing truck - 1 No

(k) Bus riser to extend the bus bar chamber of existing VCB to match with new VCB with matching
size/rating busbars, including making good the disturbed surfaces to match with existing finishes all as
directed