Beruflich Dokumente
Kultur Dokumente
The
configuration of these systems depends on the rated power of the generator as well as on the power system
structure, i.e. whether the generator is in busbar connection or connected to a unit transformer, as shown in
Figure 4. This article will describe solutions for testing selected protective functions effectively for the above
connection configurations. As a starting point, experience recommends to structure the tests according to the
following criteria:
Step 1: Testing protective functions that only use voltage measurements (e.g. ANSI 59, ANSI 81, etc.)
Step 2: Testing protective functions that only use current measurements (e.g. ANSI 50, ANSI 87, ANSI 46,
etc.)
Step 3: Testing protective functions that use both voltage and current measurements (e.g. ANSI 32, ANSI
90/40, etc.)
Test philosophy for overlapping protective functions
Generator protection systems can trip different breakers such as the network circuit breaker (CB), the
generator CB, and the de-excitation CB. This so called trip command matrix depends on the activated
protective functions, the technical philosophy as well as the power system structure.
Therefore it is recommended to test the correct behavior of each protection function. This is only possible
without deactivating any protective functions during the tests.
Application examples
For the following protective functions, the relevant technical background will be explained and practical settings
for testing will be derived:
Testing the ANSI 90 protective function (underexcitation)
Testing the ANSI 46 protective function (negative sequence / unbalanced load)
Primary testing of the ANSI 59GN protective function (directional 90% stator ground fault)
Testing of ANSI 90
A synchronous generator
always requires a
sufficient DC voltage and
thus a DC current flow
through the excitation
winding. This is
necessary to maintain
the synchronization to
the connected power
system.
The generator capability
diagram defines the
limits of active and
reactive power resulting
from the physical
parameters of the
turbine and the
generator, see Figure 2.
The underexcitation area
is especially critical for
the stability of the
generator. In this area, the generator can lose its stability, e.g. as a result of a short-circuit in the connected
power system or a malfunction of the automatic voltage regulator.
The protective function ANSI 90 protects the generator from asynchronous operation in case of these events.
Depending on the
manufacturer of the
protective devices, this
function uses the impedance
measurement or the
admittance measurement.
Note: The impedance
measurement method is not
part of this article, because it
is possible to transfer all
necessary relay settings
directly in the impedance
plane of a distance relay
(Figure 1).
On the one hand, for
protection devices which use
the admittance measurement
method, the calculation of the
relay settings is a lot easier
than with the impedance
measurement, because the
admittance plane of the turbo
generator can be used
directly, see Figure 3.
On the other hand, testing the
following characteristics in the admittance plane is rather complicated. Therefore, in the following, a more
elegant method of testing admittance characteristics shall be introduced. The idea is to transform the
admittance characteristics to the impedance plane to use automated distance test routines for testing the
underexcitation protective function.
The admittance plane can be reproduced in the impedance plane using a mathematical transformation, as
shown bellow.
(equation 2)
With
Figure 6 shows the settings which are used in this
example.
The following example shows the transformation of the trip
time characteristic No. 1 to the impedance plane (equation
3) and the resulting impedance zone (Figure 7).
(equation 3a)
(equation 3b)
Biographies
Biography:
Dr.-Ing. Torsten Schierz worked for 7 years at the University of Applied Sciences Zittau/Grlitz in the area of
research and teaching. Since 1996 he has been an employee of OMICRON electronics Deutschland GmbH in
the business fields Training, Commissioning and Technical Consulting. He has more than 16 years of
experience in power system and rotating machine protection, especially in calculation and commissioning, as
well as more than 24 years of experience in teaching electrical engineering. At present he is a Senior
Consultant.
Torsten is member of the VDE (Federation of Electro Technology Electronics Information Technolog