0 BMS Design Guide COMFORT CONTROL

6. Typical Instrumentation Examples

Hardware Interface (1/2)


ON/OFF, status, alarm ON/OFF, status
I/O items
Instantaneous contact output Input Instantaneous contact output Input

Remote unit DI DI DI
(RS) ON OFF ON OFF

(DDC) IN COM IN COM COM IN


24VAC/DC 24VAC/DC
(PMX)

Wiring

CX TX 52X 51X CX TX 52X

Local
Equipments
Local Remote Local Remote

Electric, OFF TX OFF TX


Operation Operation
HVAC, circuit 52
ON CX 52X circuit 52
ON CX
52X
Plumbing,
others 52 52X 52 52X

51 51

a-a contact a-a contact


1. Contact for status confirmation uses auxiliary relay (52X). 1. Contact for status confirmation uses auxiliary relay
Remarks 2. Remote auxiliary relay (CX, TX) has spark killer. (52X).
2. Remote auxiliary relay (CX, TX) has spark killer.

ON/OFF, status, alarm ON/OFF, status ON/OFF, status lighting


I/O items
Continuous contact output Input Continuous contact output Input Remote control pulse output

Remote unit DI DI DI
ON
(RS) ON OFF ON OFF OFF

(DDC) IN COM IN COM COM IN


DI
24VAC/DC 24VAC/DC
(PMX)

Wiring
White Red
Local switch

CX 52X 51X CX 52X

Local
Remote control

Remote control

Equipments
transformer

Local Remote Local Remote AC


24V
relay

1.5A
Electric, OFF CX OFF CX OFF ON

HVAC, Operation ON Operation ON


circuit 52 circuit 52
Blue Blue
Plumbing,
others 52 52X 52 52X

51 51

1. Contact for status confirmation uses 1. Contact for status confirmation


auxiliary relay (52X). uses auxiliary relay (52X).
Remarks 2. Remote auxiliary relay (CX) has spark killer. 2. Remote auxiliary relay (CX) has
spark killer.

51
AE-AC-049E_Rev.0.0 BMS Design Guide COMFORT CONTROL

6. Typical Instrumentation Examples

Hardware Interface (2/2)


Status, alarm Status Alarm TOT(pulse) input TOT(pulse) input
I/O items
Contact input Contact input Contact input No-voltage contact pulse No-voltage contact pulse

Remote unit DI DI DI DI TOT TOT

(RS)
(DDC) IN COM IN COM COM IN COM IN COM IN
(PMX)

Wiring

Local
52X 51X 52X 51X
Equipments

Electric, Status contact Status contact Alarm contact


Alarm contact
HVAC, Totalizing Totalizing(for water
Plumbing, 1.Input meter)
others 12VDC, 10mA 1.Input
2.Input condition 12VDC, 10mA
1.Input 1.Input ON time over 30ms 2.Input condition
No-voltage a continuous No-voltage a continuous contact OFF time over 30ms ON time over 30ms
contact 2.Circuit voltage, current ON+OFF time over OFF time over 30ms
2.Circuit voltage, current DC12V, 10mA 100ms ON+OFF time over
DC12V, 10mA 100ms
Remarks over 30ms over 30ms
over 30ms over 30ms

ON ON
OFF OFF

over 100ms over 100ms

AI AI AI AO
I/O items
Temperature input Current Input Voltage input Current Output

Remote unit
(RS)
(DDC)
(PMX)

Wiring

Local
Equipments
Electric,
HVAC,
Plumbing, Pt100
resistance Transducer 4~20mA
others Transmitter

1.Input 1.Input 1.AIV1 input 1.Output signal


Pt100 , JPt100 DC4~20mA 1~5VDC 4~20mA DC
2.Circuit voltage, current 2.Input impedance Input impedance 500 2.Output voltage
DC1V, 1mA 300 2.AIV2 input 24V DC
3.Range 3.No isolation 0~5VDC 3. Max. resistance
Remarks 0~50 , -50~100 C Input impedance 5K 600
-20~80 , 50~200 3.AIV3 input 4.With isolator
-5~5VDC
Input impedance 110K
4.No isolation

52