FT2003-U1

Graphic driver (I/O)


Mounting
Installation

A6V10384377_a_en_-- Siemens Industry, Inc.


2013-06-04 Building Technologies Division
Legal notice

Legal notice
Technical specifications and availability subject to change without notice.
2013 Copyright by Siemens Industry, Inc.

Transmittal, reproduction, dissemination and/or editing of this document as well as


utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages. All
rights created by patent grant or registration of a utility model or design patent are
reserved.

Issued by:
Siemens Industry, Inc.
Building Technologies Division
8 Fernwood Road
Florham Park, NJ 07932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS

Edition: 2013-06-04
Document ID: A6V10384377_a_en_--

2
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Table of contents

1 Graphic driver (I/O) FT2003 ............................................................................4


1.1 Description .......................................................................................................4
1.2 Installation ........................................................................................................5
1.3 Views ...............................................................................................................7
1.3.1 FTI2002 connection PCB view ...........................................................7
1.3.2 FTO2007 operation view ....................................................................8
1.4 Wiring ...............................................................................................................9
1.5 FTI2002 connection PCB pin assignments ...................................................... 11
1.5.1 X1 supply and circuit connection ...................................................... 11
1.5.2 X2 LEDs, mimic display indicator ..................................................... 12
1.5.3 X3 LEDs, mimic display indicator ..................................................... 14
1.5.4 X5 mimic display operation ..............................................................16
1.6 Adjustment elements ......................................................................................18
1.7 Technical data ................................................................................................ 20
2 FCC Statement.............................................................................................. 21

3
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 Description

1 Graphic driver (I/O) FT2003

1.1 Description
The graphic driver (I/O) FT2003-U1 is a remote display and operating unit that is
supplied without an enclosure or display panel. It consists of the FTI2002 connection
PCB and the FTO2007 operation, which are screwed together. Four spacer bolts
enable it to be installed in a 1HU enclosure. The graphic driver (I/O) is supplied via the
system supply of the associated panel.

Properties
Communication interface via the RS485 module class A to the fire control panel
A maximum of 8 graphic drivers (I/O) can be connected to an RS485 circuit
Supply inputs for a 24 V supply
Connections for 34 external LED mimic display indicators
Connections for 16 external mimic display buttons
Connection for an external key switch

4
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
Installation
1

1.2 Installation
X402
1
X2

X1 X400

X3
2

X4
4
X1
X5
3

Installation and assembly of the graphic driver (I/O) FT2003

1 Printed circuit board of the FTO2007 operation


2 Ribbon cable of FTI2002 connection PCB for FTO2007 operation
3 FTI2002 connection PCB
4 4 spacer bolts, 15 mm, and fixing screws for securing the enclosure
5 4 spacer bolts, 15 mm, and fixing screws for securing the printed circuit board
X1 FTO2007 operation: connection to X4, connection PCB FTI2002
X1 FTI2002 connection PCB: terminal strip for supply and RS485 circuit
X2 LED mimic display indicator connections 1...17
X3 LED mimic display indicator connections 18...34
X4 Connection to X1, FTO2007 operation
X5 Mimic display operation connections
X400 Connection of peripheral data bus output to further graphic drivers (I/O)
X402 Connection of peripheral data bus input from further graphic drivers (I/O)

5
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 Installation

Preparation
The FT2003-U1 graphic driver (I/O) is supplied as a component that the operator
installs in a 1HU enclosure. The power supply must be provided via the system supply
of an FC20xx or FT2050 panel.
The following components are also required to operate the graphic driver (I/O):
1HU enclosure
Front panel, LED indicators, operating buttons, and optional key switch for the
mimic display panel
Power supply via the system supply of an FC20xx or FT2050 panel
Molex 87586-3493 multipoint connectors (Siemens no. A5Q 00005805) for mimic
display connections
Ribbon cable, 34 pin x 1 m, for mimic display connections
RS485 module class A FCA2016 for connection to the control panel

Installation
1. Using the 4 spacer bolts and the fixing screws (4), install the assembled FT2003
graphic driver (I/O) in the enclosure.
2. Install the power supply and the mimic display elements according to the pin
assignments listed below.

6
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
Views
1

1.3 Views

1.3.1 FTI2002 connection PCB view

1 2 1 2

X2 X4

33 34 33 34

1 2 1 2

X3 X5

33 34 33 34

X1
1

FTI2002 connection PCB layout

Element Des. Function

Plugs and terminals X1 Supply and RS485 connection


X2 LED mimic display indicator connections 1...17
X3 LED mimic display indicator connections 18...34
X4 Connection to FTO2007 operation
X5 Mimic display operation (16x) and optional key switch

7
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 Views

1.3.2 FTO2007 operation view

X402 X400

H433

H432 H434

H431

H401 H430
H201

H429

H402 H428

H427

H403 H426

H425
H205
H404 H424

H423

H405 H422 X1

H421

H406 H420

H419

H407 H418

H417
ON
H408 S20 H416

H415

H409 H414

H435 H436 H413

H410 H412

H411

FTO2007 operation layout

X400 Connection of peripheral data bus output to further graphic drivers (I/O)
X402 Connection of peripheral data bus input from further graphic drivers (I/O)
H401H434 not used (corresponding 'HWLED' LEDs on connection PCB X2 and X3)
H205 Watchdog
H201 Buzzer
S20 (16) DIP switch for configuration
X1 Connecting plug to connection PCB FTI2002

8
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
Wiring
1

1.4 Wiring
1

FT2003
X5 X2 X3

X4
FTI2002 FTO2007
X1

X1

Vsys RS485

Station
X2 FCM20xx
RS485
FCA2016

X201 X3

Periphery board PMI & mainboard

Graphic driver (I/O) FT2003 basic circuit diagram

1 Remote LED alarm indicator in 1HU enclosure


2 LED mimic display panel (LED connections and external buttons)
FTI2002 Connection PCB
FTO2007 Operation
FT2003 Graphic driver (I/O)

The graphic driver (I/O) is operated as a remote mimic display indicator at a distance of
up to 3280 ft/1000 m from the panel. The FT2003 graphic driver (I/O) consists of an
FTI2002 connection PCB and an FTO2007 operation, but has no indicator panel.
The graphic driver (I/O) is installed in a 1HU enclosure. The associated LED indicators
are arranged according to the layout plan. It is connected to the RS485 class A module
on the PMI & mainboard of the 'Panel'. It is supplied via an FC20xx or FT2050 'Panel'.

9
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 Wiring

Graphic driver (I/O) FT2003 wiring diagram


A maximum of 8 FT2003 graphic drivers (I/O) can be connected to the RS485 circuit.
The circuit can be created as a class A circuit (style 6) or a class B circuit (style 4). You
will find detailed information about the RS485 circuit in the description of the FCA2016
RS485 class A module (isolated).
Remote LED Annunciator
FT2003 FT2003 FT2003
Master Slave Slave
FTO2007 FTO2007 FTO2007

X400

X400
X400

X402

X402
X402

X1 X1 X1

FTI2002 FTI2002 FTI2002

LED LED X4 LED X4


X2 X4 X2 X2
1...17 1...17 1...17

Button
LED 1...16, LED Button LED Button
X3 X5 X3 18...33 1...16 X5 X3 18...33 1...16 X5
18...34 Key
switch
X1 X1 X1

Fire control
panel Aux Power

RS485-Line

Example wiring diagram with three graphic drivers (I/O) as a class A circuit (style 6)

X1 FTI2002 connection PCB: Supply and RS485 circuit connection


X1 FTO2007 operation: connection of X4 connection PCB
X2 LED mimic display connection 1...17
X3 LED mimic display connection 1834 with master or 1833 with slave
X4 Connection to X1 of the FTO2007 operation
X5 Mimic display connection key 1...16, key switch
X400 Peripheral data bus output to the following graphic driver (I/O)
X402 Peripheral data bus input from the preceding graphic driver (I/O)

10
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
FTI2002 connection PCB pin assignments
1

1.5 FTI2002 connection PCB pin assignments

1.5.1 X1 supply and circuit connection


Pin Designation Description

10 VSYS Supply input from the power supply ()


9 VSYS Supply input from the power supply ()
8 VSYS+ Supply input from the power supply (+)
7 VSYS+ Supply input from the power supply (+)
6 RS485_B Input connection B
5 RS485_A Input connection A
4 COMMON GND
3 not used
2 not used
1 not used

X1
VSYS - - 10
VSYS - - 9
VSYS + + 8
VSYS + + 7
6 Fire
RS485_B
control
RS485_A 5 panel
COMMON 4
Tn Tx T1
3
2
1

Pin assignment X1 on the connection PCB using the example of style 4 wiring

Tn = last node

NOTICE

Observe polarity for connections A and B.


The last node connection must have a resistance of 120 .

11
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 FTI2002 connection PCB pin assignments

The FT2003 graphic driver (I/O) is connected to the FCA2016 RS485 class A module
(isolated). Note that the graphic driver (I/O) has a fixed baud rate of 9,600 kbps and
can only be operated together with and on the same circuit as the FT2014 remote
display and the FT2015 remote terminal if these two devices are set to the same
baud rate. No other combinations are possible.

Baud rates are specified in the documentation for the corresponding components.

1.5.2 X2 LEDs, mimic display indicator


Pin Connection for LED LED ID in configuration

1, 2 H405 (green) HWLED_1


3, 4 H409 (green) HWLED_2
5, 6 H406 (green) HWLED_3
7, 8 H410 (green) HWLED_4
9, 10 H407 (green) HWLED_5
11, 12 H417 (yellow) HWLED_6
13, 14 H416 (red) HWLED_7
15, 16 H415 (yellow) HWLED_8
17, 18 H414 (red) HWLED_9
19, 20 H413 (yellow) HWLED_10
21, 22 H412 (red) HWLED_11
23, 24 H408 (green) HWLED_12
25, 26 H411 (yellow) HWLED_13
27, 28 H404 (green) HWLED_14
29, 30 H403 (green) HWLED_15
31, 32 H402 (green) HWLED_16
33, 34 H401 (green) HWLED_17

12
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
FTI2002 connection PCB pin assignments
1

X2
A
H405 'HWLED_1'
K
A
H409 'HWLED_2'
K
A
H406 'HWLED_3'
K
A
H410 'HWLED_4'
K
A
H407 'HWLED_5'
K
A
H417 'HWLED_6'
K
A
H416 'HWLED_7'
K
A
H415 'HWLED_8'
K
A
H414 'HWLED_9'
K
A
H413 'HWLED_10'
K
A
H412 'HWLED_11'
K
A
H408 'HWLED_12'
K
A
H411 'HWLED_13'
K
A
H404 'HWLED_14'
K
A
H403 'HWLED_15'
K
A
H402 'HWLED_16'
K
A
H401 'HWLED_17'
K

Pin assignment X2 on the connection PCB

13
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 FTI2002 connection PCB pin assignments

1.5.3 X3 LEDs, mimic display indicator


Pin LED connection LED ID in configuration

1, 2 H422 (red) HWLED_18


3, 4 H426 (red) HWLED_19
5, 6 H423 (yellow) HWLED_20
7, 8 H427 (yellow) HWLED_21
9, 10 H424 (red) HWLED_22
11, 12 H434 (red) HWLED_23
13, 14 H433 (green) HWLED_24, operating indicator (master)
15, 16 H432 (yellow) HWLED_25
17, 18 H431 (yellow) HWLED_26, connection error
19, 20 H430 (red) HWLED_27
21, 22 H429 (yellow) HWLED_28
23, 24 H425 (yellow) HWLED_29
25, 26 H428 (red) HWLED_30
27, 28 H421 (yellow) HWLED_31
29, 30 H420 (red) HWLED_32
31, 32 H419 (yellow) HWLED_33
33, 34 H418 (red) HWLED_34

14
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
FTI2002 connection PCB pin assignments
1

X3
A
H422 'HWLED_18'
K
A
H426 'HWLED_19'
K
A
H423 'HWLED_20'
K
A
H427 'HWLED_21'
K
A
H424 'HWLED_22'
K
A
H434 'HWLED_23'
K
A
H433 'HWLED_24' *
K
A
H432 'HWLED_25'
K
A
H431 'HWLED_26'
K
A
H430 'HWLED_27'
K
A
H429 'HWLED_28'
K
A
H425 'HWLED_29'
K
A
H428 'HWLED_30'
K
A
H421 'HWLED_31'
K
A
H420 'HWLED_32'
K
A
H419 'HWLED_33'
K
A
H418 'HWLED_34'
K

Pin assignment X3 on the connection PCB

* Only used with master graphic driver (I/O)

15
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 FTI2002 connection PCB pin assignments

1.5.4 X5 mimic display operation


Pin Connection key Key ID in configuration

1, 2 S1 HWKEY_1
3, 4 S2 HWKEY_2
5, 6 S3 HWKEY_3
7, 8 S4 HWKEY_4
9, 10 S5 HWKEY_5
11, 12 S6 HWKEY_6
13, 14 S7 HWKEY_7
15, 16 S8 HWKEY_8
17, 18 S9 HWKEY_9
19, 20 S10 HWKEY_10
21, 22 S11 HWKEY_11
23, 24 S12 HWKEY_12
25, 26 S13 HWKEY_13
27, 28 S14 HWKEY_14
29, 30 S15 HWKEY_15
31, 32 S16 HWKEY_16
33 SUK_EXT External key switch
34 (GND) GND for external key switch

16
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
FTI2002 connection PCB pin assignments
1

X5

S1 HWKEY_1'

S2 'HWKEY_2'

S3 'HWKEY_3'

S4 'HWKEY_4'

S5 'HWKEY_5'

S6 'HWKEY_6'

S7 'HWKEY_7'

S8 'HWKEY_8'

S9 'HWKEY_9'

S10 'HWKEY_10'

S11 'HWKEY_11'

S12 'HWKEY_12'

S13 'HWKEY_13'

S14 'HWKEY_14'

S15 'HWKEY_15'

S16 'HWKEY_16'

SUK_EXT 'External key switch'

Pin assignment X5 on the connection PCB

17
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 Adjustment elements

1.6 Adjustment elements


The graphic driver (I/O) is configured with the S20 switch on the FTO2007 operation.

Each address can only be issued once per panel.


The factory setting is always set for the corresponding application.

Setting for one graphic driver (I/O) or master

S20 switch Meaning

1 2 3 4 5 6
S0 S1 S2 Master 2 Syn 1 (Empty
)
ON ON Device address 1
ON ON ON Device address 2
ON ON ON Device address 3
ON ON ON ON Device address 4
ON ON ON Device address 5
ON ON ON ON Device address 6
ON ON ON ON Device address 7
ON ON ON ON ON Device address 8
X X X ON ON Mimic display outputs are controlled and
queried (LEDs, buttons, and key switches)

Empty fields = switch in 'OFF' position


X = switch setting according to address 1 to 8
1 The S20/5 (Syn) switch must be set to the ON position with the graphic driver (I/O).

This deactivates the LEDs on the FTO2007 operation.


2 In the case of the first graphic driver (I/O) and for every master, S20/4 (Master) must

be set to the ON position.

18
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
Adjustment elements
1

Setting for second graphic driver (I/O) or slave

S20 switch Meaning

1 2 3 4 5 6
S0 S1 S2 Master 2 Syn 1 (Empty
)
OFF ON Device address 1
ON OFF ON Device address 2
ON OFF ON Device address 3
ON ON OFF ON Device address 4
ON OFF ON Device address 5
ON ON OFF ON Device address 6
ON ON OFF ON Device address 7
ON ON ON OFF ON Device address 8
X X X OFF ON Mimic display outputs are controlled and
queried (LEDs, buttons, and key switches)

Empty fields = switch in 'OFF' position


X = switch setting according to address 1 to 8
1The S20/5 (Syn) switch must be set to the ON position with the graphic driver (I/O).
This deactivates the LEDs on the FTO2007 operation.
2Multiple graphic drivers (I/O) may not be operated at the same address on a panel.
With the second and every additional graphic driver (I/O), the address must be set 1
higher. For slave operation, S20/4 must be set to the OFF position.

19
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Graphic driver (I/O) FT2003
1 Technical data

1.7 Technical data


Graphic driver (I/O) FT2003
Mechanical data Dimensions (L x W x H) 206 x 121 x 50 mm
Weight 200 g

FTI2002 connection PCB


Supply Operating voltage DC 2032 V
Operating current Max. 1 A (21 V)
Depending on the configuration
LED operating currents Master indicator 34 x 13 mA/3.3 V/1.5 W
Slave indicator 33 x 13 mA/3.3 V/1.4 W
Connection terminals Supply and RS485 connection
Design Screw terminals
Admissible cable cross-section 0.21.5 mm
Inputs and outputs
Mimic display connections and peripheral Plug connection for ribbon cable
data bus
Mechanical data Dimensions (L x W x H) 130 x 121 x 32 mm
Weight 90 g

FTO2007 operation
Supply input Voltage DC 2032 V
Operating current 19.5 mA
Alarm current 32 mA
Supply output Voltage DC 2032 V
Current Looped, max. 1 A
LEDs Quantity 34 for operating indicator
1 for trouble (watchdog)
Function Can be configured with Desigo Fire Safety
Works
Connections Peripheral data bus (input and output) Plug connection with ribbon cable
Mechanical data Dimensions (W x H x D) 185 x 96 x 12 mm
Weight 70 g

20
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
FCC Statement
2

2 FCC Statement
WARNING

Installation and usage of equipment is not in accordance with instructions manual


Radiation of radio frequency energy
Interference to radio communications
Install and use equipment in accordance with instructions manual.
Read the following information.

This equipment generates, uses, and can radiate radio frequency energy and if not
installed and used in accordance with the instructions manual, may cause interference
to radio communications.
It has been tested and found to comply with the limits for a Class A computing device
pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection
against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference in which
case the user at his own expense will be required to take whatever measures may be
required to correct the interference.

21
Siemens Industry, Inc. A6V10384377_a_en_--
Building Technologies Division 2013-06-04
Issued by 2012-2013 Siemens Industry, Inc.
Siemens Industry, Inc. Technical specifications and availability subject to change without notice.
Building Technologies Division
8 Fernwood Road
Florham Park, NJ 07932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS

Document ID A6V10384377_a_en_-- SAP order no.: A5Q00054475


Edition 2013-06-04