Pumps Head calculations

MASAA AC PLANT AT AGYAD PROJECT


PUMPS HEAD CALCULATIONS
pumps head calcul-TP-01-GR-01
(Schedule Q = 39.7 I/S , H = 25.6 mt)

Chilled Chilled Equivlent


Pipe Wall Cross Pipe Total
Pipe No. of water Out side water lenghth for head loss
Fittings type size thickness sectional section length
section fittings flow dia mm velocity fitting& ft
mm mm. area m2 length m ft
Lps. m/s valves ft

Pipe 6.0
Elbow 900 2 32
111.8 2.908
Tee branch 2 60
SK 6.0 92
0 1 39.7 150 168.3 7.11 0.01863641 2.13
Gate valve 2 0.709 NIBCO

Check valve 1 0.359 NIBCO (Approved)

Globe valve 1 4.140 NIBCO


Suction Diffuser 1 2.310 BELL&GOSSETT (Approved)

1 2 Pipe 2.0
Tee branch 6 79.4 200 219.1 8.18 0.03226625 2.46 240 246.6 6.083
SK 2.0 240
2 3 Pipe 26.0
Elbow 900 2 40
74.29 200 219.1 8.18 0.03226625 2.30 205.8 4.488
Tee branch 2 80
SK 26.0 120
3 4 Pipe 58.0
Elbow 900 4 80
72.1 200 219.1 8.18 0.03226625 2.23 351.4 7.250
Tee branch 2 80
SK 58.0 160
4 5 Pipe 20.0
Tee branch 2 72.1 200 219.1 8.18 0.03226625 2.23 80 146.0 3.012
SK 20.0 80
5 6 Pipe 18.0
Tee branch 2 56.1 200 220.1 8.18 0.03258534 1.72 60 119.4 1.511
SK 18.0 60
6 7 Pipe 22.0
Tee branch 2 39.53 150 168.3 7.11 0.01863641 2.12 60 132.6 3.422
SK 22.0 60
7 8 Pipe 4.0
Tee branch 2 30.2 150 168.3 7.11 0.01863641 1.62 60 73.2 1.147
SK 4.0 60
8 9 Pipe 13.0
Tee branch 2 20.89 100 114.3 6.02 0.00820883 2.54 42 84.9 4.953
SK 13.0 42
9 10 Pipe 13.0
Tee branch 2 11.5 100 114.3 6.02 0.00820883 1.40 42 84.9 1.640
SK 13.0 42
###10 11 Pipe 19.0
Elbow 900 2 10
Tee branch 2 6.6
113.3 2.749
suction strainer 1 14
2.25 50 60.3 3.91 0.00216201 1.04
balance valve 1 20
SK 19.0 50.6
2-way control valve 1 1.250 NIBCO

Gate valve 2 0.111 NIBCO

WATER PRESSURE DROP (Pa) FOR (AHU-01-RF-02) = 33800 pa = 0.338 bar = 3.38 mt = 11.154 ft 11.154

TOTAL PRESSURE DROP FOR NETWORK (FT) 59.196


TOTAL PRESSURE DROP FOR NETWORK (MT) 18.0477
TOTAL PRESSURE DROP FOR NETWORK (MT) WITH SAFETY 10 % 19.8525

Remarks

*Equivlent length for fitting from carrier standard.

*WATER PRESSURE DROP FOR (AHU-01-RF-02) is taken From design schedule (more safe) and the computer selection from
the supplier is too small (1 kpa) . we check this value with the supplier.