Beruflich Dokumente
Kultur Dokumente
3
Electromechanical relays
Attracted armature,
moving coil,
inductions disc and
inductions cup type relays.
Electromagnetic relays contain
an electromagnet and
moving part.
4
Static relay contain
electronic circuit
transistor,
ICs, diodes and
other electronic components.
a comparator circuit in the relay, .
OCR Characteristics
Definite-time
Instantaneous
Inverse-time Definite Minimum Time (IDMT)
Very Inverse-time
Exteremely Inverse 6
Definite-time Over current Relay
The operating time is constant,
irrespective of the magnitude of the current
Instantaneous Over current Relay
The operating time is constant,
irrespective of the magnitude of the currents
There is no intentional time delay.
It operates in 1s or less.
Inverse-time Over current Relay
The operating time depends on the magnitude of current.
The operating time decrease as the current increases. .
7
Inverse Definite Minimum Time (IDMT)
Gives an inverse-time current characteristic at lower
values of the fault current and definite-time Characteristic
at higher values of the fault current.
Inverse time characteristic is obtained if the value of the
plug setting multiplier between 10 and 20,
the characteristic tend to become a straight line, i.e.
toward the definite time characteristic.
These relays are widely used for the protection of lines.
8
Very Inverse-time
Gives more inverse characteristic than previous ones.
Characteristic gives better selectivity than the IDMT
Can be used where an IDMT relay fails in selectivity,
Extremely inverse relays
Its time-current characteristic according to I 3.5 t = K.
Very suitable for the protection against overheating for
machines, power transformers, grounding transformers, and
expensive cables.
9
INVERSE TIME CHARACTERISTIC
Operating time
Pick Up Value
Actuating Quantity
13.5
Very Inverse t=
I 1
80
Exttremely Inverse t= 2
I 1
12
The time-current curves by the following equation
A
t = TD P + B
M 1
14
The Plug Setting Multiplier
PSM = Secondary Current / Relay Current Setting
= (Primary fault current)/(Relay current setting x C.T.ratio)
Time Setting
There are 10 steps and over.
The values of TMS are 0.1, 0.2, , 0.9, 1.0
15
Time-current characteristics
for different values of TMS
Figure 5.3
16
Example:
An over current relay (OCR) available current tapping
are 2.5, 3.75, 5, 6.25, 7.5,10 A.
Fault current = 6.000 A, CT ratio is 400/5.
TMS likes in Figure 5.3.
Determine the operating time of the relay
17
Differential Relay
The principle operating of differential relay
based on Kirchhoffs current law.
Not operated for external fault and operated for
fault in protected zone
Using two pairs CT in each phases
Using CT ratio gives the same secondary current
18
Fig. a typical differential connection in normal condition.
19
Figure Differential relay with internal fault
(trip relay)
20
Fig. Percentage Differential relay
T = K1 I2 K2V2
24
For the operation of the relay, the following
condition should be satisfied.
K1 I2 > K2V2 or K2V2 < K1 I2
or
V K1
<
I K2
V
< K where K is a constant
I Or Z < K
25
The Characteristics
of impedance relay
26
Faults in transformer can be divided in two classes:
External and
Internal faults.
27
External faults
Overloads cause the transformer to over heat. One cause
of overload may be due to unequal sharing of parallel
transformers or unbalance loading of three phase banks.
Over voltage can be either due to short term transient
conditions or long-term power frequency conditions.
Transient over voltage cause end turn stresses and possible
breakdown
Under frequency also is caused by a major system disturbance
that causes an imbalance between generation and load
The conditions is similar to over voltage in that exciting current
is greatly increased at low frequencies, causing over- fluxing of
the transformer circuits.
External system short circuits are external to the transformer
protection zone, but cause high transformer currents,
28
can cause transformer winding damage.
Two classifications of internal fault namely:
Incipient faults and
Active faults
30
Transformer protection using differential relay
is recommended For large transformers (>10 MVA).
N N C 3I LY 3VLL
n= = = =
N Y N CY I L VLLY
I S N CY I LY
= 3 =0
I SY N C I L 32
Over current relay
Protection of transformers of rating 100 kVA
and below 5 MVA.
Used as back up protection where differential protection
is used as primary protection.
For small transformer, OCRs are used for both overload
and fault protection.
An extremely inverse relay for overload and light faults
Instantaneous OCR for heavy faults.
A very inverse residual ocr with instantaneous relay
is suitable for ground faults.
33
POWER
TRANSFORMER
CT CT
RESIDUAL
OVER CURRENT RELAY
RESTRICTED EARTH
FAULT RELAY
34
Distance relaying.
As back up protection.
Using Directional distance relaying when the
Setting or coordination of the over current relays is
a problem.
The directional distance relays are connected to
operate when the fault current flows toward the
protected transformer.
They are set to reach into, but not beyond the
transformer.
35
Over excitation protection,
May result in thermal damage to cores due to excessively
high flux in the magnetic circuits.
Excess flux saturates the core steel and flows into the adjacent
structure, causing high eddy current losses in the core.
A transformer designed for a voltage limit of 1.2 p.u at rated
frequency will experience over excitation whenever the per
unit volts/hertz exceed 1.2.
36
Protections against magnetizing inrush current.
When a transformer is first energized, a transient magnetizing
or exiting inrush current may flow. Magnetizing inrush current
has a high harmonic content (the second harmonics).
A high speed biased differential scheme incorporating
a harmonic restraint.
Over-heating protection
Caused by Over loading
The maximum allowed temperature is about 950C and
depend on insulations class.
The protection against overload is usually measured
by thermal relay. 37
Buchholz relay
To detect incipient faults which are initially minor faults but
may cause major faults in due course of time.
When a fault develops slowly, it produces heat, thereby
decomposing solid or liquid insulating material in the transform.
The decomposing solid or liquid insulating material produces
inflammable gases give alarm.
38
Sudden pressure relay (SPR)
Capable of detecting a rapid rise of pressure
It operates with a sealed air or gas chamber above oil level.
The SPR relay is recommended for all units of 5 MVA or more.
It operating time varies from one-half cycle to 37 cycles.
Over-fluxing protection.
The magnetic flux increase when voltage increases.
This results in increased iron loss and magnetizing current
and the lamination insulation is affected.
Protection against over-fluxing due to sustained over-voltage
can occur
39
Protection Transformer Bank
Legend
87 T :Transformer differential relays
50/51 : Inverse time CO relay
(phase fault)
50G : Ground fault relay (GFR)
50/51N : Back up GFR
151G : Feeder ground back up
which trip breaker 52-11
63 : SPR 40
Bus-bar Protection.
3. Ring bus
41
42
Information is required for the scheme selections, relay
selections, and setting calculations;
i). Bus-bar configuration such as in Figure 5.11.
ii). Maximum and minimum bus fault current.
iii).Current transformer information including
location, ratio, accuracy class and saturation
curve of current transformers.
43
The Other Bus Bar protection
44
Figure 5.13. Connection of one CA-16 relay per phase to protect a bus
with three equivalent circuits.
45
Figure 5.14. Connection of one CA-16 relay per phase
to protect a bus with four equivalent circuits.
46