EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
RELAY 3K
DRIVE 4K
CIRCUIT RELAY
5K STATUS
6K FEEDBACK
7K AND LINE
VOLTAGE
INPUTS
SAFETY RELAY
STATUS CIRCUIT 1K
LEDS
1 120 VAC, 50/60 Hz POWER SUPPLY, RM7830A; 220-240 VAC, 50/60 Hz POWER SUPPLY, EC7830A.
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
M15183B
Fig. 1. Internal block diagram of EC/RM7830A (see Fig. 3 for detailed wiring instructions).
3 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
L1
HOT N
1
4 2
SAFETY RELAY
STATUS 1K
CIRCUIT
LEDS
POWER SUPPLY CONTROL
ES1 POWER
18
ES3
19
ES2
17
3K2 AL
16
LOS RT
20 6 2K2 5K1
IGN
2 10
LD2 4K1
1K1 PV1
7 8
7K1
PV2
21
2K1 MV
9
6K1
FAN
5
3K1
AL
3
HIGH FIRE
OPTIONAL KEYBOARD 12
DISPLAY MODULE INDICATES FEEDBACK SENSING
8K1
DDL COMMON OF RELAY CONTACT STATUS
RS485 13 AND LINE VOLTAGE INPUTS
5 8K2 LOW FIRE
DDL 1 F G ... 22 USER TERMINALS
2 15
COMMUNICATIONS REMOTE 9K1
3 RESET 9K2 RELAY CONTACT OPEN
MODULATE
14
RELAY CONTACT CLOSED
1 120 VAC, 50/60 Hz POWER SUPPLY, RM7850A; 220-240 VAC,
50/60 Hz POWER SUPPLY, EC7850A. PROVIDE DISCONNECT RELAY COIL
MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FIELD WIRING
2 TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED INTERNAL WIRING M15184B
SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
Fig. 2. Internal block diagram of EC/RM7850A (see Fig. 4 for detailed wiring instructions).
66-10922 4
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
Q7800 LEGEND
AL ALARM
G 12 (NORMALLY OPEN)
N 13 ES2 PREIGNITION
INTERLOCK INPUT
AL 3 14 FAN BURNER/BLOWER
MOTOR
FAN 4 15 IGN IGNITION
L1 LINE VOLTAGE SUPPLY
5 (L1) 16
LOS LOCKOUT INPUT
RT 6 17 ES2 LD2 AIRFLOW SWITCH INPUT
MV MAIN FUEL VALVE
LD2 7 18
PV1 PILOT VALVE 1
PV1 8 19 (INTERRUPTED)
1 12O VAC, 50/60 Hz POWER SUPPLY (RM7830A). 220-240 VAC, 50/60 Hz POWER SUPPLY
(EC7830A). PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
POWER
PILOT
FLAME
,,
MAIN
ALARM
IGNITION 10
PILOT VALVE 8
V2 21
MAIN VALVE 9
OPERATING
PREIGNITION INTERLOCK 17
CONTROLS
AND
INTERLOCKS LIMITS AND BURNER CONTROL CLOSED 6
LOCKOUT INPUT 20 3
1 10 sec 2
AFS CHK AIRFLOW SWITCH CHECK 7 AFS CHK
4 5 6 6 6
3 sec 3 or 5 sec 5 sec 3 or 5 sec 5 sec 2, 15 or 30 sec
2 sec AFS CHK
OPTIONS
1 IF ON AT CALL FOR HEAT, HOLD (120 sec). LOCK OUT IF STILL ON. 4 SELECT VIA ST7800A PURGE TIMER CARD.
2 IF OFF AFTER 10 SEC OF FAN, LOCK OUT. 5 DUE TO ONE EXTRA SECOND FOR SAFETY RELAY TEST, TIMING CAN VARY FROM 3 TO 4 SECONDS.
3 TAKE LOCKOUT ACTION, CONTINUE POSTPURGE TIMING. 6 SELECT VIA CONFIGURATION JUMPERS OR MODEL NUMBERS.
M15185B
Fig. 3. Wiring subbase and sequence chart for EC/RM7830A.
5 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
SERIES 90 LEGEND
FIRING RATE SERIES 90
CONTROLLER AL ALARM
Q7800 MOTOR (NORMALLY OPEN)
HIGH FIRE ES1 LOW FIRE SWITCH
G 12 B B INPUT
COMMON ES2 PREIGNITION
N 13 R R INTERLOCK INPUT
AL MODULATE ES3 HIGH FIRE SWITCH
3 14 W W INPUT
LOW FIRE FAN BURNER/BLOWER
4 (L1) 15 MOTOR
IGN IGNITION
FAN 5 16
L1 LINE VOLTAGE SUPPLY
RT 6 17 ES2 LOS LOCKOUT INPUT
LD2 7 18 ES1 LD2 AIRFLOW SWITCH INPUT
MV MAIN FUEL VALVE
PV1 8 19 ES3
PV1 PILOT VALVE 1
(INTERRUPTED)
MV 9 20 LOS
PV2 PILOT VALVE 2
IGN 10 21 PV2 (INTERMITTENT)
RT LIMITS AND BURNER
F 22 1 CONTROL
L1
2
N
FLAME
DETECTOR
1 120 VAC, 50/60 HZ POWER SUPPLY, RM7850A; 220-240 VAC, 50/60 HZ POWER SUPPLY, EC7850A.
POWER
PILOT
FLAME
MAIN
ALARM
,
BURNER BURNER/BLOWER MOTOR 5
IGNITION 10
PILOT VALVE 8
V2 21
MAIN VALVE 9
OPERATING 21
PREIGNITION INTERLOCK
CONTROLS
AND
INTERLOCKS LIMITS AND BURNER CONTROL CLOSED 6
LOCKOUT INPUT 20 3
1 10 sec 2
AFS CHK AIRFLOW SWITCH CHECK 7 AFS CHK
HF Sw 19 LF Switch 18
MOD
HF MOD
HF
LF
LF
MOTOR
4 5 6 6 6
2 sec AFS CHK 3 sec 3 or 5 sec 5 sec 3 or 5 sec 5 sec 2, 15 or 30 sec
OPTIONS
1 IF ON AT CALL FOR HEAT, HOLD (120 SEC). LOCK OUT IF STILL ON. 5 DUE TO ONE EXTRA SECOND FOR SAFETY RELAY TEST,
TIMING CAN VARY FROM 3 TO 4 SEC.
2 IF OFF AFTER 10 SEC OF FAN, LOCK OUT.
6 SELECTION VIA CONFIGURATION JUMPERS OR MODEL NUMBERS.
3 TAKE LOCKOUT ACTION. CONTINUE POSTPURGE TIMING.
M15186B
4 SELECT VIA ST7800A PURGE TIMER CARD.
66-10922 6
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
The KDM, Data ControlBus Module (for remote mounting or communications) or Communication Interface ControlBus
Module must be wired in daisy chain configuration, 1(a)-1(a), 2(b)-2(b), 3(c)-3(c). The order of interconnection of all the devices
listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string
require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors for connections
longer than 100 feet (31 meters).
7. Recommended wire routing of leadwires: b. Flame Detector leadwires: The maximum flame
a. Do not run high voltage ignition transformer wires sensor leadwire length is limited by the flame
in the same conduit with the flame detector, Data signal strength.
ControlBus Module, or Remote Reset Module c. Remote Reset leadwires: The maximum length of
wiring. wire is 1000 feet (305 meters) to a Remote Reset
b. Do not route flame detector, Data ControlBus pushbutton.
Module, or Remote Reset Module leadwires in d. Data ControlBus Module: The maximum Data
conduit with line voltage circuits. ControlBus Module cable length depends on
c. Enclose flame detector leadwires without armor the number of system modules connected, the
cable in metal cable or conduit. noise conditions and the cable used. The
d. Follow directions in flame detector, Data maximum length of all Data ControlBus Module
ControlBus Module, or Remote Reset Module interconnecting wire is 4000 feet (1219 meters).
Instructions. 10. Be sure loads do not exceed the terminal ratings. Refer
8. The KDM is powered from a low voltage, energy limited to the label on the relay module or to the terminal
source. Mount the KDM outside of a control panel when ratings in Tables 3A, 3B, 3C and 3D.
it is protected from mechanical damage.
IMPORTANT
Final Wiring Check
A 13 Vdc power supply must be used any time more
than one KDM is used. A maximum of two KDM, 1. Check the power supply circuit. The voltage and
Data ControlBus Modules or S7810B Multi-Drop frequency tolerance must match those of the relay
Switch Modules are allowed in any combination. module. (A separate power supply circuit can be
required for the relay module.) Add the required
9. Maximum wire lengths: disconnect means and overload protection.
a. EC/RM7830A and EC/RM7850A leadwires: The 2. Check all wiring circuits and complete the Static
maximum leadwire length is 300 feet (91 meters) Checkout in Table 4 or 5 before installing the relay
to terminal inputs (Control, Running/Lockout module on the subbase.
Interlock). 3. Install the relay module.
4. Restore power to the panel.
7 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
66-10922 8
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
9 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
Mounting EC/RM7830A; 4. Mount the relay module by aligning the four L shaped
corner guides and knife blade terminals with the
EC/RM7850A Relay Module bifurcated contacts on the wiring subbase and securely
tightening the two screws without deforming the plastic.
1. Mount the relay module vertically on the Q7800
Subbase, or mount horizontally with the knife blade
terminals pointing down. When mounted on the
Q7800A, the relay module must be in an electrical
STATIC CHECKOUT
enclosure.
2. When mounting in an electrical enclosure, provide After checking all wiring, perform this checkout before
adequate clearance for servicing, installation and installing the relay module on the wiring subbase. These tests
removal of the relay module, KDM, flame amplifier, verify that the Q7800 Wiring Subbase is wired correctly and
flame amplifier signal voltage probes, electrical signal the external controllers, limits, interlocks, actuators, valves,
voltage probes and electrical connections. transformers, motors and other devices are operating
a. Allow an additional 2 in. (51 mm) below the relay properly.
module for the flame amplifier mounting.
b. Allow an optional 3 in. (76 mm) minimum on both
sides of the relay module for electrical signal
WARNING
voltage probes. Fire or Explosion Hazard.
3. Make sure no subbase wiring is projecting beyond the Can cause property damage, severe injury
terminal blocks. Tuck in wiring against the back of the or death.
subbase so it does not interfere with the knife blade Close all manual fuel shutoff valves before starting
terminals or bifurcated contacts. this test to prevent an explosion.
IMPORTANT
Install the relay module with a plug-in motion rather
than a hinge action.
66-10922 10
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
Use extreme care when testing the system. Line voltage is General Instructions
present on most terminal connections when power is on.
Ensure proper selection of configuration jumpers before
starting the burner operation. 1. Perform all applicable tests listed in the Static
Checkout, Table 4 or 5, in the order listed.
2. Make sure all manual fuel shutoff valves are closed.
CAUTION 3. For each test, open the master switch and install the
jumper wire(s) between the subbase wiring terminals
Electrical Hazard.
Can cause equipment damage. listed in the Test Jumpers column.
Do not perform a dielectric test with the relay module 4. Close the master switch before observing operation.
installed. Internal surge protectors break down and 5. Read the voltage between the subbase wiring terminals
conduct a current. This can cause the relay module to listed in the Voltmeter column.
fail the dielectric test or destroy the internal lightning 6. If there is no voltage or the operation is abnormal,
and high current protection. check the circuits and external devices as described in
the last column.
1. Open the master switch before installing or removing a 7. Check all wiring for correct connections, tight terminal
jumper on the subbase. screws, correct wire, and proper wiring techniques.
2. Before continuing to the next test, be sure to remove 8. Replace all damaged or incorrectly sized wires.
test jumper(s) used in the previous test. 9. Replace faulty controllers, limits, interlocks, actuators,
3. Replace all limits and interlocks that are not operating valves, transformers, motors and other devices, as
properly. Do not bypass limits and interlocks. required.
10. Make sure normal operation is obtained for each
required test before continuing the checkout.
Equipment Recommended 11. After completing each test, be sure to open the master
switch and remove the test jumper(s).
Voltmeter (1M ohm/volt minimum sensitivity) set on the 0 to
300 Vac scale and two jumper wires, No. 14 wire, insulated,
12 in. (304.8 mm) long with insulated alligator clips at both
ends.
Table 4. EC/RM7830A Static Checkout.
If Operation is Abnormal ,
Test No. Test Jumpers Voltmeter Normal Operation Check the Items Listed Below
1 None 5-L2 Line voltage at terminal 5. 1. Master switch.
2. Power connected to the master
switch.
3. Overload protection (fuse, circuit
breaker, etc.) opened the power
line.
2 None 17-L2 Line voltage at terminal 17. Preignition interlocks.
3 5-16 Alarm (if used) turns on. Alarm.
NOTE: Disconnect horn at this time (if used).
4 5-16 2-20 Line voltage at terminal 20. Limits in Lockout Circuit.
5 5-16 2-6 Line voltage at terminal 6. 1. Recycle limits.
2. Burner control.
6 5-16 2-7 1. Fan (Burner Motor or Blower) 1. Fan circuit.
starts. a. Manual fan switch.
5-4
2. Line voltage at terminal 7. b. Fan power supply,
overload protection and
starter.
c. Fan.
2. Running Limits or Airflow Switch
(LD2 input).
NOTE: Remove jumpers and reconnect alarm (if used).
7 5-10 Ignition spark (if ignition 1. Watch for spark or listen for buzz.
transformer is connected to a. Ignition electrodes are clean.
terminal 10). b. Ignition transformer is okay.
8 5-8 1. Ignition spark (if ignition 1. Watch for spark or listen for buzz.
transformer is connected to a. Ignition electrodes are clean.
terminal 8). b. Ignition transformer is okay.
2. Automatic pilot valve opens (if 2. Listen for click or feel head of
connected to terminal 8). valve for activation.
NOTE: Refer to wiring diagram of a. Actuator if used.
system being tested. b. Pilot valve.
(continued)
11 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
66-10922 12
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
3. PURGE Period
WARNING a. Preignition Interlock opens anytime during purge.
Explosion hazard. b. Flame signal detected during purge.
Can cause serious injury or death. c. High Fire Switch fails to close within five minutes
Be sure all manual fuel shutoff valves are closed. after the firing rate motor is commanded to drive
to high fire position at start of purge (EC/
Mounting Other System Components (Fig. 5) RM7850A).
d. Low Fire Switch fails to close within five minutes,
after firing rate motor is commanded to drive to
Refer to the applicable specifications for mounting other low fire position at end of purge (EC/RM7850A).
system components. e. Airflow Switch Input does not close within 10
seconds.
f. If Airflow Switch is disabled, there is no jumper
PRINCIPAL TECHNICAL FEATURES between terminals 6 and 7.
g. Airflow Switch opens during PURGE.
The EC/RM7830A or EC/RM7850A Relay Module provide all h. Lockout Input opens during purge.
customary flame safeguard functions as well as significant i. Ignition/pilot valve/intermittent pilot valve terminal
advancements in safety, annunciation, and system is energized.
diagnostics. j. Main valve terminal is energized.
k. Internal system fault.
l. Purge card is removed.
Safety Shutdown (Lockout) Occurs If: m. Purge card is defective.
4. PREIGNITION
1. INITIATE Period a. Lockout Input opens during PREIGNITION.
a. Purge card is not installed or removed. b. Airflow Switch opens during PREIGNITION.
b. Purge card is defective. c. Preignition Interlock opens during PREIGNITION.
c. Configuration jumpers were changed (after 200 d. Flame signal detected during PREIGNITION.
hours of operation). e. Ignition terminal is not energized.
d. AC line power errors, see Operation. f. Pilot valve/intermittent pilot valve terminal is
e. Four minute INITIATE period is exceeded. energized.
2. STANDBY Period g. Main valve terminal is energized.
a. Flame signal is present after 40 seconds. h. Internal system fault.
b. Preignition Interlock is open an accumulative time i. Purge card is removed.
of 30 seconds. j. Purge card is defective.
c. Airflow Switch feature is enabled and the Airflow 5. SAFETY 1 PERIOD
Switch is closed for 120 seconds with Limits and a. Lockout Input opens during SAFETY 1.
Burner Control closed. b. Airflow Switch opens during SAFETY 1.
d. Ignition/pilot valve/intermittent pilot valve terminal c. Low Fire Switch opens (EC/RM7850A).
is energized. d. No flame is present at the end of SAFETY 1.
e. Main valve terminal is energized. e. Ignition terminal is not energized.
f. Internal system fault. f. Pilot valve/intermittent pilot valve terminal is not
g. Purge card is not installed or removed. energized.
h. Purge card is defective. g. Main valve terminal is energized.
i. Lockout Input opens during STANDBY. h. Internal system fault.
i. Purge card is removed.
j. Purge card is defective.
13 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
6. PILOT STAB. PERIOD restarts. If the condition is not corrected and the hold
a. Lockout Input opens during PILOT STAB. condition exists for four minutes, the relay module locks out.
b. Airflow Switch opens during PILOT STAB. Causes for hold conditions in the INITIATE sequence:
c. Low Fire Switch opens (EC/RM7850A). a. AC line dropout detection.
d. No flame is present. b. AC line noise that can prevent a sufficient reading of the
e. Ignition terminal is energized. line voltage inputs.
f. Pilot valve/intermittent pilot valve terminal is not c. Low line voltage brownouts.
energized.
g. Main valve terminal is energized. The INITIATE sequence also delays the burner motor starter
h. Internal system fault. from being energized and de-energized from an intermittent
i. Purge card is removed. AC line input or control input.
j. Purge card is defective.
7. MAIN TRIAL PERIOD Standby
a. Lockout Input opens during MAIN TRIAL.
b. Airflow Switch opens during MAIN TRIAL. The relay module is ready to start an operating sequence
c. Low Fire Switch opens (EC/RM7850A). when the operating control input determines a call for heat is
d. No flame is present. present. The burner switch, limits, operating limit control and
e. Ignition terminal is energized. all microcomputer-monitored circuits must be in the correct
f. Pilot valve/intermittent pilot valve terminal is not state for the relay module to continue into the PURGE
energized. sequence.
g. Pilot valve is energized during MAIN TRIAL
stabilization.
h. Main valve terminal is not energized. Normal Start-Up Purge
i. Internal system fault.
j. Purge card is removed. The relay module provides PURGE timing selectable from two
k. Purge card is defective. seconds to thirty minutes with power applied and the
8. RUN Period. operating control indicating a call for heat.
a. No flame is present. 1. The Preignition Interlocks, Limits and Burner Control,
b. Lockout Input opens. Run/Test Switch, Airflow Switch Input, Lockout Input,
c. Ignition/interrupted pilot valve terminal is and all microcomputer-monitored circuits must also be
energized. in the correct operating state.
d. Main valve terminal is not energized. 2. The blower motor output, terminal 5, is powered to start
e. Internal system fault. the PURGE sequence. The firing rate motor is driven to
f. Purge card is removed. the high fire position (EC/RM7850A). The PURGE
g. Purge card is defective. timing does not begin until the Airflow Switch Input and
h. Airflow Switch Input opens. High Fire Switch (EC/RM7850A) are both closed.
9. POSTPURGE Period 3. The Preignition Interlock Input must remain closed
a. Ignition/pilot valve/intermittent pilot valve terminal throughout PURGE or a safety shutdown occurs.
is energized. 4. The Airflow Switch Input must close by ten seconds into
b. Main valve terminal is energized. PURGE or a safety shutdown occurs.
c. Internal system fault. 5. After the firing rate motor reaches the PURGE rate
d. Purge card is removed. position and PURGE timing is completed, the motor
e. Purge card is defective. drives to the low fire position (EC/RM7850A).
Ignition Trials
OPERATION 1. Preignition: With the firing rate motor at the low fire
position (EC/RM7850A), the ignition transformer,
Sequence of Operation terminal 10, is energized for three seconds.
2. First Safety Time (SAFETY1):
The relay modules have the operating sequences listed a. With the firing rate motor at the low fire position
below; see Fig. 3 and 4. The relay module LED provide (EC/RM7850A):
positive visual indication of the program sequence: POWER, (1) The pilot valves and ignition transformer,
PILOT, FLAME, MAIN and ALARM. terminals 8, 10 and 21, are energized.
Terminal 8 is an interrupted pilot valve and
terminal 21 is an intermittent pilot valve.
Initiate (2) During SAFETY1, the Low Fire Switch Input
must be closed. If it opens, a safety
The relay module enters the INITIATE sequence when the shutdown occurs (EC/RM7850A).
relay module is initially powered. The relay module can also (3) The Preignition Interlock Input is ignored
enter the INITIATE sequence if the relay module verifies during SAFETY1, PILOT STAB., MAIN
voltage fluctuations of +10/-15% or frequency fluctuations of TRIAL, RUN and POSTPURGE.
10% during any part of the operating sequence. The b. Flame must be proven by the end of three or five
INITIATE sequence lasts for two seconds unless the voltage seconds to allow the sequence to continue. A
or frequency tolerances are not met. When not met, a hold safety shutdown occurs if there is no flame.
condition is initiated and displayed on the optional KDM for at 3. Pilot stabilization (PILOT STAB.): With flame proven, the
least five seconds; when met, the INITIATE sequence ignition, terminal 10, is de-energized. The duration of
this state is five seconds.
66-10922 14
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
WIRING
SUBBASE
RUN/TEST
SWITCH HONEYWELL
RELAY
MODULE
CONFIGURATION
JUMPERS
PURGE
TIMER
SEQUENCE
STATUS
LED PANEL
RESET
BUTTON
CAPTIVE
MOUNTING
DUST SCREW
COVER
BURNER CONTRO
L FLAME
AMPLIFIER
M15187A
15 66-10922
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
2. In the measured PURGE sequence, the Run/Test SERVICE NOTE: Clipping and removing a site-configurable
Switch, placed in the TEST position, causes the jumper enhances the level of safety.
PURGE timing to stop. The firing rate motor is in the
RUN/TEST SWITCH SELECTABLE CONFIGURATION
High Fire position. JUMPERS
3. In Purge Drive to Low Fire position, the Run/Test
Switch, when placed in the TEST position, holds the
burner in PURGE with the firing rate motor in the Low
Fire position (EC/RM7850A).
4. During the PILOT STAB. period, the Run/Test Switch,
when placed in the TEST position, stops the timer,
allowing for pilot turn-down test and other burner
adjustments. This activates a 15-second flameout timer
that permits pilot flame adjustment without nuisance
safety shutdowns.
5. During Run, the Run/Test Switch, when placed in the
TEST position, drives the firing rate motor to the Low
Fire position.
IMPORTANT
When the relay module is switched to the TEST
mode, it stops and holds at the next Run/Test Switch M7701B