Sie sind auf Seite 1von 6

WHITEPAPER

HOW TO TROUBLESHOOT A PRESSURE TRANSDUCER


Hands-On Troubleshooting For Voltage Sensors

Whats Inside

Section 1:
Troubleshooting
Assumptions

Section 2:
Pressure transducers today are more rugged and reliable than ever before. Made of rugged
3-Wire Transducer
stainless steel construction, they provide abundant overpressure protection, improved to-
Removed
tal error band (TEB) and offer negligible orientation and vibration effects. They are ideal for From a Pipeline
long-term use in harsh environments of extreme temperature, humidity and vibration.
Section 3:
Still, pressure transducer installations occasionally fail. Typical problems include: improper 3-Wire Transducer
wiring, incorrect polarity, short circuits, inadequate power supply, multiple grounds, system Connected
operations issues or a problem with the pressure transducer itself. To a Pipeline

Fortunately, its easy for technicians to perform simple troubleshooting techniques to de- Section 4:
4-Wire Transducer
termine if the transducer is operational, regardless of whether its a 3-wire voltage output,
Removed
4-wire voltage output, or a 4-20 mA loop transmitter. The troubleshooting procedures be-
From a Pipeline
low will help a technician quickly and easily determine transducer status.
Section 5:
1. Troubleshooting Assumptions 4-Wire Transducer
Connected
These troubleshooting guidelines assume that the technician is trained, has access to a 24 To a Pipeline
VDC power source and knows how to properly use a digital multimeter to measure voltage
(voltmeter), current (milliamp meter) and resistance. Section 6:
4-20 mA Transducer
Removed
This guide also assumes that the technician knows that the best and safest method to test
From a Pipeline
any transducer is to remove it entirely from the pipeline and control circuit. Thats because
an installed transducer can be injected with unwanted voltage from another source. For Section 7:
example, consider the actual application of an original equipment manufacturer (OEM) that 4-20 mA Transducer
mounted a transducer in a chillers water pipe. Unknowingly, another companys arc weld- Connected
ing operation in an adjacent building used a ground clamp on that same water pipe. Inter- To a Pipeline
mittent arc restrikes induced huge sporadic voltage spikes that were carried through the
pipe and water to the transducer, ruining its circuitry and functionality. This problem can Section 8:
be eliminated by removing the sensor from the pipeline to a workbench, which allows the Customer Application
Stories
troubleshooting technician to focus solely on troubleshooting the transmitter.

Although the machine is being built on the OEMs manufacturing floor, consideration should
also be given to the environment into which the machine ultimately will be installed. For

1
example, a pressure transducer installed on a steam line very close to where the steam is
being generated can cause a negative change in the dynamics of the sensor. This issue can
be eliminated by moving the transducer further away from the steam line.

2. 3-Wire Transducer Removed From a Pipeline

The 3-wire voltage output transducer is the most commonly used and easiest to trouble-
shoot voltage transducer. Typically, the problem with this type of unit is either no signal or
the signal is different from what was expected.

After the transducer has been removed from the pipeline and control circuit, the technician
must first identify all terminals (+excitation, excitation, +signal, signal and ground) for the
unit being examined. This is necessary because transducer terminal configurations vary by
both model and manufacturer, which can be found in the models operation instructions.
Additionally, the technician must understand that the excitation and signal are com-
moned within a 3-wire transducer. (Common refers to both negatives.)

Once terminal configuration has been determined, the technician can power the unit by
placing the +24VDC power supply to the transducers +excitation and 24 VDC to the ex-
citation. To establish if the transmitter is operating properly, place the voltmeter +lead onto
the +signal and then the voltmeter lead onto common.

With no pressure applied the voltmeter, the reading should equal the analog signal for zero
applied pressure such as 0.0 VDC, 0.1 VDC or 0.03 VDC. The transducer is operating if the
reading is what was expected.

3. 3-Wire Transducer Connected to a Pipeline

Although it may not be practical to remove the transmitter from the pipeline and control
circuit, it still must be tested. First, make sure +24 VDC is connected to the transducers +ex-
citation and 24 VDC to common. Next, disconnect the wire that runs from the transmit-
ters +signal to the control circuit. This disconnects the sensor from the control circuit, while
leaving the transducer in the pipeline. Now place the voltmeter +lead onto the transducers
+signal and the voltmeter lead onto common.

With no pressure applied, the transmitter should provide a voltage output as specified on
the units data sheet, confirming that its operational. However, one more check is necessary.
Reconnect the control circuit wire that runs from the transmitters +signal to the control cir-
cuit. Once again, place the voltmeter +lead onto the transducer +signal and the voltmeter
lead onto common. The voltage reading should display just as before. If not, the cause is a
circuit-wiring problem, not a faulty transducer. It is up to the technician to carefully trouble-
shoot all wiring connections. The manufacturers operating instructions should be reviewed
to verify terminal identification and check that all wiring was connected properly.

4. 4-Wire Transducer Removed From a Pipeline

A 4-wire voltage output transducer has several different troubleshooting steps compared
to the 3-wire transducer. Again, it is assumed a trained technician has access to a 24 VDC
power source, knows how to properly use a digital multimeter and can identify all of the
units terminals.

2
What differentiates the 4-wire transducer configuration from the 3-wire system is that the
-excitation and signal are not common within the transducer. Instead they are electrically
at a separate voltage potential and all four wires must remain isolated from each other.
There is a VDC difference between excitation and signal in a 4-wire circuit, known as a
Common Mode Voltage (CMV), whereas the two minus signals are at the same potential in
a 3-wire circuit. This is a very important difference, and the technician must understand it
because if the worker commons the signal and excitation, a short circuit will occur.

Once the unit has been removed from the pipeline and control circuit and terminal configu-
ration has been determined, the technician can power the unit by connecting the +24 VDC
power supply to the transducers +excitation and 24 VDC to the excitation. To determine if
the unit is operational, connect the voltmeter +lead to the +signal, then place the voltmeter
lead onto the signal. When no pressure is applied, the voltmeter reading should equal the
analog signal for zero applied pressure.

5. 4-Wire Transducer Connected to a Pipeline

With the transducer connected to the pipeline and control circuit, confirm that +24 VDC
is connected to the transducers +excitation and 24 VDC to the excitation. Next, discon-
nect the wire that runs from the transmitters +signal to the control circuit. This disconnects
the sensor from the control circuit, while leaving the transducer in the pipeline. Place the
digital voltmeter +lead onto the transducers +signal and the digital voltmeter lead onto
the transducers signal. With no pressure applied, the transducer should provide a voltage
output specified on the units data sheet. If it is, then the transducer is operational with one
caveat.

If the digital meter reading is 0.0 VDC, the functionality of the transducer cant be estab-
lished. To determine functionality, the technician must disconnect the transducer +signal
and signal from the circuit wiring. By placing the voltmeter +lead to the transducer -signal
and the voltmeter lead to the transducer excitation, you should be able to read the CMV.
Relocating the voltmeter +lead to the transducer +signal should provide the same CMV
reading. This establishes that the transducer is functioning. Keeping the voltmeter attached
as above, touch the transducer lead to the input terminal. You should be able to read the
CMV, if not the two negatives are shorted together someplace in the system. It is now up to
the technician to determine the cause and location of the short circuit.

Generally, this problem originates from technicians familiar with 3-wire systems, but un-
familiar with 4-wire systems. They dont understand that the input channels to their data
acquisition systems are all common to themselves. Although power is taken from a nearby
source, and the wire is tied to the + and terminals of the input card, that input card neg-
ative is also tied to the power supply. This causes the two negatives get shorted out. Not
isolating the two negatives is the most common error on 4-wire transducers.

6. 4-20 mA Transducer Removed From a Pipeline

Troubleshooting a 4-20 mA transducer is more difficult, because the only instrument that
directly measures current is an analog meter, which uses a pointer to indicate current. In an
analog meter, electric current flows through a coil to produce a magnetic field creating a
magnetic torque that causes a pointer needle to deflect proportionally to the current. To-
day, digital instrumentation is more commonly used than an analog meter.

3
Digital metering is based on voltage values. Heres how it works for current. The technician
powers the transducer by connecting its +terminal (red wire) to the +terminal of the 24
VDC power supply. 4-20 mA flows from the transducers terminal (black wire) that is then
connected to the +lead of a digital milliamp meter. The meters lead is then connected to
the terminal of the 24 VDC power supply. This meter has an internal dropping resistor that
develops a voltage, which is converted to a milliamp value displayed on the meters screen.
This is the same method used in automation control. A 250 ohm dropping resistor is placed
in series with the output of the transducer and the terminal of the power source. The volt-
age developed (1 to 5 VDC) across this resistor is fed into a channel of the control system. (A
500 ohm resistor converts 4-20 mA current to 2-10 VDC).

If the milliamp readout is 4 mA with no pressure applied, the transducer is operational.


Technicians can use these steps to troubleshoot any 4-20 mA circuit, whether its a tempera-
ture sensor, pressure sensor, vibration sensor or transducer.

7. 4-20 mA Transducer Connected To a Pipeline

If the technician is to troubleshoots transducer while still connected to the pipeline and
control circuit, follow the next steps. As in earlier examples, these steps are different from
troubleshooting with the unit removed from the pipeline.

Connect the 24 VDC to the red wire (+terminal) of the transducer. (Note: Check the trans-
ducer models operating instructions because some manufacturers may use different no-
menclature). Disconnect the wire from the transducer that is connected to the control cir-
cuit and place the +lead from the digital milliamp meter to the black wire (terminal) of the
transducer. Next, connect the lead from the digital milliamp meter to the lead going to the
control circuit.

In this wiring configuration, power goes through the digital milliamp meter and small re-
sistor, into the control circuits larger 250 ohm resistor, back to the terminal of the power
source.

If the transducer provides a 4 mA output signal with no pressure applied, then the sensor is
operational. If the transducer provides 0.0 mA output, then the problem is either with the
transducer or the input to the control circuit. Whichever it is, it has been established that
there is no conductive path from the transmitter terminal back to the post of the power
source. If the circuit is the problem, the typical cause is the absence of the dropping resistor
in the circuit. When 0.0 mA readout occurs, it is recommended that the technician remove
the unit from the pipeline and control circuit to determine if the transmitter is working.

If the technician has completed these troubleshooting steps for 3-wire, 4-wire or 4-20 mA
transducers and still cant solve the problem, contact the transducer manufacturers tech-
nical support. They may be able to provide other troubleshooting steps, engineer a unique
solution or go on-site to diagnose the problem. If the suppliers technical support cant re-
solve the issue, return the unit to the manufacturer for repair. The manufacturer can only
determine what the problem is, not the cause. If the transducer is found to be operational,
then the problem exists within the installation and will be up the technician to correct it.

8. Customer Application Stories

Below are customer testimonials on how Setra engineers have diagnosed various transduc-
er problems.

4
A customer had complained that Setras gauge pressure sensors were getting damaged
during their fluid control loop. A phone call with the customer wasnt successful in deter-
mining the problem, so Setra engineers went out to visit the installation. The first thing
the customer did was walk the engineers through a normal system operation of all of their
processes. By observing each step within the process, the engineers were able to pinpoint
the moment that the sensor output went to full scale and didnt return to normal condition.

Next, the engineers reviewed the system programing to see what was being triggered in
the control system. It was determined that poor valve timing was causing a fluid hammer in
the water line that was damaging the transducers. The valves were closing so quickly that
a pressure wave was created in the fluid. Since the fluid was incompressible, the pressure
wave created a very brief but high pressure spike that damaged the transducer. The engi-
neers were able to solve the problem by preventing the fluid hammer effect from occurring.
By modifying the timing and the speed of the valves, they were able to stop the generation
of the damaging pressure wave.

The customer found that the best option was to prevent the fluid hammer effect, but if it
wasnt preventable more options were available. For example, Setra could have provided
a snubber or restrictor on the transducer. A snubber is often an adaptor screwed onto the
pressure connection side of the pressure transducer. It evens out the rate of the fluid enter-
ing the pressure transducer. Inside the snubber is a porous disk or filter-like screen that dis-
rupts a pressure wave, allowing normal fluid pressure measurements. A restrictor is a small
orifice installed inside of the pressure side of the pressure transducer. This small hole does
the same job as the snubber, but eliminates the need for an adaptor.

Another customer had called Setra about their high accuracy transducers that appeared to
be drifting in the engine test cell equipment. During a phone conversation, the application
setup appeared to be correct. Returned units were still in calibration and the engineers
couldnt replicate the failure in the factory.

A Setra engineer went to the customers factory to look at the process, and concluded that
the test cell appeared to be functioning properly. While looking at historical data, however,
they noticed that a pressure drift happened daily from 12-1 pm, which corresponded to the
technicians lunch. To discover if this time frame had anything to do with the recurring drift,
the engineer asked to sit in and observe just before the technicians lunch. At noon all of the
associates left their station and opened a large garage door to have lunch together outside.
The open door raised the ambient room temperature, causing larger-than-normal thermal
errors in all of the transducers. The high accuracy transducer drift was actually caused by
external factors. When the door was kept shut, the engine test cell and the transducers at-
tached remained at a constant temperature and worked properly.

A manufacturer of factory mobile equipment and forklifts had a problem with pressure
transducers failing while their equipment was being assembled. The sensors were returned
to Setra and the failure analysis showed that the sensors electronics were exposed to high
voltages, causing their failure. Setra reengineered and supplied the customer with a more
electrically robust sensor. This prevented the transducer from getting damaged during as-
sembly, but the customer started experiencing failures in more expensive equipment.

The customer asked Setra for the original units so they could replace a sensor instead of a
more expensive part. When a Setra engineer visited the customer months later and watched
the assembly process, the manufacturing team admitted that when they had a short cir-
cuit in the system and turned it on, there was a power surge that damaged the pressure

5
transducer. The engineer recommended that the manufacturing team use an ohmmeter
to check for short circuits before turning the power on, conducting that simple check, the
customer eliminated failures during assembly.

Author Bio:
Dick Pansire is a Senior Application Engineer at Setra Systems, Inc. A 35 year expert in pressure sensing and capacitance
technology, Dick provides customer troubleshooting and support for HVAC and Industrial products. Dick has a background in
manufacturing, engineering and technical support.
About Setra:
Founded by former professors of Engineering at Massachusetts Institute of Technology (M.I.T.), Setra has been designing and
manufacturing sensor products since 1967. Our specialty is in the pressure and sensing in a wide range of markets including
HVAC/R building automation, pharmaceutical, energy, medical sterilization, industrial OEM, test & measurement, meteorology
and semiconductor.

Setra Creates Solutions:


Over 40 years of expertise in sensing and sensing applications
R&D and Design Engineerings focused providing application solutions
Sensors cover a wide range of pressure rages with unique expertise in low pressures
Sales and manufacturing in the U.S., Europe, and Asia for fast solutions and products

Das könnte Ihnen auch gefallen