Sie sind auf Seite 1von 7

See

discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/257873704

INDUCED OVER VOLTAGE SENSITIVITY


ANALYSIS USING STIDA

Conference Paper September 2002

CITATION READS

1 19

1 author:

Miguel Martinez-Lozano
Universidad De La Salle Bajo
74 PUBLICATIONS 39 CITATIONS

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Sizing optimization of PV systems under commercial electricity tariffs scehemes in Mexico View
project

Effect of Seasonal Variations on the Performance of Distribution Lines View project

All content following this page was uploaded by Miguel Martinez-Lozano on 02 June 2014.

The user has requested enhancement of the downloaded file.


3p.6
ICLP 2002 Cracow, Poland September 2-6, 2002 237

2. SIMULATIONS
3. DISCUSSION
In the simulations two standard overhead lines, one
For the sensitivity analysis the induced voltage for 1440
horizontal [7] and the other vertical, were used. For both
cases were obtained. The results are presented in the figures
cases the influence of the ground wire were studied. The
3 to 15. In these figures the first bar corresponds to the
locations of the conductors in the two configurations are
smallest value of the variable involve and the last one to the
shown in the Figure No.2. All the distances are in meters.
largest value. As can be seen, the peak voltages calculated
1.12
are in the range of 100 kV. The peak induced voltage
0.6
0.6
decreases with increasing distance to the strike point. Note
1.12
0.6 also that the maximum over voltage takes place at the
1.64 0.6 distance of 2000 meters from the center of the line when
10 10
the ground is perfectly conducting. Note that the positive
peak of the over voltage decreases with decreasing
conductivity at 1500 m and 2000 m. At 500 m it remains
Figure No.2: Overhead lines configurations. more or less the same. On the other hand, the negative
Several studies have been done previously in order to peak of the induced over voltage increases with
determine the location on the line where the maximum decreasing conductivity. Observe also that the negative
over voltage takes place when lightning flashes are peak for low conductivity is larger than the positive peak
located along the perpendicular bisector of the line. It has obtained for perfectly conducting ground. The reason for
been reported by Montao et al. [5] that this point is this is that the negative peak is mainly created by the
located around 1 and 1.5 km from the center of the line. horizontal field over finitely conducting ground and that it
They called this distance the Critical Over voltage increases with decreasing conductivity. Observe that for a
Distance (COD). However, that study was of limited given peak current, the magnitude of the over voltage
value because the results are based on a single conductor decreases with increasing rise time of the current. The
line. In the present study the induced voltage was reason for this is that the peak of the horizontal field
calculated at three points located at 500, 1500 and 2000 decreases with increasing rise time of the current. This is
meters from the center of the line. In the analysis the the case since the content of higher frequencies in the
voltage at each conductor was calculated and the electromagnetic fields decreases with decreasing rise time
maximum was selected. The conductivity of the ground of the current. Comparison of the magnitudes of the
was assumed to vary between 0.01 and 0.0001 S/m. The induced voltages of the two main configurations,
relative dielectric constant of the ground was kept horizontal and vertical, shows that the voltages induced in
constant at 10 [2]. The striking distance to the power line the vertical configuration are higher than for the
was calculated from the relationship: horizontal one. The reason for this is that the height of the
conductors of the vertical configuration are larger than
S = 10 I 0.65 those of the horizontal one. For example, the upper
where, S is the striking distance in meters and I is the peak conductor of the vertical configuration is 1.2 meters
current in kA. During the simulations, the peak current was above the horizontal ones. This will increase the voltage
kept constant in 50 kA. Hence, the minimum distance to the induced in the line through the coupling of the vertical
strike point at ground is equal to 150 meters. In studying electric field. In analyzing the effects of the return stroke
the effect of the rise time of the current and the return velocity on induced voltages, the distance of the
stroke speed on the induced voltages the point of strike was discharge and the return stroke current were kept constant
kept at this minimum distance. In the calculation the initial at 150 meters and 50 kA respectively. From the data one
return stroke speed, Vo, was changed from 110 m/ s to 200 can see that in the case of perfectly conducting ground the
m/ s in ten steps. The way in which the rise time of the induced voltages reduces with increasing return stroke
current, tf , was varied in the calculations is depicted in velocity. The reason for this is the following. When the
Table 1. In studying the effect of the distance to the point ground is perfectly conducting and when the striking
of strike on the induced voltages, the point of strike was point is located close to the line, the peak induced voltage
varied in ten steps from 150 m from the line to 1500 m. In is determined mainly by the static component of the
these calculations the peak of the current at the base of the electric field. The peak value of this component decreases
channel was kept at 50 kA with a rise time of 1.2 s and a with increasing return stroke velocity if the return stroke
decay time of 50 s. current is kept constant. The reason for this is that in the
TCS model, the effective charge per unit length of the
Study Case return stroke channel decreases with increasing speed of
1 2 3 4 5 6 7 8 9 10 the return stroke. Thus the above result is model
tf [ s] 0.5 1 1.5 2 2.5 3 5 7 9 10 dependent. With decreasing conductivity, the contribution
to the induced voltage from the horizontal field caused by
Table No.1: Rise time values selected for induced voltage the finite conductivity increases. This component of the
calculation field increases with increasing return stroke velocity for a
238 26th International Conference on Lightning Protection

given peak current. Therefore, at low conductivities the 5. REFERENCE


induced voltage increases with increasing return stroke
speed. This one can observe in the figures. No2 and 8. [1] Heidler F., C. Hopf, "Measurement Results of the
Electric Fields in Cloud-To-Ground Lightning
Note how the polarity of the peak induced voltage in Nearby Munich", IEEE Transactions on
changes with conductivity. The negative peak increases Electromagnetic Compatibility, Special Issue on
with decreasing conductivity. The reason for this is that Lightning, Vol.40, No.4, November 1998.
the contribution of the horizontal electric field generated [2] Voislav, Jankov. Estimation of the Maximal
by the finitely conducting ground to the induced voltage Induced Over voltage on an Overhead Line due to
is negative and this contribution increases with decreasing Nearby Lightning , IEEE Transactions On power
ground conductivity. Delivery Vol.12, No.1, pp. 315-324, Jan 1997.
Observe that an introduction of an overhead ground [3] Rachidi F., C.A. Nucci, M. Ianoz, C. Mazzetti,
wire decreases the voltages induced in the line. In order to Influence of a lossy ground on Lightning Induced
analyze this effect we define a protective ratio as follow: Voltages on Overhead lines, IEEE Transactions
on Electromagnetic Compatibility, Vol.38, pp. 250-
Induced Voltage with Ground wire 264, August 1996.
Pr otective Ratio =
Induced Voltage without Ground wire [4] Cooray V., Scuka V., Lightning-induced voltages
in Power lines: Validity of Various approximations
The average protective ratios for different configurations Made in Overvoltages Calculations, IEEE
are given in tables 2 and 3. This ratio determine the Transactions on Electromagnetic Compatibility,
effectiveness of the ground wire on the reduction of the Vol.40, pp. 355-363, August 1996.
induce voltage. [5] Montao R., Cordero A, Martinez M., Sensibility
4. CONCLUSSIONS analysis of induced overvoltages by lightning
An analysis of the way in which the lightning stroke near Distribution system Using ATP-
induced voltages in power lines vary with the EMTP. Proceeding of the International
configuration of the line, ground conductivity and the Conference on Power Systems Transients
return stroke velocity has been presented. The results (IPST99), pp353-358, June 1999,
show that the effectiveness of the overhead ground [6] Rachidi F., C.A. Nucci, M. Ianoz, C. Mazzetti,
wire in reducing the positive induced over voltages Lightning-induced voltages on overhead lines,
decreases with increasing (or decreasing) IEEE Transactions on Electromagnetic
conductivity. Compatibility, Vol.35, pp. 75-85, February 1993
[7] IEE Std 1410-1997. IEEE Guide for improving
the lightning performance of Electric Overhead
Distribution Lines

Horizontal Configuration Vertical Configuration


Inf 0.01 0.001 0.0001 Inf 0.01 0.001 0.0001
tf 0.75 0.77 0.78 0.78 0.64 0.63 0.65 0.75
500 m Vo 0.71 0.69 0.72 0.67 0.63 0.61 0.66 0.67
Yo 0.64 0.62 0.64 0.62 0.63 0.61 0.66 0.71
tf 0.73 0.76 0.77 0.78 0.63 0.60 0.64 0.85
1500 m Vo 0.71 0.68 0.69 0.96 0.63 0.59 0.63 0.96
Yo 0.68 0.70 0.68 0.75 0.63 0.62 0.66 0.86
tf 0.74 0.77 0.78 0.87 0.63 0.60 0.65 0.91
2000 m Vo 0.71 0.67 0.70 1.15 0.64 0.59 0.66 1.15
Yo 0.68 0.71 0.72 0.95 0.64 0.63 0.70 1.03
Table No.1: Average Protective Ratio for the maximum positive peak achieved .

Horizontal Configuration Vertical Configuration


Inf 0.01 0.001 0.0001 Inf 0.01 0.001 0.0001
tf 1.00 1.6 0.63 0.60 1.00 1.6 0.80 0.77
500 m Vo 1.00 1.65 0.76 0.73 1.00 1.5 0.78 0.74
Yo 1.00 0.85 0.68 0.59 1.00 1.57 0.73 0.78
tf 1.00 1.04 0.62 0.59 1.00 1.40 0.81 0.75
1500 m Vo 1.00 0.76 0.74 0.72 1.00 0.79 0.75 0.72
Yo 1.00 0.65 0.57 0.56 1.00 0.92 0.74 0.71
tf 1.00 1.17 0.62 0.59 1.00 1.89 0.83 0.74
2000 m Vo 1.00 0.85 0.77 0.72 1.00 0.89 0.78 0.72
Yo 1.00 0.60 0.57 0.56 1.00 0.80 0.72 0.70
Table No.2: Average Protective Ratio for the minimum negative peak achieved.
ICLP 2002 Cracow, Poland September 2-6, 2002 239

(a)
100 (d)
Yo: 150
Yo: 300 150
Yo: 450 Yo: 150
Yo: 600 Yo: 300
50 Yo: 750 100 Yo: 450
Yo: 900 Yo: 600
Yo: 1050 Yo: 750
Yo: 900
Yo: 1200 50 Yo: 1050
Yo: 1350
0 Yo: 1500 Yo: 1200
1 2 3 4 0 Yo: 1350
Yo: 1500
(b) 1 2 3 4
Induced Voltage [kV]

100 (e)

Induced Voltage [kV]


200

50
100

0
1 2 3 4 0
(c) 1 2 3 4
100 (f)
200

50
100

0
1 2 3 4 0
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001 1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 3: Induce voltage at different observation points for the horizontal configuration without ground wire when Yo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m, (d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a)
150 Vo: 110
(d)
Vo: 120 200 Vo: 110
Vo: 130
100 Vo: 140
Vo: 120
Vo: 130
Vo: 150 Vo: 140
50 Vo: 160 100 Vo: 150
Vo: 170 Vo: 160
Vo: 180 Vo: 170
Vo: 190 Vo: 180
0 Vo: 200 Vo: 190
1 2 3 4 0 Vo: 200
(b) 1 2 3 4
Induced Voltage [kV]

100 (e)
Induced Voltage [kV]

300

50 200

100
0
1 2 3 4 0
(c) 1 2 3 4
100 (f)
300

50 200

100
0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 4: Induce voltage at different observation points for the horizontal configuration without ground wire when Vo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m, (d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a)
150 (d)
tf:
tf:
0.5 us
1 us
200 tf: 0.5 us
tf: 1.5 us tf: 1 us
100 tf: 2 us tf: 1.5 us
tf: 2.5 us tf: 2 us

50 tf: 3 us 100 tf: 2.5 us


tf: 5 us tf: 3 us
tf: 7 us tf: 5 us
tf: 9 us tf: 7 us
0 tf: 10 us tf: 9 us
1 2 3 4 0 tf: 10 us
1 2 3 4
Induced Voltage [kV]

(b)
(e)
Induced Voltage [kV]

150
300
100
200
50
100
0
1 2 3 4 0
1 2 3 4
(c) (f)
150
300
100
200
50
100
0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 5: Induce voltage at different observation points for the horizontal without ground wire configuration when tf is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m, (d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a)
100 (d)
Yo: 150 100 Yo: 150
Yo: 300
Yo: 300
Yo: 450
Yo: 450
Yo: 600
Yo: 600
50 Yo: 750
50 Yo: 750
Yo: 900
Yo: 900
Yo: 1050
Yo: 1050
Yo: 1200
Yo: 1200
Yo: 1350
0 Yo: 1500
0
Yo: 1350
1 2 3 4 1 2 3 4
Yo: 1500
Induced Voltage [kV]

(b)
Induced Voltage [kV]

100 (e)
150

100
50
50
0 0
1 2 3 4 1 2 3 4
(c) (f)
100 150

100
50
50

0 0
1 2 3 4 1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001 Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 6: Induce voltage at different observation points for the horizontal with ground wire configuration when Yo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m,(d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
240 26th International Conference on Lightning Protection

(a)
100
Vo: 110 (d)
Vo: 120 150
Vo: 130 Vo: 110
Vo: 140 Vo: 120
50 Vo: 150 100 Vo: 130
Vo: 160 Vo: 140
Vo: 170 Vo: 150
Vo: 160
Vo: 180 50 Vo: 170
Vo: 190
0 Vo: 200 Vo: 180
1 2 3 4 0 Vo: 190
Vo: 200
1
Induced Voltage [kV]

(b) 2 3 4
100

Induced Voltage [kV]


(e)
200

50
100

0
1 2 3 4 0
(c) 1 2 3 4
100 (f)
200

50
100

0
1 2 3 4 0
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001 1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 7: Induce voltage at different observation points for the horizontal with ground wire configuration when Vo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m,(d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a)
100 (d)
tf: 0.5 us
tf: 1 us 100 tf: 0.5 us
tf: 1.5 us tf: 1 us
tf: 2 us tf: 1.5 us
50 tf: 2.5 us tf: 2 us
tf: 3 us 50 tf: 2.5 us
tf: 5 us tf: 3 us
tf: 7 us tf: 5 us
tf: 9 us tf: 7 us
0 tf: 10 us tf: 9 us
1 2 3 4 0 tf: 10 us
1 2 3 4
Induced Voltage [kV]

(b)
100 (e)
Induced Voltage [kV]

150

50 100

50
0
1 2 3 4 0
(c) 1 2 3 4
100 (f)
150

50 100

50
0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 8: Induce voltage at different observation points for the horizontal with ground wire configuration when t f is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m,(d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a)
150 (d)
Yo: 150 150
Yo: 300 Yo: 150
Yo: 450 Yo: 300
100 Yo: 600 Yo: 450
Yo: 750
100 Yo: 600
Yo: 900 Yo: 750
50 Yo: 1050 Yo: 900
Yo: 1200
50 Yo: 1050
Yo: 1350 Yo: 1200
0 Yo: 1500 Yo: 1350
1 2 3 4 0 Yo: 1500
(b) 1 2 3 4
Induced Voltage [kV]

Induced Voltage [kV]

150 (e)
200
100

50 100

0
1 2 3 4 0
(c) 1 2 3 4
150 (f)
200
100
100
50

0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 9: Induce voltage at different observation points for the vertical configuration without ground wire when Yo
is changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m, (d) Minimum at 500 m, (e)
Minimum at 1500 m, (f) Minimum at 2000 m.
(a)
150 (d)
Vo: 110 200 Vo: 110
Vo: 120
Vo: 130 Vo: 120
100 Vo: 140
Vo: 130
Vo: 140
Vo: 150
Vo: 160 100 Vo: 150
50 Vo: 170
Vo: 160
Vo: 170
Vo: 180
Vo: 180
Vo: 190
0 Vo: 200
0
Vo: 190
1 2 3 4 1 2 3 4
Vo: 200
(b)
Induced Voltage [kV]

Induced Voltage [kV]

(e)
150 300
100 200
50 100
0 0
1 2 3 4 1 2 3 4
(c) (f)
150 300
100 200
50 100

0 0
1 2 3 4 1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 10: Induce voltage at different observation points for the vertical configuration without ground wire when Vo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m, (d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
ICLP 2002 Cracow, Poland September 2-6, 2002 241

(a)
150 (d)
tf: 0.5 us
tf: 1 us 150
tf: 0.5 us
100 tf:
tf:
1.5 us
2 us tf: 1 us
tf: 2.5 us 100 tf:
tf:
1.5 us
2 us
tf: 3 us
50 tf: 5 us tf: 2.5 us
tf: 3 us
tf: 7 us 50 tf: 5 us
tf: 9 us
0 tf: 10 us tf: 7 us
1 2 3 4 tf: 9 us
0 tf: 10 us
(b) 1 2 3 4
Induced Voltage [kV]

150 (e)

Induced Voltage [kV]


300
100
200
50
100
0
1 2 3 4 0
(c) 1 2 3 4
150 (f)
300
100
200
50
100
0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001 Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 11: Induce voltage at different observation points for the vertical without ground wire configuration when t f is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m, (d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a)
100 Yo: 150
(d)
Yo: 300 100 Yo: 150
Yo: 450 Yo: 300
Yo: 600 Yo: 450
50 Yo: 750 Yo: 600
Yo: 900 50 Yo: 750
Yo: 1050 Yo: 900
Yo: 1200 Yo: 1050
Yo: 1350 Yo: 1200
0 Yo: 1500 Yo: 1350
1 2 3 4 0 Yo: 1500
1 2 3 4
Induced Voltage [kV]

(b)
100 (e)
Induced Voltage [kV]

150

50 100

50
0
1 2 3 4 0
(c) 1 2 3 4
100 (f)
150

50 100

50
0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 12: Induce voltage at different observation points for the vertical with ground wire configuration when Yo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m,(d) Minimum at 500 m, (e)
Minimum at 1500 m, (f) Minimum at 2000 m.
(a)
100 (d)
Vo:
Vo:
110
120
150 Vo: 110
Vo: 130 Vo: 120
Vo: 140 Vo: 130
50 Vo: 150
100 Vo: 140
Vo: 160 Vo: 150
Vo: 170 Vo: 160
Vo: 180
50 Vo: 170
Vo: 190 Vo: 180
0 Vo: 200 Vo: 190
1 2 3 4 0 Vo: 200
1 2 3 4
Induced Voltage [kV]

(b) (e)
Induced Voltage [kV]

100
300

200
50
100
0
1 2 3 4 0
(c) 1 2 3 4
100 (f)
300

200
50
100
0
1 2 3 4 0
1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 13: Induce voltage at different observation points for the vertical with ground wire configuration when Vo is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m,(d) Minimum at 500 m, (e) Minimum
at 1500 m, (f) Minimum at 2000 m.
(a) (d)
100 tf: 0.5 us 150
tf: 1 us tf: 0.5 us
tf: 1.5 us tf: 1 us
tf: 1.5 us
tf: 2 us 100 tf: 2 us
50 tf: 2.5 us
tf: 2.5 us
tf: 3 us
tf: 3 us
tf: 5 us 50 tf: 5 us
tf: 7 us
tf: 7 us
tf: 9 us
0 tf: 10 us
0
tf: 9 us
1 2 3 4 1 2 3 4
tf: 10 us
Induced Voltage [kV]

(b)
Induced Voltage [kV]

(e)
100 200

50 100

0 0
1 2 3 4 1 2 3 4
(c) (f)
100 150

100
50
50

0 0
1 2 3 4 1 2 3 4
Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001 Case 1: Sigma Infinite;Case 2: Sigma 0.01; Case 3: Sigma 0.001; Case 4: Sigma 0.0001

Figure No. 14: Induce voltage at different observation points for the vertical with ground wire configuration when t f is
changed. (a) Maximum at 500 m, (b) Maximum at 1500 m, (c) Maximum at 2000 m,(d) Minimum at 500 m, (e)
View publication stats

Minimum at 1500 m, (f) Minimum at 2000 m.

Das könnte Ihnen auch gefallen