FEATURES
* 90A switching capability at Resistance load
* IEC62055-31 UC3 Compliant
* High operating temperature(85C)
* Outline Dimensions : (35.5 x 35.0 x 17.0mm)
* Stronger dielectric strength than typical latching relay(between motor and contacts)
CONTACT SPECIFICATION
Contact Arrangement 1 Form B (Double-Contact of 1 Form B)
Contact Gap Minimum 0.65mm
Contact Pressure 500-600g or 4.9-5.88N
Contact Material AgSnO
Contact Resistance Maximum 1m at initila value(at 90A)
Contact Capacity Max 90 Amps at 250VAC Cos=1
Relay should not fire or exploded after 3 times 10ms current impacts
Surge Current of 6,000A
In accordance with UC3 standard
Max Switching Voltage 440VAC
Mechanical Endurance Minmum 100,000 OPS at Off Load Condition with 0.5Hz
MOTOR CHARACTERISTICS
Power Consumption 1.28W10%
Rated Voltage 5~20VDC
Rated Width of Input Pulse 100ms
Max Width of Input Pulse 200ms *
Max. Allowable Voltage 30VDC
Coil Resistance 19 10%
Operating Time Maximum 80ms
Releasing Time Maximum 50ms
* Input pulse width over 200ms may cause a malfunction of relay.
1
BDJ005
ELECTRICAL CHARACTERISTICS
Total 10,000 Ops
Electrical Endurance At 90A/250VAC, 5,000 Ops(cos=1) and 5,000 Ops(cos=0.5)
Close 10 sec and Open 20 sec in accordance with UC3 standard
100 operations. 120A/250VAC Cos=1
Cycled at 3 seconds rated load current and 12 seconds without
Overload
rated load current
The relay satisfies the requirement of the specification.
Electrical 20 operations/minute
Maximum Operating Frequency
Mechanical 30 operations/minute
Between Signal-lines &
4,000VAC(50/60Hz for 1 minute, leakage current < 1mA)
Dielectric Contacts
Strength
Between Contacts 2,000VAC(50/60Hz for 1 minute, leakage current < 1mA)
ORDERING INFORMATION
Type
2
BDJ005
OUTLINE DIMENSIONS