Colt EN OPV (One Per Vent) is an Proven performance software is configured to suit the
intelligent electronic control system, As life safety equipment, all EN OPV automatic scheme requirements and
which enables all addressable equipment components meet the most stringent should these change, it is a simple matter
to be integrated within a total smoke manufacturing and test procedures. Its of reprogramming the software
control system. communication network uses the proven accordingly.
and robust Apollo protocols.
Whilst it is primarily intended for fire Ventilation equipment is generally
safety applications, it may be designed to Conforming to the latest standards configured into operational zones.
assume the role of a building management EN OPV has been designed to be in However individual control can be
system controlling all manner of natural compliance with PrEN 12101-9 (Smoke provided to meet specific building
ventilators and dampers. and heat control systems - Control Panels) requirements if needed.
and PrEN 12101-10 (Smoke and heat
control systems - Power Supplies). The Complete control
system will be tested and CE marked to Besides the ability to re-configure the
these standards as soon as they are finally system in response to alterations in the
published. In the absence of any scheme, the user can operate the system
Standards in force, EN OPV complies manually at the control panel keypad and
with EN 54 (Fire Detection and Alarm can amend the daily parameters such as
Systems). the temperature settings and operating
times.
EN OPV is CE marked for compliance
with the Machinery Directive, The Low Monitoring and diagnostics
Voltage Directive and the Electro- Software and hardware watchdogs detect
magnetic Compatibility Directive. faults in the system and then act upon
these in a logical controlled fashion.
Flexible These actions extend from merely
Each EN OPV panel can control up to flagging up an alarm to putting the
1000 addressable units and 20 control system into failsafe mode, depending on
zones. With additional remote fire their severity. Faults are recorded in an
override panels, the number of control event log. This feature obviates the
zones can be increased to 80. The potential for system freeze.
maximum number of these remote panels
is 15. Low maintenance
OPV systems are very low in
Addressable maintenance requirements.
Addressability provides accurate control.
EN OPV Main control panel Each addressable unit can be controlled Minimal power requirements
individually and as part of the specified 230v / 1 ph / 1A load for control panel.
automatic control system. The control 3A fuse recommended.
2
The Colt OPV System is the
most advanced smoke control
system available on the market
HOW IT WORKS
3
EN OPV System Overview
Kameleon Meteor
Car Parks Natural Glazed Ventilator Natural Flap Ventilator
Shopping Centres
EN Seefire as fan
termination Power in Power in Power in
Liberator
Power in
* VENT STATUS
VENT FAULT
Open / Close
Configure
Power in
OPERATING INSTRUCTIONS
CONTROL FAULT This panel is for the day to day control of
ventilators. Use the arrow keys to choose
from the menu the function required.
CANCEL SELECT Press the SELECT key to carry out this
function. To return back through the menu
FIRE SIGNAL
EN Seefire
press the CANCEL key. Use the diagram
below to guide you.
MAIN STRUCTURE
SUPPLY HEALTHY
Main Menu
7 8 9
Natural 4 5 6
Vent Status Open / Close Configure
S/W Channel
Open Close
Louvred Ventilators 1 2
1
3
//
All Zone Individual
Time Control
Set Points
OVERRIDE
ENABLE KEY
monitors the
AUTO AUTO AUTO AUTO AUTO
communicates
any problems
which arise
Cyclone
Apollo Comms Line
Car Park Vent
Power in
Power in
Signals from fire detection system
AUTO AUTO
AUTO
AUTO AUTO
AUTO AUTO
AUTO AUTO
Mains in
AUTO AUTO
AUTO AUTO
AUTO
Temperature Sensor
TS Power in Power in
r in
Power in
Power in Power in
Power in
Power in
Defender
Smoke Damper
Power in
Power in Power in
5
Technical Information
Introduction
All dimensions are in mm. Manufacturer Programmable via RS 232 link, and BMS
Colt International Limited, New Lane, compatible, to provide both automatic
230 Havant, Hampshire. PO9 2LY emergency smoke extract ventilation, dual
Tel. 023 9245 1111 purpose day to day ventilation with
Fax. 023 9245 4220 facility for temperature / timer / rain
STATUS VENTILATION CONTROL PANEL
* VENT STATUS
VENT FAULT
Open / Close
Configure
OPERATING INSTRUCTIONS
CONTROL FAULT This panel is for the day to day control of
ventilators. Use the arrow keys to choose
from the menu the function required.
MAIN STRUCTURE
SUPPLY HEALTHY
Main Menu
7 8 9
4 5 6
S/W Channel
Open Close
1 2 3 Time Control
Set Points
Product Reference
All Zone Individual
1 //
* Colt International Ltd,
LAMP ALARM New Lane, Havant, Hampshire,
TEST SILENCE RESET PO9 2LY.
600
OVERRIDE
ENABLE KEY
EN OPV Control System Re-programmable, to accommodate future
revised or additional control zones.
FIREMAN'S OVERRIDE SWITCHES
Description
AUTO AUTO AUTO AUTO AUTO
Uses processor control technology for Single 230V / 1Ph / 50Hz electrical power
380 control of compatible intelligent smoke supply to control panel with control
ventilators and other Colt smoke control signalling via an Apollo network.
products using EN OPV I/O interfaces. Individual or zoned ventilators powered
Weight - approximately 25 kg
by a mains fed battery backup system.
Protection - IP 2X BS 5490 The system consists of the following:
Continuous ventilator, system fault and
Panel LCD to provide menu driven status monitoring, with thermal fuses to
control, with push button zonal FOP achieve fail safe operation (to open or
(firemans override) and auto/open/close close).
185
indication, with diagnostic capability.
AUTO AUTO
AUTO AUTO
AUTO
AUTO AUTO
AUTO AUTO
380
AUTO AUTO
AUTO AUTO
AUTO
CANCEL SELECT
FOP RS 485
Input/Output Boards MAIN STRUCTURE
Main Menu
Set Points
Fire Detection Input
1 //
and to Fans, Smoke * All Zone Individuals
Curtains etc)
WITCHES
AUTO
ZONE 22
AUTO
ZONE 23
AUTO
ZONE 24
AUTO
ZONE 25
AUTO
15 remote FOP
Input/Output ZONE 26
AUTO
ZONE 27
AUTO
ZONE 28
AUTO
ZONE 29
AUTO
ZONE 30
AUTO
units can be
ZONE 31
AUTO
ZONE 32
AUTO
ZONE 33
AUTO
ZONE 34
AUTO
ZONE 35
AUTO
installed
WeatherBeater (optional) ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 providing a
maximum of 80
control zones
2x12V Battery Backup
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25 ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30 ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35 ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35
FIREMAN'S OVERRIDE SWITCHES FIREMAN'S OVERRIDE SWITCHES
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40
ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25 ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30 ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35 ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35
FIREMAN'S OVERRIDE SWITCHES FIREMAN'S OVERRIDE SWITCHES
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40
ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25 ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30 ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35 ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO
ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40
8
Typical wiring schematic for shaft
ventilation.
9
THE COLT PACKAGE COLT SERVICE
Colt International offers the following Other reasons to choose Colt: Part of the Colt Group of companies,
services: Colt Service offers a comprehensive
Colt Smoke Control systems are suited range of maintenance packages
Scheme design of all types of Smoke to both commercial and industrial incorporating the maintenance and
and Heat Exhaust Ventilation Systems buildings, and may be adapted to suit repair of all building services equipment
(SHEVS) most architectural requirements. including non Colt products.
Scheme design of pressurisation
systems Over the years Colt has funded a large Colt Service provides a 24 hour, 365
Scheme design of smoke containment proportion of the research into smoke day emergency cover as standard.
systems control, and its representatives
Provision of performance specifications maintain an unparalleled level of MAINTENANCE
Project management technical expertise.
Supply, installation, commissioning Maintenance of a smoke control system
and maintenance of systems, including Colt's in-house research and is essential. Regular maintenance
all necessary controls, which will be development capability ensures that protects your investment and brings
designed to interface with others' Colt smoke control systems are peace of mind that the system will
control systems. designed, tested and updated by Colt operate effectively in an emergency.
to meet or exceed relevant legislation
A free full system check will be carried and standards. The British Standard BS 5588-12
Colt and the Colt logo are registered trademarks of Colt International
People feel better in Colt conditions Architectural Solutions Colt International Limited
New Lane Havant