Smoke Control

EN OPV - one per vent


Intelligent Electronic Control System
Introduction
EN OPV - Introduction

INTRODUCTION FEATURES & BENEFITS

Colt EN OPV (One Per Vent) is an Proven performance software is configured to suit the
intelligent electronic control system, As life safety equipment, all EN OPV automatic scheme requirements and
which enables all addressable equipment components meet the most stringent should these change, it is a simple matter
to be integrated within a total smoke manufacturing and test procedures. Its of reprogramming the software
control system. communication network uses the proven accordingly.
and robust Apollo protocols.
Whilst it is primarily intended for fire Ventilation equipment is generally
safety applications, it may be designed to Conforming to the latest standards configured into operational zones.
assume the role of a building management EN OPV has been designed to be in However individual control can be
system controlling all manner of natural compliance with PrEN 12101-9 (Smoke provided to meet specific building
ventilators and dampers. and heat control systems - Control Panels) requirements if needed.
and PrEN 12101-10 (Smoke and heat
control systems - Power Supplies). The Complete control
system will be tested and CE marked to Besides the ability to re-configure the
these standards as soon as they are finally system in response to alterations in the
published. In the absence of any scheme, the user can operate the system
Standards in force, EN OPV complies manually at the control panel keypad and
with EN 54 (Fire Detection and Alarm can amend the daily parameters such as
Systems). the temperature settings and operating
times.
EN OPV is CE marked for compliance
with the Machinery Directive, The Low Monitoring and diagnostics
Voltage Directive and the Electro- Software and hardware watchdogs detect
magnetic Compatibility Directive. faults in the system and then act upon
these in a logical controlled fashion.
Flexible These actions extend from merely
Each EN OPV panel can control up to flagging up an alarm to putting the
1000 addressable units and 20 control system into failsafe mode, depending on
zones. With additional remote fire their severity. Faults are recorded in an
override panels, the number of control event log. This feature obviates the
zones can be increased to 80. The potential for system freeze.
maximum number of these remote panels
is 15. Low maintenance
OPV systems are very low in
Addressable maintenance requirements.
Addressability provides accurate control.
EN OPV Main control panel Each addressable unit can be controlled Minimal power requirements
individually and as part of the specified 230v / 1 ph / 1A load for control panel.
automatic control system. The control 3A fuse recommended.
2
The Colt OPV System is the
most advanced smoke control
system available on the market

HOW IT WORKS

EN OPV offers two independent power


sources to operate ventilators, as
prescribed by EN 12101-10. During
normal operation the ventilator is powered
from the mains, which also charges the
integrated battery back up module. The
control system monitors the health of the
communications network.

The system is so designed that if there is a


power failure and no fire signal, all
ventilators powered from the UPS move
to a default operational position
maintained for a minimum time period
before reverting to their pre-programmed
emergency position, unless power is
restored. In normal circumstances the
default operational position will make the
ventilators close thereby reducing the
prospect of water ingress. The minimum
time period is determined at the design
stage and varies between 12 and 72 hours
depending on the number of battery
packs.

3
EN OPV System Overview

Kameleon Meteor
Car Parks Natural Glazed Ventilator Natural Flap Ventilator

Shopping Centres

Single Storey Buildings


& Warehouses

Residential & Office Power in Power in Power in Power in Power


Buildings

EN Seefire as fan
termination Power in Power in Power in

Rain Sensing Head


Power in

(Wired directly into the OPV


panel, or connected via the
Power in

Colt Smoke Curtains Apollo network, as required)

Liberator
Power in

Powered Extract Ventilators


Power in

Colt Fire Curtains


STATUS VENTILATION CONTROL PANEL

* VENT STATUS
VENT FAULT
Open / Close
Configure
Power in

OPERATING INSTRUCTIONS
CONTROL FAULT This panel is for the day to day control of
ventilators. Use the arrow keys to choose
from the menu the function required.
CANCEL SELECT Press the SELECT key to carry out this
function. To return back through the menu
FIRE SIGNAL

EN Seefire
press the CANCEL key. Use the diagram
below to guide you.

MAIN STRUCTURE
SUPPLY HEALTHY
Main Menu

7 8 9
Natural 4 5 6
Vent Status Open / Close Configure

S/W Channel
Open Close

Louvred Ventilators 1 2
1
3
//
All Zone Individual
Time Control

Set Points

* Colt International Ltd,


LAMP ALARM New Lane, Havant, Hampshire,
TEST SILENCE RESET PO9 2LY.
Tel: (01705) 451111

OVERRIDE
ENABLE KEY

Breakglass The control panel FIREMAN'S OVERRIDE SWITCHES

monitors the
AUTO AUTO AUTO AUTO AUTO

health of the AUTO AUTO AUTO AUTO AUTO

Colt system AUTO AUTO AUTO AUTO AUTO

and instantly AUTO AUTO AUTO AUTO AUTO

communicates
any problems
which arise
Cyclone
Apollo Comms Line
Car Park Vent
Power in

Interface to building management system

Power in
Signals from fire detection system

FIREMAN'S OVERRIDE SWITCH


AUTO AUTO AUTO
AUTO AUTO

AUTO AUTO
AUTO
AUTO AUTO

AUTO AUTO
AUTO AUTO
Mains in

AUTO AUTO
AUTO AUTO
AUTO

4 Firemans Override Panel (FOP)


Upto 15 FOP units can be installed
Wind Sensor

Temperature Sensor

TS Power in Power in
r in

Power in
Power in Power in

Power in
Power in

Extensions can be made to the Colt system without


Power in

the need for costly alterations to the control panels


and control line installation.

For natural ventilators, as an additional safety


feature, once the air adjacent to the ventilator
reaches a set temperature, and if no fire alarm or Smoke Detector
overide signal has been received, the ventilator will
failsafe to its open position by the actuation of a
thermal fuse.

Defender
Smoke Damper
Power in

Power in Power in Power in Power in


Doorman
Door Operator
Power in

Power in Power in

5
Technical Information
Introduction

Colt can offer a Windows based user interface to control


Colt equipment, either via a PC with a touch screen display,
or via a modem or Local Area Network (LAN) to a
conventional PC.
6
DIMENSIONS SPECIFICATION

All dimensions are in mm. Manufacturer Programmable via RS 232 link, and BMS
Colt International Limited, New Lane, compatible, to provide both automatic
230 Havant, Hampshire. PO9 2LY emergency smoke extract ventilation, dual
Tel. 023 9245 1111 purpose day to day ventilation with
Fax. 023 9245 4220 facility for temperature / timer / rain
STATUS VENTILATION CONTROL PANEL

* VENT STATUS
VENT FAULT
Open / Close
Configure
OPERATING INSTRUCTIONS
CONTROL FAULT This panel is for the day to day control of
ventilators. Use the arrow keys to choose
from the menu the function required.

www.coltgroup.com sensor control. All set points to be


CANCEL SELECT Press the SELECT key to carry out this
function. To return back through the menu
FIRE SIGNAL press the CANCEL key. Use the diagram
below to guide you.

MAIN STRUCTURE
SUPPLY HEALTHY
Main Menu

7 8 9

adjustable at the control panel.


Vent Status Open / Close Configure

4 5 6
S/W Channel
Open Close

1 2 3 Time Control

Set Points

Product Reference
All Zone Individual
1 //
* Colt International Ltd,
LAMP ALARM New Lane, Havant, Hampshire,
TEST SILENCE RESET PO9 2LY.
600

Tel: (01705) 451111

OVERRIDE
ENABLE KEY
EN OPV Control System Re-programmable, to accommodate future
revised or additional control zones.
FIREMAN'S OVERRIDE SWITCHES

AUTO AUTO AUTO AUTO AUTO

AUTO AUTO AUTO AUTO AUTO

Description
AUTO AUTO AUTO AUTO AUTO

AUTO AUTO AUTO AUTO AUTO


Addressable intelligent electronic All ventilators to operate simultaneously,
controller of smoke control systems. without cascade control or time delays.

Uses processor control technology for Single 230V / 1Ph / 50Hz electrical power
380 control of compatible intelligent smoke supply to control panel with control
ventilators and other Colt smoke control signalling via an Apollo network.
products using EN OPV I/O interfaces. Individual or zoned ventilators powered
Weight - approximately 25 kg
by a mains fed battery backup system.
Protection - IP 2X BS 5490 The system consists of the following:
Continuous ventilator, system fault and
Panel LCD to provide menu driven status monitoring, with thermal fuses to
control, with push button zonal FOP achieve fail safe operation (to open or
(firemans override) and auto/open/close close).
185
indication, with diagnostic capability.

FIREMAN'S OVERRIDE SWITCHES

AUTO AUTO AUTO AUTO AUTO


Compatibility with additional remote fire
override panels to increase the number of
300

AUTO AUTO AUTO AUTO AUTO

AUTO AUTO AUTO AUTO AUTO

control zones. FIREMAN'S OVERRIDE SWITCH


AUTO AUTO AUTO AUTO AUTO
AUTO AUTO AUTO AUTO AUTO

AUTO AUTO
AUTO AUTO
AUTO

AUTO AUTO

AUTO AUTO

380
AUTO AUTO
AUTO AUTO
AUTO

Weight - approximately 10 kg The firemans override panel has a


Protection - IP 2X, If outside building lockable glass door to avoid
IP66 (jet proof) unwanted tampering
7
Technical Information

Driver Cards Front Panel RS 485

TILATION CONTROL PANEL


RS 232 Configuration Input
OPERATING INSTRUCTIONS

CANCEL SELECT
FOP RS 485
Input/Output Boards MAIN STRUCTURE
Main Menu

7 8 9 Vent Status Open/Close Configure

(Interface from Fire 4 5 6


Auxiliary RS 485
Open Close S/W Channel

Detection System 1 2 3 Time Control

Set Points
Fire Detection Input
1 //
and to Fans, Smoke * All Zone Individuals

Colt International Ltd


AMP ALARM New Lane Havant
RESET
EST SILENCE Hampshire PO9 2LY
Tel (01705) 451111

Curtains etc)

WITCHES

AUTO AUTO AUTO AUTO Remote FOP


Unit
Power Supply In AUTO AUTO AUTO AUTO

AUTO AUTO AUTO


FIREMAN'S OVERRIDE SWITCHES

AUTO AUTO AUTO AUTO AUTO


A maximum of
WeatherBeater ZONE 21

AUTO
ZONE 22

AUTO
ZONE 23

AUTO
ZONE 24

AUTO
ZONE 25

AUTO
15 remote FOP
Input/Output ZONE 26

AUTO
ZONE 27

AUTO
ZONE 28

AUTO
ZONE 29

AUTO
ZONE 30

AUTO
units can be
ZONE 31

AUTO
ZONE 32

AUTO
ZONE 33

AUTO
ZONE 34

AUTO
ZONE 35

AUTO
installed
WeatherBeater (optional) ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 providing a
maximum of 80
control zones
2x12V Battery Backup

FIREMAN'S OVERRIDE SWITCHES FIREMAN'S OVERRIDE SWITCHES

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25 ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30 ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35 ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35
FIREMAN'S OVERRIDE SWITCHES FIREMAN'S OVERRIDE SWITCHES
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40
ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25 ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30 ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35 ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35
FIREMAN'S OVERRIDE SWITCHES FIREMAN'S OVERRIDE SWITCHES
AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40
ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25 ZONE 21 ZONE 22 ZONE 23 ZONE 24 ZONE 25

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30 ZONE 26 ZONE 27 ZONE 28 ZONE 29 ZONE 30

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35 ZONE 31 ZONE 32 ZONE 33 ZONE 34 ZONE 35

AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO

ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40 ZONE 36 ZONE 37 ZONE 38 ZONE 39 ZONE 40

8
Typical wiring schematic for shaft
ventilation.

Typical multi-zone wiring


schematic.

9
THE COLT PACKAGE COLT SERVICE

Colt International offers the following Other reasons to choose Colt: Part of the Colt Group of companies,
services: Colt Service offers a comprehensive
 Colt Smoke Control systems are suited range of maintenance packages
 Scheme design of all types of Smoke to both commercial and industrial incorporating the maintenance and
and Heat Exhaust Ventilation Systems buildings, and may be adapted to suit repair of all building services equipment
(SHEVS) most architectural requirements. including non Colt products.
 Scheme design of pressurisation
systems  Over the years Colt has funded a large Colt Service provides a 24 hour, 365
 Scheme design of smoke containment proportion of the research into smoke day emergency cover as standard.
systems control, and its representatives
 Provision of performance specifications maintain an unparalleled level of MAINTENANCE
 Project management technical expertise.
 Supply, installation, commissioning Maintenance of a smoke control system
and maintenance of systems, including  Colt's in-house research and is essential. Regular maintenance
all necessary controls, which will be development capability ensures that protects your investment and brings
designed to interface with others' Colt smoke control systems are peace of mind that the system will
control systems. designed, tested and updated by Colt operate effectively in an emergency.
to meet or exceed relevant legislation
A free full system check will be carried and standards. The British Standard BS 5588-12
Colt and the Colt logo are registered trademarks of Colt International

out approximately 9 months after a recommends that smoke control systems


Smoke Control System has been installed  The majority of Colt's Smoke Control
Licensing Limited. Colt International Licensing Limited 2006.

should be serviced at least once a year


and commissioned by Colt. Besides the systems are manufactured in the UK and tested weekly.
Subject to modification. Publication number PD 12: 11/06

opportunity to check that the system is under BS EN ISO 9001:2000 and BS


performing as designed, this will allow EN ISO 14001:2004.
for any further training of local personnel
that may be necessary. Assuming that this
visit falls within the warranty period, any
defective parts are replaced free of
charge. A test certificate will be issued.

People feel better in Colt conditions Architectural Solutions Colt International Limited
New Lane Havant
terna
In t Climate Control Hampshire PO9 2LY
io

Tel +44(0)23 9245 1111


Colt

nal

Smoke Control Fax +44(0)23 9245 4220


info@coltgroup.com
6
1

3
0
9

1 - 2 0 Service and Maintenance www.coltgroup.com