(Fig. 10 in 11), span SM23 SM24, we gathered data on at 2.30p.m., OHL turned on, I = 135A, ambient temperature
3
DEMSEE'15 10th International Conference on Deregulated Electricity Market Issues in South Eastern Europe
24-25 September 2015, Budapest, Hungary
4
DEMSEE'15 10th International Conference on Deregulated Electricity Market Issues in South Eastern Europe
24-25 September 2015, Budapest, Hungary
5
DEMSEE'15 10th International Conference on Deregulated Electricity Market Issues in South Eastern Europe
24-25 September 2015, Budapest, Hungary
During this period we carried out calculations (DTR) Senj, it inevitability influences their operation. A major
with indirect methods (mathematical model), t.i. part of the current problems is connected to the energy
measurements with only ambient data, and with a direct placement, especially in the hydro-abundant periods,
method (conductor measurement method) with ambient when this line is overloaded with energy from the south
data taken into account. We had at our disposal published hydro plants and with no additional energy input from the
empirical formulas CIGRE [7-12], IEC [13] and IEEE wind power plant [17, 18].
[14-16]. This will continue to be a problem until the 110kV
To determine the conductor current we decided to use network is reinforced, especially if the HPP power output
the latest CIGRE [7] formula with ambient data and we will increase to the planned 66MW.
additionally built in an "anchor" or measured conductor Fig. 9 shows alarm states or STR+ on OHL, which
temperature data. We are sure that in this way we came was built in 1960 and has been constructed for 40C
close to the actual real-time physical conditions of the conductor temperature. The OTLM device notified the
conductor and therefore we can assure a more reliable operator that during the observation period the
calculation of the existing DTR/DLR or ampacity. The temperatures exceeded 50 C.
same applies to the indirect method, in which numerous
factors (constant factors and parameters, conductor aging
or the actual state of conductor surface, absorption,
radiation, etc.) influence the tolerance area.
We have to emphasise that today some transmission
companies operate based on long-term operator
experiences. To prevent overloads or conductor
overheating they use overcurrent protection, which turns
off conductors when they reach critical loads. Their only
progress is that they set currents seasonally (winter,
summer). Only some companies actively run networks
with the support of DTR/DLR features. Fig. 8 OHL located by the sea
6
DEMSEE'15 10th International Conference on Deregulated Electricity Market Issues in South Eastern Europe
24-25 September 2015, Budapest, Hungary
7
DEMSEE'15 10th International Conference on Deregulated Electricity Market Issues in South Eastern Europe
24-25 September 2015, Budapest, Hungary
References
[1] Lesjak, S., Lovreni, V., Dimovi, Z.,
Mekhanoshin, B., Borodin, A., Shkaptsov, V.,
Salnikov, A. "Overhead line uprating using ALS and
Fig. 11 Calculated forces on the conductor fixing point at real time monitoring of conductor temperature," 15th
measurement temperature T=+29.5C and ambient temperature International Symposium on High Voltage
+17.39C (measurements from 9.7.2014) Engineering (IHS), Ljubljana, Slovenia, Aug. 27
31, 2007.
The numerous measurements carried out in the field [2] Lovreni, V., Gabrovek, M., "Temperature
have confirmed and excellent correlation between monitoring of overhead lines (OHLs) is Smart Grid
measured sags in the field and the sags that were solution for power grid," Conference on Smart Grids
determined with a mathematical model "OTLM-SAG", 2010, Sibiu, Romania, Nov. 2123, 2010.
which confirms that the data can be used as an alarm [3] Lovreni, V., Gabrovek, M., Marinek, M., Polak,
when the critical sag or safety height are reached. M. "Conductor temperature monitoring in the
Slovenian transmission network," Transmission &
Distribution Europe 2010, Amsterdam, Netherlands,
Mar. 2931, 2010.
8
DEMSEE'15 10th International Conference on Deregulated Electricity Market Issues in South Eastern Europe
24-25 September 2015, Budapest, Hungary
[4] Kova, M., Lovreni, V., Kozjek D., Krevelj M. [8] CIGRE, TB 207, "Thermal behaviour of overhead
"Statino in dinamino doloanje obremenjenosti conductors," Working group 22.12, 2002.
DV 2x110 kV Slovenj Gradec Dravograd na [9] CIGRE, TB 244, "Conductors for the uprating of
podlagi spremljanja tokovne in vzdolne meritve overhead lines, " 2004.
temperature," (Static and dynamic load rating for [10] CIGRE, TB 299, "Guide for selection of ambient
OHL 2x110 kV Slovenj Gradec Dravograd, parameters for bare overhead conductor ratings,"
determined with spot and whole line temperature Working group B2.12, 2006.
measurements), 11th Slovenian Power Engineering [11] CIGRE, TB 324, "Sag-Tension Calculation Methods
Conference CIGRE CIRED, Lako, Slovenia, May for Overhead Lines," Task Force B2.12.3, 2007.
2729, 2013. (in English) [12] CIGRE, TB 498, "Guide for Application of Direct
[5] Lovreni, V., Marinek, M., Kozjek, D., Kova, Real-Time Monitoring Systems," WG B2.36, 2012.
M., Gabrovek, M. "Tokasto i uzduno mjerenje [13] IEC TR3 1597:1995, "Overhead electrical
temperature osnova za statiko i dinamiko conductors Calculation methods for stranded bare
odreivanje optereenja DV 2x110 kV Slovenj conductors," 1995.
Gradec Dravograd," (Spot and longitudinal [14] IEEE Std 738-1993, "Standard for Calculating the
temperature measurements base for static and Current-Temperature Relationship of Bare Overhead
dynamic thermal rating of OHL 2x110 kV Slovenj Conductors, (Revision of IEEE Std 738-1986),"
Gradec Dravograd), 11th Conference HRO- IEEE-SA Standards Board, Jun. 17, 1993.
CIGRE, Cavtat, Croatia, Nov. 1013, 2013. (in [15] IEEE Std 738-2006, "Standard for Calculating the
English) Current-Temperature of Bare Overhead Conductors
[6] Lovreni, V., Gubeljak, N., Bani, B., Ivec, A., (Revision of IEEE Std 738-1993)," IEEE-SA
Kozjek, D., Jarc, M. "Monitoring za posredno Standards Board, Nov. 16, 2006.
odreivanje promjene horizontalne sile u zavisnosti [16] IEEE Std 7382011, "IEEE Standard for Calculating
od promjene temperature i nagiba nadzemnog voda the Current-Temperature Relationship of Bare
dalekovoda prijenosnog sustava," (On-line Overhead Conductors", 2011.
monitoring for direct determination of horizontal [17] Mandi, N., Tenera, T., Valenti, V. "Utjecaj
forces vs. temperature and incline angle of vjetroelektrana na sigurnost i voenje", (The
transmission conductor, Fourth session of Cired influence of wind power plants on safety and
management), 9th Symposium on power system
Croatian National Committee), 11th Symposium on management HRO-CIGRE, Zadar, Croatia, Oct. 8,
power system management HRO-CIGRE, Opatija, 2010. (in English)
Croatia, Nov. 1012, 2014. (in English) [18] Mandi N. "Utjecaj VE vratarua na sigurnost i
[7] CIGRE, TB 601, "Guide for Thermal Rating voenje elektroenergetskog sustava," (The influence
Calculations of Overhead Lines," Working group of wind power plants on safety and management of
B2.43, 2014. power systems), EGE, 1/2011, pp. 102106. 2011.
(in English)