Beruflich Dokumente
Kultur Dokumente
DIMENSIONS
Dimensions, in.
Specimen No.
A B C D
1 0.015
12 approximately
11 16 2 0.005 214 min
2 34 0.031 1 approximately 2 0.005 214 min
4 0.005 412 min
3 1 0.062 112 approximately 2 0.005 214 min
4 0.005 412 min
4 112 .125 2 approximately 2 0.010 214 min
4 0.015 412 min
8 0.020 9 min
5 .002
14 approximately
38 1 0.003 1 14 min
given in Test Methods E8/E8M. or before separating it as in Fig. A2.4 (b), and may be done hot
A2.2.2.2 The width should be measured at each end of the or cold; but if the flattening is done cold, the specimen may
gauge length to determine parallelism and also at the center. subsequently be normalized. Specimens from tubes or pipe for
The thickness should be measured at the center and used with which heat treatment is specified, after being flattened either
the center measurement of the width to determine the cross- hot or cold, shall be given the same treatment as the tubes or
sectional area. The center width dimension should be recorded pipe. For tubes or pipe having a wall thickness of less than 34
to the nearest 0.005 in. (0.127 mm), and the thickness in. (19 mm), the transverse test specimen shall be of the form
measurement to the nearest 0.001 in. and dimensions shown in Fig. A2.5 and either or both surfaces
A2.2.3 Transverse Strip Test Specimens: may be machined to secure uniform thickness. Specimens for
A2.2.3.1 In general, transverse tension tests are not recom- transverse tension tests on welded steel tubes or pipe to
mended for tubular products, in sizes smaller than 8 in. in determine strength of welds, shall be located perpendicular to
nominal diameter. When required, transverse tension test the welded seams with the weld at about the middle of their
specimens may be taken from rings cut from ends of tubes or length.
pipe as shown in Fig. A2.4. Flattening of the specimen may be A2.2.3.2 The width should be measured at each end of the
done either after separating it from the tube as in Fig. A2.4 (a), gauge length to determine parallelism and also at the center.
The thickness should be measured at the center and used with
the center measurement of the width to determine the cross-
sectional area. The center width dimension should be recorded
to the nearest 0.005 in. (0.127 mm), and the thickness
measurement to the nearest 0.001 in. (0.025 mm).
A2.2.4 Round Test Specimens:
FIG. A2.4 Location of Transverse Tension Test Specimens in A2.2.4.1 When provided for in the product specification, the
Ring Cut from Tubular Products. round test specimen shown in Fig. 4 may be used.
28