MARINE ELECTROTECHNOLOGY
TIME ALLOWED - 3 HOURS
MORNING PAPER

Instructions
1. All questions carry equal marks.
2. Neatness in handwriting and clarity in expression carries weightage
3. Illustration of an answer with clear sketches / diagrams carries weightage
4. All unused pages of answer script must be cancelled out by two line (X) across the page
Q1. Two Diesel Generators running in parallel with D/G # 1 having 2000 KW capacity having 3 % speed droop
setting and D/G # 2 having 2000 KW capacity with 4% speed droop settings. The frequency for Diesel
Generator on no load has been set at 62 Hz.
A) Calculate the load on each Diesel Generator KW if total ship load is 1000 KW. B) Justify the load difference
shared by both Diesel Generator.
2017/SR08

Q2. Two Alternators running in parallel with D/G # 1 having 2000 KW capacity with 4 % speed droop and D/G #
2 having 1000 KW capacity with 4% speed droop. The no load frequency is 62 Hz. How much KW load shared
by each alternator if total ship load is 1200 KW?
2017/SR08

Q3. What would be value of Neutral Earthing Resister in a high voltage ship of three phase alternators to limit
the earth fault current to the full load of rating of a 4 MW having 0.8 power factor generating 6600 volts?
2017/SR08

Q4. A) Calculate the Line and Phase current at full load of a 50 kW, 440 Volt 3 phase deltas connected motor
having full load efficiency 90% and power factor O.8 lagging. B) Calculate the starting current if motor is started
by star/delta starter and Auto transformer starter which has transformer tapping 65 %
2017/SR08

Q5. A three-phase transformer has 900 turns in primary and 104 turns in secondary winding respectively. The
primary winding is connected with power supply of 6600 Volt from HV switch board. Calculate the secondary line
voltage when transformer is connected in A) Star-Delta B) Delta-Star
2017/SR08

Q6. An alternator having 8 pole driven by 900 rpm Diesel engine supplies power to load of Synchronous motor
having 24 poles and Induction motor of 8 poles and 2 % slip. A) Calculate the frequency and speed of
Synchronous Motor. B) Calculate the frequency and Speed of Induction Motor.
2017/SR08

Q7. Two 10 MVA 3 phase Alternator operate in parallel to supply at 0.8 power factor with lagging load of 15
MVA. If the output of one Alternator is 8 MVA at 0.9 lagging. A. Calculate the output of second Alternator. B.
Calculate the value of Power factor of second Alternator.
2017/SR08

WWW.DIESELSHIP.COM
WWW.DIESELSHIP.COM 2
Q8. An AC Voltage Of 24 V is connected in series with the silicon diode and load resistance 500 Ohm having
forward resistance 1O Ohms. Calculate the peak output voltage.
2017/SR08

Q9. With reference to adjoining circuit calculate following. (a) Current in each branch of circuit. (b) Total current.