Sie sind auf Seite 1von 2

Sheet1

For Water Sample


compressor hot water transfer

1 Flow in m3/hr 50 125 10 140 27 3000

2 Pipe Dia in m 0.1 0.1 0.05 0.2 0.08 0.75

3 Velocity in m/sec 1.77 4.42 1.42 1.2384996 1.49 1.89

4 Equivalent length of pipe in m 500 100 20 100 50 200

5 Reynolds No. 176928.520877565 442321.302194 70771.408 247699.93 119426.752 1415428.16702052

6 e/D 0.0004573171 0.0004573171 0.0009146 0.0002287 0.00057165 6.09756097561E-05

7 Find f from Moody Tables for the 0.018 0.019 0.026 0.0175 0.021 0.015
value of e/D

8 Friction loss in metres 14.3741486479 18.9658905771 1.0630481 0.6847685 1.49233562 0.7268705292

Values in Yellow Boxes indicate Also cooling water


INPUT supply

Sl No. Pipe material Value of e in Ft


1 CS Steel 0.00015
2 Asphalted cast iron 0.0004
3 Galvanised iron 0.0005
4 Cast Iron 0.00085
5 Wood Stave .0006-.003
6 Concrete .001-.01
7 Riveted steel .003-.03

-1-
Sheet1

hot water FOR DUCTILE FOR DUCTILE


transfer PIPE PIPE
275 100 100

0.25 0.2 0.2

1.56 0.88 0.88

1000 6146 5000

389242.74593 176928.520878 176928.52088

0.0001829268 0.0012957317 0.0012957317

0.016 0.0222 0.0222

7.9156200625 27.239251257 22.160145832

Also cooling
water supply

-2-