PRODUCT INTRODUCTION
WORKING PRINCIPLE
The piezoelectric component is used to drive the tuning fork and feedback signal, which produces the
resonation on the fork. When the fork comes into contact with a material, the fork will release some frequency
signal as feedback. It will be converted into the output of the contact signal when the circuit detects the
frequency decrease of the signal.
The product relies on the damping effect by covering the testing material on the tuning fork which reduces the
vibration frequency of the tuning fork and outputs a switch signal. Therefore, there is no signal amplification
circuit inside, which can eliminate the trouble of frequent sensitivity adjustment due to the material change.
Dimensions
271 25 273 25 258 25
(Unit:mm) HEX38 HEX38 HEX38
25 f29 25 f29 25 f29
1PT 1PT 1PT
Max. Max. Max.
f27 250mm f27 250mm f27 250mm
20 23 20 23 20 23
Standard Type Extension Type Standard Type Extension Type Standard Type Extension Type
Operating temp.
-40~80LC
in ambient air
Storage temp. -40~85LC
Magnetic testing Output function test performed by putting magnets near the indicated spot
Vibrating 350~370Hz
frequency
Green light:indicate power supply
Status indication Red light:indicate operating mode
Housing
SUS304
material
Fork material SUS304, SUS316, SUS316L
Conduit Valve plug DIN 43650 M12x1 Connector(180L / 90L) Cable connector
2
MINI-TYPE
17 17 17 17 17 17
Standard Type Extension Type Standard Type Extension Type Standard Type Extension Type
Operating temp.
-40BC~80BC
in ambient air
Storage temp. -40BC~85BC
Magnetic testing Output function test performed by putting magnets near the indicated spot
Vibrating
1 KHzK10%
frequency
Green light:indicate power supply
Status indication Red light:indicate operating mode
Housing SUS304
material
Fork material SUS304, SUS316, SUS316L
Mounting 3/4"more
Conduit Valve plug DIN 43650 M12x1 Connector(180L / 90L) Cable connector
3
STANDARD TYPE
f113
f113
108
f113 1/2"NPTx2
108
1/2"NPTx2
20
108 20
1"PT
1/2"NPTx2
Dimensions 1"PT
20
(Unit:mm) 25 1" PT f29
f27 f27.2 130~250mm
105 250mm~3M
f27
f27
105
105
Conduit 1/2"NPTx2
Power
10VA
consumption
Operating temp.
-40LC~60LC
in ambient air
Operating temp. -40LC~130LC
in bin
Relay, SPDT, 5A/250Vac/ 28Vdc, 1 set or 2 set
Signal output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1 set or 2 set
Min. material
Solid:0.07g/cm3, Liquid: 0.7g/cm3
density sensed
Time delay 0.6 Second / Operate; 1~3 Seconds / Reset
Vibrating 350~370Hz
frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
sensitivity
4
STANDARD TYPE
f113 f113
108 108
1/2"NPTx2 1/2"NPTx2
Dimensions
(Unit:mm)
105 105
SC1540 SC1600
Model No.
Corrosion Proof Type Sanitary Type
Level sensor
Aluminum / IP65
housing
Probe
316L Coating TEFLON 316L
construction
Mounting 1" Flange (min.) 2" Sanitary
Conduit 1/2"NPTx2
Power
10VA
Consumption
Operating temp.
-40LC~60LC
in ambient air
Operating temp. -40LC~130LC
In bin
Relay, SPDT, 5A/250Vac/ 28Vdc, 1 set or 2 set
Signal output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1 set or 2 set
Min. material
Solid: 0.07g/cm3, Liquid: 0.7g/cm3
density sensed
Time delay 0.6 Second / Operate; 1~3 Seconds / Reset
Vibrating 350~370Hz
frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
sensitivity
5
NEPSI PROOF No.GYJ111212 Ex d IIC T3~T6
PTB PROOF No. 09 ATEX 1058 II 2G Ex d IIB T4 Gb
EX-PROOF TYPE II 2D Ex tb IIIC T80BC ~ T130BC Db IP65
f113
108
f113 1/2"NPTx2
20
108 1"PT
1/2"NPTx2
Dimensions
20
(Unit:mm) 1" PT
f27.2
105
250mm~3M
f27
105
Conduit 1/2"NPTx2
Power
10VA
consumption
Operating temp.
-20LC~70LC
in ambient air
Operating temp. -40LC~130LC
in bin
Relay, SPDT, 3A/250Vac/ 28Vdc, 1 set or 2 set
Signal output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1 set or 2 set
Min. material
Solid: 0.07g/cm3, Liquid: 0.7g/cm3, viscosity : 1~10000 cst
density sensed
Time delay 0.6 Second / Operate; 1~3 Seconds / Reset
Vibrating 350~370Hz
frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
sensitivity
6
NEPSI PROOF No.GYJ14.1150 DIP A20/21 TA ,T2~T6 IP66/67
f84
f84
f84
1/2"PF 1/2"PF
1/2"PF
16
16
16 1-1/2"PT
1-1/2"PT 1-1/2"PT
f42
Dimensions 225
155
(Unit:mm) f42 225~4000
750~20000
34
f42
34
34
f84 f84
104 104
1/2"PF 1/2"PF
121 121
Dimensions 1-1/2"PT
1-1/2"PT
(Unit:mm)
225~4000
Probe
Max. 1.5 W
construction
Voltage endurance
3.7 kV
capability
Overvoltage
overvoltage category II
protection
Storage temp. -40~85 BC
Operating temp.
-40~85 BC
in ambient air
Medium temp. -40~280 BC
Measuring
140 Hz 5 Hz
frequency
Material
Max.10 mm
dimension
Conduit 1/2PF / 1/2NPT(Ex-proof type only supports 1/2NPT)
External diameter
of cable applicable f6~f10 mm
to conduit
Pressure 25 Bar
resistance
Output signal 2 sets of SPDT relay output/2 sets of transistor output
f84
f84
f84
107
107
1/2"PF
107 1/2"PF
1/2"PF 14.7
Dimensions 14.7
3/4"PT
14.7 3/4"PT
(Unit:mm) 3/4"PT
f21
f22.7
75 f21 120
40 120~3000
f22.7
40
16.9 f21
16.9
16.9
Output type 8~16mA output type 3 wires (NPN/PNP) output type Dual-relay output type
Working voltage 11 ~36 Vdc 10 ~55 Vdc 19~253Vac/dc,50/60Hz
Power consumption 600mW 830mW Max. 1.3W
Input protection Reversed power supply protection function NA
Overvoltage
overvoltage category III
protection
Measuring error Max.1mm
Repeatability 0.5mm
Hysteresis band Approx.2mm
Storage temp. -40~85 BC
Operating temp.
-40~85 BC
in ambient air
Medium temp. -40~90 BC
Applicable density
liquid 0.5 g/cm3 or 0.7 g/cm3
It shall combine with the ex-proof fence meeting level Ex ia to form the intrinsically safe system. Please refer to page 23
for more details. 9
SC38 MULTI-FUNCTIONAL TUNING FORK LEVEL SWITCH
f84
f84
f84
107
1/2"PF
107
107 1/2"PF
1/2"PF
f42
120.2
f42
f42
Dimensions 120.2
120.2
14.7
(Unit:mm) 3/4"PT
14.7
14.7
3/4"PT
3/4"PT f22.7
f21
75 f22.7 120~3000
40 f21 120
40 f21
16.9
16.9 40
16.9
Output type 8~16mA output type 3 wires (NPN/PNP) output type Dual-relay output type
Working voltage 11 ~36 Vdc 10 ~55 Vdc 19~253Vac/dc,50/60Hz
Power consumption 600mW 830mW Max. 1.3W
Input protection Reversed power supply protection function NA
Overvoltage
overvoltage category III
protection
Measuring error Max.1mm
Repeatability 0.5mm
Hysteresis band Approx.2mm
Storage temp. -40~85 BC
Operating temp.
-40~85 BC
in ambient air
Medium temp. -40~150 BC
Applicable density
liquid 0.5 g/cm3 or 0.7 g/cm3
It shall combine with the ex-proof fence meeting level Ex ia to form the intrinsically safe system. Please refer to page 23
for more details. 10
WIRING INSTRUCTIONS (STANDARD TYPE)
SENSITIVITY SENSITIVITY
PWR SIGNAL FSL FSH L H PWR SIGNAL FSL FSH L H
20~250VAC 20~250VAC
20~250VDC 20~250VDC
Relay output type(SPDT) SSR(MOSFET) output type Relay output type (DPDT) SSR(MOSFET) output type
RT2 RT1 NC COM NO N- L+ RT2 RT1 N- L+ RT2 RT1 COM2 NC2 NO2 COM1 NC1 NO1 N- L+ RT2 RT1 2 2 1 1 N- L+
SENSITIVITY ADJUSTMENT
The SENSITIVITY is located on the right side of the panel. The
user is able to do the minor adjustment by the screw driver when it
rotates for 22 turns. If it turns to H position clockwise, the sensitivity
FSL FSH
increases; if it turns to L position anti-clockwise, the sensitivity
decreases. The sensitivity is originally set at max. value. The Level
switching point is at 15mm from the tip of the tuning fork.The
switching point position will be changed by the sensitivity value. If
the sensitivity adjusts to lower value, the switching point position is Contact
form NO COM NC NO COM NC
moving backward; if the sensitivity adjusts to high value, the NO COM NC NO COM NC
switching point position is moving forward. User may change the Indication
switching point position by adjusting the sensitivity. The changing
range of switching point is about 60mm. For example, if the Status Fail Normal Normal Fail
switching point needs to be moved backward by 30mm, the user
needs to adjust SENSITIVITY anti-clockwise by 10 turns. In general
cases, there is no need for sensitivity adjustment.
11
WIRING INSTRUCTIONS (LITE-TYPE/MINI-TYPE)
PE N - L+ PE N - L+
PE N- L+ PE N- L+
DIN Wiring Diagram M12x1Cable Wiring Diagram
Low(Min.)Mode:
Black Black
Pin 1 (Brown) connects to N-. Pin 2 (Black)
Black Black
Blue Blue
Brown
Blue Blue
Brown
connects to L+. To output, Pin 3 (Blue) connects to
Brown Brown
Yellow Green Yellow Green Yellow Green Yellow Green N- with relay. Pin 4 (Yellow Green) should contact
to tank ground.
PE N- L+ PE N- L+ PE L+ N- PE L+ N-
M12x1Cable Wiring Diagram NPN wiring
Figure 2 PNP / NPN Output Wiring Diagram High(Max.) Mode:
Pin 1 (Brown) connects to L+. Pin 3 (Blue)
connects to N-. To output, Pin 2 (Black) connects to
L+ with relay. Pin 4(Yellow Green) should contact
to tank ground.
Low(Min.)Mode:
Pin1 (Brown) connects to L+. Pin 2 (Black)
connects to N-. To output Pin 3 (Blue) connects to
L+ with relay. Pin 4 (Yellow Green) should contact
to tank ground.
12
WIRING INSTRUCTIONS (SC35)
F.S.
NO1 COM1 NC1 NO2 COM2 NC2 NO2 COM2 NC2
MAX
O.S.
L N NO1 COM1 NC1 NO2 COM1 NC2 GND
F.S.
NO1 COM1 NC1 NO2 COM2 NC2 NO2 COM2 NC2
O.S.
Fuse
Load Load
0.5A F.S.
NO1 COM1 NC1 NO2 COM2 NC2 NO2 COM2 NC2
MIN
Output1 Output2 O.S.
19~253 Vdc/Vac
50/60Hz F.S.
NO1 COM1 NC1 NO2 COM2 NC2 NO2 COM2 NC2
O.S.
Dual-transistor output
Output signal LED indicators
Failure Material
output2 Power Status Alarm
mode level output1
S.S. OFF S.S. ON Green Yellow Red
L N NO1 COM1 NO2 COM2 GND O.S.
NO1
lL COM1 NO2
lL COM2 NO2
lL COM2
F.S.
MAX
O.S.
Fuse NO1
<100mA
COM1 NO2
<100mA
COM2 NO2
lL COM2
Load Load
0.5A F.S.
Output1 Output2
19~253 Vdc/Vac NO1
lL COM1 NO2
lL COM2 NO2
lL COM2 O.S.
50/60Hz
F.S.
MIN
O.S.
NO1
<100mA
COM1 NO2
<100mA
COM2 NO2
lL COM2
F.S.
U max. 60Vdc@I L max. 350mA Viscous material Maintain the previous state <100mA
F.S.
Extermal load R must be connected
NO1 COM1 NO2 COM2 NO2 COM2
NO2 COM2
NO1 COM1
Maintain the <100mA
Output1>350mA <100mA
previous state
Output2>350mA
: ON : Flash : OFF
13
WIRING INSTRUCTIONS (SC38)
SC38
+ ~16mA O.S.
1 2
+ <3.6mA
Ex-proof area Ex ia Instrument failure
2 1
H
Non-Ex-proof area
I : ON : Flash : OFF
~16mA=16mA K5%
L
- + ~8mA=8mA K6%
Fuse F.S.
NO1 COM1 NC1 NO2 COM2 NC2
0.5A R R
Instrument failure
Output1 Output2 NO1 COM1 NC1 NO2 COM2 NC2
19~253 Vdc/Vac
50/60Hz R: External load : ON : Flash : OFF
PNP/NPN Output
IL O.S.
F.S. D.T. S.G. S. I. F.S.
Calibration button MAX S H F .S. MAX
Test MIN L L O.S.
O.S.
<100mA
F.S.
SC38
O.S.
U-10...55VDC IL
PWR SIG
PNP: L+ L- O/P F.S.
NPN: L- L+ O/P GND
MIN
O.S.
<100 m A
F.S.
<100 m A
Fuse R Instrument failure
50mA
R : External load
U max. 55Vdc@IL max. 350mA
14
TUNING AND INDICATION DETAILS
S.G.<1g/cm 3
Trigger Point
Testing
moves upward point
Trigger
point Magnet
S.G.>1g/cm 3 23mm
Trigger Point
moves downward
S.G.<1g/cm 3
Trigger Point
moves upward
Sensing spot
10 mm
S.G.>1g/cm 3
Trigger Point
moves downward
Output Status for Relay Output Status for PNP / NPN Transistor
Low (Min.) Mode: Tuning fork switch will be active Low(Min.) Mode : Tuning fork switch will be
after 3 seconds while power on. Relay is on active after 3 seconds while power on. Output
NO status and red LED indication is off. When transistor is on NO status and red LED indication
tuning fork is covered by testing medium, the vibration is off. When tuning fork covered by testing medium,
will stop and relay becomes NC status. vibration will stop and output transistor becomes NC
Red LED indication then is on. status. Red LED indication is on.
High(Max.) Mode: Tuning fork switch will be active High(Max.) Mode: Tuning fork switch will be
after 3 seconds while the power on. Relay is on active after 3 seconds while power on. Output
NC status and red LED indication is on. When tuning transistor is on NC status and red LED indication
fork covered by testing medium, the vibration stops and is on. When tuning fork covered by testing medium,
relay becomes NO status. Red LED indication is on. vibration will stop and output transistor becomes
NO status. Red LED indication is off.
Min. Mode Max.Mode Min. Mode Max.Mode
Level Level
Contactless PNP/
electronic NPN
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
switch Output
Switch open Switch closed Switch closed Switch open Switch open Switch closed Switch closed Switch open
Red Red
LED LED
15
DESCRIPTION OF FEATURES (SC35)
PANEL INTRODUCTION
Option
Abbreviation Function Remarks
Description
Test button Reverse the It is for the test after the installation
2 Test
signal output is completed.
3 MAX: High It is for the high and low Fail-Safe
1 F.S. D.T. S.G. S.D. S.S. S.I.
F.S. Fail-Safe
MAX S H OFF
MIN L L ON
OFF F.S.
ON O.S.
MIN: Low mode.
Test
4
Covered by material: 0.5s
Not covered by material:
S: General setting 150BC:1.5s
AC/DC D.T. Delay Time L: Delay for 230/280BC:2s
19~253V PWR ALM 5
SIG 5 seconds Switch to L to set it at 5 seconds
L N GND
for either covered or not covered
by material.
Specific H: 0.05 g/cm3 The switch to set the material
S.G. Gravity density.
L: 0.01 g/cm3
Detect the wear of the tuning fork
Self OFF: Disabled
1 :Test button S.D.
Diagnosis ON: Enabled
or the viscous material and control
the ON/OFF of the alarm indicator
2 :Function adjustment button
Switch the second set of output
3 :Power indicator
Super OFF: Disabled switch to the alarm indicator of the
4 :Status indicator S.S.
Switch ON: Enabled wear of the tuning fork or the
5 :Alarm indicator viscous material for output
SEDIMENT DETECTION
1. It is only used to detect the sediment under the water, but cant be
used for the level detection of the liquid or the doped liquid. F.S. D.T. S.G. S.D. S.S. S.I.
MAX S H OFF OFF F.S.
MIN L L ON ON O.S.
2. S.G. (Specific Gravity) shall be adjusted to H position. H 2O
3. S.D. (Self Diagnosis) shall be switched to OFF position.
4. SC352 cable type is inapplicable to this working environment
120 B F
(50 B C)
Ta cooling pipe
A
Ta 185 B F
T a
Tp
(85 B C) -40 B F 32 B F 374 B F 446 B F
(-40 B C) (0 B C) (190 B C) (230 B C)
120 B F
(50 B C)
-40 B F
T p B (-40 B C)
Tp 120 B F
(50 B C)
-40 B F insulating layer
(-40 B C)
Tp
-40 B F 32 B F 446 B F 536 B F
(-40 B C) (0 B C) (230 B C) (280 B C)
-40 B F
: Standard/Extension (-40 B C)
: Cable wire B:The cooling pipe in insulating layer
: With cooling pipe A:The cooling pipe out of insulating layer
PANEL INTRODUCTION
4
Option
Abbreviation Function Remarks
1
F.S. D.T. S.G. S. I. Description
MAX S H F .S. 5
Test MIN L L O.S.
Test button Reverse the It is for the test after the installation
Test
signal output is completed.
2
SC38 Fail-Safe
MAX: High It is for the high and low Fail-Safe
F.S.
MIN: Low mode.
PWR SIG
Covered by material:
Approx. 0.5s
S: General setting Not covered by material:
D.T. Delay Time L: Delay for Approx. 1s
5 seconds Switch to L to set it at 5 seconds
for either covered or not covered
by material.
1 :Test button
Specific H: 0.7 g/cm3 The switch to set the material
2 :Operation point calibration button S.G. Gravity L: 0.5 g/cm3 density.
3 :Function adjustment button
Turn ON/OFF the yellow indicator
4 :Power indicator Signal F.S.: Fail-Safe mode
S.I. based on the output status or the
Indication O.S.: Output mode
5 :Status indicator fail-safe status.
Settings
1.Keep pressing Calibration Button for 3 seconds. When the red and green LED indicators flash in turn
every 0.5 second, it enters the calibration mode. Press the calibration button again to enter the Empty Bin
Calibration mode.
[Empty Bin Calibration]
2.Calibration status: The red LED indicator flashes every 0.5 second, and the output current switches to
operate every 0.5 second (8<->16mA).
3.This mode is to calibrate the vibration frequency of the tuning fork in the air. Thus, it shall press Calibration
Button when the tuning fork doesnt sense any material. In this case, it will write the vibration frequency in
the air, and enter the operation point calibration mode.
[Operation Point Calibration]
1. Calibration status: The red LED indicator flashes every 0.25 second, and the output current switches to
operate every 0.25 second (8<->16mA).
2. Cover the material to the desired operating point position under this mode, and then press Calibration
Button. It will be adjusted to the corresponding operating point position according to the H/L setting of the
S.G.
17
DESCRIPTION OF FEATURES (SC38)
85LC
Ta
(175LF)
50LC
Tp
-40LC 0LC 90LC 150LC
(-40LF) (32LF) (194LF) (300LF)
Tp
-40LC
( -40 LF)
18
ORDER INFORMATION
Order No.
1400: Tuning Fork Standard Type
1410: Tuning Fork Ultra Extension Type
1420: Tuning Fork Extension Type
1540: Tuning Fork Corrosion Proof Type
1600: Tuning Fork Sanitary Type
1740: Explosion Proof Tuning Fork Standard Type
1741: Explosion Proof Tuning Fork Ultra Extension Type
19
ORDER INFORMATION
SC
Order No.
24: 100mm 28: 40mm
20
ORDER INFORMATION (SC35)
SC35 0
Probe type
0: Standard 1: Extended 2: Cable
280(High-temp type) 5 6
10: 501~1000 mm
Extension Type: Max length is 4m
...
A9: 18001~19000 mm
95: 9001~9500 mm B0: 19001~20000 mm Cable Type: Max length is 20m
21
ORDER INFORMATION (SC38)
SC38 0
Probe type
0: Standard 1: Extended 2: Ultra Extended
15: 1001~1500 mm
20: 1501~2000mm SS: Length for special specifications
Extension Type: Max length is 3m
(For other lengths, please consult the sales representative of the company)
22
OVERVIEW OF THE TX10 ISOLATED SAFETY BARRIER
WORKING PRINCIPLE
The barrier is provided to isolate the power supply of the transmitter in the hazardous area, which also
isolates and transmits the current signal generated by the transmitter to the safe side. The maximum input is
0~20mA, and the conversion is the analogue output such as 0~20mA/4~20mA/0~5V/0~10V.
FEATURES
1 set of current input can be connected to the current conduction or current output product, and can be
applied in the hazardous area.
The 3 output sets are Relay output, current output and RS485. Simple user interface allows the user to
judge the current device status through the LED indicators.
Different functions can be selected with the DIP switch.
The settings can be made upon shipment/delivery according to the customers requirements.
The self-diagnosis function can detect whether the system works normally any time.
Set Relay output as Alarm mode, provide the customer with the external alarming device.
RS485 interface is provided to set the device parameters and read the current power value.
The new product design conforms to the ex-proof standards.
The 2 sets of dual-color LED indicators are described as below
PWR LED: Green LED indicates system works normally, while red LED indicates system fault.
OUT/CHK LED: Yellow LED indicates Relay is in operation, while red flashing LED indicates input
current error.
WIRING
S 10
+
8
Output
- 7
11
D+
+ 6
9 RS-485
10 9 5
10 D-
+
11 4
Power
3 -
2
Relay
1
23
STANDARD SPECIFICATIONS
1 2 3 4
1 2 3 4 13 14 15 16
Dimensions
5 6 7 8
5 6 7 8
Output: 5 0~20mA 5 4~20mA
Input: 5 0~20mA 5 4~20mA
11
10
10
9
9
Hazardous
Hazardous
Areas
Areas
(Unit:mm)
OUT
5 0~5V
5 0~5V
PWR /CHK
PWR
99 99
5 20~250Vac/Vdc
5 20~250Vac/Vdc
Non-hazardous
Non-hazardous
5 0~10V
5 0~10V
Areas
Areas
SW1
5
6
5
2
7
8
6
2
7
8
1
1
5 Disable
5 Enable
5 Disable
5 Enable
5 Disable
5 Enable
5 Disable
5 Enable
SW2
D+
D+
RS-485
RS-485
D-
D-
Power
Output
Power
Output
Relay
Relay
+ +
-
-
SW3
SW4
9 10 11 12
9 10 11 12
Distribution
> 15 Vdc (Load 20 mA)
voltage
Safe Area
Current: 0~20/4~20 mA Load impedance: <550 ohm
Output or
Voltage: 0~5/0~10 V Load impedance: <20k ohm
Reaction time 5 ms (Reach 90% of the final value)
Transmission 0.1 % F.S. (20BC)
precision
Temp. coefficient < 100 ppm/BC
2500 VacLeakage current <1 mA1min
Insulation
1. Intrinsically safe end and non-intrinsically safe end
strength
2. Non-intrinsically safe power supply end and output end
Operating temp.
-20~60 BC
in ambient air
Application
Area 0 , Area 1, Area 2, IIAIIBIIC T4~T6
environment
Field equipment 1. Two-wire sensor 2. Three-wire sensor 3. Current output sensor
24
ORDER INFORMATION
TX10
Input type
2: 4~20mA
3: 0~20mA
Output type
CR - 0: Current output 0~20mA
CR - 1: Current output 4~20mA
CV - 0: Voltage output 0~5V
CV - 1: Voltage output 0~10V
CRG0: Current output 0~20mA+ Relay
CRG1: Current output 4~20mA+ Relay
CVG0: Voltage output 0~5V+ Relay
CVG1: Voltage output 0~10V+ Relay
Digital output
0: None
3: RS-485
Explosion certification
EX1:NEPSI
25
Global Network
Germany
China
U.S.
Taiwan U.S.
Singapore
China
FINE AUTOMATION CO., LTD. - Shanghai Factory
No.451 DuHui Rd, MinHang District, Shanghai,
China 201109
TEL: 86-21-6490-7260
FAX: 86-21-6490-7276
EMAIL: info.sh@fine-tek.com Distributor:
Singapore
FINETEK PTE LTD. - Singapore Office
No. 60 Kaki Bukit Place, #07-06 Eunos
Techpark 2 Lobby B, Singapore 415979
TEL: 65-6452-6340
FAX: 65-6734-1878
EMAIL: info.sg@fine-tek.com
08-SC02-B3-EP, 09/01/2015