Sie sind auf Seite 1von 14

SECTION 2.

0 INSTALLATION

2.1 General

The following instructions explain how to install an Electric Remote BOP


Control System manufactured by AXON Pressure Products. These
guidelines have been developed to ensure that drilling operations begin
safely and all equipment is fully operational.

The drawings and bills of materials necessary to properly install this


equipment can be found in the Equipment Section (Section 3.0) of this
manual.

While reviewing these instructions please pay particular attention to the


notes and cautions which have been included to ensure the safety of all
personnel using this equipment.

Please note the following:

There are two (2) major steps, which must be performed during all phases
of equipment use:

1. STOP PUMPS

a. CLOSE the air supply valve(s) on the air pump(s).


b. Turn the triplex pump motor starter to the OFF position.

2. START PUMPS

a. OPEN the air supply valve(s) on the air pump(s).


b. Turn the triplex pump motor starter to the AUTO position.

2.2 Accumulator Unit Module (Typical Unit)

2.2.1 Set-Up Location

The distance recommended to provide maximum protection for the


accumulator unit module during a blowout or other emergency, is
approximately 100 to 150 feet from the well bore.

AXON Pressure Products

1
SECTION 2.0 INSTALLATION

When locating the accumulator unit module you should also


consider:

Accessibility for maintenance and service


Lighting
Ventilation

The accumulator unit module should not be placed near oxygen


storage or in an environment where there would be high heating
effects from the surrounding rig equipment. Also, the user should
be aware that dust filled environments will shorten component life.

2.2.2 Reservoir - Inspection

OPEN the 4 inspection / fill ports on the fluid reservoir and ensure
that the tank is free of any debris that could contaminate the
system.

Inspect the reservoir vent(s) to ensure that it is clear.

Make sure that all reservoir connections are tight and breathers
are installed on top side of reservoir.

2.2.3 Fill Reservoir

The reservoir should be filled to within eight (8) inches of the top
with high quality SAE 10wt. hydraulic oil. AXON Pressure Products
recommends high quality hydraulic oil such as ISO 22, AXON
Pressure Products part number 7200-0150. Water based fluid
(AXON Pressure Products part number 7201-0100) may be used,
but care must be taken to ensure that adequate glycol (AXON
Pressure Products part number 7201-0180) is added to prevent
freezing in cold weather.

2.2.4 Check Accumulator Pre-Charge

1. OPEN the accumulator manifold bleeder valves.

2. OPEN the accumulator manifold isolation valves.

AXON Pressure Products

2
SECTION 2.0 INSTALLATION

3. REMOVE the guard from the valve stem on the accumulator


and attach a charging and gauging assembly.

Bottom Loading 1000-9400-EU

4. ATTACH the gauge and tighten down the air chuck T handle.

5. CHECK the gauge pressure reading. The pressure reading


should be 1,000-PSI +/- 100, or as indicated on the hydraulic
schematic found in the Equipment Section (Section 3.0).

Note: If the gauge indicates a LOW PRE-CHARGE:

6. ATTACH the pre-charge line from the nitrogen bottle to the


charging and gauging assembly.

CAUTION: DO NOT USE OXYGEN!

7. OPEN the nitrogen bottle valve until the pre-charge pressure


reaches 1,000-PSI.

8. CLOSE the nitrogen bottle valve and verify that the gauge
continues to read 1,000-PSI.

Note: If the gauge indicates a HIGH PRE-CHARGE:

9. OPEN the charging and gauging assembly bleeder valve until


the pre-charge drops to1,000-PSI.

10. CLOSE the bleeder valve and verify that the gauge reading is
still 1,000-PSI.

Note: A charging and gauging assembly should always be


accessible to the accumulator unit module.

2.2.5 Check Hydraulic Filter

1. Verify no pressure exist in system.

2. Remove filter bowl.

3. Ensure a clean element is installed in filter bowl.

AXON Pressure Products

3
SECTION 2.0 INSTALLATION
4. Install filter bowl.

2.2.6 Setup Air Pump(s)

1. The air lubricator should be full of SAE 10wt. lubricating oil.

2. CLOSE the air supply valve(s).

3. CONNECT an airline to the air supply connection on the


accumulator unit module.

2.2.7 Check Electric Pump

1. Turn OFF the electrical power at the motor control center.

2. Ensure that the accumulator unit skid is properly GROUNDED.


Use a minimum of #6 AWG Copper Wire.

3. Turn the triplex pump / motor starter switch to the OFF position.

4. CHECK the resistance, voltage, and current of the power lines


to be connected.

5. CONNECT the electrical power lines to the three-phase terminal


connections in the triplex pump motor starter. Similar metal
conductors should be used (i.e., copper). Check ground.

6. The triplex pump crankcase should be full of oil. The weight


varies with the ambient temperature and pump model. See
Section 5 for specific information.

7. Turn ON the electrical power at the motor control center.

8. CHECK the rotation of the motor by turning the triplex pump /


motor starter switch to AUTO and then to OFF. If the rotation is
backwards from the arrow indication on the belt guard or pump
crankcase, swap any two-phase terminal connections to reverse
the motor rotation.

AXON Pressure Products

4
SECTION 2.0 INSTALLATION

Note: Rotation should be towards the pump fluid end when


standing behind the pump.

9. If using conduit, seal conduit using a compound with a melting


point of at least 2000F and pour the electrical conduit seal. The
seal should be at least 5/8 thick.

2.2.8 Interconnect Piping

1. INSTALL the interconnect piping from the swivel joints to the


connections on the Blowout Preventer Stack.

2. CONNECT the swivel-joints to the function outlets on the back


of the accumulator unit module if equipped.

CAUTION: DO NOT CONNECT SWIVEL JOINTS TO THE


BOP STACK!

3. Use piping and fittings rated for at least 3000-PSI working


pressure.

2.2.9 Interconnect Cabling

1. The marine armored shipboard electric cable should comply


with API RP14F standards and terminate properly in the BICC
glands that have been provided.

2.2.10 Check All Valve Positions

1. The four-way control valves on the hydraulic control manifold


should be in the CENTER position.

2. The control manifold regulator bypass / should be in the LOW


position.

3. The manifold bleeder valve should be.OPEN.

4. The suction valves on all the pumps should be..OPEN.

5. All accumulator isolation valves should be..OPEN.

6. The accumulator manifold bleeder valves should beCLOSED.

AXON Pressure Products

5
SECTION 2.0 INSTALLATION

2.2.11 Verify Gauges

1. All gauges on the hydraulic control manifold should read zero


(0) PSI.

2. The air supply gauge should read the RIG AIR PRESSURE.

2.2.12 Start Pump(s)

1. With the manifold bleeder valve in the OPEN position,


alternately OPEN the air supply valve(s) to each air pump to
ensure that each pump operates smoothly and does not leak.

2. CLOSE the air supply valve(s) to all air pump(s).

3. With the motor control center power ON, place the triplex pump
/ motor starter switch in the AUTO position. The pump should
run smoothly and without leaks.

4. CLOSE the control manifold bleeder valve.

5. OPEN all the air supply valve(s).

6. SET the air pump lubricator to six (6) drops per minute.

7. The pumps should continue running until the accumulator


pressure reaches 3,000-PSI.

2.2.13 Check Pressure Switch (3,000-PSI)

1. When the system pressure is at 3,000-PSI and the pumps have


stopped, OPEN the bleeder valve.

2. The air pump(s) should automatically start at 2,600-PSI and


stop at 2,900-PSI. Adjust as necessary. See Section 5

3. The electric pump should automatically start when the


accumulator pressure falls to 2,700-PSI. If the start point is
lower, the pressure switch will need adjustment. See Section 5

AXON Pressure Products

6
SECTION 2.0 INSTALLATION

2.2.14 Check Gauge Readings

1. The accumulator pressure gauge should read .3,000-PSI

2. The manifold pressure gauge should read.1,500-PSI

3. The pilot pressure gauge should read.1,000-PSI

Alternately decrease and increase the setting of the manifold


regulator and verify the correct response on the manifold
pressure gauge. Tighten the lock handle on the regulator after
adjusting.

Move the manifold regulator bypass into the high-pressure


(handle right) position and verify that the manifold pressure
gauge increases to 3,000-PSI.

4. The annular pressure gauge should indicate the pressure


setting recommended by the annular preventer manufacturer.

Alternately decrease and increase the setting of the annular


regulator and verify the correct response on the annular
pressure gauge.

2.2.15 Connecting the BOP Stack

1. Move the manifold regulator bypass into the low-pressure


(handle left) position.

2. STOP PUMPS.

3. OPEN the control manifold bleeder valve and relieve the system
pressure.

4. Make sure that the swivel-joints or hammer union connections


on the function outlets are TIGHT AND SECURE.

5. START PUMPS.

6. OPEN each four-way control valve to flush the OPEN function


line.

AXON Pressure Products

7
SECTION 2.0 INSTALLATION
CAUTION: DO NOT FLUSH WITH HIGH-PRESSURE. COLLECT
ANY HYDRAULIC FLUID THAT IS NOT
ENVIROMENTALLY SAFE.

7. CLOSE each four-way control valve to flush the CLOSE function


line.

8. STOP PUMPS.

9. Return the control valves to the CENTER position.

10. OPEN the 4 inspection / fill ports and check control valves for
leaks. Add fluid to the reservoir as necessary.

11. CONNECT AND SECURELY TIGHTEN the connections at the


BOP Stack.

12. Close the control manifold bleeder valve, start pumps and bring
system to normal operating pressure.

13. OPERATE each function to ensure correct function operation.

CAUTION: A JOINT OF DRILL PIPE SHOULD BE IN THE HOLE


TO PREVENT ANY DAMAGE TO THE RUBBER
ELEMENT WHEN FUNCTION TESTING THE
ANNULAR PREVENTER.

14. STOP PUMPS.

15. OPEN the control manifold bleeder valve and relieve all system
pressure.

2.2.16 Refill Reservoir

1. Check the fluid level of the reservoir after line flushing.

2. Refill the reservoir to 8 from the top.

2.3 Electric Remote Control Panel(s)

2.3.1 Set-Up Location

1. Install the electric remote control panel(s) securely on


permanent structures.

AXON Pressure Products

8
SECTION 2.0 INSTALLATION
When locating the remote control panel(s) it is important that
you consider:

Accessibility for operation, maintenance, and service


Lighting
Ventilation
Heat effects from the surrounding equipment

2. The Drillers Panel should be installed on the drill floor at, or


near the Drillers position.

3. The Auxiliary Panel should be installed approximately 100 to


150 feet from the well bore. (If equipped)

2.3.2 Connect Interface Junction Box

CAUTION:

NEVER OPEN AN ELECTRICAL ENCLOSURE WHEN IT


CONTAINS LIVE POWER!

The electrical interconnect cable(s) should be installed, run, and


supported in a manner to:

Avoid damage and stress at the termination fittings.


Stay out of traffic flow.
Stay away from mechanical equipment.

DO NOT HANG OVER SHARP EDGES OR BEND AROUND


SHARP CORNERS.

Adhere to the recommended cable bend radii to prevent tearing


insulation and subsequent short circuiting of the conductors.
Electrical equipment is sensitive and should be handled carefully.

DO NOT DISCONNECT WHILE ENERGIZED!

The electrical connection of the electric remote control panels to the


interface junction box supplies the power to the electric remote
control panels and should not be unplugged while energized.

2.3.3 Electric Remote Control Panels Installation Procedures

AXON Pressure Products

9
SECTION 2.0 INSTALLATION
1. Ensure that the interface junction box circuit breaker is in the
OFF position.

2. Ensure that the interior of the electric remote control panels


enclosure is dry.

3. Turn off the power supply at the motor control center.

4. Connect the incoming power (copper wire connections) to the


two (2) circuit breaker terminals in the circuit breaker enclosure.
Ensure that a good ground connection has been established.

DO NOT TURN ON POWER AT THIS TIME!

5. If the interconnect cables have the multi-conductor connectors,


carefully align the connector and rotate until the guide key slots
are aligned.

CAUTION: NEVER FORCE CONNECTIONS!

6. Plug into the interface junction box receptacle connector.

7. Plug into the electric remote control panels connector receptacle.

8. If the interconnect cables are to be hardwired to the panels,


measure the length of internal cable required to go from the
enclosure cable gland to the terminal boards where the cables will
terminate. Allow ample length for the terminal and door service
loops.

9. Strip the outer sheath, armor and internal sheath to the desired
length of cable measured above.

10. Terminate the individual conductors to the appropriate terminals


per unit schematics.

11. Check the continuity of the cable lines with a volt ohmmeter.

12. Switch on the power supply at the motor control center.

13. Turn on circuit breaker at the interface junction box. Observe


for shorts or smoking from inside the interface junction box and
remote panels.

AXON Pressure Products

10
SECTION 2.0 INSTALLATION
2.3.4 Check Meters

1. Ensure the circuit breaker is in the ON position.

2. Observe for smoke or short.

3. Send "0" PSI (no pressure) to the transmitter assemblies.

4. Turn the "Zero Adjust" screw to give a meter reading of "0" PSI.

2.3.5 Panel Check Out

1. Ensure that the panel function indication lights are not


illuminated as control valves are in CENTER position.

2. Operate the lamp test.

3. Ensure that the lock handle on the annular regulator is locked


so that the adjustment handle does not rotate freely.

4. Close the bleeder valve on the unit.

5. Turn the motor starter to the AUTO position to start up the


electric pump module.

6. Check for the pump running indication light on the Driller's


Panel.

7. Observe that the BYPASS indication light shows low-pressure


position as the system builds up pressure.

8. Calibrate the electric remote control panel meters to read the


same as the unit gauges.

8.1 The given amount of pressure "X" PSI reading should be


transmitted to each corresponding meter.

8.2 Turn the "Span Adjust" screw on the meter calibration


board for each meter until they match the gauge readings
on the unit.

9. Press the PUSH AND HOLD TO OPERATE control push button


to:

9.1 Operate each function.


AXON Pressure Products

11
SECTION 2.0 INSTALLATION

CAUTION: MAKE SURE THAT THE DRILL PIPE IS IN THE


HOLE WHEN OPERATING THE ANNULAR
PREVENTER TO AVOID DAMAGING THE
RUBBER ELEMENT!

9.2 Ensure that the corresponding 4-way control valve on the


hydraulic control manifold is changing to the correct
position.

9.3 Check that the correct lamp is illuminated on the electric


remote control panels.

9.4 Operate the annular INCREASE / DECREASE button on


the electric remote control panels.

9.5 Observe for coordinating pressures on the annular meter


with the unit gauge.

9.6 Move the manifold regulator bypass to the high-pressure


position.

9.7 Ensure that the correct indicators are illuminated on the


electric remote control panels.

10. Close and tighten all cover bolts of the electric remote control
panel enclosures.

11. Seal all open conduit connections with an acceptable sealing


compound. Seal at least 5/8" (16mm) thick with a melting point
of at least 200F.

12. See Drill Ahead Status Positions.

2.4 Drill Ahead Status Positions

The following list identifies the normal operating position of the shutoff
valves and control valves on the BOP Control System:

SHUTOFF VALVES

Air pump supply valvesOPEN

Air and electric pump suction valvesOPEN

Accumulator manifold isolation valves.OPEN


AXON Pressure Products

12
SECTION 2.0 INSTALLATION

Accumulator bleeder valves..CLOSED

Control Manifold bleeder valveCLOSED

CONTROL VALVES

Annular..OPEN

Pipe and Blind Rams..OPEN

Choke and Kill Valves.CLOSED

Control Manifold Regulator..LOW PRESSURE

Annular Regulator Lock HandleTIGHTEN (for remote operation)

2.5 Pump Installation Data

2.5.1 Electric Pump Module

Each electric pump module includes an electric motor starter. The


customer must provide the power to the starter as indicated by the
MOTOR DATA TAG on the motor. Also please note the following:

1. The customer furnished wiring must meet applicable codes and


standards for installation.

2. The maximum allowable voltage variation is.+/- 10%.

3. The maximum allowable frequency variation is+/- 5%.

4. Similar metal conductors should be usedi.e., Copper.

Model # HP Volts * Approximate Full Load Ph HZ


Current (Amps)
UET10HT460 10 460 13 3 60
UET15HT460 15 460 20 3 60
UET20HT380 20 380 27 3 50
UET20HT460 20 460 22 3 60
UET25HT460 25 460 31 3 60
UET30HT380 30 380 42 3 50
UET30HT460 30 460 36 3 60
UET40HT460 40 460 47 3 60
UET50HT460 50 460 61 3 60
UET60HT460 60 460 74 3 60
AXON Pressure Products

13
SECTION 2.0 INSTALLATION

* See motor nameplate for actual full load current.

2.5.2 Air Pump Module

1. Flow capacities approximate based upon minimum air supply


pressure of 90-PSI.

2. Customer should ensure that the air supply is clean and dry.
Excessive moisture and other contaminants can cause
operational problems.

Model # Air Motor Diam. # of Pumps CFM GPM @ 3,000-PSI

UA6316 6 3/8" 1 150 3


UA6326 6 3/8" 2 300 6
UA6336 6 3/8" 3 450 9
UA6346 6 3/8" 4 600 12
UA7316 7 3/8" 1 76 1.98
UA7326 7 3/8" 2 160 3.96
UA7336 7 3/8" 3 236 5.94
UA8516 8 1/2" 1 112 3.20
UA8526 8 1/2" 2 235 6.40
UA8536 8 1/2" 3 347 9.60
UA8546 8 1/2" 4 448 12.80
UA7034 11 3 540 24.00

AXON Pressure Products

14

Das könnte Ihnen auch gefallen