NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E 2007
To E 2069
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 7 6
wt. of Core Cutter ( W1) 960 948
wt. of Core Cutter + Wet Soil (W2) 3130 3170
wt. of Wet material (Ww=W2-W1) (g) 2170 2222
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.172 2.224
MOISTURE CONTENT
Container No. 113 204
Weight of empty container, gm (W1) 53.32 38.35
Weight of wet soil + container, gm (W2) 167.66 129.03
Weight of dry soil + container, gm (W3) 156.4 119.4
Weight of water, gm (W4 = W2 - W3) 11.26 9.63
Weight of dry soil, gm W5 = W3 - W1) 103.08 81.05
Moisture content, % (MC = W4/W5x100) 10.92 11.88
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.96 1.99
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 111.87 113.57
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL

For KJIP FOR NTPC (CCD)


NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER P


N FIELD QUALITY ASSURANCE DEPAR
FIELD DENSITY TEST (SAND REPLACEMENT
As per IS 2720 (Part 28)
Dt.22/09/2011 Tray No
N-580 wt. of empty Tray
N -593 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
8 wt. of empty Container gm
960 wt. of wet Soil + Container gm
3010
2050
999.3
2.051

203
40.05
101.82
95.16
6.66
55.11
12.08

1.83
1.75
13.23
104.59
95%
PASS / FAIL

For KJIP

For NTPC (FQA)


NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From
To
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 8 7
wt. of Core Cutter ( W1) 960 960
wt. of Core Cutter + Wet Soil (W2) 3090 3100
wt. of Wet material (Ww=W2-W1) (g) 2130 2140
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.131 2.141
MOISTURE CONTENT
Container No. 70 126
Weight of empty container, gm (W1) 37.78 44.96
Weight of wet soil + container, gm (W2) 158.74 150
Weight of dry soil + container, gm (W3) 146.51 139.82
Weight of water, gm (W4 = W2 - W3) 12.23 10.18
Weight of dry soil, gm W5 = W3 - W1) 108.73 94.86
Moisture content, % (MC = W4/W5x100) 11.25 10.73
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.92 1.93
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 109.48 110.51
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
wt. of empty Tray
wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
6 wt. of empty Container gm
948 wt. of wet Soil + Container gm
3200
2252
999.3
2.254

71
46.27
161.15
148.67
12.48
102.4
12.19

2.01
1.75
13.23
114.79
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From RESERVOIR
To
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 6 1
wt. of Core Cutter ( W1) 948 901
wt. of Core Cutter + Wet Soil (W2) 3016 2968
wt. of Wet material (Ww=W2-W1) (g) 2068 2067
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.069 2.068
MOISTURE CONTENT
Container No. 208 203
Weight of empty container, gm (W1) 38.48 40.05
Weight of wet soil + container, gm (W2) 124 138
Weight of dry soil + container, gm (W3) 112 125
Weight of water, gm (W4 = W2 - W3) 12 13
Weight of dry soil, gm W5 = W3 - W1) 73.52 84.95
Moisture content, % (MC = W4/W5x100) 16.32 15.30
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.78 1.79
Lab. Max dry density (Ymdd ) (g/cc) 1.77 1.77
Optimum mositure content (%) 15.86 15.86
Compaction obtainted (100xYd/Ymdd) (%) 100.51 101.35
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-16/09/2011 Tray No
TRIAL wt. of empty Tray
wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
8 wt. of empty Container gm
960 wt. of wet Soil + Container gm
3222
2262
999.3
2.264

126
44.96
186
171
15
126.04
11.90

2.02
1.77
15.86
114.29
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E1800
To E1814
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 8 7
wt. of Core Cutter ( W1) 960 960
wt. of Core Cutter + Wet Soil (W2) 3150 3120
wt. of Wet material (Ww=W2-W1) (g) 2190 2160
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.192 2.162
MOISTURE CONTENT
Container No. 124 117
Weight of empty container, gm (W1) 46.74 46.26
Weight of wet soil + container, gm (W2) 148.81 129.21
Weight of dry soil + container, gm (W3) 138.9 119.91
Weight of water, gm (W4 = W2 - W3) 9.91 9.3
Weight of dry soil, gm W5 = W3 - W1) 92.16 73.65
Moisture content, % (MC = W4/W5x100) 10.75 12.63
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.98 1.92
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 113.07 109.67
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
N-631 wt. of empty Tray
N-568 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
6 wt. of empty Container gm
948 wt. of wet Soil + Container gm
2980
2032
999.3
2.033

119
50.36
152.02
141.46
10.56
91.1
11.59

1.82
1.75
13.23
104.13
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E1814
To E1818
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 6 8
wt. of Core Cutter ( W1) 948 960
wt. of Core Cutter + Wet Soil (W2) 3130 3100
wt. of Wet material (Ww=W2-W1) (g) 2182 2140
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.184 2.141
MOISTURE CONTENT
Container No. 110 62
Weight of empty container, gm (W1) 48.42 54.28
Weight of wet soil + container, gm (W2) 139.88 153.82
Weight of dry soil + container, gm (W3) 130.3 143.23
Weight of water, gm (W4 = W2 - W3) 9.58 10.59
Weight of dry soil, gm W5 = W3 - W1) 81.88 88.95
Moisture content, % (MC = W4/W5x100) 11.70 11.91
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.95 1.91
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 111.70 109.35
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
N-568 wt. of empty Tray
N-548 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
7 wt. of empty Container gm
960 wt. of wet Soil + Container gm
3150
2190
999.3
2.192

68
36.14
132.36
122.37
9.99
86.23
11.59

1.96
1.75
13.23
112.23
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E1818
To E1881
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 7 6
wt. of Core Cutter ( W1) 960 948
wt. of Core Cutter + Wet Soil (W2) 3210 3090
wt. of Wet material (Ww=W2-W1) (g) 2250 2142
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.252 2.144
MOISTURE CONTENT
Container No. 76 199
Weight of empty container, gm (W1) 33.73 42.8
Weight of wet soil + container, gm (W2) 107.65 131.73
Weight of dry soil + container, gm (W3) 99.52 121.64
Weight of water, gm (W4 = W2 - W3) 8.13 10.09
Weight of dry soil, gm W5 = W3 - W1) 65.79 78.84
Moisture content, % (MC = W4/W5x100) 12.36 12.80
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 2.00 1.90
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 114.51 108.59
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
N-548 wt. of empty Tray
N-558 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
8 wt. of empty Container gm
960 wt. of wet Soil + Container gm
2990
2030
999.3
2.031

120
44.88
165.02
151.4
13.62
106.52
12.79

1.80
1.75
13.23
102.92
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E1881
To E1945
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 8 6
wt. of Core Cutter ( W1) 960 948
wt. of Core Cutter + Wet Soil (W2) 3200 3130
wt. of Wet material (Ww=W2-W1) (g) 2240 2182
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.242 2.184
MOISTURE CONTENT
Container No. 213 74
Weight of empty container, gm (W1) 36.62 48.06
Weight of wet soil + container, gm (W2) 96.28 155.56
Weight of dry soil + container, gm (W3) 90.48 144.17
Weight of water, gm (W4 = W2 - W3) 5.8 11.39
Weight of dry soil, gm W5 = W3 - W1) 53.86 96.11
Moisture content, % (MC = W4/W5x100) 10.77 11.85
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 2.02 1.95
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 115.64 111.55
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
N-558 wt. of empty Tray
N-568 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
7 wt. of empty Container gm
960 wt. of wet Soil + Container gm
3180
2220
999.3
2.222

208
38.48
167.92
153.93
13.99
115.45
12.12

1.98
1.75
13.23
113.23
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E1945
To E2007
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 6 7
wt. of Core Cutter ( W1) 948 960
wt. of Core Cutter + Wet Soil (W2) 3180 3120
wt. of Wet material (Ww=W2-W1) (g) 2232 2160
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.234 2.162
MOISTURE CONTENT
Container No. 215 109
Weight of empty container, gm (W1) 41.24 44.38
Weight of wet soil + container, gm (W2) 122.99 113.16
Weight of dry soil + container, gm (W3) 113.7 106.1
Weight of water, gm (W4 = W2 - W3) 9.29 7.06
Weight of dry soil, gm W5 = W3 - W1) 72.46 61.72
Moisture content, % (MC = W4/W5x100) 12.82 11.44
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.98 1.94
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 113.13 110.84
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
N-568 wt. of empty Tray
N-580 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
8 wt. of empty Container gm
960 wt. of wet Soil + Container gm
3150
2190
999.3
2.192

106
49.42
146.39
135.96
10.43
86.54
12.05

1.96
1.75
13.23
111.76
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From E2069
To E3132
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No. 7 6
wt. of Core Cutter ( W1) 960 948
wt. of Core Cutter + Wet Soil (W2) 2980 3150
wt. of Wet material (Ww=W2-W1) (g) 2020 2202
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.021 2.204
MOISTURE CONTENT
Container No. 200 121
Weight of empty container, gm (W1) 39 47.5
Weight of wet soil + container, gm (W2) 115 147.68
Weight of dry soil + container, gm (W3) 107.07 136.68
Weight of water, gm (W4 = W2 - W3) 7.93 11
Weight of dry soil, gm W5 = W3 - W1) 68.07 89.18
Moisture content, % (MC = W4/W5x100) 11.65 12.33
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.81 1.96
Lab. Max dry density (Ymdd ) (g/cc) 1.75 1.75
Optimum mositure content (%) 13.23 13.23
Compaction obtainted (100xYd/Ymdd) (%) 103.46 112.09
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Dt:-12/09/2011 Tray No
N-593 wt. of empty Tray
N-605 wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
8 wt. of empty Container gm
960 wt. of wet Soil + Container gm
3190
2230
999.3
2.232

122
46.73
145.12
134.12
11
87.39
12.59

1.98
1.75
13.23
113.26
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


NTPC SOLAPUR

SOLAPUR SUPER THERMAL POWER PROJECT


FIELD QUALITY ASSURANCE DEPARTMEN
FIELD DENSITY TEST (CORE CUTTER METHOD)
As per IS 2720 (Part 29)
Location
From
To
RFI No:
Layer No and Thickness 600
Depth of Hole (mm) 250
Source of Material (name & chainage) INSIDE PLANT
FIELD DENSITY TEST
Core Cutter No.
wt. of Core Cutter ( W1)
wt. of Core Cutter + Wet Soil (W2)
wt. of Wet material (Ww=W2-W1) (g) 0 0
Volume of Core Cutter ( V3) (g) 999.3 999.3
Bulk density of material {Yb=(Ww/V3) } (g/cc) 0.000 0.000
MOISTURE CONTENT
Container No.
Weight of empty container, gm (W1)
Weight of wet soil + container, gm (W2)
Weight of dry soil + container, gm (W3)
Weight of water, gm (W4 = W2 - W3) 0 0
Weight of dry soil, gm W5 = W3 - W1) 0 0
Moisture content, % (MC = W4/W5x100) #DIV/0! #DIV/0!
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) #DIV/0! #DIV/0!
Lab. Max dry density (Ymdd ) (g/cc) 1.66 1.66
Optimum mositure content (%) 18.55 18.55
Compaction obtainted (100xYd/Ymdd) (%) #DIV/0! #DIV/0!
% Compaction required (%) 95% 95%
Remarks : PASS / FAIL
For KJIP FOR NTPC (CCD)
NTPC SOLAPUR NTPC SOLAPUR

ECT SOLAPUR SUPER THERMAL POWER PRO


N FIELD QUALITY ASSURANCE DEPARTM
FIELD DENSITY TEST (SAND REPLACEMENT MET
As per IS 2720 (Part 28)
Tray No
wt. of empty Tray
wt. of Soil + Tray
wt. of wet material from Hole
600 Pouring Cylinder No
250 wt. of Sand + Cylinder before Pouring
INSIDE PLANT wt. of Sand + Cylinder after Pouring
Container No.
wt. of empty Container gm
wt. of wet Soil + Container gm

0
999.3
0.000

0
0
#DIV/0!

#DIV/0!
1.66
18.55
#DIV/0!
95%
PASS / FAIL

For KJIP
For NTPC (FQA)
NTPC SOLAPUR

R SUPER THERMAL POWER PROJECT


QUALITY ASSURANCE DEPARTMEN
DENSITY TEST (SAND REPLACEMENT METHOD)
As per IS 2720 (Part 28)

03 Large

FOR NTPC (CCD) For NTPC (FQA)


FIELD Quality plan
ITEM :CIVIL Work Qp No. 1 Sewage Treatment Plants at
Doddabele,Yellamalappachetty
Rev.NO. 0 and Intermediate Sewage pumping Station
KEC WATERLEAU (JV) and Pumping Mains at Sadarmangala

Contract No. S1e

FIELD DENSITY TEST (CORE CUTTER METHOD)


As per IS 2720 (Part 29)

Location :
From :
To : Lab. Max dry density (Ymdd )= 2.04 g/cc Optimum mositure content=12%

Date of testing :
Layer No and Thickness :

Name & Source of Material :

FIELD DENSITY TEST


Sample No. 1 2 3
wt. of Core Cutter ( W1) (g)
wt. of Core Cutter + Wet Material (W2) (g)
wt. of Wet material (Ww=W2-W1) (g)
Volume of Core Cutter ( V3) (/4xd2xh) (cc)
Bulk density of material {Yb=(Ww/V3) } (g/cc)

MOISTURE CONTENT (by Sand Bath method)


Weight of empty container, gm (W1)

Weight of wet material + container, gm (W2)

Weight of dry material + container, gm (W3)

Water Content (Wc) = (W2-W3/W3-W1)*100

RESULTS
Field max.dry density {Yd=100XYb/(100+Mc)} (g/cc)

Compaction obtainted (100xYd/Ymdd) (%)

Average compaction (%)


% Compaction required (%)

Remarks : PASS / FAIL

Note :

KEC-Waterleau SMC NMT BWSSB


FIELD DENSITY TEST
Core Cutter No.

wt. of Core Cutter + Wet Soil (W1) 3135 3114 3128 3130 3122 3116 3128 3133 3109
wt. of Core Cutter ( W2) 974 974 974 970 970 970 970 970 970
wt. of Wet material (Ww=W2-W1) (g) 2161 2140 2154 2160 2152 2146 2158 2163 2139
Volume of Core Cutter ( V3) (g) 1022 1022 1022 1022 1022 1022 1022 1022 1022
Bulk density of material {Yb=(Ww/V3) } (g/cc) 2.114 2.094 2.108 2.114 2.106 2.100 2.112 2.116 2.093
MOISTURE CONTENT (by Rapid Moisture meter method) 10.5 10 10 12 11 11.5 11 12 11
Moisture content, % 11.73 11.11 11.11 13.64 12.36 12.99 12.36 13.64 12.36
RESULTS
Field max.dry density {Yd=100XYb/(100+M)} (g/cc) 1.892 1.885 1.897 1.860 1.874 1.858 1.879 1.862 1.863
Lab. Max dry density (Ymdd ) (g/cc) 1.95 1.95 1.95 1.95 1.95 1.95 1.95 1.95 1.95
Optimum mositure content (%) 12 12 12 12 12 12 12 12 12
Compaction obtainted (100xYd/Ymdd) (%) 97.05 96.64 97.28 95.38 96.11 95.30 96.37 95.51 95.52
% Compaction required (%) 95% 95% 95% 95% 95% 95% 95% 95% 95%

FIELD DENSITY TEST


Core Cutter No.
wt. of Core Cutter + Wet Soil (W1) 3125 3130 3116 3127 3116 3122 3133 3143 3110
wt. of Core Cutter ( W2)
wt. of Wet material (Ww=W2-W1) (g) 970 970 970 970 970 970 970 970 970
Volume of Core Cutter ( V3) (g) 2155 2160 2146 2157 2146 2152 2163 2173 2140
Bulk density of material {Yb=(Ww/V3) } (g/cc) 1022 1022 1022 1022 1022 1022 1022 1022 1022
MOISTURE CONTENT (by Rapid Moisture meter method) 2.109 2.114 2.100 2.111 2.100 2.106 2.116 2.126 2.094
Moisture content, % 12 11 11.5 10.5 11 12 11.5 12 11
RESULTS 13.64 12.36 12.99 11.73 12.36 13.64 12.99 13.64 12.36
Field max.dry density {Yd=100XYb/(100+M)} (g/cc)
Lab. Max dry density (Ymdd ) (g/cc) 1.856 1.881 1.858 1.889 1.869 1.853 1.873 1.871 1.864
Optimum mositure content (%) 1.95 1.95 1.95 1.95 1.95 1.95 1.95 1.95 1.95
Compaction obtainted (100xYd/Ymdd) (%) 12 12 12 12 12 12 12 12 12
% Compaction required (%) 95.16 96.46 95.30 96.87 95.84 95.03 96.05 95.95 95.57
95% 95% 95% 95% 95% 95% 95% 95% 95%
3115
970
2145
1022
2.099
10
11.11

1.889
1.95
12
96.87
95%

3111

970
2141
1022
2.095
10.5
11.73

1.875
1.95
12
96.15
95%
RAPID MOISTURE METER READING TO MOISTURE CONTENT

RMM Moisture RMM Moisture content in


Reading content Reading %
in %
0.5 0.50 30.5 43.88
1 1.01 31 44.93
1.5 1.52 31.5 45.99
2 2.04 32 47.06
2.5 2.56 32.5 48.15
3 3.09 33 49.25
3.5 3.63 33.5 50.38
4 4.17 34 51.52
4.5 4.71 34.5 52.67
5 5.26 35 53.85
5.5 5.82 35.5 55.04
6 6.38 36 56.25
6.5 6.95 36.5 57.48
7 7.53 37 58.73
7.5 8.11 37.5 60.00
8 8.70 38 61.29
8.5 9.29 38.5 62.60
9 9.89 39 63.93
9.5 10.50 39.5 65.29
10 11.11 40 66.67
10.5 11.73 40.5 68.07
11 12.36 41 69.49
11.5 12.99 41.5 70.94
12 13.64 42 72.41
12.5 14.29 42.5 73.91
13 14.94 43 75.44
13.5 15.61 43.5 76.99
14 16.28 44 78.57
14.5 16.96 44.5 80.18
15 17.65 45 81.82
15.5 18.34 45.5 83.49
16 19.05 46 85.19
16.5 19.76 46.5 86.92
17 20.48 47 88.68
17.5 21.21 47.5 90.48
18 21.95 48 92.31
18.5 22.70 48.5 94.17
19 23.46 49 96.08
19.5 24.22 49.5 98.02
20 25.00 50 100.00
20.5 25.79
21 26.58
21.5 27.39
22 28.21
22.5 29.03
23 29.87
23.5 30.72
24 31.58
24.5 32.45
25 33.33
25.5 34.23
26 35.14
26.5 36.05
27 36.99
27.5 37.93
28 38.89
28.5 39.86
29 40.85
29.5 41.84
30 42.86

Das könnte Ihnen auch gefallen