U-Series
Air Circuit Breaker
HYUNDAI ACB meets your demands for high
breaking capacity, full line-up, and optimized
panel size. Various accessories and connection
methods realize user-friendly handling.
U-Series / Air Circuit Breaker
Features
| Full line-up |
U-Series ACB maximize your choice and satisfaction with compact size and dual (UAN/UAS) model.
460mm
766mm
624mm
D frame1)
399mm [150kA]
36
C frame
8m
328mm
m
[100kA] 4,000-6,300A(UAN)
B frame
A frame [100kA] 4,000-5,000A(UAN)
[85kA] 2,000-4,000A(UAN)
2,000-3,200A(UAS)
630-2,000A(UAN)
630-1,600A(UAS)
| Applications |
U-Series ACB offering high breaking capacity and advanced protection trip relay is suitable to cover various applications
including buildings, data centers, industrials and so on. U-Series ACB protects these facilities from harmonic frequency by
100% capacity of N phase.
4
ACB
Approval
ISO 18001, 14001, 9001
KS/KOREA Korea Quality Certificate Standard Association
CE Community European
GOST-R/RUSSIA Government Standard of Russia
CCC/CHINA China Compulsory Certification
KR/KOREA Korean Register of Shipping
GL/GERMANY Germanischer Lloyd
LR/U.K Lloyd's Register of Shipping
ABS/U.S.A American Bureau of Shipping
BV/FRANCE Bureau Veritas
NK/JAPAN Nippon Kaiji Kyokai
CB type test
DEKRA Formerly KEMA Quality Registered
KERI Korea Electrotechnology Research Institute
Features
| Various accessories |
[ Body side ]
6
ACB
[ Cradle side ]
Features
Ordering 50Hz 33 35 36 37
code 60Hz 43 45 46 47
Externals
8
ACB
Standard connection
- Changing connector is available only for UAN/UAS A frame 630-1,600A, UAN/UAS B frame 2,000-3,200A.
- Front connection type is suitable the panel requirement for limited installation space.
- Changing connection above 4,000A needs additional component, please contact us.
Features
| Easy-to-install |
Fixed type
Installed in a switchboard directly.
Draw-out type
Consists of ACB and cradle.
Cradle is fixed to a switchboard.
ACB may be in the position of CONNECTED, TEST, ISOLATED,
and REMOVED.
Switchboard door may be closed in ISOLATED position. [ Draw-in/out guide rail ]
(Connected Position)
- Main and control circuit are all connected. - Main circuit is isolated, control circuit is connected.
- Normal condition of use - Control test is possible when switchboards door is closed.
- Main and control circuit are all isolated. - ACB is totally drawn out from the cradle.
- Switchboard door may be closed in isolated position.
10
ACB
Structure
| Externals |
[ Front ]
[ Cradle ]
[ Inside ] [ Rear ]
Structure
| Internals |
12
ACB
Ratings
W D
W D
| Overview |
PTA: Pre-trip alarm
LTD: Long time delay
STD/INST: Short time or instantaneous tripping
GFT/ELT: Ground fault trip or earth-leakage trip
TAL: Temperature alarm
Phase indication Iine
Ir: Long time current setting knob
Tr: Long time tripping delay setting knob
Isd: Short time current setting knob
Tsd: Short time tripping delay setting knob
Ii: Instantaneous current setting knob
GFT/STD, MCR setting knob
Ip: Pre-trip alarm current setting knob
Tp: Pre-trip alarm delay setting knob
Ig: Ground fault current setting knob
Tg: Ground fault tripping delay setting knob
Rated current setting knob
Test jack
Earth leakage pick-up and
tripping delay setting knob
14
ACB
Externals
Control power - -
Power supply
Self power
Long time delay (LTD)
Short time delay (STD)
Instantaneous trip (INST)
Protection Pre trip alarm - -
Ground fault trip - -
Field test - -
Failsafe
True RMS detection
Fault indication LED - -
Indication
Overload indication LED - -
Display window - -
Integrated instantaneous - - PTA: 1a -
contact (1a)
L/S/I/G: 2a
Output contact
Individual continuous LTD: 1a
- PTA: 1a -
contact (4a) S/I: 1a
L/S/I/G: 2a PTA:1a
MCR
Temperature detection - - - -
Optional
Event/Fault recording - -
function
Earth leakage trip (ELT) - - - - -
Communication - - - - -
: Standard : Option
O
rdering codes
| UPR-1L-GL |
Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional
Self power
1a DO (Digital output)
Characteristic
I2t off Ii
I2t off
Protection
16
ACB
| UPR-2L-GS, UPR-2L-GM |
Characteristic
Protection
| UPR-1D-GT |
Characteristic
Protection
18
ACB
| UPR-1S-AL |
Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional (for STD)
Self power
1a DO (Digital output)
Characteristic
I2t on
Isd
tsd
I2t off Ii
Protection
| UPR-2S-AS |
Characteristic
I2t off Ii
Protection
20
ACB
| Operation characteristics |
I2t off I n
Isd Tp(S type)
Tsd
Ip
Instantaneous trip (INST)
Standard current setting T
t Ii I - The scale is markedt as magnification of [In]. I
Tp
I - Setting range: (Non, 2, 3, 4, 6, 8, 10, 12, 15)In (9I modes)
- No protection in case of non setting of [Ii].
Ii
Tp
I I
Tp(S type)
Ip
Ii
Tp
I I
| Operation characteristics |
Ig2t off
Ig
t
Tg
I
Ig2t on
tt Ig Ig2t off
t I n
t
T
I
I n Tp(S type)
Ip
T Standard current setting
tPre-trip alarm (PTA)
Tp I L type
I - The scale is marked as magnification of [In] with definite time operation.
- Setting range: (Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0)In (10 modes)
S type
Tp(S type) - The scale is marked as magnification of [In] with inverse time operation.
t Ip - Setting range: (Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1.1)In (10 modes)
22
ACB
| Circuit diagrams |
UPR-1L-GL
NCT
k
R S T 21 29 30
R S T N L/S
I/G
NCT NCT
1 2
UPR-1L-GL
Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22
UPR-2L-GS
AC,DC100-250V S0 - S2
Source
NCT + -
k
R S T 21 23 29 30 19
R S T N L PT NCT NCT S2
1 2
UPR-2L-GS
ZO ZO
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2 1 2
A C TN TP S 0
CT3
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22 24 26 31 32 33 34 20
+ - + -
In Out
ZSI
| Circuit diagrams |
UPR-1D-GT
AC,DC100-250V S0 - S2
Source
ZCT NCT + -
k k
R S T 21 23 27 28 29 30 19
UPR-1D-GT
1a for
MCR
Rn Sn Tn 22 24 26 31 32 33 34 35 36 20
+ - + - + -
In Out Communication
ZSI
UPR-2L-GM
AC,DC100-250V S0 - S2
Source
NCT + -
k
R S T 21 23 29 30 19
UPR-2L-GM
1a for MCR
Rn Sn Tn 22 24 26 31 32 33 34 20
+ - + -
In Out
ZSI
24
ACB
UPR-1S-AL
R S T 21
R S T L/
N SI
UPR-1S-AL
Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22
UPR-2S-AS
AC,DC100-250V S 0 - S2
Source
+ -
R S T 21 23 19
R S T N L PT S2
UPR-2S-AS
Rn Sn Tn Nn Ac S/I ZI ZI ZO ZO A C TN TP S 0
CT3 1 2 1 2
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22 24 31 32 33 34 20
+ - + -
In Out
ZSI
| Characteristic curves |
General feeder
4
3
Hour
2
1
50
40
30
20
10
8
Minute
6
5
4
3
2
1
50
40
30
Operating time
20
10
8
6
5
4
3
2
1
0.8
0.6
0.5 500ms 500ms
0.4
Second
0.3
0.2
0.1
0.08
0.06 50ms 50ms
0.0
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
1000
1500
2000
2500
3000
100
100
125
150
200
250
300
400
500
600
700
800
900
10
15
20
30
40
50
60
70
80
90
60
70
80
90
7
8
9
Percent for rated primary current of OCR [ICT] Percent for base current of OCR [Io]
Long time delay current setting range Instantaneous tripping current setting range Pre-trip alarm current setting range
Short time delay current setting range Ground fault trip current setting range
26
ACB
Generator
4
3
Hour
1
50
40
30
20
10
8
Minute
6
5
4
3
2
1
50
40
30
Operating time
20
10
8
6
5
4
3
2
1
0.8
0.6
0.5 500ms
0.4
Second
0.3
0.2
0.1
0.08
0.06
0.05
0.0
50ms
0.04
0.03
0.02
0.01
0.008
0.006
0.005
1000
1500
2000
2500
3000
100
125
150
200
250
300
400
500
600
700
800
900
10
15
20
30
40
50
60
70
80
90
7
8
9
Long time delay current setting range Instantaneous tripping current setting range
Short time delay current setting range Pre-trip alarm current setting range
Example
In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site
sends ZSI signal to halt upstream breakers operation.
To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay.
The
upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time delay for
protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously.
For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will
react before upstream ones under overcurrent/short time delay/ground fault situations.
ZSI connecting line needs to be maximum 3m.
ACB 1
Out
Zone 1 In
In In In
ZSI connecting
28
ACB
| System diagram |
R S T N
ACB trip
ACB
Display
(LCD, LED)
MHT
Trip
Rogowski Relay operation
CT Measurement
part selection
PTA contact
MCU
processing
LTD contact
External
contact STD/INST contact
GFT contact
Power
CT Self power COMMON contact
Trip relay
ZSI output +
ZSI output -
ZSI
ZSI input +
ZSI input -
SMPS Test
110V - 220V power terminal
| Communication function |
Modbus-RTU / RS-485
SCADA system
Operation mode: Differential
Distance: Max.1.2km
Modbus/RS-485
Cable: RS-485 shielded twist 2-pair cable
Baud rate: 9,600, 19,200, 38,400 bps
Transmission method: Half-duplex
Termination: 150
Accessories
| Overview |
30
ACB
Accessories
| Overview |
32
ACB
Accessories
| Overview |
34
ACB
Accessories
| Motor |
Manual charging method and geared motor charging
by external power source.
Operating voltage range: 85-110%
R
atings Wire ratings C
onnection diagram
O
rdering code
Ordering code 2 16
Application
Item Complete parts Specification Mounting position
2 Spare
16 part UAN UAS
of ACB/Cradle
M1 UANS M1 AC/DC110V
M2 UANS M2 AC/DC220V
M3 UANS M3 AC380V
Motor M4 UANS M4 AC440V Inside of ACB body
M7 UANS M7 DC24V
M8 UANS M8 DC48V
M9 UANS M9 DC125V
36
ACB
| Closing coil |
A control device which closes a circuit breaker
remotely, when applying 85-110% of rated control
voltage over 150ms to coil terminals (3,4).
O
rdering code
R
atings C
onnection diagram
3
Power supply (Vn) Power consumption (VA) OpeningSource
time
Operating limits Source
DC (V) AC (V) Inrush Steady-state (ms) PB
PB
(Close)
(Close)
24 - 0.85-1.1Vn
3
100-130 100-130 0.85-1.1Vn 300 10 60 3
CC
W
ire ratings
4
4
Accessories
| Trip coil |
A control device which trips a circuit breaker
remotely, when applying 70-110% of rated control
voltage over 150ms to coil terminals (7,8).
O
rdering code
R
atings C
onnection diagram
24 - 0.7-1.1Vn
PB(Open)
7
100-130 100-130 0.7-1.1Vn 300 10 40
7
200-250 200-250 0.7-1.1Vn
Source
W
ire ratings
PB(Open)
8
8
TC
38
8
ACB
O
rdering code
R
atings C
onnection diagram
PB(Open)
24 - 0.7-1.1Vn
100-130 100-130 0.7-1.1Vn
Source Source 300 10 40 7 9
PB(Open)
7 9
W
ire ratings
Source Source
PB(Open)
DC24 ADC110/220 TC TC
7 9
AWG Insulation level (V) AWG Insulation level (V)
20 300 20 300
TC TC
8 10
TC TC
8 10
8 10
U-Series / Air Circuit Breaker
Accessories
O
rdering code
Source
R
atings C
onnection diagram
PB(Open)
24 - 0.7-1.1Vn
PB(Open)
Supervision
100-130 100-130 0.7-1.1Vn 300 10
Supervision 40 7 59
7 59
200-250 200-250 0.7-1.1Vn
W
ire ratings
TC
20 300 20 300
8
8
40
ACB
| UVT coil |
If the voltage of the main or the control power is
under 70% of the standard, UVT breaks the circuit
automatically.
Connect instantaneous type with both terminals
(9,10) and connect with time delay type in order to
present time delay controller.
- The circuit breaker is opened with trip unit power
supply voltages below 70%.
- The circuit breaker is closed with unit power supply
voltage above 85%.
Instantaneous type can not be used with double trip
coil.
O
rdering code
COM
a
U8 UANS U8 DC48V b
U2
Controller
U9 UANS U9 DC125VT2 C1
PB(Open)
UVT
C2
T1
R
atings C
onnection diagram
a COM
U2
b a U2
b
24 -
Controller
C1
Controller
PB(Open)
UVT
T2 C1
PB(Open)
UVT
T2
C2
110 (100-130) 110 (100-130) UVT T1
T1
C2
9
9
220 (200-250) 220 (200-250) Above 0.85Vn Below 0.35Vn 300 10 60
- 380
- 440
10
W
ire ratings
UVT
UVT
Accessories
O
rdering code
COM
a
V1 UANS V1 b
U2
AC/DC110V
V2 UANS V2 C1 AC/DC220V Controller: outside
Controller
T2
UVT
controller V3 UANS V3 T1
C2
AC380V of ACB body &
& V4 UANS V4 AC440V
9
cradle
UVT coil V7 UANS V7 DC24V UVT coil: inside of
(Instantaneous type) V8 UANS V8 DC48V ACB body
V9 UANS V9 DC125V
C
onnection & Operating time C
onnection diagram
UVT
C
onnection diagram
120 U1
Source
COM
102 a U2
b
Controller
C1
V Source
PB(Open)
ACB UVT T2
UVT
V Source 10
ACB UVT U1 C2
Source
CONTROLLER COM T1
CONTROLLER 0
a U2 9
b
0
Controller
128
142
T2
UVT
trip Output-Contact
DELAY Voltage
UVT
Coil 0.5 1.0 1.5 3.0 9
0
CAUTION
UVT
10
42
10
ACB
| Auxiliary switch |
A contact to monitor On/Off position of ACB remotely.
3a3b is provided as standard for UAS type and 5a5b is
standard for UAN type.
Applicable AUX switch is up to 6a6b. Add AA on your order.
When working with monitoring contact for trip coil the
AUX switch will be 3a3b. When working with OCRs MCR
function it will be 4a5b. When both monitoring contact and
MCR function working together it will be 3a4b.
When ordering short badditionally it will be attached to
bcontacts 51, 52 when the product is out. The additional
short b which enclosed in the product is applicable as the
number of the b contact.
5a5b is separate product and available. Add UANS AS on
extra order.
R
atings W
ire ratings C
onnection diagram
O
rdering code
41 43 45 47 49 51 53 55 57 59
| Test jumper |
A connecting device to make the body of auto connection
Used for short b contact (Option)
Used for SHT supervision (Option)
42 44 46 48 50 52 54 56 58 60
Ordering code: UANS AJ (Spare part)
42 44 46 48 50 52 54 56 58 60
Accessories
| Position switch |
This switch is for indicating the position of ACB in the
cradle. It is mounted on the side of cradle.
Indicating position Connected/Test/Isol/Insert.
Only one switch is applicable.
R
atings
Composition
44
ACB
O
rdering code
C
TD operating sequence C
onnection diagram
Source
72 130 1 6
CONDENSER TRIP DEVICE
6 7 U V
WITH RECTIFIER
2- R1
CDT
SA R2 R3 P N
72
22
PB(Open)
SW C1 NL
2 7
80 5
90 3 4
YC
R
atings
Accessories
| Lifting lug |
A device to make an ACB easy to shift.
Hang it to both handles of the arc shield, cradle, and ACB.
When handling products, please be sure to use crane. In
case of products under 3,200A and handling cradle only,
please comply with safety regulation.
Offered 2ea of 1set as a standard in 5,000AF "C" frame.
O
rdering code
| Dummy ACB |
The dummy ACB which is a frame to apply electric current can conduct
ACBs function temporarily when the maintenance work takes long due to
malfunction.
When connecting the dummy ACB please check the primary power is out
since the CB is close.
The early stage of each frame is maximum rated current.
O
rdering code
46
ACB
O
rdering code
Accessories
| Terminal busbar |
Standard connection U-Series ACB have the following front types:
Vertical Horizontal Front Vertical, horizontal, top vertical-bottom
horizontal and top horizontal-bottom vertical
type. There are also P-types which have no
terminal cradle and fixed body type. For these
models (P and fixed body type) separate
terminal is additionally supplied.
Separate terminal is applicable for only
A-frame 630-1,600[A] and B-frame
Mixed connection (Top/Bottom) 2,000- 3,200[A].
Vertical/Horizontal Horizontal/Vertical Vertical/Front
Ordering code
48
ACB
O
rdering code
O
rdering code
Accessories
C
onnection diagram
Item Specifications
K
ey Pad E
xternals
110.60
HIPDS-D
193.40
START STOP
DC24V
44.60
50
ACB
| Key interlock |
Configure the system with three breaker mounted key lock device. Only two breakers are possible to input with 2EA key, and
the other breaker can supply stable load with interlocking.
Accessories
M
ounting position according to rated current
1 A
1 2 A B
3 2 C B
4 D 1 A
3 C 2 B
1 A
5 4 E D
2 B
6 F 3 C
1 3
2 4
A C
5 E 4 D
3 5 C E
B D
7 6 G F
4 6 D F
1 A
5 E
5 7 E G 3
2
C
B
7 G 6 F
6 F 4
7 G 5 E
D
7 G
6 F
7 G
52
ACB
O
rdering code
Accessories
O
rdering code
54
ACB
| Arc shield |
Arc which may arise while breaking fault current is
extinguished first by arc chute in main body of circuit
breaker and then completely extinguished by arc cover.
O
rdering code
O
rdering code
Accessories
| Control terminal |
Two types of connecting control power. Auto connection
type which the body connected or isolated from control
power automatically and manual connection type which
the connector is inserted to the body manually.
Fixed type is provided with manual control plug type as
standard.
Draw-out type's ordering code: "A" for auto connection,
"J" for manual control plug type.
O
rdering code
| Short b contact |
A contact which keeps the external control circuit in
normal by auxiliary contact which disconnects AUX "b"
when ACB is moved from connected position to test
position.
The number of "Shorting "b" contact" corresponds to the
number of AUX "b" (5b).
Ordering code: AK, UANS AK (Spare part)
ACB operating
ACB close ACB open
ACB position (AUX b off) (AUX b on)
Off On
Connected position
(Short b off) AUX "b" Short "b" AUX "b" Short "b"
Off On
Test position
(Short b on) AUX "b" Short "b" AUX "b" Short "b"
56
ACB
| Fixing block |
The fixing block can reinforce safety gear to prevent
malfunction from vibration.
Able to strengthen bodies, cradles, and panel supporter
together.
It will have been installed when the product is out.
Add AF on main body of ACB and cradles order
respectively.
O
rdering code
| Counter |
Displays the total number of on/off operation of ACB
The counter displays the total number of on/off operation
of ACB.
Extra order is unnecessary (It is a primary component of
UAN/UAS).
Ordering code: UANS AD (Spare part)
Accessories
C
ontact specification
O
rdering code
58
ACB
| Temperature sensor |
The RCTU is used with temperature sensor installed
inside of the ACB.
The temperature sensor is installed in designated
position. However user can change the position to
applicable extra site.
O
rdering code
Accessories
| Draw-in/out handle |
Draw-in/out handle is attached on the side of cradle as
standard.
Ordering code: UANS L handle or UANS U handle
UANS L handle
UANS U handle
O
rdering code
60
ACB
| Neutral CT |
The NCT is additionally applied for 3-pole circuit breaker
when it is connected to distribution line (3 phases 4 lines).
For distribution line (3 phases 4 lines) 3pole circuit
breaker can protect the ground fault however, we can not
classify unbalanced load and ground fault. To complement
this when only a ground fault occurs the NCT senses the
N phase load and operates the GFT.
When connecting a relay or electric instrument checking
phase is mandatory. Please connect the designated
terminal.
It is a separate product. Refer to the table below (Rated
current level) and check the item on your order.
O
rdering code
K 4- 4-
1 1
0 4 4
8
175
Sec. M5 5 0
13 20
300
240
300
300
240
300
97
25
80
107 100
75 SUS 2T
30
30
30 240 40 30 240 40
17.5
300 300
10
Accessories
| Door flange |
Protects the protruding front of ACB and the cutting
side of panel door by attaching it to the panel door.
Both fixed/draw-out type are the same size of the
panel cutting, even if the dust cover is installed.
Refer to dimension for panel cutting size.
Protection rating of IP30.
292
103.5 100 103.5 R5
4-
122.5
Door flange
345
115
Panel door
4
-
122.5
12
7.5
Bottom
7.5
25.6
O
rdering code
| Dust cover |
A protective cover which completely protects the
292
103.5 100
front
103.5
panelR5 of ACB from dust and moisture, with a
4-
protection rating of IP54.
Locks the cover in the test or connected position.
122.5
122.5
12
7.5
292
Bottom 103.5 100 103.5 R5
4-
7.5
25.6
122.5
345
115
O
rdering code
4
-
122.5
12
7.5
of ACB/Cradle
Dust cover - UANS DC for IP52 -
62
ACB
Features
ACB1 ACB2
O
rdering code
Accessories
Description of mode
Stop mode
Time delay State display of controller
This mode is for compulsory trip of ACB1 (Electric power
t1: 0.1-30sec
company) or ACB2 (Power station) when UN (Power supply of On, Off, Fault
t2: 0.1-240sec
electric power company) or UR (Power supply of power
station) is available.
220/240V 50/60Hz 2 4 t1
Auto mode N UN R UR N UN=0
1
0.5
8
15
0.1 30
This mode is for transferring a circuit breaker automatically
On/I On/I
to available power supply of UN or UR. 0.5s 0.5s
Off/0 Off/0
N mode t2 15 30
8 60
This mode is for compulsory closing of ACB1 when UN is 4 120
Fault Fault 0.1 240 UN=I R
available.
Reset
R mode Stop Auto
Manu
This mode is for compulsory closing of ACB2 during the use
of UR regardless of that UN is available or not.
N R
Operation characteristic
UN or KT
UR
KR
QN
QR
T1(ms) T2(ms)
64
ACB
System operation
N R
4-position switch
ACB1 / ACB2 Normal
Off (N, UN supplied)
Trip manually On
I O
ACB2 Trip
Auto mode UN loss above +1 or received
auto-switching command
t0.5s
ACB1 Trip
Reset 1sec
ACB1 Input
t0.5s
Reset end
Stand- ACB1 closed
ACB2 Input
by ON
NR
Operation stop
ACB2 Input
N R I O
4-position switch
I O
UN exist during t t2 or stop
auto-switching command R mode
("Stand-by" ON compulsory)
ACB2 Trip
4-position switch
t0.5s
(N, UN supplied)
ACB2 Input
ACB2 Input
N R
Accessories
B1
A1
A1
offSW.
Aux. SW.
1
Control circuit terminal block
1
1 2 TC M CC
Control circuit terminal block
Common 2
2 3
Stop 7
1 Standard model is equipped switch on the controller (Control terminal type is not standard model).
UN UR 20
1
19
3
18
7
17
19
T 16
20
15
ATS Terminal block
26
14
24
13
R S T R S T 45
12
UN UR 46
11
MCCB MCCB 47
10
48
9
55
Controller IVE 56
8
7
N R 57
6
58
5
4
3
2
1
1 20
3 19
18
7
17
19
16
20
15
ATS Terminal block
26
14
24
13
45
12
46
11
47
10
48
9
55
UN ACB 56
8
7
57
6
58
5
4
3
2
UR ACB 1
66
ACB
ACB2, Stand-by UR
26 24 OCR DO
43 44 Aux. switch a
53 43 26 7 1 3
53 54 Aux. switch b
A1
OFFSW.
54 44 24 8 2 4
1
PB(Close) Do not supply power, ATS
3
ATS controller UN Normal 7
PB(Open) controller is power ON.1)
control voltage (AC220V) ACB 19 OCR control ACDC100-250 S0-S2
ATS Terminal block
20 terminal
N R 26
24 OCR+OCGR 1acontact
45
46
47
48 Aux. SW. 2a-2b
55
56
57
58
1
PB(Close)
Do not supply power, ATS
Stand-by 3
PB(Open) controller is power ON.1)
7
ACB 19 OCR control
ATS Terminal block
1) Do not supply additional control power in case of operating remote, open/close power is supplied from ATS controller (Terminal No. 1, 7, 16).
Accessories
Dimensions
(unit: mm)
UAN(S)06-16 A frame
[ UAN(S)06-16 A, Front ] [ UAN(S)06-16 A, Vertical type ] [ UAN(S)06-16 A, Horizontal type]
40 470
89 220 89
27.5
46.3
46.3
39.9 79 39.9 79
50 94.1 50
15
159.1
343
20.1
15
1810
420.9
455.9
1440
615
50 94.1 50
15
159.1
343
20.1
15
357.05
374.55
250
UAN20 A frame
[ UAN20 A, Front ] [ UAN20 A, Vertical type ]
40 89
27.5
128 36 154
20.5
245
46.3
39.9 79
75 69.1 75
343
20.1
1810
395.9
1440
615
75 69.1 75
343
20.1
344.6
250
68
ACB
(unit: mm)
UAN(S)20-25 B frame
[ UAN(S)20-25 B, Front ] [ UAN(S)20-25 B, Vertical type ] [ UAN(S)20-25 B, Horizontal type ]
140
40 89 89
27.5
128 36 154
20.5
245
75 68.1 75
20 20
163.1
343
20.1
1810
396.9
451.9
1440
615
75 68.1 75
163.1
20 20
343
20.1
345.05
372.55
250
UAN32 B frame
[ UAN32 B, Front ] [ UAN32 B, Vertical type ] [ UAN32 B, Horizontal type ]
140
40 89 89
27.5
128 36 154
20.5
245
123.1
343
20
20.1
1810
615
381.9
1440
615
20
90 53.1 90
163.1
343
20
20.1
372.55
337.55
250
Accessories
Dimensions
(unit: mm)
UAN40 B frame
[ UAN40 B, Front ] [ UAN40 B, Vertical type ] [ UAN40 B, Horizontal type ]
140
40
27.5
128 36 154 89 89
20.5
245
15
125
40 128 40
15
343
68
15
125
20.1
15
1810
407
297
1440
15
615
68 125
128 40
15
343
15
40
125
20.1
15
362.55
295.05
250
70
ACB
(unit: mm)
UAN40-50 C frame, 3P
[ UAN40-50 C, 3P, Front ] [ UAN40-50 C, 3P, Vertical type ] [ UAN40-50 C, 3P, Horizontal type ]
240
40 89 89
128 36 154
27.5
20.5
245
20
110 86.1 110
125 69.1 125
20
343
20
20
20.1
1810
295.9
308.9
1440
615
20
110 86.1 110
125 69.1 125
20
343
20
20
20.1
301.1
294.5
250
UAN40-50 C frame, 4P
[ UAN40-50 C, 4P, Front ] [ UAN40-50 C, 4P, Vertical type ] [ UAN40-50 C, 4P, Horizontal type ]
440
40 128 36 154 89 89
27.5
20.5
245
20
20
20.1
1810
295.9
308.9
1440
615
20
20
20.1
301.1
294.5
250
Circuit Diagrams
ZSI
NCT In Out PB
(Close)
Spring
charge
off SW.
UPR-2L-GS
Protection trip relay
NCT In Out
ZSI
S
ymbol description
72
ACB
PB (Open)
C
ontrol terminal lay-out
OCR
OCR Contact
V input
Dimensions
Front
296 381
404.4
404.4
270
270
168.7 253.7
337.4 422.4
[ 3P ] [ 4P ]
85 85 85 85 85
15 15
5
5
186.8
152.5
186.8
152.5
14 14
20
20
109
109
[ 630-1,600A ] [ 2,000A ]
35 13
35 13 3-
2-
50
75
50
50
25
15 15
144
330
144
330
75
50
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6
74
ACB
(unit: mm)
5
5
152.5
186.8
152.5
186.8
14 14
20
20
109
109
35 13
2-
15
50
25
15
129
144
330
15
132
33
60 49 186.8
295.8 43. 6
5
152.5
152.5
186.8
186.8
14 14
20
20
109
109
35 13
2-
526
50
25
15
330
33
60 49 186.8
295.8
118
15
252.4
Dimensions
Front
440 525
416 501
438 (Manual control plug type)
1 2
.1
.1
278.3
270 270
164 164 164 249
328 413
[ 3P ] [ 4P ]
85 85 85 85 85
15 15
28.8
28.8
250
250
368.4
368.4
1 1
4 4
210 59 210 85
[ 630-1,600A ] [ 2,000A ]
(Test) 26.5 60 Arc shield surface (Test) 26.5 60 Arc shield surface
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)
35 13 35 13
119.3 6 2- 119.3 6 3-
50
50
50
75
75
465.8
465.8
25
144
(Option) (Option)
330
50
75
132
15
132
13 13 15
50 250 50 250
33.1
33.1
15
15
328.8 328.8
352.8 352.8
39.6 381.6 39.6 381.6
421.2 421.2
76
ACB
(unit: mm)
28.8
250
250
368.4
368.4
1 1
4 4
210 59 210 85
119.3 6 35 13
2-
15
50
465.8
Fixing block
25
15
129
144
(Option)
330
15
132
13 15
50 250
33.1
15
328.8
352.8
39.6 381.6
421.2
28.8
250
250
368.4
368.4
1 1
4 4
210 59 210 85
(Test) 26.5 60
20.4 Arc shield surface
(Isol) 11.5 (Option)
35 13
119.3 6 2-
50
526
25
465.8
Fixing block 15
330
(Option)
328.8
13 15
33.1
39.6 50 250
15
118
329.6 15
352.8
Dimensions
Front
367 482
404.4
404.4
270
270 204.2 319.2
408.4 523.4
[ 3P ] [ 4P ]
5
186.8
152.5
186.8
152.5
14 14
20
20
109
109
[ 630-2,500A ] [ 3,200A ]
35 13 35 13
3- 3-
75
50
90
75
50
90
15
144
144
330
330
15
75
90
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43. 6 295.8 43. 6
78
ACB
(unit: mm)
5
186.8
152.5
186.8
152.5
14 14
20
20
109
109
[ 630~2,500A ] [ 3,200A ]
35 13 35 13
3- 3-
50
75
90
50
15
330
144
15
330
144
20
20
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43.6 295.8 43. 6
5
152.5
152.5
186.8
186.8
14 14
20
20
109
109
35 13
3-
75
50
644
15
330
33
60 49 186.8
118
295.8
20
257.4
Dimensions
Front
511 626
487 602
1 2
1 2
.1
.1
278.3
278.3
270 270
199.5 199.5 199.5 314.5
399 514
[ 3P ] [ 4P ]
250
250
368.4
368.4
1 1
4 4
[ 630-2,500A ] [ 3,200A ]
(Test) 26.5 60 (Test) 26.5 60
Arc shield surface Arc shield surface
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)
35 13
35 13 3-
119.3 6 3- 119.3 6
90
90
50
75
75
50
465.8
465.8
15
330
(Option) (Option)
143
15
90
75
132.5
132.5
13 15 13 15
50 250 50 250
33.1
15
15
33.1
328.8 328.8
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2
80
ACB
(unit: mm)
28.8
UAN32 90
250
250
368. 4
368. 4
1 1
4 4
[ 630-2,500A ] [ 3,200A ]
(Test) 26.5 60 (Test) 26.5 60
Arc shield surface Arc shield surface
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)
35 13 35 13
119.3 6 3- 119.3 6 3-
20
20
50
75
50
90
465.8
465.8
Fixing block Fixing block
15
143
124
330
330
(Option)
143
124
(Option) 15
20
20
132.5
132.5
13 15 13 15
50 250
33.1
33.1
50 250
15
15
328.8 328.8
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2
28.8
250
250
368.4
368.4
1 1
4 4
(Test) 26.5 60
20.4 Arc shield surface
(Isol) 11.5 (Option)
35 13
119.3 6 3-
525.5
465.8
50
75
Fixing block
330
(Option) 15
328.8
13 15
33.1
50 250
15
39.6
117.5
329.6 20
352.8
Dimensions
Front
367 482
404.4
404.4
270
270
204.2 319.2
408.4 523.4
[ 3P ] [ 4P ]
186.8
152.5
186.8
152.5
14 14
20
20
109
109
35 13
5-
25*4=100
125
125
330
169
44
15
125
119.5
57
33
60 49 186.8
295.8 87
82
ACB
(unit: mm)
405 520
152.5 152.5 140 140 140
100 100
5
5
186.8
152.5
186.8
152.5
14 14
20
20
109
109
3
35 1
3-
25*3=75
100
40
330
144
15
15
10
15
132
33
60 49 186.8
295.8 58.6
Dimensions
Front
511 626
487 602
1 2
1 2
.1
.1
278.3
278.3
270 270
199.5 199.5 199.5 314.5
399 514
[ 3P ] [ 4P ]
28.8
250
250
368.4
368.4
1 1
4 4
(Test) 26.5 60
Arc shield surface
(Isol) 11.5 20.4 (Option)
13
35 5-
119.3 6
25*4=100
125
125
465.8
Fixing block 15
330
193
68
(Option)
125
107.5
13 15
50 250
33.1
15
328.8
352.8
39.6 425.6
465.2
84
ACB
(unit: mm)
28.8
28.8
250
250
368.4
368.4
1 1
4 4
(Test) 26.5 60
Arc shield surface
(Isol) 11.5 20.4 (Option)
3
1
35 3-
15
119.3 6
25*3=75
10
100
15
465.8
Fixing block 15
168
330
(Option)
40
132.5
13 15
50
33.1
250
15
328.8
352.8
39.6 399.6
439.2
Dimensions
Front
592 762
404.4
404.4
270 270
464.7 168.7 549.7 253.7
633.4 803.4
[ 3P ] [ 4P ]
5
186.8
152.5
152.5
186.8
20
20
109
109
13
35 5-
25*4=100
125
125
15
194
69
330
125
107
33
60 49 186.8
44.5
295.8 63.6
86
ACB
(unit: mm)
5
186.8
152.5
152.5
186.8
20
20
109
109
13
35 5-
20
25*4=100
110
125
70
20
15
330
196
86
110
106
51
33
60 49 186.8
295.8 63.6
Dimensions
Front
736 906
712 882
460 (Auto connection type)
12
.1
.1
278.3
278.3
270 270
460 164 545 249
624 794
12
6
103.8
103.8
368.4
368.4
175
175
4 4
1 1
50
50
13
35 5-
119.3 6
25*4=100
125
125
465.8
Fixing block
(Option) 15
194
330
69
125
107
13 15
44.5
50 175
33.1
15
328.8
352.8
39.6 401.6
441.2
88
ACB
(unit: mm)
103.8
103.8
368.4
368.4
175
175
4
1
4
1
50
50
13
35 5-
20
119.3 6
25*4=100
110
125
70
465.8
Fixing block
15
20
196
(Option)
330
86
110
106
13 15
51
50 175
33.1
15
328.8
352.8
39.6 401.6
441.2
122.5
U-Series / Air Circuit Breaker
330
345
115
B
4
Dimensions
122.5
12
Rear panel
7.5
(IP30)
C
31
32
25.6
33.1
7.5 4
Panel door
(25) (323)
Operaing
panel center
ACB center
292
R5 A
103.5 100 103.5 4-
122.5
144
330
345
115
B
75
4
-
122.5
12
132
7.5
33
25.6
C
7.5 (95) (188)
Rear panel
Panel door (IP30)
R
eal panel cutting size
Model A B C
90
ACB
(Test)26.5 60
Operaing
panel center (Isol)11.5 20.4
292
R5 ACB center
103.5 100 103.5 4-
A
122.5
330
345
115
B
4
-
122.5
12
Rear panel
7.5
(IP30)
C
31
32
25.6
33.1
7.5 4
Panel door
(25) (323)
Operaing
panel center
ACB center
R
eal panel cutting
292 size R5 A
103.5 100 103.5 4-
Model A B C
122.5
122.5
132
7.5
Ordering Codes
| UAN type |
UAN 12 A 3 J M2
Frame size &
Type Rated current Pole Terminal connection Motor
pole arrangement
UAN 06 630A 2,000AF, 630-2,000A 3 3 Pole Draw-out type/ M0 Manual type
A
08 800A 3P: RST, 4P: RSTN 4 4 Pole Control terminal connection M1 AC/DC 110V
10 1,000A 2,000AF, 630-2,000A A Auto connection M2 AC/DC 220V
W
12 1,250A 4P: NRST J Manual connection M3 AC380V
16 1,600A 4,000AF, 630-4,000A Fixed type/ M4 AC440V
B
201) 2,000A 3P: RST, 4P: RSTN Terminal busbar arrangement M5 DC24V
25 2,500A 4,000AF, 630-4,000A H Horizontal type M6 DC48V
X
32 3,200A 4P: NRST V Vertical type M7 DC125V
40 4,000A 5,000AF, 3,200-5,000A Line side: Horizontal
C T
3P: RST, 4P: RSTN Load side: Vertical
50 5,000A
Line side: Vertical
L
5,000AF, 3,200-5,000A Load side: Horizontal
Y
4P: NRST P2) Front type or others
DUN 12 A 3 A H AE
Frame size & Control terminal Terminal busbar
Type Rated current Pole Accessories
pole arrangement connection arrangement
DUN 630-1,600A, 3 3 pole H Horizontal type AE Safe shutter lock
16 A 2,000AF, 630-2,000A A
Auto
A frame 3P: RST, 4P: RSTN/NRST 4 4 pole connection V Vertical type AF Fixing block
2,000A, B 4,000AF, 630-4,000A Manual Line side: Horizontal Short "b" contact for auto
20 J T AK
A frame 3P: RST, 4P: RSTN/NRST connection Load side: Vertical connection terminal
25
630-2,500A, C 5,000AF, 3,200-5,000A L
Line side: Vertical
AW
Wrong insertion
B frame 3P: RST, 4P: RSTN/NRST Load side: Horizontal preventer
3,200-5,000A,
50
C frame
92
ACB
C2 S2 45 K AB
Protection trip relay
Closing coil Trip coil CT3) Accessories
(OCR)
C0 N/A S0 N/A 00 N/A 0 N/A Instantaneous type (UVT coil)4) Double trip coil4)
C1 AC/DC 110V S1 AC/DC 110V General feeder, 50Hz I 80A U1 AC/DC 110V S1 AC/DC 110V
C2 AC/DC 220V S2 AC/DC 220V 33 UPR-1L-GL B 160A U2 AC/DC 220V S2 AC/DC 220V
C3 AC380V S3 AC380V 35 UPR-2L-GS O 200A U3 AC380V S3 AC380V
C4 AC440V S4 AC440V 36 UPR-1D-GT V 320A U4 AC440V S4 AC440V
C7 DC24V S7 DC24V 37 UPR-2L-GM E 400A U7 DC24V S7 DC24V
C8 DC48V S8 DC48V General feeder, 60Hz T 630A U8 DC48V S8 DC48V
C9 DC125V S9 DC125V 43 UPR-1L-GL H 800A U9 DC125V S9 DC125V
45 UPR-2L-GS J 1,000A Time delay type4)
46 UPR-1D-GT K 1,250A (UVT coil with UVT controller) Trip supervision coil5)
47 UPR-2L-GM L 1,600A V1 AC/DC 110V T1 AC/DC 110V
M 2,000A V2 AC/DC 220V T2 AC/DC 220V
Generator, 50Hz N 2,500A V3 AC380V T3 AC380V
38 UPR-1S-AL P 3,200A V4 AC440V T4 AC440V
39 UPR-2S-AS Q 4,000A V7 DC24V T7 DC24V
Generator, 60Hz S 5,000A V8 DC48V T8 DC48V
48 UPR-1S-AL X 6,300A V9 DC125V T9 DC125V
49 UPR-2S-AS
AF Fixing block Position switch8)
AW Wrong insertion preventer AQ Test 1C, Connected 1C
AM ON/OFF button cover AR Connected 2C
Additional 1a1b auxiliary
AA 6)
switch AS Test 2C
AB Key lock device AT Isolated 1C, Inserted 1C
1) Vertical type is the only applicable terminal busbar for A frame, 2,000A. B8 5) OCR MCR function AU Inserted 2C
2) Code P is for user installation, and applicable for A frame, 630-1,600A & B frame
630-3,200A. Please refer to page 48. BR OCR manual reset device AV Isolated 2C
3) CT Application OCR manual reset &
Frame A/W: 80-2,000A BA alarm switch reset device P4 Test 2C, Connected 2C
Frame B/X: 400-4,000A OCR auto reset &
BM alarm switch reset device PS Isolated 1C, Test 1C,
Connected 2C
Frame C/Y: 3,200-5,000A
Internal part for
4) UVT coil and double trip coil cannot be installed at the same time. B07) mechanical interlock PQ Inserted 1C, Isolated 1C,
Test 1C, Connected 1C
5) Standard auxiliary switch of UAN type is 5a5b. Trip supervision coil use 1a1b of
standard auxiliary switch, and OCR MCR function use;1a. B6 Spring charge switch P8 Inserted 2C, Isolated 2C,
Test 2C, Connected 2C
6) Additional 1a1b auxiliary switch and mechanical interlock cannot be installed at
the same time. B7 ATS controller PR Inserted 1C, Isolated 1C,
Test 3C, Connected 3C
7) Mechanical interlock kit can be ordered separately, please refer to page 47.
8) Only one type position switch is selectable. SP ACB body only
Ordering Codes
| UAS type |
UAS 12 A 3 J M2
Frame size &
Type Rated current Pole Terminal connection Motor
pole arrangement
UAS 06 630A 2,000AF, 630-2,000A 3 3 Pole Draw-out type/ M0 Manual type
A
08 800A 3P: RST, 4P: RSTN 4 4 Pole Control terminal connection M1 AC/DC 110V
10 1,000A 2,000AF, 630-2,000A A Auto connection M2 AC/DC 220V
W
12 1,250A 4P: NRST J Manual connection M3 AC380V
16 1,600A 4,000AF, 630-4,000A Fixed type/ M4 AC440V
B
201) 2,000A 3P: RST, 4P: RSTN Terminal busbar arrangement M5 DC24V
25 2,500A 4,000AF, 630-4,000A H Horizontal type M6 DC48V
X
32 3,200A 4P: NRST V Vertical type M7 DC125V
Line side: Horizontal
T
Load side: Vertical
Line side: Vertical
L
Load side: Horizontal
P2) Front type or others
DUN 12 A 3 A H AE
Frame size & Control terminal Terminal busbar
Type Rated current Pole Accessories
pole arrangement connection arrangement
DUN 630-1,600A, 3 3 pole H Horizontal type AE Safe shutter lock
16 A 2,000AF, 630-2,000A A
Auto
A frame 3P: RST, 4P: RSTN/NRST 4 4 pole connection V Vertical type AF Fixing block
20
2,000A, B 4,000AF, 630-4,000A J
Manual
T
Line side: Horizontal
AK
Short "b" contact for auto
A frame 3P: RST, 4P: RSTN/NRST connection Load side: Vertical connection terminal
94
ACB
C2 S2 43 K AB
Protection trip relay
Closing coil Trip coil CT3) Accessories
(OCR)
C0 N/A S0 N/A 00 N/A 0 N/A Instantaneous type (UVT coil)4) Double trip coil4)
C1 AC/DC 110V S1 AC/DC 110V General feeder, 50Hz I 80A U1 AC/DC 110V S1 AC/DC 110V
C2 AC/DC 220V S2 AC/DC 220V 33 UPR-1L-GL B 160A U2 AC/DC 220V S2 AC/DC 220V
C3 AC380V S3 AC380V 35 UPR-2L-GS O 200A U3 AC380V S3 AC380V
C4 AC440V S4 AC440V 37 UPR-2L-GM V 320A U4 AC440V S4 AC440V
C7 DC24V S7 DC24V General feeder, 60Hz E 400A U7 DC24V S7 DC24V
C8 DC48V S8 DC48V 43 UPR-1L-GL T 630A U8 DC48V S8 DC48V
C9 DC125V S9 DC125V 45 UPR-2L-GS H 800A U9 DC125V S9 DC125V
47 UPR-2L-GM J 1,000A Time delay type4)
K 1,250A (UVT coil with UVT controller) Position switch8)
Generator, 50Hz L 1,600A V1 AC/DC 110V AQ Test 1C, Connected 1C
38 UPR-1S-AL M 2,000A V2 AC/DC 220V AR Connected 2C
39 UPR-2S-AS N 2,500A V3 AC380V AS Test 2C
Generator, 60Hz P 3,200A V4 AC440V AT Isolated 1C, Inserted 1C
48 UPR-1S-AL Q 4,000A V7 DC24V AU Inserted 2C
49 UPR-2S-AS S 5,000A V8 DC48V AV Isolated 2C
X 6,300A V9 DC125V P4 Test 2C, Connected 2C
PS Isolated 1C, Test 1C,
Connected 2C
AA6) Additional
switch
1a1b auxiliary
1) Vertical type is the only applicable terminal busbar for A frame, 2,000A. AB Key lock device
2) Code P is for user installation, and applicable for A frame, 630-1,600A & B frame
630-3,200A. Please refer to page 48.
B8 5) OCR MCR function
3) CT Application
BR OCR manual reset device
Frame A/W: 80-2,000A
Frame B/X: 400-4,000A OCR manual reset &
BA alarm switch reset device
Frame C/Y: 3,200-5,000A
OCR auto reset &
4) UVT coil and double trip coil cannot be installed at the same time. BM alarm switch reset device
5) Standard auxiliary switch of UAN type is 5a5b. Trip supervision coil use 1a1b of
Internal part for
standard auxiliary switch, and OCR MCR function use;1a. B07) mechanical interlock
6) Additional 1a1b auxiliary switch and mechanical interlock cannot be installed at
the same time. B6 Spring charge switch
7) Mechanical interlock kit can be ordered separately, please refer to page 47.
8) Only one type position switch is selectable.
SP ACB body only
Technical Data
A
| Insulation distance |
ACB A B
B B
Fixed type 120mm 50mm
Draw-out Without Arc shield 120mm 50mm
type With Arc shield 0mm 50mm B B
M
inimum insulation distance at charging side D
Insulating voltage D
[V] 600V 8mm
600V [V] 1,000V 14mm
96
ACB
A
ltitude Item Altitude 2,000m 3,000m 4,000m 5,000m
U-Series ACB is designed for operation at altitudes Withstand voltage[V] 3,500 3,150 2,500 2,100
under 2,000m. At altitudes higher than 2,000m, Average insulating voltage[V] 1,000 900 700 600
Max. operation voltage [V] 690 590 520 460
change the ratings upon service condition.
Rectificated rated current [A] 1In 0.99In 0.96In 0.94In
Technical Data
| Derating table |
A frame Ambient temperature outside of the switchboard: Ta (IEC 60439-1)
4
3
Switchboard composition 2
1
connection type
H 4 800
4 800
Non ventilated switchboard 3 800 800 1,000
(IP41/54) Ta=35C
2 800 800 800 1,000 1,000
4 800
4 800
98
ACB
4
3
Switchboard composition 2
1
connection type
H 4
H 3 1,250 1,000
Ta=45C
2 1,250 1,250 1,600 1,000 1,000
4
Non ventilated switchboard 3 1,250 1,000
(IP41/54) Ta=35C
2 1,250 1,250 1,600 1,000 1,000
3 1,250 1,000
H Ta=45C
2 1,250 1,250 1,500 1,000 1,000
H
1 1,250 1,250 1,250 1,250 1,480 1,600 1,600 1,000 1,000
3 1,250 1,000
D W Ta=55C
D
2 1,250 1,250 1,400 1,000 1,000
W
1 1,250 1,250 1,250 1,250 1,400 1,520 1,500 1,000 1,000
Technical Data
| Derating table |
B frame Ambient temperature outside of the switchboard: Ta (IEC 60439-1)
4 4 4 4
3 3 3 3
Switchboard composition 2 2 2 2
1 1 1 1
connection type
H 4
H 3 2,000
Ta=45C
2 2,000 2,000 2,000 2,300 2,400 2,900 3,100 3,200 3,550
1
D W 4
D W 3 2,000
Ta=55C
Area of inlet vents: 350cm 2
2 2,000 2,000 2,000 2,200 2,300 2,700 2,900 3,000 3,300
Area of outlet vents: 350cm2
1
4
Non ventilated switchboard 3 2,000
(IP41/54) Ta=35C
2 2,000 2,000 2,000 2,115 2,275 2,650 2,850 3,040 3,320
3 1,900
H Ta=45C
2 1,900 1,960 1,960 2,000 2,150 2,550 2,700 2,880 3,120
H
1
3 1,780
D W Ta=55C
D 2 1,800 1,920 1,920 1,900 2,020 2,370 2,530 2,720 2,960
W
1
100
ACB
4 4 4 4 4
3 3 3 3 3
Switchboard composition 2 2 2 2 2
1 1 1 1 1
connection type
Applicable ACB UAN40 (C) UAN50 (C) UAN40 (D) UAN50 (D) UAN63 (D)
Busbar dimensions (mm) 4EA x 100 x 10 4EA x 125 x 10 4EA x 100 x 10 4EA x 125 x 10 4EA x 150 x 10
4
Ventilated switchboard (IP31) 3
Ta=35C
2 2,900 4,000 4,750 4,800 4,000 4,000 4,750 5,000 5,850 6,300
H 4
H 3
Ta=45C
2 3,850 3,900 4,350 4,650 4,000 4,000 4,450 4,850 5,670 5,850
1
D W 4
D W 3
Ta=55C
Area of inlet vents: 350cm2
2 3,800 3,850 4,200 4,400 4,000 4,000 4,200 4,600 5,350 5,670
Area of outlet vents: 350cm2
1
4
Non ventilated switchboard 3
(IP41/54) Ta=35C
2 3,800 3,900 4,200 4,550 4,000 4,000 4,400 4,650 5,350 5,000
3
H Ta=45C
2 3,650 3,800 3,950 4,250 4,000 4,000 4,100 4,400 5,040 5,350
H
1
3
D W Ta=55C
D
2 3,550 3,650 3,700 4,050 3,900 3,950 3,850 4,150 4,730 5,040
W
1
Technical Data
| Discrimination table |
Upstream Breaking capacity: at AC380/415V
Downstream
ACB
UAN/UAS A frame UAN/UAS B frame UAN C frame
Recognition
630 800 1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
category Model Rated
current Breaking
(A) capacity [Icu] 85 85 85 85 85 85 100 100 100 100 100 100
(kA r.m.s)
1 4.5 T T T T T T T T T T T T
2 4.5 T T T T T T T T T T T T
5 4.5 T T T T T T T T T T T T
6 4.5 T T T T T T T T T T T T
HiBD63-NS 10 4.5 T T T T T T T T T T T T
B, C curve 16 4.5 T T T T T T T T T T T T
20 4.5 T T T T T T T T T T T T
25 4.5 T T T T T T T T T T T T
32 4.5 T T T T T T T T T T T T
40 4.5 T T T T T T T T T T T T
1 6 T T T T T T T T T T T T
2 6 T T T T T T T T T T T T
3 6 T T T T T T T T T T T T
4 6 T T T T T T T T T T T T
5 6 T T T T T T T T T T T T
6 6 T T T T T T T T T T T T
10 6 T T T T T T T T T T T T
HiBD63-N 13 6 T T T T T T T T T T T T
MCB B, C, D curve 15 6 T T T T T T T T T T T T
16 6 T T T T T T T T T T T T
20 6 T T T T T T T T T T T T
25 6 T T T T T T T T T T T T
32 6 T T T T T T T T T T T T
40 6 T T T T T T T T T T T T
50 6 T T T T T T T T T T T T
63 6 T T T T T T T T T T T T
1 10 T T T T T T T T T T T T
2 10 T T T T T T T T T T T T
3 10 T T T T T T T T T T T T
4 10 T T T T T T T T T T T T
5 10 T T T T T T T T T T T T
HiBD63H
6 10 T T T T T T T T T T T T
B, C, D curve
10 10 T T T T T T T T T T T T
13 10 T T T T T T T T T T T T
15 10 T T T T T T T T T T T T
16 10 T T T T T T T T T T T T
20 10 T T T T T T T T T T T T
Can be blocked all sectors. Can not be blocked.
102
ACB
ACB
UAN/UAS A frame UAN/UAS B frame UAN C frame
Recognition
630 800 1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
category Model Rated
current Breaking
(A) capacity [Icu] 85 85 85 85 85 85 100 100 100 100 100 100
(kA r.m.s)
25 10 T T T T T T T T T T T T
32 10 T T T T T T T T T T T T
HiBD63h
40 10 T T T T T T T T T T T T
B, C, D curve
50 10 T T T T T T T T T T T T
MCB 63 10 T T T T T T T T T T T T
63 10 T T T T T T T T T T T T
HiBD125 80 10 T T T T T T T T T T T T
B, C, D curve 100 10 T T T T T T T T T T T T
125 10 T T T T T T T T T T T T
5 30 T T T T T T T T T T T T
10 30 T T T T T T T T T T T T
15 30 T T T T T T T T T T T T
20 30 T T T T T T T T T T T T
UAB100 30 30 T T T T T T T T T T T T
C, R, S 40 30 T T T T T T T T T T T T
50 30 T T T T T T T T T T T T
60 30 T T T T T T T T T T T T
75 30 T T T T T T T T T T T T
100 30 T T T T T T T T T T T T
15 50 T T T T T T T T T T T T
20 50 T T T T T T T T T T T T
30 50 T T T T T T T T T T T T
MCCB
40 50 T T T T T T T T T T T T
UCB100
50 50 T T T T T T T T T T T T
R, S, H, L
60 50 T T T T T T T T T T T T
75 50 T T T T T T T T T T T T
100 50 T T T T T T T T T T T T
125 50 T T T T T T T T T T T T
100 50 T T T T T T T T T T T T
125 50 T T T T T T T T T T T T
150 50 T T T T T T T T T T T T
UCB250
175 50 T T T T T T T T T T T T
R, S, N, H, L
200 50 T T T T T T T T T T T T
225 50 T T T T T T T T T T T T
250 50 T T T T T T T T T T T T
Can be blocked all sectors. Can not be blocked.
Technical Data
| Discrimination table |
Upstream Breaking capacity: at AC380/415V
Downstream
ACB
UAN/UAS A frame UAN/UAS B frame UAN C frame
Recognition
630 800 1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
category Model Rated
current Breaking
(A) capacity [Icu] 85 85 85 85 85 85 100 100 100 100 100 100
(kA r.m.s)
250 100 T T T T T T T T T T T T
300 100 T T T T T T T T T T T T
UCB400
320 100 T T T T T T T T T T T T
R, S, N, H, L
350 100 T T T T T T T T T T T T
400 100 T T T T T T T T T T T T
104
ACB
Operating Conditions
| Atmospheric conditions |
Do not apply under corrosive or ammonia gas circumstances (H2S, SO2, NH3).
Use in clean air condition.
| Altitude |
Altitude
Item
2,000m (6,600 feet) 2,600m (8,500 feet) 3,900m (13,000 feet)
Isolation voltage [V] 1,000 950 800
Operating voltage [V] 690 655.5 552
Allowed current [A] 1 x In 0.99 x In 0.96 x In
Degree of protection
First characteristic numeral Second characteristic numeral
0 Non-protected Non-protected (OPEN)
1 Protected against solid foreign objects of 50mm and greater Protected against vertically falling water drops
2 Protected against solid foreign objects of 12.5mm and greater Protected against vertically falling water drops when enclosure tilted up to 15
3 Protected against solid foreign objects of 2.5mm and greater Protected against spraying water (at an angle up to 60)
4 Protected against solid foreign objects of 1.0mm and greater Protected against spraying water (Splash proof)
5 Dust-protected (Ingress of dust is not totally prevented) Protected against spraying jets (Hose proof)
6 Dust-tight (No ingress of dust) Protected against powerful water jets (Deckwater proof)
Protected against the effects of temporary immersion in water
7 -
(Under pressure and time)
Protected against the effects of continuous immersion in water
8 -
(Submersible)
Ordering Sheet
To indicate your choice, check the applicable boxes and enter the appropriate information corresponding to your choice.
Frame size AF
A (630-2,000AF)2) B (630-4,000AF)3) C (3,200-5,000AF) D (4,000-6,300AF)
Phase type Standard type (R, S, T, N) Reverse phase type (N, R, S, T)
Number of poles 3 pole 4 pole
Type of equipment Draw-out type Fixed type
Terminal
connection Manual connection Auto connection
(Draw-out type)
Terminal busbar
arrangement Horizontal Vertical Horizontal/Vertical (Line/Load) Vertical/Horizontal (Line/Load) Front type or others4)
(Fixed type)
Charging Manual closing
Electrical closing
AC/DC110V DC125V DC24V DC48V
Motor operating voltage
AC/DC220V AC380V 5) AC440V 5)
Closing voltage AC/DC110V DC125V AC/DC220V DC24V DC48V AC380V AC440V
Trip voltage AC/DC110V DC125V AC/DC220V DC24V DC48V AC380V AC440V
Protection trip NO
relay YES
Ground
50Hz 60Hz Model LCD/LED Application fault Signal NCT ELT Comm7) MCR Memory Adaptor
detection6)
33 43 UPR-1L-GS - General feeder Integrated instantaneous 1a - - - -
35 45 UPR-2L-GS General feeder Individual continuous 4a - -
36 46 UPR-1D-GT General feeder Individual continuous 4a
37 47 UPR-2L-GM General feeder Integrated continuous 3a8) - -
38 48 UPR-1S-AL - Generator - Integrated instantaneous 1a - - - - -
39 49 UPR-2S-AS Generator - Individual continuous 3a9) - - -
Auxiliary switch 3a3b (Standard for UAS) 5a5b (Standard for UAN) 6a6b (Maximum)
OCR MCR wire Complete parts of ACB/Cradle Spare part
OCR & Alarm switch BR: OCR (Only for manual reset button) BA: OCR manual reset+Alarm switch
reset button BM: OCR (Auto reset)+Alarm switch
Counter (Standard)
Fixing block11) Complete parts of ACB/Cradle Spare part
Wrong insertion preventer11) Complete parts of ACB/Cradle Spare part
Key lock device Complete parts of ACB/Cradle Spare part
ON/OFF button lock Complete parts of ACB/Cradle Spare part
Mechanical interlock12) Complete parts of ACB/Cradle Spare part
Spring charge switch Complete parts of ACB/Cradle Spare part
106
ACB
Terminal busbar
Horizontal Vertical Horizontal/Vertical (Line/Load) Vertical/Horizontal (Line/Load) Front type or others4)
arrangement
1) In case of UAS, A frame size is in the range of 630-1,600AF and B frame size is in the range of 2,000-3,200AF.
2) In case of UAN 20A, only vertical type is available.
3) In case of UAN, B frame size of 630-1,600AF is possible.
4) Front type/User installation need to be ordered separately and attached by the customer. 630-1,600AF is available
for A frame and 2,000-3,200AF is available for B frame.
5) Motor of AC380/440V is available from June. 2013.
6) Standard function for general feeder: Ground fault detection.
7) Communication function is not available under no control voltage.
8) LTD/STD/INST/ELT (except. PTA)
9) LTD/STD/INST/PTA (except. GFT)
10) In case of ordering UVT, double trip coil is not available.
11) In case of ordering fixing block and wrong insertion preventer, mark on both ACB and cradle ordering sheet.
12) MI is separate purchasing item, only assembled parts interacting inside of the body are delivered.
13) In case of ordering safety shutter-attachment type, shutter lock is automatically implemented.
14) Fixing block and wrong insertion preventer have to be marked on both the body and cradle orders.
15) Control terminal protection cover is only available for automatic connection type.
16) UVT controller and position switch can be offered as mounted.