Sie sind auf Seite 1von 3

JOB NO.

WKVECS-WE408-001
CALCULATION Cooling Tower Make Up Water Tank
DATE November 27, 2017
SERVICES Vertical Transportation
JOB DESCRIBTION
REF. NO. WKVECS-WE408-ACMV-C-01

Detail #1 #2 #3 #4
Capacity, RT 2,000 2,000 2,000 2,000
Cooling Tower Detail Condenser Water Flow, L/s 270.00 270.00 270.00 270.00
Daily Operational Hour, hr 12 12 12 12
Evaporation Loss, % 0.850 0.850 0.850 0.850
Drift Loss, % 0.005 0.005 0.005 0.005
Water Loss
Blowdown Loss, % 0.250 0.250 0.250 0.250
Total Loss, % 1.105 1.105 1.105 1.105
Storage Day, day 1 1 1 1
Minimum Storage Required, m3 128.89 128.89 128.89 128.89
Make Up Water Tank Capacity
Safety Factor, % 5 5 5 5
Total Storage Required, m3 135.33 135.33 135.33 135.33
Type of Tank FRP FRP FRP FRP
Tank Height, m 4 3 2 1
Tank Top Clearance, m 0.30 0.30 0.30 0.30
Tank Bottom Clearance, m 0.50 0.50 0.50 0.50
Make Up Water Tank Detail Tank Effective Height, m 3.20 2.20 1.20 0.20
Tank Length, m 2 2 2 2
Tank Width, m 22 31 57 339
Tank Effective Volume, m3 140.80 136.40 136.80 135.60
Status Check Yes Yes Yes Yes
Water Weight, kg 140,800 136,400 136,800 135,600
Tank Panel Density, kg/m3 3,000 3,000 3,000 3,000
Tank Panel Thickness, mm 5 5 5 5
Tank Weight
Total Tank Surface Area, m2 280 322 464 2038
Tank Weight, kg 4,200 4,830 6,960 30,570

file:///conversion/tmp/scratch/372735786.xlsx Page 1 of 3
Tank Weight

Total Tank Weight, kg 145,000 141,230 143,760 166,170

file:///conversion/tmp/scratch/372735786.xlsx Page 2 of 3
Services Tank Tier (Tank Height) 1
Hydraulic 2
Fire Protection 3
ACMV 4
Natural Gas
LPG
Vertical Transportation
BAS

Das könnte Ihnen auch gefallen