Sie sind auf Seite 1von 6

Transient Impedance Characteristics of Grounding Electrodes in

Lightning Protection System


Bok-Hee Lee, Su-Bong Lee, Tae-Hyung Lee, Hyun-Uk Jung and Dong-Cheol Jeong
Research Center for Next-Generation High Voltage and Power Technology,
Department of Electrical Engineering, Inha University
#253, Yonghyun-dong, Nam-ku, Inchon 420-751, Korea

Abstract

This paper presents the transient impedance behaviors of grounding systems to lightning impulse currents. Also, the
apparent soil resistivity at the test site was measured. The dynamic characteristics of the deeply driven ground rod
and grounding grid subjected to the impulse current with various rise time were examined. It was found that the
transient ground impedance characteristics strongly depend on the configuration and size of grounding electrodes and
the impulse current shapes and the reduction of grounding electrode inductance is an important factor to improve the
transient ground impedance characteristics.

Keywords: Transient ground impedance, soil resistivity mapping, effective ground impedance, surge
protection, GPR

1 INTRODUCTION lightning current flows through a grounding system.


The transient ground impedances are dependent on the The experiments were performed in the deeply driven
size and configuration of the grounding electrodes and ground rod of 30 m long and grounding grids. The
grids, the soil characteristics and largely on the shape potential rise and effective impulse ground impedance
and magnitude of impulse currents. Lightning currents of the test grounding electrodes were measured as a
flowing through a ground system lead to the ground function of the rise time of impulse currents. Also, the
potential rise and can cause danger and injury in the apparent two-dimensional profile of soil resistivity at
vicinity power equipments. The effective grounding the test site was analyzed using the soil resistivity
systems with low transient impedance against measurement device based on the dipole-dipole
lightning surges or electronic noises in method.(Syscal Pro, IRIS instrument)
microelectronics and high-technology branches are
strongly needed. It is highly desirable to evaluate the 2 EXPERIMENTAL PROCEDURE
transient ground impedances as a measure of
performance of grounding systems. [1-4] 2.1 Experimental Setup
The experiments have been carried out using the
The transient ground impedance characteristics play an actual-sized ground rod and grids. Basically, the
important role in the protection of electrical measurement of the ground impedance of largesized
equipments against lightning. The protection grounding systems is based on the conventional
efficiency of lightning protection system is affected by fall-of-potential method. However, in case of the
transient ground impedances. The transient ground impulse injection current and high frequency test
impedance is a decisive factor in evaluating the current, the method produces a serious problem in
protecting performance of grounding system against relation to significant measurement errors caused by
lightning. For instance, if the transient ground mutual coupling between the long current injection
impedance is too high, the protection efficiency of wire and the reference potential wire. Therefore, in
lightning surge arresters will be reduced. To evaluate this work, the modified fall-of potential method
the dynamic impedance characteristics of actual-sized recommended by IEEE 81.2-1991 was employed.[5]
grounding systems, the present work is forced on the The current injection line make a right angle with the
measurement and analysis of the transient ground potential probe wire to reduce the effect of the
impedance characteristics that may occur when a inductive coupling between them as shown in Figure 1.
The deeply driven ground rod and the grounding grids rate, and the current and voltage signals are registered
were tested in this work. The grounding electrode of on a personal computer.
30 m long was installed perpendicular to the surface of
ground. Two copper wires of 100 was connected 3 RESULTS AND DISCUSSION
to the specially designed ground rod of 9 m long. The
grounding grid consists of a main grid of 20 m20 m 3.1 Soil Resistivity Mapping at the Test Site
mesh buried 0.75 m deep. The main grid is composed Generally, the measurement of soil resistivity is
of 100 copper wires. The auxiliary grounding important for assessing the performance of grounding
electrodes comprised 8 rods, each 2.4 m long, buried systems. The measured data is used to develop a
perpendicular to the surface of ground. The grounding model of soil structure that is an important factor in
electrode being tested is alternately changed by designing the grounding system to meet the relevant
making and breaking the switches S1 and S2. safety criteria. The Wenner test method is the most
suitable technique for grounding system investigations,
where the apparent resistivity variations with probe
spacing give an indication of the soil resistivity profile
with depth. However, in the case of tower bases, the
soil conditions may vary considerably along the line
spans, and use of one-dimensional surveying
techniques may give inaccurate data. Consequently,
tow-dimensional techniques that are more elaborate
may be needed.[1]

Figure 1. Circuit diagram for measuring the ground


impedance

2.2 Measurements
The combination 8/20 and 1.2/50 waveform
generator is used to inject a double exponential current Figure 2. Soil resistvity mapping at the test site
to the test grounding electrode. The 8/20 impulse
current waveform is specified under short-circuit The apparent soil resistivity at the test site was
condition, and the 1.2/50 impulse voltage measured using the soil resistivity measurement device
waveform is specified under open-circuit condition. based on the dipole-dipole method.(Syscal Pro, IRIS
The test impulse current waveform is changed with the instrument) Figure 2 shows the measured soil
ground impedance to be measured. The impulse resistivity mapping. The soil resistivity is varied with
current generator is composed of an R-L-C series the depth of the actual soil. The soil structure of the
circuit, and the capacitance of charge capacitor is test site is very complex and is considered as a
controlled to adjust the rise time of test impulse multi-layer earth model. The soil resistivity of the top
current. The capacitance and rated voltage of energy layer ranges from approximately 20 m to 100 m.
storage capacitor are 30 F and 10 kV, respectively. The soil resistivity of the bottom layer is remarkably
increased and reaches 1000 m at a depth of
The test current was measured by a current probe with approximately 20 m.
a frequency bandwidth of 400 connected at the
output of the current sources. Also, the potential rise 3.2 Characteristics of Transient Ground Impedances
was measured by an active voltage probe with high
The measured static ground resistance of the deeply
input impedance and a frequency bandwidth of 75 .
driven ground rod of 30 m long, the ground grid of 20
The waveforms of the incident impulse currents and
m20 m and combination of the two grounding
grounding electrode potential are measured by digital
electrodes were 3.87, 1.63 and 1.29 , respectively.
storage oscilloscope with 500 , 2.5 GS/s sampling
The static ground resistance of the long ground rod is
greater than that of the ground grid.

Figure 3 shows the typical waveforms of the incident


impulse current and potential rise according to the
types of the test grounding electrodes The peak
amplitude and rise time of the injection impulse
current are 100 A and 8 , respectively. The
measurements have been made at relatively low
impulse voltages of less than 2 . There is no
indication in waveforms of the measured injection
current and potential rise that the ionization of soil was
occurred. (b) Ground grid of 20 m20 m

The incident impulse current shape is determined by


the test circuit consisting of the current source, current
lead wire and ground conductor under test. The
difference between the rise times of the incident
impulse current are caused by the static ground
resistance of grounding electrode to be measured. The
rise time of grounding electrode potential is shorter
than that of the incident impulse current as shown in
Figure 3. The grounding electrode potential waveform
is dependent on both the ground resistance and the
inductance of the ground conductors. i.e., The ground
conductor potential could be expressed as (c) Combination of the 30 m ground rod and ground
grid of 20 m20 m
di (t ) (1)
V (t ) = Ri (t ) + L
dt
1: Potential rise [100 V/div, 10 /div]
Where the resistance R is the sum of the ground 3: Incident current [50 A/div, 10 /div]
resistance and the resistance of ground conductor and
L is the inductance of ground conductor. Figure 3. Typical waveforms of the incident impulse
current and potential rise according to the types of the
The front time of 30 m ground rod potential is slower
than that of the ground grid of 20 m20 m because of test grounding electrodes
the high static resistance of 30 m ground rod. The
inductive component in the potential waveform of the Figure 4 illustrates the transient ground impedance
ground grid of 20 m20 m is dominant. characteristic curves (Z-t curves) of three grounding
electrodes under test. The transient ground impedance
can be determined from the following expression:

v(t )
Z (t ) = (2)
i (t )
Where v (t ) is the instantaneous value of the
potential rise on the grounding electrode under test,
and i (t ) is the instantaneous value of the incident
current.

In general, characteristics of the transient ground


(a) Ground rod of 30 m long impedances depends on a number of factors such as
the configuration and size of the grounding electrode,
the ground conductor impedance, the soil resistivity,
and the magnitude and shape of the incident currents,
and etc.

Figure 5. Definition of the effective impulse ground


Figure 4. Z-t curves according to the type of the test
impedance
grounding electrodes(: Ground rod, : Ground grid,
: Ground rod + Ground grid) The effective impulse ground impedances of the test
grounding electrodes were measured as a function of
The transient ground impedances decrease the rise time of the incident impulse current as shown
exponentially to steady-state levels up to the time of in Figure 6. The characteristic curves of the effective
20 . The transient ground impedance of 30 m ground impedance versus the rise time of incident
ground rod is greater than that of the ground grid of 20 current are upturned in the short time range. The
m20 m. The upturning of the transient ground effective impulse ground impedance is strongly
impedances of the ground grid of 20 m20 m in the dependent of the rise time of incident current and the
time ranges of less than 20 is pronounced. This types of grounding electrodes.
means that the inductive component of transient
ground impedances is dominant. In detail, after 15 Ground rod Ground grid Ground rod + Ground grid
the transient ground impedances are nearly flat due to 14
Effective ground impedance [ ]

the slow rates of change of the incident current. 12

10
3.3 Characteristics of Effective Impulse Ground 8
Impedances 6
The shape and magnitude of test current is changed in 4
the grounding electrode to be measured. Thus, it is 2
very difficult to investigate the transient characteristics
0
of ground impedance against the same shape and 0 2 4 6 8 10 12 14 16 18
magnitude of incident impulse current. The essential Rise time []
propose of a grounding system is to control the
potential rise developed by fault current or lightning Figure 6. Characteristic curves of the effective impulse
currents. It is very important to reduce the ground ground impedance against the rise time of the injection
impedance at the instant when the potential rise of impulse currents for three types of the test grounding
grounding electrode is arrived at the peak value. The electrodes
effective impulse ground impedance Zeff is defined as
the following formula:[6,7]
The crossover between the curves of the effective
V (3) ground impedance against the rise time of incident
Z eff = max
I current of the 30 m ground rod and the ground grid of
Where Vmax is the peak value of ground rod potential 20 m20 m was observed. In other words, when the
under test and I is the magnitude of the incident rise time of incident current is in the range of less than
impulse current at the time instant when Vmax has been 6 , the effective impulse ground impedance of 30 m
reached, as is shown in Figure 5. ground rod is lower than that of the ground grid of 20
m20 m. On the contrary, when the rise time of
incident current is in the range of above 6 , the REFERENCES
effective impulse ground impedance of 30 m ground [1] IEEE Std 80-2000, IEEE guide foe safety in AC
rod is higher than that of the ground grid of 20 m20 Substation Grounding, The Institute of Electrical and
m. It is considered that the effect of the inductive Electronics Engineers, 2000.
component on the effective impulse ground impedance [2] Bok-Hee Lee, Dong-Cheol Jeong, Su-Bong Lee
is dominant in the short time range. and Keun-Chul Chang, Effective Impulse
In our experimental conditions, the 30 m ground rod is Impedances of Deeply Driven Grounding Electrodes,
relatively less sensitive to the rise time of incident KIEE International Trans on EA, vol. 4-C, no. 5, pp.
current and the ground impedance characteristic 207214, 2004.
against the surge current is stable. However, the [3] S. Karaki, et al, "Transient Impedance of GIS
impulse ground impedance characteristics of the Grounding Grid", IEEE Trans., vol. PD-10, no. 2,
ground grid of 20 m20 m are very changeable in pp.723738, 1995.
short time range. The grounding electrode inductance [4] T. Takahashi, "A Part of Grounding for Lightning
may play an important role in the conduction Protection Technique", J. of the Institute of Electrical
mechanism of the impulse current to the ground. To Installation Engineers of Japan, vol.9, pp.671676,
design the optimal grounding system flowing impulse Sep. 1989.
currents to ground effectively, the reduction of [5] IEEE Std 81.2-1991, IEEE guide for
grounding electrode inductance is just as important as Measurement of Impedance and Safety Characteristics
the static ground resistance. of Large, Extended or Interconnected Grounding
System, IEEE Inc., pp.1731, Dec. 1991.
4 CONCLUSION [6] Z. Stojkovic, M.S. Savic, J.M. Nahman, D.
The impulse ground impedance characteristics against Salamon and B. Bukorovic, "Sensitivity Analysis of
the rise time of injection impulse current were Experimentally Determined Grounding Grid Impulse
experimentally studied, and the apparent soil Characteristics", IEEE Trans., vol. PD-13, no. 4,
resistivity at the test site was measured. As a pp.11361141, Oct. 1998
consequence, the results could be concluded as [7] B. H. Lee, J. S. Park and S. C. Lee, Experimental
follows: Investigations of Transient Impedances of Some
Grounding Systems, 1997 Japan-Korea Joint Syms.
(1) The transient ground impedance characteristics are ED & HVE, pp.237~240, 1997
strongly dependent on the rise time of injection
impulse current and the shape and size of the
grounding electrodes. Bok-Hee Lee
Bok-Hee Lee was born in Korea
(2) The curves of the effective ground impedance on June 29, 1954. He received his
against the rise time of incident current of the 30 m B.S. degree in Electrical
ground rod and the ground grid of 20 m20 m were Engineering from Inha University
crossed over. The grounding electrode inductance in 1980, his M.S. degree in
plays a major role in the dispersion of the impulse Electrical and Electronic
current to the ground. Engineering from Hanyang
University in 1993 and his Ph. D
(3) The transient ground impedance is significantly degree in Electrical Engineering from Inha University in
dependent on the self and mutual inductance of 1997, respectively. He has been with the school of Electrical
grounding electrodes. As a result, the most effective and Electronics Engineering at Inha University, Incheon,
way to obtain the excellent transient ground Korea where he became a Professor in 1999. During 1988 to
impedance behaviors is to determine the optimal 1989, he was a post-doctoral research fellow at the Institute
configuration and size of the grounding electrodes that of Industrial Science, University of Tokyo. From Apr. 1999
reduce the grounding electrode inductance as well as to Feb. 2000, he was a Visiting Professor in the University of
the static ground resistance. Cincinnati. Since Oct. 2002, he has been a Director in the
Research Center for Next-Generation High-voltage and
This work was financially supported by MOCIE Power Technology, Inha University. His research interests
through EIRC program. are in the area of lightning, lightning protection, grounding
systems, surge protection, GIS, gas discharges, high voltage
engineering and electromagnetic compatibility. Tel.
032-860-7398, Fax. 032-863-5822, http://hierc.inha.ac.kr, Hyun-Uk Jung
e-mail: bhlee@inha.ac.kr Hyun-Uk Jung was born in Korea
on May 26, 1978. He received his
B.S. degree in Electrical
Su-Bong Lee Engineering from Inha University
Su-Bong Lee was born in Korea in 2004. . He is currently working
on April 13, 1979. He received his toward a M.S. degree in the
B.S. degree in Electrical Department of Electrical
Engineering from Kyungnam Engineering at Inha University.
University in 1998 and his M.S. His research interests are in the area of grounding, lightning
degree in Electrical Engineering and high voltage engineering.
from Inha University in 2003. He Tel.032-860-8847, Fax.032-866-8836
is currently working toward a Ph. e-mail: uka55577@hotmail.com
D. degree in the Department of Electrical Engineering at
Inha University. His research interests are in the area of
lightning, lightning protection, grounding and high voltage Dong-Cheol Jeong
engineering. Tel. 032-860-8847, Fax. 032-863-5822, Dong-Cheol Jeong was born in
e-mail: lsbong1@naver.com Korea on September 18, 1964. He
received his B.S. degree in
Electrical Engineering from
Tae-hyung Lee Yeungnam University in 1989 and
Tae-hyung Lee was born in Korea his M.S. degree in Electrical
on June 21, 1978. He received his Engineering from Korea
B.S. degree in Electrical University in 2002. . He is
Engineering from Inha University currently working toward a Ph. D.
in 2004. He is currently working candidate in the Department of Electrical Engineering at
toward a M.S. degree in the Inha University. He has been working at Hanjin Heavy
Department of Electrical Industries & construction. His research interests are in the
Engineering at Inha University. area of lightning and high voltage engineering. Tel.
His research interests are in the 032-860-7398, Fax. 032-863-5822,e-mail:
area of grounding, lightning and high voltage engineering. dcjeong2000@korea.com
Tel. 032-860-8847, Fax. 032-866-8836, e-mail:
tanghi@empal.com

Das könnte Ihnen auch gefallen