RELAY (P111)
PAGE :
3. General Inspection : OK
4. Service settings:
TESTED BY WITNESSED BY
TEST REPORT FOR FEEDER PROTECTION SHEET : 2 OF: 6
RELAY (P111)
PAGE :
On 1 On 1 On 1 On 1
TESTED BY WITNESSED BY
TEST REPORT FOR FEEDER PROTECTION SHEET : 3 OF: 6
RELAY (P111)
PAGE :
Phase .Ref Set Current(A) Operating Current (A) Set Time (S) Op. Time (S)
R,Y,B 15.8 15.9 0.20 0.208
TESTED BY WITNESSED BY
TEST REPORT FOR FEEDER PROTECTION SHEET : 4 OF: 6
RELAY (P111)
PAGE :
TESTED BY WITNESSED BY
TEST REPORT FOR FEEDER PROTECTION SHEET : 5 OF: 6
RELAY (P111)
PAGE :
TESTED BY WITNESSED BY
TEST REPORT FOR FEEDER PROTECTION SHEET : 6 OF: 6
RELAY (P111)
PAGE :
7. Comments : Nil.
8. Remarks : Relay found healthy.