Beruflich Dokumente
Kultur Dokumente
1. Introduction
Worldwide, population and economic growth has reduced the distance separating
residential areas and odour sources. Annoyance can result from not only obnoxious odours
but also prolonged pleasant odours such as produced by a chocolate or frying factory.
Odours indirectly affect human health through stress (Evans & Cohens, 1987) and their
impact is greater when humans are exposed to a continuous rather than an intermittent
source. People with a problem coping style (seeking a solution to the odour problem) can
become more annoyed by odours than those using comforting cognition (telling themselves
that the situation will improve) or having an emotional oriented style (those looking for a
diversion) because the solution is often out of hand (Cavalini et al., 1991). Although pleasant
odours can become annoying when too concentrated or persistent, malodours are perceived
as unpleasant under most if not all conditions. Malodours are also known to activate a
different area of the brain, as compared to pleasant odours (Zald & Pardo, 2000). According
to Jacob et al. (2003), the response of humans to malodours is quite consistent and it differs
compared to that of pleasant odours which produce a wider range of response.
Furthermore, Jacob et al. (2003) found that the detection of any odour increases with dose
and duration, but that the change in response of humans is much more important for small
increases of malodour concentrations when presented at a low level just above their
detection threshold.
Accordingly, odour dispersion models must take into consideration the olfactory response
of humans. Noxious odours are likely much easier to model because most humans will
classify them as an annoyance, as opposed to pleasant odours where the response is more
variable. Furthermore, the human olfactory sense will detect the presence of an odour at a
low level and if noxious, will immediately classify it as a nuisance. As the air concentration
of the odorous gas increases, the relative level of annoyance does not increase as quickly.
Furthermore, at a specific odorous gas air concentration, the response becomes intolerable
and increasing the concentration any further will not increase the level of annoyance. To be
accurate, this type of response must be incorporated into an odour dispersion model.
The use of separation or setback distances for odour sources conveniently insures the
dilution of malodours to acceptable levels in the vicinity of neighbours (Redwine & Lacey,
2000). Nevertheless, conventional separation distances rely on the generalized odour
www.intechopen.com
182 Computational Fluid Dynamics Technologies and Applications
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 183
whereas the method used by Lin et al. (2007b, 2009a, b) is designed to measure odour levels
in the vicinity of the threshold values. In determining separation distances, the threshold
values can be most useful.
Windbreaks were suggested in the late 1990s as a possible odour dispersion technique.
Based on Asian research demonstrating the successful reduction of odours, North American
livestock producers have used natural and artificial windbreaks on the fan side of livestock
shelters to reduce odours emissions. The effect of a porous wall was studied by means of
smoke emitters and simulated using a Gaussian model (Bottcher et al., 2000; Bottcher et al.,
2001). The porous wall was found to vertically divert the odours from the exhaust fans and
promote mixing with the wind flowing over the building, but not to be as effective as tall
stacks. In Asia, solid walls have been used around livestock barns to precipitate dust
released by the ventilation system (Bottcher, 2000). Dust has been shown to carry odours
(Das et al., 2004). Such application requires a windbreak with a high porosity capable of
reducing wind velocity and turbulence. The same principle has been applied to control
snow and sand accumulation, reduce pesticide drift, increase crop yield and reduce heat
losses from animals and buildings (Plate, 1971; Heisler & Dewalle, 1988; Wang & Takle,
1997; Ucar & Hall, 2001; Guan et al., 2003; Vigiak et al., 2003; Wilson & Yee, 2003a).
Accordingly, several North American cooperative extension services offer information on
planting natural windbreaks or tree shelter belts, suggesting a high porosity in the absence
of solid scientific testing.
The objective of the present chapter is therefore to present the development of a model
simulating the dispersion of odours or the size of the odour plume formed downwind from
a natural shelter belt or windbreak located at a specific distance from an odour source. The
purpose of the model was to identify the best management practices for the implementation
of natural windbreaks minimizing the size of the odour plume; best management practices
pertain to the properties of the windbreak itself, its location with respect to the odour source
and the general climatic environment for the given region. The model uses Computational
Fluid Dynamics (CFD) to estimate the size and intensity of the odour plume to establish the
necessary separation distance between the source and the neighbouring receptor susceptible
to annoyance. The model development includes the selection of a computational method
capable of handling conditions of high turbulence, the addition of an olfactory perception
equation and finally the output validation.
In summary and with the windbreak dispersion model developed, this Chapter will
examine the features of natural windbreaks which enhance atmospheric dispersion and
maximize the reduction in odour plume length. Finally, this Chapter will examine the effect
of various climatic conditions on the performance of windbreak and their effectiveness in
shortening odour plumes.
www.intechopen.com
184 Computational Fluid Dynamics Technologies and Applications
also varied. In all, 39 different field tests were conducted to obtain data for the calibration
and validation of the model.
Fig. 1. The odour generator carried on a truck to be positioned at specific distances upwind
from the windbreak (Lin et al., 2006)
During each field test and installed on a 7.6 m high tower, a weather station was positioned
200 m upwind from the windbreak to avoid disturbance. At one minute intervals, a
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 185
computer recorded the temperature, wind direction and wind speed. The wind direction
was measured before hand to estimate the range of the field odour plume and to direct
panellists into the odour plume zone. Air stability values were obtained from the weather
station at the Pierre Elliott Trudeau Airport (Montreal, Canada) located 50 km north of the
field sites. This weather station was the nearest measuring Pasquill-Gifford atmospheric
stability conditions.
www.intechopen.com
186 Computational Fluid Dynamics Technologies and Applications
Site 1 one row of mature poplars Site 2 mixed mature deciduous trees
Fig. 2. The four experimental windbreaks each offering a different type of tree and/or
porosity (Lin et al., 2006)
After operating the odour generator for 15 minutes, the groups of panellists would start
covering their specified overlapping zigzagged path and measure the odour plume. At each
measurement point, the group would stop walking, removed their face masks and evaluate
for one minute the hedonic tone (HT) of the ambient air using the scale of 0 to -10. An odour
point was defined as a point in the field where at least 50 % (2 out of 4) of the panellists
detected an odour. The HT of the ambient air at an odour reading point was averaged from
the four panellist evaluations.
During each test day, the odour plume was observed in the morning by 12 trained
panellists. Then, in the afternoon, the same 12 panellists evaluated the air samples collected
at the odour generator using the laboratory olfactometer. This laboratory work served two
purposes: measure the odour concentration (OC in OU m-3) of each odorous air sample, and;
correlate the measured field hedonic tone (HT) observed by the panellists with odour
concentration values. This correlation was then used to translate the HT plumes into OC
plumes.
During 18 days between the end of August and the beginning of December 2003, 39
different tests were conducted on the 4 windbreak sites and the single control site (Lin et al.,
2006). On the control site without a windbreak, 6 repeated tests were conducted on 4
different days. Then, 33 tests were conducted on the 4 windbreak sites. A total of 12, 11, 9
and 1 tests were conducted with the odour generator located 15, 30, 60 and 49 m upwind
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 187
from the windbreak, respectively. Tests on site 4 were conducted in December 2003, because
of delays in finding a suitable windbreak site.
During each test, the odour generator emitted a decreasing odour level and, from one test to
other, the odour level varied. Each odour plume was therefore standardized for purposes of
comparison. Thus, the odour concentration measured at every station by each group of
panellists, at a given period in time, was divided by the odour concentration of the
generator at that time, and multiplied by the average odour level of 471.6 OU m-3 calculated
from all 39 tests.
Description Site
1 2 3 4
Tree type poplar mixed mature conifers conifers
deciduous
Windbreak
- length (m) 2100 1050 405 380
- height (m) 18.3 9.2 7.6 15.2
- depth (m) 7 6
- optical porosity 0.55 0.35 0.55 0.35
(fraction)
- porosity at the base 0.70 0.30 0.70 0.40
(fraction)
www.intechopen.com
188 Computational Fluid Dynamics Technologies and Applications
3. Model development
The Computational Fluid Dynamic used for this modelling was based on the SST k- model
capable of considering a high level of turbulence (Fluent inc., 2005). The model development
respected the following steps: 1) determining the governing equations; 2) meshing the
computational domain; 3) selecting the solver capable of defining the fluid properties and its
components such as the windbreak, and; 4) setting boundary conditions.
+ ( ui ) = 0 (1)
t xi
ui u j 2 u1 u2 u3
ij
xi x j x j xi 3 x1 x2 x3
p
( ui ) = ( ui u j ) + + + +
t x j
(2)
+
x j ( ) 1
ui/u/j + gi ui C ir umag ui
2
( E ) + u j ( E + p ) = keff hi J i + ui ( ij ) eff + Sh
T
x j
(3)
t x j x j i
( Yi ) + ( uYi ) = J i (4)
t
where is fluid density; t is time; ui (i=1, 2, 3, indicating x, y, and z direction) is the mean
velocity u in ith direction; ui is the fluctuating component of the instantaneous velocity; is
fluid viscosity; ij is the unit tensor; p is the static pressure; gi is the gravitational acceleration
constant in the ith direction; is the aerodynamic porosity or permeability of the windbreak;
-1 is the viscous resistance coefficient; Cir is the inertial resistance coefficient caused by the
windbreak; umag is the magnitude of the velocity (Hinge, 1975; Saatjian, 2000); E is the total
energy; keff is the effective thermal conductivity; Sh represents all volumetric heat sources
such as those of chemical reactions; T is temperature, and; (ij)eff is the effective deviatoric
stress tensor.
The coefficients Yi, Ji and hi are the mass fraction, diffusion flux and the sensible enthalpy of
the ith atmospheric species (Bird et al., 2002; Fox & McDonald, 1992). The term ui uj is
called the Reynolds stresses.
In Eq. (4), the diffusion flux Ji of the atmospheric species i, arises due to concentration
gradients. The diffusion flux for turbulent flow is:
t T
J i = ( Di , m + )Yi DT , i (5)
Sct T
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 189
where Yi is mass fraction of the species i; Di,m is the diffusion coefficient for species i in the
mixture; and DT,i is the thermal diffusion coefficient; Sct is the turbulent Schmidt number
generally equal to 0.7, and; t is the turbulent viscosity (Saatjian, 2000; Bird et al., 2002).
0 @ windbreak u 1 dz
H
0 @ inlet u1dz
= H
(7)
The relationship between optical and aerodynamic porosity is defined according to the wind
tunnel measurements of Guan et al. (2003):
= 0.4 (8)
where is the aerodynamic porosity and is the optical porosity. Accordingly, an optical
porosity of 0.35 results in an aerodynamic porosity of 0.66, implying that 66 % and 34 % of
the air flows through and over the windbreak, respectively.
To calibrate and validate the model, the field work in this project observed the effect of tree
types (poplar and deciduous, Fig. 3) and size forming the windbreaks using sites 1, 2 and 3
(Table 1). On site 1, the windbreak consisted of mature deciduous trees offering an averaged
optical porosity of 0.35 but the optical porosity at its base was 0.30 while that over the rest of
its profile was 0.40. Therefore, the inertial resistance Cir was defined as proportional to the
density (1.0 minus its porosity) of the windbreak:
www.intechopen.com
190 Computational Fluid Dynamics Technologies and Applications
w1 h
w1 w2
z z h1
C ir =
w2 w2 w3 ( z h1 )
1
(9)
h1 < z H
H h1
(a) (b)
Fig. 3. The structure of the trees forming the windbreak, where H is the total height;
a) conifer; b) poplar (Lin et al., 2007b)
where z is the coordinate value in the vertical direction; H is the height of the windbreak; h1
is the height at which the porosity of the windbreak changes (0 < h1 < H), and; w1, w2, and
w3 are three constants corresponding to the thickness of the real windbreak, set in the
simulation to allow 66 % of the air to pass through.
For the windbreak on site 2, the averaged optical porosity was 0.35: the optical porosity at
the base was 0.40; that between heights of 3 to 14 m was 0.3, and; above 14 m, the porosity
was gradually increased from 0.3 to 1.0. Therefore Cir was:
w1 h
w1 w2
z z h1
C ir = w2
1
h1 < z h2 (10)
w2 2
w w3
( z h2 ) h2 < z H
H h2
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 191
where w1, w2, and w3 were set at 0.27, 0.39 and 0.05, and; h1, h2 and H were set at 3, 14 and 15
m, respectively. Again, such conditions allowed 66 % of the air to pass through the windbreak.
The windbreak on site 3 offered an average optical porosity of 0.55. Its porosity was
assumed to be 0.7 at a height of 1.0 m, to linearly decrease to 0.47 at a height of 3 m, to
remain constant between the height of 3 to 15 m, and; then, to increase to 1.0 at the tree top.
These conditions produced an average air permeability of 0.79 and a Cir calculated as:
w1
z h1
w2 w1
w1 + ( z h1 ) h1 < z h2
C ir =
h 2 h1
w2
(11)
h2 < z h3
w2
w2 ( z h3 ) h3 < z H
H h3
where w1 and w2 were set at 0.1 and 0.205, and; h1, h2, h3 and H were set at 1, 3, 15 and 18 m,
respectively.
ui u j 2
ui/u/j = t k + t ij
ui
x j xi
+ (12)
3 xi
www.intechopen.com
192 Computational Fluid Dynamics Technologies and Applications
dissipation rate . The SST k- accounts for the principal turbulent shear stress and uses a
cross-diffusion term in the equation to blend both the k- and k- models and to ensure
that the model equations behave appropriately in both the near-wall and far-field zones.
Thus, the SST k- model offers a superior simulation performance as compared to the
individual k- and k- models (Menter et al., 2003).
The Fluent 6.2 steady 3-dimension segregated solver was used to solve the SST k- model
through second and quick orders of discretisation schemes converting the governing
equations into algebraic equations solved numerically while increasing the calculation
accuracy. The second order scheme was used to compute the pressure, the second order
upwind scheme was used to compute odour dispersion and the quick scheme was used to
compute momentum, turbulence kinetic energy, turbulence dissipation rate and energy. The
SIMPLE method was applied to the velocity and pressure coupling (Fluent inc., 2005).
OC g mH2 S
Y2 = (13)
Pa M1
+ OC g mH2 S
RT
where Y2 is the odour mass fraction (OMF) at the odour inlet, or the ratio of the odour mass
to the total air and odour mass in 1.0 m3, dimensionless; Pa is the atmospheric pressure of
101325 Pa at sea level; T is temperature in K; M is the molecular weight of dry air or 0.028966
kg mol-1; R is the universal gas constant or 8.31432J mol-1 K-1 (ASHRAE, 2009); OCg is the
odour source concentration, in OU m-3, and; mH2S is the mass of H2S required to produce one
odour unit, expressed as kg OU-1 and mH2S = 7.0 10-9 kg OU-1 (Blackadar, 1997).
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 193
The modelled fluid was defined using the physical properties of clean dry air and H2S,
including density, specific heat capacity, thermal conductivity, viscosity, mass and thermal
diffusion coefficients for the mixture and individual species. The modelled fluid was
considered incompressible and its density varied with temperature but not with pressure
because of a Mach number under 10 %. The fluid's specific heat capacity, thermal
conductivity and viscosity were calculated using the mass mixing-law and the thermal
diffusion coefficient was calculated using the kinetic-theory (Table 2).
Fig. 4. The computational volume schematics used to predict odour dispersion. In this case,
the z coordinate is magnified 2 times and the windbreak optical porosity is 0.35. The green
bar represents the windbreak and the odour emission surface centre of the odour generator
is located at x = 0, y = 0 and z = 1.562 m
www.intechopen.com
194 Computational Fluid Dynamics Technologies and Applications
u*3 C pT
LMO = (14)
ka gH F
where u* is the friction velocity; ka is the von Karman constant ranging from 0.35 to 0.43 and
usually equal to 0.4; T is the surface temperature; Cp is the specific heat of air; HF is the
vertical heat flux; the air density, and; g is the gravitational acceleration constant (Schnelle,
2000). When the convective heat flux is upward, LMO is negative and the air is unstable.
When the earth absorbs heat energy, the heat flux is negative, LMO is positive and hence the
air is stable. However, when the heat flux is zero, LMO is infinite and the air stability
conditions are neutral.
The vertical profile of the horizontal mean wind velocity is calculated by:
u*
ln
z
hABL / LMO = 0 neutral
k a z0
u*
umag ( z) = ln ln
2
(
( 1 + x ) 1 + x2 )
z
( ) ( )
1 1
+ 2 tan x 2 tan x hABL / LMO < 0 unstable (15)
0
2
( )
k a z0 ( 1 + x 0 ) 1 + x0
2
u* z 5( z z0 )
k ln z + L
a
hABL / LMO > 0 stable
0 MO
16 z 4
1
x = 1
LMO
where (16)
16 z0 4
1
x0 = 1
LMO
(17)
where umag is the magnitude of the horizontal mean wind velocity at height z above the
surface (z z0); z0 is the roughness length of the surface, hABL is the height of the atmospheric
boundary layer, and LMO is the Monin Obukhov length (Panofsky & Dutton, 1984;
Blackadar, 1997; Jacobson, 1999).
Assuming that the potential temperature is equal to the temperature at zs, the vertical
temperature profile T(z) can be calculated as (Panofsky & Dutton, 1984):
d ( z zs ) + T
hABL / LMO = 0 neutral
16 z
hABL / LMO < 0 unstable
1+ 1
T ( z) = d ( z zs ) + Ts 1 + 2
2
a gLMO zs
u* z LMO
ln 2 ln (18)
16 zs
1+ 1
LMO
u*2 z 5( z zs )
d ( z zs ) + Ts 1 + 2
a gLMO zs LMO
ln + hABL / LMO > 0 stable
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 195
where zs is a height of 1.35 m above ground; Ts is the temperature at height zs; g is the
gravitational acceleration constant, and; d is the dry adiabatic lapse rate of 0.01 K m-1.
The vertical turbulence kinetic energy profile within the surface atmospheric layer can be
defined as:
1 2
k( z ) =
2
(
u + v2 + u2 ) (19)
where k(z) is the turbulence kinetic energy (TKE), and; u, v and w are turbulence
components in the x, y, z coordinates.
For neutral conditions, hABL/LMO = 0, TKE linearly decreased with height, and at the top of
the atmospheric boundary layer, equals 20 % of its value at the ground level (Carruthers &
Dyster, 2006). The TKE for neutral condition is:
k( z) = 5.97 u*2TWN
2
(20)
z z0
where TWN = 1 as (21)
h ABL z0
where as = 0.8.
For unstable conditions (hABL/LMO < 0), the TKE is:
k( z) = 5.97 u*2TWN
2
(
+ w*2 0.3 + 0.2TWC
2
) (22)
z z0 3
1
h ABL z0 3
1
w* = u*
ka LMO
(24)
3
k( z) = 5.97 u*2TWN
2
(25)
1
k( z ) 2
( z) = 1
(26)
0.09 4 l
where l is the turbulence length scale set as twice the height of the ground surface roughness
length (2z0) based on a calibration of the horizontal velocity recovery rate downwind from
the windbreak (Schnelle, 2000; Menter, 2003).
www.intechopen.com
196 Computational Fluid Dynamics Technologies and Applications
The parameters defining the surface layer conditions in the SST model, namely z0, LMO, hABL,
u* and Ts are determined according to the simulation conditions. Corresponding to the
physical conditions of the ground surface, z0 was 0.13 m (Lin et al., 2007b). The coefficient
LMO was estimated from the Pasquill atmospheric stability categories. When z0 was 0.13 m,
the average LMO was -20 m for the Pasquill stability category B, and was 20 for the stability
category F (Golder, 1972). The coefficient hABL was designated as the average rural mixing
height for each stability category measured at the weather station. Once z0, LMO and hABL
were determined, u* and Ts were calculated from the temperature and wind velocity
measured at a height of 10 m and using Eqs. (15) and (18), respectively.
Temperature effects were tested under unstable, neutral and stable atmospheric stability
categories, using simulations 10, 11 and 12 with average December 2003 temperatures of
269, 270 and 265 K, and simulations 2, 5 and 8 with average September temperature of 293,
291 and 287 K.
Simulations 13 to 19 tested the effect of the wind direction, measured from the positive x-
axis and set at 0, -15, -30, -45, -60, -75 and -90, respectively. The weather atmospheric
stability category D was assumed and T, LMO, hABL and wind velocity were 291 K, , 2090 m
and 5.4 m s-1, respectively.
The effect of the atmospheric stability was tested twice. Simulations 2, 5 and 8 compared
average values of wind velocity, atmospheric boundary layer height and temperature.
Simulations 4, 20 and 21 were also similar except for their respective stability categories B, D
and F. For these three simulations, wind velocity, hABL and T were set at 3.0 m s-1, 2090 m
and 291 K, respectively, which are mean values for the atmospheric stability categories B, D
and F.
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 197
www.intechopen.com
198 Computational Fluid Dynamics Technologies and Applications
OC =
0 AHT = 0
0.45 AHT (27)
1.3 e 1 AHT 10
OMF
SOMC = mH2 S 10 9 (28)
Y2
OC g
where SOMC is simulated odour (H2S) mass concentration in g m-3; OMF is the odour
(H2S) mass fraction computed by the model for a given point in space, dimensionless; Y2
and OCg are the odour mass fraction and odour concentration at the odour source as
defined by Eq. (28), which are respectively dimensionless and in OU m-3, and; mH2S is the
mass of H2S required to produce 1.0 OU m-3 in kg OU-1 as described by Eq. (28).
Secondly, the SOMC were transformed into SAHT by correlating the 5 field test AHT
(absolute HT readings) with SOMC:
where SAHT is simulated absolute hedonic tone, and; SOMC is defined by Eq. (29). The
field test correlation indicated a statistically significance (P < 0.01) relationship between
AHT and SOMC (Lin et al., 2007b). In this procedure, the odour mass fraction of 506.5 g m-
3 results in AHT of 10 for an OC of 117 OU m-3.
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 199
generator were evaluated for their threshold dilution and hedonic tone by the same 12
panellists in the afternoon using the olfactometer. There was a dual purpose to this exercise:
evaluate the odour concentration (OC) of the sample collected at the odour generator, and;
obtain a correlation between odour concentrations (OC) in OU m-3 and hedonic tones (HT)
measured in the field while sizing the odour plume.
Several interesting aspects can be concluded from Fig. 5: correlation between the odour
concentration (OC) and the hedonic tone (scale of 0 to -10) is quite variable although typical
of panellist response (Edeogn et al., 2001); the present panellist response differs from that of
Lim et al. (2001) and Nimmermark (2006), despite the n-butanol rating of all panellists
before hand, according to standards (ECN, 2001; ASTM 1997a, b).This difference resulted
from culture, tolerance, and previous historical exposure to odorous situations, and; above
the observed OC of 117 OU m-3, the response in HT reached its peak value of -10, explaining
the larger variability in reported OC value.
Fig. 5. Compared to data collected by Lim et al. (2001) and Nimmermark (2006), typical
relationship between hedonic tone (HT) and odour concentration (OC) for the 56 air sample
(minimum, average and maximum) curves (Lin et al., 2007b)
www.intechopen.com
200 Computational Fluid Dynamics Technologies and Applications
The control without a windbreak (field tests 37, 38 and 39 on site 5) is compared (Fig. 6a) to
that of site 2 with a mature deciduous windbreak (field tests 5, 8, 12 and 16, on site 2) and
the odour generator located 30 m upwind (Fig. 6b). The average air temperature was 26.4
and 22.6C, respectively, for the control and windbreak sites. On site 2, the wind direction
ranged between 20 to 90 with respect to the windbreak, 90 being perpendicular. Both
odour plumes were observed in late August and early September under similar landscape
and weather conditions.
Fig. 6. Odour plumes on field sites 2 and 5 with and without a windbreak. (a) without a
windbreak (tests 37, 38 and 39); (b) with windbreak on the site 2 (tests 5, 8, 12 and 16). An
odour concentration of 2 OU m-3 is used to draw the final contour of the odorous zones (Lin
et al., 2006)
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 201
Fig. 6 demonstrates that the plume developed without a windbreak reached a much longer
distance downwind, compared to that developed with the windbreak. Measured furthest
away, the windbreak created an odour zone of 2.0 OU m-3 ending at 500 m away from the
source, compared to the same level of odour extending beyond 550 m for the control site.
Without a windbreak, the control produced an odour plume with a maximum odour peak
of 16 OU m-3 at a distance of 69 m while the windbreak produced a plume with a peak of 50
OU m-3 at a distance of 117 m. Accordingly, the windbreak is observed to concentrate or trap
the odours on its leeward position before further dispersion.
The most significant parameter affecting the length of the odour plume was found to be the
foliage porosity (Fig. 7). Despite the greater tree height on site 1, the more open foliage
(optical porosity of 0.55) produce a longer odour plume covering 150 m in width by 600 m in
length, compared to that of the windbreak on site 2 with a porosity of 0.35, generally
covering a width of also 150 m but a shorter length of 300 m.
Fig. 7. The mean length of the odour plume (LOP) for the 4 field sites with a windbreak and
the single control site without a windbreak; the error bars illustrates the standard error of
1.96 meter (Lin et al., 2007c)
The furthest measured odour concentrations for the windbreak optical porosity of 0.55 and
0.35 had values of 3.2 and 4.0 OU m-3 at a respective distance of 601 and 281 m. However,
the windbreak optical porosity of 0.55 produced a maximum odour peak of 22 OU m-3 at a
distance of 138 m while that with an optical porosity of 0.35 produced a maximum odour
peak of 50 OU m-3 at a distance of 117 m. Again, the smaller odour plume corresponded to a
more intense odour trapping in the leeward position of the windbreak.
In summary and for the field observation, the more open windbreak produce an odour
plume similar to that of the control without a windbreak, likely because a porous windbreak
produces less turbulent energy and therefore less odour mixing and odour dilution,
compared to a denser windbreak. The denser windbreak with a foliage porosity of 0.35 was
www.intechopen.com
202 Computational Fluid Dynamics Technologies and Applications
able to reduce the length of the odour plume by 25 %, as compared to no windbreak, but the
peak odour concentration was several times higher immediately downwind from the
windbreak.
Fig. 8. Comparison of the simulated and measured wind speeds at windbreak half height
where u is the wind speed, u0 is the undisturbed wind speed, and H is the height of the
windbreak (Lin et al., 2007a). The measured wind speed is taken from Eimern et al. (1964)
The model was also validated for odour concentration simulation (Fig. 9). The correlations
between MAHT and SAHT for the 11 tests, as a function of distance from the source, were
found to be statistically significant (P = 0.01), implying that the standard k- model can
accurately predicts odour HT downwind from windbreaks. As illustrated in Figure 5 a, c, e,
and g for tests 2, 5, 7, and 8, the simulated lines are found in the centre of the range of
MAHT, which is a good indication that the model can reproduce the observations.
Depending on the test, the R2 value ranged between 0.48 and 0.90. If all values within 150 m
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 203
of the windbreak are excluded to remove the odour puff effect, then R2 exceeds 0.75 for all
simulations.
Fig. 9. For the field tests 2, 5 , 7 and 8, a, c, e, g give the measured and simulated absolute
hedonic tone where AHT is the absolute hedonic ton, MAHT and SAHT are the measured
and simulated hedonic tone, respectively, R2 is the correlation coefficient between the
MAHT and SAHT and n is odour points measured; b, d, f, h give the measured and
simulated odour concentration where OC is odour concentration, MOC and SOC are
respective measured and simulated OC, and R2 is the correlation coefficient between MOC
and SOC. The x axis indicates the distance from the odour source (Lin et al., 2009a)
www.intechopen.com
204 Computational Fluid Dynamics Technologies and Applications
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 205
When the odour is released from a building ventilated naturally, the windbreak should be
positioned at least 24 m away, a condition which does not necessarily optimise odour
dispersion.
Fig. 10. Contours of the odour plume (z = 1.5 m) for an aerodynamic porosity of (a) 0.2, (b)
0.4 and (c) 0.66, respectively. The green bar is the windbreak and the unit of the odour
concentration is OU m-3 (Lin et al., 2009a)
www.intechopen.com
206 Computational Fluid Dynamics Technologies and Applications
represents the degree of air convection or air movement in the vertical direction. It can
compete against wind and it defines air temperature gradient with height. Accordingly and
when simulating the effect of the main climatic factors of wind velocity and air temperature,
atmospheric stability must be examined in parallel.
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 207
then F, because Categories B and F generally exhibit lower wind speeds compared to
Category D.
Fig. 11. Effect of wind velocity for: upper) unstable atmosphere for wind velocities of (a) 1.0
m s-1; (b) 1.8 m s-1 , and; (c) 3 m s-1 ; lower) neutral atmosphere for wind velocities (a) 3 m s-1;
(b) 5.4 m s-1 , and; (c) 6.4 m s-1. The green bar is the windbreak; the odour concentration is in
OU m-3 (Lin et al., 2009b)
www.intechopen.com
208 Computational Fluid Dynamics Technologies and Applications
Fig. 12. Effect of wind direction on the odour plume for an horizontal plane at z = 1.5 m,
when the wind direction from the positive x-axis is (a) 0; (b) 15; (c) 30, and; (d) 45. The
green bar is the windbreak (Lin et al., 2009b)
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 209
For the same atmospheric boundary layer height, and wind velocity and air temperature at
a height of 10 m, but for Stability Categories B, D and F, odour plumes measured in length
267, 272 and 253 m, respectively because of a different typical profile for wind velocity,
temperature and turbulence. The turbulent kinetic energy on the upwind side of the
windbreak decreases from Stability Category B, to that of D and then F but then increases in
the opposite order on the downwind side of the windbreak, thus shortening the odour
plume (Lin et al., 2007b).
For Stability Categories B, D and F, the vertical wind velocity profile was different for 3 m s-1
at a 10 m height. Stability Category B produced a profile slightly smaller than that obtained
with Category D, but for Categories B and D, the profile was much smaller than that for
Category F.
For a temperature of 291 K at a 10 m height, the vertical temperature profile was quite
different for Stability Categories D, B and F. For Stability Category D (neutral conditions),
this profile decreased with height at a rate 0.01 K m-1, but for that of B (unstable conditions),
it dropped much faster over a height of 0 to 10 m and then deceases at a slower rate but still
faster than that obtained with Stability Category D. The temperature profile for Stability
Category F (stable conditions) increased with height and produced the inverse of stable
effects. Because Stability Category F produced larger profile differences for wind velocity
and temperature, between heights of 0 and 73.6 m in the computational domain, compared
to D and B, the resulting odour plume was shorter.
Generally, the odour plume length for neutral atmospheric conditions (Category D) was
shorter than that for unstable (Category B) and stable conditions (Category F), because of the
corresponding different wind velocity. However, when all the conditions were the same
except for atmospheric stability conditions, Category F produced a slightly shorter odour
plume compared to that under neutral and unstable conditions.
5. Conclusions
The objective of the project was to develop a model from the Computational Fluid Dynamics
method based on SST k- computations (Fluent inc., 2005) to simulate odour dispersion
around windbreaks and then to use this validated model to observe the effect on odour
plume size of windbreak characteristics and climatic factors. The model was calibrated for
odour dispersion using field data measured by panellists.
www.intechopen.com
210 Computational Fluid Dynamics Technologies and Applications
6. Nomenclature
AHT is absolute hedonic tone
AS is atmospheric stability
as is a factor involved in determining TKE
Cir is the inertial resistance coefficient
Cir0 is the constant
Cp is specific heat of air
D1 and D2 are the tree diameters
Di,m is the diffusion coefficient for species i in the gaseous mixture
DT,i is the thermal diffusion coefficient for species i in the gaseous mixture
DWO is the distance between the windbreak and the odour source
E is the total energy
Fi is the resistance to wind flow
g is acceleration of gravity
gi is the component of the gravitational vector in the ith direction
H is the total height of the windbreak
HF is the vertical heat flux
hi is the height at which the rate of the gradient of the tree diameter changed at the ith height
hABL is the height of the atmospheric boundary layer
Hi is the sensible enthalpy of ith species
HT is the odour hedonic tone
Ji is the diffusion flux of species i
ka is the van Karman constant ranging from 0.35 to 0.43, and n9ormally equal to 0.4
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 211
www.intechopen.com
212 Computational Fluid Dynamics Technologies and Applications
7. Acknowledgment
The authors wish to acknowledge the financial contribution of Consumaj inc., CDAQ, the
Livestock Initiative Program, Agriculture and Agro-Food Canada and the Natural Sciences
and Engineering Research Council of Canada.
8. References
ASHRAE. (2009). Handbook of Fundamentals. American Society of Heating, Refrigeration and
Air Conditioning, Atlanta, Georgia, U.S.A, pp.13.1-13.6.
ASTM (1997a). Standard Practice for Defining and Calculating Individual and Group Sensory
Thresholds from Forced-Choice Data Sets of Intermediate Size. E1432-91. West
Conshohocken, PA, American Standards of Testing and Measurement
International.
ASTM (1997b). Standard Practice for Determination of Odour and Taste Thresholds by a Forced-
Choice Ascending Concentration Series Method of Limits. E679-91. West Conshohocken,
PA, American Standards of Testing and Measurement International.
ASTM (1999). Standard practice for referencing supra-threshold odour intensity. E544-75.
Philadelphia, Pa, USA, American Standards of Testing and Measurement
International.
Bird, R.B.; Stewart, W.E & Lightfoot, E.N. (2002). Transport phenomena. John Wiley, New
York, USA.
Blackadar, A.C. (1997). Turbulence and diffusion in the atmosphere: lectures in environmental
sciences. Springer Berlin Publishers, New York, USA.
Bottcher, R.W.; Munilla, R.D.; Baughman, G.R. & Keener, K. M. (2000). Designs for
windbreak walls for mitigating dust and odour emissions from tunnel ventilated
swine buildings. In: Swine Housing, Proc. of the 1st International Conference, Oct. 9-11,
2000, Des Moines, Iowa. American Society of Agricultural Engineers, 2950 Niles
road, St. Joseph, Mi. USA. pp. 174-181.
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 213
Bottcher, R.W.; Munilla, R.D.; Keener, K.M. & Gates, R.S. (2001). Dispersion of livestock
building ventilation using windbreaks and ducts. 2001 ASAE Annual International
Meeting,paper 01-4071. 2950 Niles Road, St. Joseph, Mi. USA.
Carruthers, D.J. & Dyster, S.G. (2006). Boundary layer structure specification. ADMS 3
P09/01T/03 http://www.cerc.co.uk/software/pubs/3-1techspec.htm visited in
April 2006.
Cavalini, P. M.; Koeter-Kemmerling, L. G. & Pulles, M. P. J. (1991). Coping with odour
annoyance and odour concentratioons: three field studies. Journal of Environmental
Psychology, Vol. 11, pp.123-142.
CEN (2001). Air quality - determination of odour concentration by dynamic olfactometry.
prEN13725. 36 rue de Stassart, B-1050 Brussels, European Committee for
Standardization.
Chen, Y. C.; Bundy, D. S.; Hoff, S. (1998). Development of a model of dispersion parameters
for odour transmission from agricultural sources. Journal of Agricultural Engineering
Research, Vol. 69,pp. 229-238.
Choinire, D. & Barrington, S. (1998). The conception of an automated dynamic
olfactometer. CSAE/SCGR paper 98-208. Winnipeg, Manitoba, Canada.
Das, K.C.; Kastner, J.R.& Hassan, S.M. (2004). Potential of particulate matter as a pathway
for odour dispersion. ASAE paper 04-4125. American Society of Agricultural
Engineering, St Joseph, Michigan, USA.
Edeogn, I.; Feddes, J.J.R.; Qu, G.; Coleman, R. & Leonard, J. (2001). Odour measurement and
emissions from pig manure treatment/storage systems. Final report, University of
Alberta, Edmonton, Canada.
Eimern, J.V.; Karschon, R.; Razumova, L.A. & Robertson, G.W. (1964).Windbreak and shelter
belts. Report of a working group of the Commission for Agricultural Meteorology,
World Meteorological Organization, Technical note 59, Secretariat of the World
Meteorological Organization, Geneva, Switzerland.
Evans, G. W. & Cohen, S. (1987). Environmental stress. In D. Stokols & I. Altman Eds.,
Handbook of Environmental Psychology, New York: Wiley, pp. 571-610.
Fluent inc. (2005). Fluent 6.2 user's guide. Fluent Inc., Centerra Resource Park, Lebanon, NH,
USA.
Fox, R.W. & McDonald, A.T. (1992). Introduction to fluid mechanics. John Wiley, New York,
USA.
Gassman, P. W. (1993). Simulation of odour transport: A review. ASAE Paper 92-4517. St
Joseph, Michigan, USA, American Society of Agricultural Engineering.
Golder, D. (1972). Relations among stability parameters in the surface layer. Boundary-Layer
Meteorology, Vol. 3, pp.47.
Guan, D.; Zhang, Y. & Zhu, T. (2003). A wind-tunnel study of windbreak drag. Agriculture,
Ecosystem & Environment, Vol. 118, pp.75-84.
Guo, Y.; Jacobson, L. D.; Schmidt, D. R. & Nicolai, R. E. (2001). Calibrating INPUFF-2 model
by resident-panellists for long-distance odour dispersion from animal production
sites. Transactions of the ASAE, Vol. 17, pp.859-868.
Heisler, G.M. & Dewalle, D.R. (1988). Effects of windbreak structure on wind flow.
Agriculture, Ecosystems and Environment. Vol. 22-23, pp.41-69.
Hinze, J.O., 1975. Turbulence, McGraw-Hill, New York, USA.
www.intechopen.com
214 Computational Fluid Dynamics Technologies and Applications
Jacob, T. J. C.; Fraser, C.; Wang, L.; Walker, V. & OConnor, S. O. (2003) Psychophysical
evaluation of responses to pleasant and mal-odour stimulation in human subjects;
adaptation, dose response and gender differences. International Journal of
Psychophysiology, Vol. 48, pp.67-80.
Jacobson, L. D.; Guo, H.; Schmidt, D. R.; Nicolai, R .E.; Zhu, J. & Janni, K. A. (2005).
Development of the OFFSET model for determination of odour annoyance free
setback distances from animal production sites: Part I. Review and experiment.
Transactions of the ASAE, Vol. 48, pp.2259-2268.
Jacobson, M.Z. (1999). Fundamentals of atmospheric modeling. Cambridge University Press,
Cambridge, UK.
Le, P. D.; Aarmink, A. J. A.; Ogink, N. W. M. & Verstegen, M.W. A. (2005). Effect of
environmental factors on odour emission from pig manure. Transactions of the
ASAE, Vol. 48, pp.757-765.
Li ,Y. & Guo, H. (2008). Evaluating the effect of computational time steps on livestock odour
dispersion using a CDF model. Transcations of the ASABE, Vol. 50, pp.2199-2204.
Lim, T.T.; Heber, A.J.;Ni, J.Q.; Sutton, A.L. Sutton & Kelly, D.T.(2001). Characteristics and
emission rates of odour from swine nursery buildings. ASBE Transactions, Vol. 44,
pp. 1275-1282.
Lin, X.-J.; Barrington, S.; Nicell, J. & Choinire, D. (2009). Evaluation of standard k- model
for the simulation of odour dispersion downwind from windbreaks. Canadian
Journal of Civil Engineering. Vol. 36, pp. 895-910.
Lin, X.J.; Choinire, D. & Prasher, S. & Barrington, S. (2009b). Effect of weather on
windbreak odour dispersion. Journal of Wind Engineering and Industrial
Aerodynamics, Vol 97, pp.487-496. ISSN: 0167-6105.
Lin, X.-J.; Nicell ,J.; Choinire, D.; Vzina, A. & Barrington, S. ( 2006). Field odour dispersion
plume produced by different natural windbreaks. Journal of Agriculture, Ecosystems
& Environment, Vol. 116, pp. 263-272. ISSN: 0167-8809.
Lin, X.-J.; Nicell, J.; Choinire, D. & Barrington, S. (2007b). Simulation of the effect of
windbreak characteristics on odour dispersion. Biosystems Engineering, Vol. 98, pp.
347-363. ISSN: 1537-5110.
Lin, X.-J.; Nicell, J.; Choinire, D. & Barrington, S. (2007c). Effect of natural windbreaks on
maximum odour dispersion distance. Journal of Canadian Biosystems Engineering,
Vol. 49, pp.6.21-6.32.
Lin, X.-J.; Nicelle, J.; Choinire, D. & Barrington, S. ( 2007a). Livestock odour dispersion as
affected by natural windbreaks. Journal of Soil, Water and Air Pollution, Vol 182,
pp.263-273.
McPhail, S. (1991). Modeling the dispersion of agricultural odours . Proceedings of a workshop
on agricultural odours. Toowoomba, Queensland, Australia. AMLRDC Report No.
DAQ 64/7. Feedlot Services Group, Queensland Department of Primary Industries.
Toowoomba, Queensland, Australia.
Menter, R.R.; Kuntz, M. & Langtry, R. (2003). Ten years of industrial experience with the SST
turbulence model. In: K. Hanjalic, Y. Nagano and M. Tummers (Editors),
Turbulence, Heat and Mass Transfer 4. Begell House Inc, Redding, CT, pp.625-632.
Nimmermark, S. (2006). Characterization of odour from livestock and poultry operation by the
hedonic tone. Paper number 064157. In: ASABE Annual International Meeting,
www.intechopen.com
Simulating Odour Dispersion about Natural Windbreaks 215
www.intechopen.com
216 Computational Fluid Dynamics Technologies and Applications
Wilson, J.D. (2004). Oblique, stratified winds about a shelter fence. Part II: Comparison of
measurements with numerical models. Journal of Applied Meteorology, Vol. 43,
pp.1392-1409.
Xing, Y.; Guo, Y.; Feddes, J. & Shewchuck, S. (2006). Evaluation of air dispersion models
using swine odour plume measurement data. CSAE Paper 06-172. Canadian Society
of Agricultural Engineering, Winnipeg, Manitoba, Canada.
Zald, D. H. & Pardo, J. V. (2000). Functional neuroimaging of the olfactory system in
humans. International Journal of Psychophysiology, Vol. 36, pp.1165-1181.
Zhang, Q.; Feddes, J.; Edeogu, I.; Nyachoti, M.; House, J.; Small, D.; Liu, C.; Mann, D. &
Clark, G. (2002). Odour production, evaluation and control. Manitoba Livestock
manure Management Initiative Inc., Winnipeg, Manitoba, Canada.
Zhang, Q.; Zhou, X. J.; Cicek, N. & Tenuta, M. (2007). Measurement of odour and
greenhouse gas emissions in two swine farrowing operations. Canadian Biosystems
Engineering, Vol. 49, pp.6.13-6.20.
Zhu, J.; Jacobson, L. D.; Schmidt, D. R. & Nicolai, R. (2000). Evaluation of INPUFF-2 model
for predicting downwind odours from animal production facilities. Applied
Engineering in Agriculture, Vol. 16, pp.159-164.
www.intechopen.com
Computational Fluid Dynamics Technologies and Applications
Edited by Prof. Igor Minin
ISBN 978-953-307-169-5
Hard cover, 396 pages
Publisher InTech
Published online 05, July, 2011
Published in print edition July, 2011
This book is planned to publish with an objective to provide a state-of-art reference book in the area of
computational fluid dynamics for CFD engineers, scientists, applied physicists and post-graduate students.
Also the aim of the book is the continuous and timely dissemination of new and innovative CFD research and
developments. This reference book is a collection of 14 chapters characterized in 4 parts: modern principles of
CFD, CFD in physics, industrial and in castle. This book provides a comprehensive overview of the
computational experiment technology, numerical simulation of the hydrodynamics and heat transfer processes
in a two dimensional gas, application of lattice Boltzmann method in heat transfer and fluid flow, etc. Several
interesting applications area are also discusses in the book like underwater vehicle propeller, the flow behavior
in gas-cooled nuclear reactors, simulation odour dispersion around windbreaks and so on.
How to reference
In order to correctly reference this scholarly work, feel free to copy and paste the following:
Barrington Suzelle, Lin Xing Jun and Choiniere Denis (2011). Simulating Odour Dispersion about Natural
Windbreaks, Computational Fluid Dynamics Technologies and Applications, Prof. Igor Minin (Ed.), ISBN: 978-
953-307-169-5, InTech, Available from: http://www.intechopen.com/books/computational-fluid-dynamics-
technologies-and-applications/simulating-odour-dispersion-about-natural-windbreaks