Sie sind auf Seite 1von 37

IFEX 3000 Impulse Fire Extinguishing Technology

IF 3001/72

Manual
Fire Extinguishing Unit With Hose Reel

1. Impulse Gun IFEX 3001 Serial-n:______________

2. Water container IFEX 3072 Fabr.-n:______________

IFEX Technologies GmbH, Hansestr.18, D-27419 Sittensen


Telephone: +49 (0) 4282 93060 Fax: +49 (0) 4282 93026 Edition
Homepage: www.ifextechnologies.com
e-mail: info@ifextechnologies.com 3012-E-10/01-20.11.12
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |2

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Table of contents
Safety Regulations ..................................................................................................................... 4
Labelling ................................................................................................................................... 5

Instruction for use and operation ................................................................................................. 6


A. Preparation..................................................................................................................... 6
B. Use and operation........................................................................................................... 6
C. After use of the IFEX Impulse Gun and trolley ................................................................... 7

Test and filling instructions .......................................................................................................... 7


1. Testing of the equipment .................................................................................................. 8
2. Testing of the IFEX 3001 Impulse Gun .............................................................................. 9
3. Testing of the hose reel.................................................................................................... 9
4. Check the water container and the mounted fittings .......................................................... 10
5. Testing of the water and air pressure hoses including couplings etc. .................................. 10
6. Testing of the container.................................................................................................. 11
7. Filling instruction water and air pressure .......................................................................... 13

Machinery and tools for maintenance ......................................................................................... 14

Technical drawings .................................................................................................................. 15


1. Impulse Gun IFEX 3001, assembly ................................................................................. 15
2. IFEX 3072 Hose reel fire extinguishing unit, complete ....................................................... 16
3. Hose reel, assembly (1) ................................................................................................. 17
4. Hose reel, assembly (2) ................................................................................................. 18
5. Mounting rack with sledge, assembly .............................................................................. 19
6. Top Filling unit and filter, IFEX 3001/72 ........................................................................... 20

Maintenance and test certification .............................................................................................. 21

Appendix A/ Tests ...................................................................................................................... 1


1. Testing the extinguishing agent container (by an expert) ....................................................... 1
2. Testing the air pressure container of the Impulse Gun (by an expert) ..................................... 1
3. Tests according to national regulations for extinguishing agent container 72l ......................... 2
4. Tests according to national regulations for air pressure chamber of Impulse Gun .................... 3

Page | 2
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |3

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Appendix B/ fitting and maintenance ............................................................................................ 1


1. Introduction ..................................................................................................................... 1
2. Routine maintenance ....................................................................................................... 2
3. Operation of the drum brakes ........................................................................................... 2
4. Brake adjustment ............................................................................................................ 2
5. Rewind problems............................................................................................................. 2
6. Leaky rotating swing joint- 3/4 water................................................................................. 3

Technical drawings .................................................................................................................... 4


1. Sliding skid, support for air cylinders ................................................................................. 4
2. Sliding skid, base frame ................................................................................................... 5
3. Water connection at hose reel .......................................................................................... 6
4. Air connection at hose reel ............................................................................................... 7

In addition: TV certificate, declaration of conformity, warranty.

Page | 3
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |4

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Safety Regulations

BEFORE USE OF THE IFEX GUN AND HOSE REEL


PLEASE READ THE INSTRUCTION MANUAL
CAREFULLY!

NEVER AIM AT ANIMALS OR HUMAN BEINGS. MINIMUM SAFETY


DISTANCE IS 6 METERS.

BEWARE OF ELECTRICAL UNITS.


USE ONLY UP TO 1000 V;
MINIMUM SAFETY DISTANCE 1 METER.

CAUTION!

IFEX TECHNOLOGIES GMBH IS NOT RESPONSIBLE FOR ANY


DAMAGE TO ANIMALS, HUMAN BEINGS OR MATERIAL CAUSED
BY WRONG OR IRRESPONSIBLE USE
AND OPERATION OF THE IFEX 3000 IMPULSE FIRE
EXTINGUISHING EQUIPMENT.

IFEX 3000 PRODUCTS ARE DESIGNED


FOR FIRE FIGHTING PURPOSES ONLY

Page| 4
Labelling

FIRE EXTINGUISHER
72 LITERS WATER
2 x 34 A

1. OPEN 2. OPEN
CYLINDER WATER
VALVE VALVE

3. RELEASE 4. PULL
TRIGGER TRIGGER TO
LOCK OPERATE
GUN

Attention
Operation by trained personal only!
Safety distance to human beings 6 meters!
Be careful at electrical devices. Up to 1000V only!
Minimum distance 1 meter.
Follow instructions of manufacturer.

AFTER USE ALWAYS RECHARGE AND KEEP READY FOR OPERATION!


THE FIRE EXTINGUISHER NEEDS TO BE TESTED ONCE A YEAR.
TO BE USED WITH RECOMMENDED FIRE EXTINGUISHER
AGENTS OR ADDITIVES ONLY.

Fire extinguishing agent: Temperature range: +5 C bis + 60 C


72 Liters Water with 36 ml PL-2/94 N of approval: P 3-6/99
Propellant: 2x6Liters Compr. air 200 bar Type: IFEX 3001/72

IFEX Technologies GmbH, Hansestr. 18, D-27419 Sittensen, Germany


IFEX 3000
Telephone: +49(0)4282 93060 Telefax: +49(0)4282 930626

Page | 5
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |6

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Instruction for use and operation

A. Preparation

1. Fill the water cylinder with extinguishing agent as described in para 7.1 of the
filling instructions.
2. Fill the air pressure cylinder with air as described in
Para 7.2 of the filling instructions.
3. The unit will be ready for operation as described in para 8 of the test and
filling instructions.
4. Put on personal safety wear and breathing apparatus as per standard
safety regulations.

B. Use and operation

1. Loose the connections of the gun at the vehicle.


2. Take the IFEX Impulse Gun, and put the strap around the shoulder.
3. Adjust the shoulder strap.
4. Hold the gun upwards at an appr. 30o vertical angle.
5. Check whether the water valve is closed.
6. Unwind the hose from the hose reel. (unlock safety catch)
7. Slowly open the air pressure cylinder valves at both air cylinders.
There will be 6 bar pressure on the water container and the water hose, and
25 bar pressure on the gun.

Note: The pressure gauge at the pressure regulator only shows the approximate
filling pressure of the air cylinder.

8. Further hold the gun upwards at an 30 vertical angle. Open the water valve.
The gun is filled, when small amounts of water spray through the splitted rubber
diaphragm of the gun. Close the water valve. Adjust the safety catch on the gun.

The Impulse Gun is ready for use.

Page| 6
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |7

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

10. Please note:


The Impulse-technology achieves a very high velocity in that water is shot from the gun
at a high speed. This leads to a short but powerful recoil of the gun. In order to minimize
this recoil it is advisory to move the gun forwards while shooting and to bend your
body forwards with your legs in a so-called walking position. Always aim slightly below
the aligned target. Pull the trigger evenly and let go immediately after the shot. The air
pressure will be refilled automatically within 3 seconds. Open the water valve and
repeat the extinguishing process as before. The most effective short range is between 1
and 10 meters. The total shot range is 16 meters.

11. When well trained in using the gun and if rapid shooting is required, simply let the
water valve open and shoot when the gun is filled. Use the refilling time to
consider where to place the next shot. For the extinguishing of smaller fires the
gun can be filled with smaller amounts of water simply by opening the water
valve for shorter periods or through a faster shooting sequence.

12. Regular training and exercise with the IFEX 3000 Impulse fire extinguishing equipment
will result in maximum fire extinguishing efficiency, reducing the time needed extinguish
fires and the amount of water used.

C. After use of the IFEX Impulse Gun and trolley

1. Close the water valve and empty the water chamber.


2. Close the air pressure cylinder valve.
3. Empty the gun by pulling the trigger repeatedly until the remaining air has left
the hoses and the gun.
4. Secure the gun by turning of the safety catch at the trigger.
5. Put the gun in the designated holder and fix it with the strap.
6. Use the rewind mechanism to roll the hose back onto the hose reel.
7. Empty the extinguishing agent container from air pressure by opening
the pressure relief valve.
8. Refill the water cylinder with fire extinguishing agent as per para 7.1 and the air
pressure cylinders as per para 7.2 of the filling instruction

Test and filling instructions

Please note carefully:


These test and filling instructions describe the standard rules for testing and maintenance by
the user of the mobile IFEX 3000 Impulse fire fighting equipment. Maintenance should be
carried out as per DIN 14406, part 4, latest edition.

Page | 7
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |8

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

WARNING!

Before testing of the IFEX 3000 Impulse fire extinguishing equipment:

1. Make sure the air pressure valve is closed.


2. Use the drain valve at the water container to release remaining pressure
3. Make sure there is no remaining pressure in the IFEX Gun or hose. This is done
by triggering the gun repeatedly until the remaining air in the hoses and the gun
is evacuated.

Caution!

Put on the gun according to the user manual as there may be a recoil due to the
remaining air in the gun.

1. Testing of the equipment


To ensure the perfect functioning of the equipment it is required to have it tested
by an expert at least once a year. The periods between testing of the equipment may
need to be reduced if this is required by local regulations.

1.1 Visual testing


Test the equipment's general condition (cleanliness, condition of the fittings, the
hoses, the water container, the pressure containers, the safety equipment, the gun,
the hose connections, the hose reel with safety catch, sledge mounting, the inscriptions
of the air cylinders). Equipment and fittings which are damaged will
need to be replaced immediately.

1.2 Spare parts


Use certified spare parts only. IFEX-original parts are certified.

1.3 Testing of the fire fighting equipment


according to the testing regulations for "IFEX 3072 Impulse fire fighting equipment".

1.4 Preparation
Before use of the fire fighting equipment IFEX 3072 according to the filling
instructions for "IFEX 3072 Impulse fire fighting equipment" as per para 8.0.

Page | 8
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation Page |9

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

2. Testing of the IFEX 3001 Impulse Gun


Caution - note warning on page 8.

2.1 Disconnect the air pressure and water hose from the gun.
2.2 Check the shoulder strap for damage.
2.3 Check the screws at the front and back strap connections.
2.4 Check the membrane at the barrel end for damage.
(The membrane has 6 incisions from the inside to the outer side, ending appr.
6 mm from the outer side).
2.5 Check the screwed cap on top of the membrane, if necessary tighten it with the
special tool.
2.6 Check the front handle for tightness, if necessary tighten with wrench KS 13.
2.7 Check the water connection at the gun and the water coupling for damage
and cleanliness.
2.8 Check the water valve for external damage and condition of operation of valve.
2.9 Check the stability of the handle at the gun (key KS 3) as the operational
condition of the mechanism for operation.
2.10 Check the air pressure connection at the gun handle for damage and cleanliness.

3. Testing of the hose reel


Caution - note warning on page 8.

3.1 Check the hose reel and hose line for damage and corrosion.
3.2 Check the tightness of the fixing screws (hose reel to sledge).
3.3 Check the tightness of the fixing screws (mounting unit to vehicle).
3.4 Check the rewind mechanism.
3.5 Check the ease with which the hose reel can be turned. If necessary grease where
needed.(see Appendix B Installation, maintenance of the hose reel)
3.6 Check the air pressure connection coupling visually.
3.7 Check the hose reel water supply connection visually.
3.8 Check whether the instruction sticker is readable. (inscription as per DIN EN 3 Part 5)
3.9 Maintenance corresponding to Appendix B Installation, maintenance of the hose reel.

Page | 9
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation P a g e | 10

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

4. Check the water container and the mounted fittings


Caution - note warning on page 8.

4.1 Disconnect all water and air hoses from the container, and check the couplings.
4.2 Remove the air pressure bottles from the holders, check straps for damage.
4.3 Check the water container for external damage, scratches in the paint and corrosion.
4.4 Check the water connection and the fittings at the container and the couplings
for damage.
4.5 Check the air pressure connection and the fittings at the container and the
couplings for damage.
4.6 Check the manometer for damage.
4.7 Remove the filling unit from the container by turning the handle anti-clockwise.
4.7.1 Check the filling unit for damage.
4.7.2 Check the screw-in thread and the o-ring sealing for damage.
4.7.3 Check the reducing valve and spindle thread for damage.
4.7.4 Check the safety valve for damage.
4.7.5 Check the safety thread at the handle for tightness (KS13).
4.8 Empty the water container and check the inside visually.
4.9 Check the type plate and instruction sticker for damage and readability.
4.10 Demount the filters (KS 21), and check for damage .(Filters are optional equipment).
4.11 Check the fixing of the water container on the sledge.

Reminder:
1. All couplings, threads and other parts of the extinguishing unit need to be
checked for cleanliness, and cleaned if necessary!
2. All parts which are demounted for testing need to be re-installed expertly.
3. After re-installation of all parts and re-connection of the water connection
the safety valve needs to be checked. Fill the container with water and air
pressure. The valve requires 6 bar +10% tolerance (6,6 bar). If the safety
valve opens before reaching 6,0 bar, or if it fails to open at 6,6 bar you
will need to exchange it.

5. Testing of the water and air pressure hoses including couplings etc.
Caution- note warning on page 8.

5.1 Water hoses:


a) Water hose from the Impulse-gun to the delta connector.
b) Co-axial water hose (with air pressure hose inside),
both ends, each with a delta connector.
c) Connection of water hose to delta connection in the hose reel
Check the water hoses visually for damage.
Check the couplings at the hoses and the hoses for damage and cleanliness.
Page | 10
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation P a g e | 11

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Check delta connector plus screws for damage and cleanliness, and check safety
screw for tightness (key KS3).

5.2 Pressure hoses:


a) Pressure hose from the delta connector to the Impulse-gun.
b) Pressure hose between the two delta connectors (this hose floats in the
water hose).
c) Pressure hoses from the pressure regulators to the hose reel.
d) Pressure hose from the hose reel to the delta connectors (inside the reel).
Check the pressure hoses visually for damage and cleanliness.
Check the couplings at the hoses and the hose swaging sockets for damage and
cleanliness.

CAUTION!

The pressure hose in the water hose can only be checked for function while
in operational condition through triggering of the gun.

5.3 -.Testing of the pressure hose para 5.2 b) between the two delta connectors
The pressure hose between the two delta connectors needs to be demounted
every 5 years. Then remove the air connector piece and pull the air pressure
hose out of the water hose.
Check the hose visually for damage.
Check the connecting pieces, threads and sealings for damage.

6. Testing of the container

The air pressure container needs to be checked for


- national pressure cylinder regulations.
- cylinder valve for damage,
- external damage,
- air pressure of the container checked per test manometer,
- the check-up needs to done as follows:
1. Make sure the cylinder valve is closed:
2. Remove the pressure regulator from the bottle, fit test manometer and slowly open
the valve and read the pressure: IFEX 3072 = 6 l./200 bar, Minimum pressure
180 bar/+20C, if less, refill.

Page | 11
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation P a g e | 12

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Note: The pressure meter at the pressure regulator shows the approximate filling
pressure of the pressure bottle.

6.1 Pressure regulator


Remove the pressure regulator from the pressure bottle valve (if not already done
as per 6.1 )
- Check the manometer glass for damage and cleanliness
- Check the couplings and thread for damage and cleanliness
Note the technical regulations TRB 502, TRB 532 and TRB 700.
Note the technical regulations TRB 502, TRB 532 and TRB 700.

6.2 Testing the fire extinguishing agent container


The fire extinguishing agent container needs to be tested by a competent person
according to Directive 2009/104/EC and national regulations.
Note appendix A, page 1, para 1.1.
Note the technical regulations TRB 502, TRB 532 and TRB 700.

6.3 Testing the air pressure container on the gun


The air pressure container needs to be tested by a competent person according to
Directive 2009/104/EC and national regulations.
Note appendix A, page 1, para 1.2.
Note the technical regulations TRB 502, TRB 532 and TRB 700.

6.4 Maintenance label:


Maintenance dates need to be entered on the label, which should not obstruct
any prints of the manufacturer.
Note DIN 14406-4 latest edition.

The Maintenance/Testing needs to be confirmed on page 20


"Maintenance record" of the manual.

Deficiencies will have to be repaired and faulty or deficient parts exchanged.


Only use original parts, note para 1.1 and 1.2.

After complete examination of the entire IFEX- Fire Extinguishing Unit


return the unit to operability according to page 13.

Page | 12
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation P a g e | 13

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

7. Filling instruction water and air pressure

7.1 Filling of the water container


a) Fill the container with fresh and clean water through the filling opening
(appr. 60 Liter).
b) Pour 36 ml (+0,05%) PL-2/94 - FC-201F in the container through the
filling opening.
c) Fill the water container with clean water 72 l -5% tolerance (-3,6 l)!
d) Tighten the top filling closure firmly.

7.2 Filling of the air pressure bottle


Check the air pressure level with a test manometer.
- Test as follows:
1. Make sure the cylinder valve is closed.
2. Remove the pressure regulator from the bottle, adjust the test manometer, open
the valve slowly and read the pressure:
IFEX 3072 = 2x6l l/200 bar, Minimum pressure 180 bar/+20C, if less, refill.

Note: check both air pressure cylinders!

Note:

Should the mobile equipment be used for training, it will suffice to fill
the water container without fire extinguishing agent and with water only.
After training it is important to refill the water container and air pressure
bottles immediately according to para 7.1 and 7.2 , to ensure the
equipment is ready for use.

8. Getting the unit ready for use

8.1 Make sure the water container and the air pressure bottles are filled according to para
7.1 and para 7.2.
8.2 Fit the air pressure bottles to the designated mounting support.
8.3 Screw the pressure regulator to the bottle valves on the air pressure bottles.
8.4 Connect the air pressure hose from the pressure regulator to the water container.
8.5 Connect the water hose (Delta connector) to the water container.
8.6 Connect the air pressure hose (Delta connector) to the pressure regulator.
Page | 13
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130

Instruction Manual
Instructions for Use and Operation P a g e | 14

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

8.7 Place the IFEX 3001 Impulse Gun in the holder and secure it with the fixing strap.
8.8 Connect the air pressure hose (Delta connector) to the pressure regulator.
8.9 Connect the air pressure hose to the IFEX 3001 gun.
8.10 Connect the water hose to the IFEX 3001 gun (The water valve needs to be closed).

The fire extinguishing unit is now ready for use!

Machinery and tools for maintenance

The following list of tools is separate from the instructions.


The listed tools are to be used for their specific purposes only.

1. Test pressure gauge 0 bar to 400 bar


2. Double open-end wrench 13 x 15mm
3. Double open end wrench 14 x 17mm
4. Open-end wrench 21mm
5. Open-end wrench 26mm
6. Open-end wrench 27mm
7. Open-end wrench 32mm
8. Open-end wrench 36mm
9. Ring-wrench 8mm
10. Pipe angle wrench 13 x 110mm
11. Hook wrench 60-90 x 5mm
12. Hexagon screwdriver 3mm
(for inner hexagon screw)
13. Grease gun with lubricating grease

Torques:

Front support grip 25 Nm


Pistol grip (SW 3 inner hexagon) 7 Nm
Fastening screws 30 Nm
Ermeto- hose screw joints DN20 -18L 100 Nm
(Co-axial hose)

Page | 14
9 Water connection 2
5 11
1 3 OPEN CLOSE 16
15
13
13 12 10

lock Diaphragm

Gun trigger lock


release

12 Air pressure connection


14 13
6 4
7
18 1000007 Special wrench for screwed cap St.
17 1000021 Burst disc with socket wrench

16 1000004 Forward support for shoulder strap 1.4301


IFEX 3000/1, Impulse Gun-compl.
1000003 Rear support for shoulder strap 1.4301
15
14 Washer DIN 125 A2
NATO-STOCK NR.
13 3 01000017 Hexagon nut 985 A2
VersNr. 4210-12-349 8251
12 2 01000016 Washer-Teflon Plastic
11 1 01000014 Screwed cap
10 1 01000008 Muzzle with split diaphragm
9 1 Shoulder strap
8
Technical drawings

7 1 01000009 Pistol grip w. trigger & locking dev.


6 1 01000012 Snap on air pressure connection
5 1 01000015 Water valve
4 1 01000040 Front support grip
3 1 High performance valve
1. Impulse Gun IFEX 3001, assembly

2 1 Water barrel
1 1 Air power chamber
Art.-n Description and type
Item Qty. IFEX Code DIN Material

IFEX Technologies GmbH Dimension without Surface Scale %


Hansestrae 18 tolerance acc. acc.
DIN 7168-m DIN ISO
D-27419 Sittensen IFEX Code:
1302 IF-3001-01
Germany
1998 Date Name
Remark: Drawn 15.12. Breese IMPULSE GUN IFEX 3001
Check. 26.09.01 Breese ASSEMBLY
Order of spare parts: Norm
Please use part list nos.
Part List
IFEX 3000 Sheet
Impulse Fire 15
IF-IG-3000-110
Extinguishing
Index Alteration Date Name Technology CAD4-Tetra\H:\HB-3012engl/Blatt15A

Page| 15
7
Cone fo r r ew inde han dle
10
18
12 11 15
6 14
9 3
FE UE R L S C HE R
WAS SER
16/17 A
8
1. Luftf l asc hen 2. W as s e r v ent i l
"X" ffne n bett i gen

3. Ls ch p i s t ol e 4. Ls ch p i s t ol e 22
entsi chern bett i gen

Ach tun g!
Einsatz nur du rch die Feuerw ehr ode r
beso nder s ge schu ltes Per sona l .
Lub ricatio n Nicht au f Mensc h oder Tier zi el en;
M i nd es t a b s t an d 6 M et er ; b e i el ek tr i s che n
13 A nl ag en nur b i s 1000 V ; M i n d es t ab s t and 1 M et er
H i nw ei s e i m H and b uc h d es H er s te l l er s b eacht e n.
4 T ank nach jed er Bettig ung neu fllen!
Lscher m ind estens 1m al im Jahr auf Einsatzb ereitschaft b er p rfen.
Deta il " X" Nur solche Lsch-/ T reib m ittel und E rsatzteile ver wend en,
di e m i t d e m a n e r k an n t e n M u s t e r b e r ei n s t i mm e n .

Lschm itte l: Wa s s e r Funktionsb e reich: 0 C b i s + 60 C


Nr. d e r A n er k e n n u n g :
Tr ei b mi t t e l : 2 x 6 Liter Druckluft 300 b ar Ty p : IFEX 300 1/3550

IFE X Gmb H , Hanses tr asse 18 , D-2741 9 Sitten sen


IF E X 30 0 0
T elef on: ( 04282 ) 930 60 T elef ax: (04282 ) 930 626

Ent lee rung/


Top of sledge 21 Draini ng
23 1 Rewin d ha nd le Part of Nr. 27055

19 22 1 Labeling as per DIN EN3, Teil 5 - english IF- HR -3 00 0 0 2 -1 0


23
Air pressure hose Water hos e
(Co-axi al Hos e) 21 1 6 5000101 P lug 1 /2 " - n icke l pla ted

20 2 01001
IFEX 3001 Impuls Gun Im p ul s G un 1 l ite r
see IF-3000-130 sheet 16 19 1 6505 5 CO-ax ial hose 55 m , assy.

18 2 0 9000035 Coupl ing with NR - 1/4 " IF- CO -3 00 00 7- 8


17 3 27000 007 Red. piece 1/4" ou tside - 1/8" insid e IF- CO -3 00 03 0- 3
16 2 63000 001 Angle 1/4" i/a

15 1 18000 055 Manometer 41, 0 - 10 bar, G 1/8" IF- AC -3 00 008 -1 1


14 2 6505 7 A ir pressur e ho se, re gulato r-ho se reel, a ssy. IF- SL -3 0 0 00 6- 6?
19
20 Im pu ls G un 6505 6
13 1 A ir pre ssu re u n it at hose r eel uni t
Remark /emerk ung:
12 1 6505 8 A i r pr essu re h o se , a ssy. IF- SL -3 0 0 00 6- 6?
Order of spare pa rts:
Please use part l ist nos. 1 6505 9 Water hose hose, assy. IF- S L- 30 000 6- 5?
Sled ge bra ke 11
Ersatzteilbestellung
nur mit Art. Nr. 10 1 65000043 E in ste llb are Wi nke lve rsc hra ub ung 22 L IF- CO -3 00 007 -4 .1
Stop per 9 2 65000041 Gerade Einschraubverschraubung 3/4" x L22 IF- RE -3 00 0 0 5 -2
Bear ing Drum br ake 65000088
8 1 Filt er 3/4" IF- A C -3 00 0 0 8 -3
7 1 1811 0 Filling unit com pl . IF- T R -30 00 02 -3

6 1 1812 0 Pressure regulator 300/7/25 bar compl. IF- RE -3 00 0 0 5 -5 -2


5 2 5400 1 A ir c ylind er 6 lite r/2 00 bar with val ve - steel IF- CY -3 0 0 0 04 -2/ 12

4 1 2705 5 Hoseree l 55 m with rewind ha ndle - left IF-H R-30 000 1-4
Sled ge 3 1 18 000063 72 liter water container IF- HR- 30 000 1-5
2. IFEX 3072 Hose reel fire extinguishing unit, complete

Sich erun gs w inkel 2 1 65 000066 M oun ting rack with sle dge IF- HR- 30 000 1-2
1 1 6500 9 Hosereel Equi pment- left/55m hose compl. with
sledge, 72 l water container, air pressure bottl es,
regulator, hoses and impulse gun IF- HR- 30 000 1-1
P o s. Oty , IFE X Co d e A rt . -n Desc ript ion and T yp e Dra wi ng- n
Fa sten ing M 1 0 Dimensi on without S urfac e S cale
IFE X Te ch n o l o g i e s G mb H %
R ac k Ha n se st ra e 1 8 tol erance ac c.
ac c .
D-2 7 41 9 S i t t e n se n D I N IS O
DIN 71 68-m
IFEX Code: IF-3000
G e rm a n y 1302
2001 Da te Nam e
D raw n 26. 09 . B rees e IFE X 3 072 H os e ree l Fir e E xti ng uis hin g Uni t
Bear ing C hec k . 26. 09. B rees e - 55 m Hose compl. -
No rm - Rewind handle left side-
Sledg e ra is in g 70 0 m m
IFE X 30 0 0
Blat t 16
Pos. 1 Im p u lse Fi re
Ext i n g ui shi n g
IF-3000-130

Page | 16
In d ex Date N am e Te ch n o l o g y
Alt erat io n H : / C A D 4 -T e t ra / I f x 3 0 7 2 -E n g l i / B l a t t 1 7 Ursprung: Pr-17-2
595 508

Greasenippel
5 3 G1/4" Air

G3/4"Water
2
3

546
6 7 2

= = 127 127 127


1
127 127 127 19 5
489 190 562 70
4x boring 10,5 1
1 - Lower (Rewind) position; Drum unbraked
7 1 1/4" Air pressure swingjoint (Part at 1) IF-HR-30001-4-2
2 - Middle (Braket) position; The brake is partially applied in order to 6 1 3/4" Water swing joint (Part at 1) IF-HR-30001-4-1
control the drum during deployment of the hose. CO-axial Hose 3/4"+1/4" Assy.
3. Hose reel, assembly (1)

5 1 65056 IF-SL-300006-2-1
3 - Upper (Locked) position; The drum is fully applied. The position should be
selected during transit or when the hose is in use is a positive lock 4 1 Rewind handle
on the drum is required. 4 3 1 G1/2" Water Connection
2 1 G1/8" Connection elbow with Plasticpipe
Hosereel compl. with 55 m hose.
Mat. steel sheet red painted,
1 1 27060 24V-E-electric rewind
IFEX
Item Qty Code Art.-n Description and type Drawing-n

Dimension without Surface Scale


IFEX Technologies GmbH %
acc.
Hansestrae 18 tolerance acc.
DIN ISO
D-27419 Sittensen
DIN 7168-m 1302 IFEX Code: IP-3100-1
Germany
1999 Date Name
Drawn 19.04. Breese
Check
Hosereel
Norm Assembly
IFEX 3000
Impulse Fire
Extinguishing
IF-3000-140E
Index Alteration Date Name Technology H:/CAD-Tetra/Ifx3072-engl/IFX30100E

Page | 17
Ursprung : H:/CAD4/IFEX/HR-002-5
Altern. 9
10

Pivot for
crank handle
drawn left
right mirrow image
8

Grease nipple
2
7

6
Air connection

10 1 27151 Air pressure hose from reg. to hose reel compl.


9 1 65100 Alt. pressure regulator 25/7bar compl.
8 1 27150 Pressure regulator 25 bar, ass.
7 1 18000031 Quick snap on connection air

6 1 27000045 Adapter " x 1/8"


5 1 70006 Air pressure hose, ass. Impulse Gun IF-SL-300006-6

4 1 70005 Water hose ass. Impulse Gun - 510mm IF-SL-300006-5


4. Hose reel, assembly (2)

CO-axial hose 3/4"+1/4" ass. IF-SL-300006-2


3 1 65055 without parts 4 and 5.
2 1 Crank handle

Water connection 3/4


Hose reel (without hose)
1 1 27000020 metal sheet red painted IF-HR-300001-4
Hose reel complete up to 55 m hose IF-HR-300001-4
1 1 27055 metal sheet red painted, crank handle left side
1
5 IFEX Drawing-n
Pos. Oty Code Art.-n Description and type

IFEX Technologies GmbH Dimensions without Surface Scale %


Hansestrae 18 tolerances acc. acc.
D-27419 Sittensen DIN 7168-m DIN ISO
3 Germany 1302 IFEX Code: IP-3100-1
2001 Date Name
Drawn 26.10. Breese
Check
Hose reel,assambly
Norm

IFEX 3000
4 Impulse Fire
Extinguishing
IF-3000-130-1
Index Alteration Date Name Technology

Page | 18
Pos. 1
5 Stopp er
Bearing Dru m brake

Pr otec ti on
angle
Sladge
4
Wa te r c on ne cti on
Sc re w Lub ri catio n
M 8 Gr un d- C on e fo r re w ind h an dl e
ges t ell
Bef es tig ung Ai r
3 /4 Fi lter pres s ure
A c onnec ti on

Slide be aring

Sledge racing 7 00 mm

Dr um b ra ke
3 S c re w M8 4 Sla dg e bra ke Sla dg e br ak e
Water cylinder
fastening

2
Air p re ss u re 4
7 Cylinder
3
6 View A
Gre as e

S ha ft for ha nd le

IFE X
TY P
CY L I NDE R 3 0 7 2
XX
Fabr. - Nr .

Ba um . XX X X

zul. Bet r. - ber 8 bar


72
I nha tl
5. Mounting rack with sledge, assembly

B a u ja h r

TE ST P RE SS . 1 0. 4 ba r

7 2 Mounting s traps for air cy linder IF- TR- 30 0 0 0 2 -1


6 1 6500 6 Air cy l. ho lder ( 2 x 6 l ) IF- HR -3 0 0 001 -2 -1
5 2 54 001 6. 0 l/200 bar Air pr. C y linder (St.)w. valve
4 1 27 055 Hos eree l 55m w ith rewind handle-l ef t
3 1 180 000 63 72 lt r. w at er c ont ainer
2 1 65000 0 6 6 IF EX 3072 M ount ing rac k with s ladge IF- HR -3 00 001 -2
Sla dg e brak e
1 1 65 009 IF EX 30 72 com pl. Ho s ereel unit 55m IF- HR -3 00 001 -1
IF EX C od e Art.-n D escriptio n and type

49
Item Oty D rawing-n
Dimension without Surf ac e
IFE X Tech nol ogi es Gmb H S ca l e 1: 5
toleranc es ac c . acc.
Hans est rae 1 8
DIN 71 68-m DIN I S O
D-27 419 Si t tens en IF-300 0
Ge rm an y 130 2 IFE X Cod e :
2 1999 Date Name
Dra wn 12.04. B rees e
IFEX 3072 Mounting rack with
Check 06.11.01 B rees e
Sid e view Sladge after compl. N or m sledge - Asse mbly
galvani zed IFEX 3 0 00
Im pu l se Fi re
E xt in g ui shi n g
IF -300 0-1 30
Index A lteration Date N am e Te ch no l o gy H: / C AD 4 / Ha n d bu ch 30 7 2 -e n g l /
Ursp run g: H:/ CA D4 /IFE X/ HR/ HR-0 02-4

Page | 19
6. Top Filling unit and filter, IFEX 3001/72

1. Top filling unit assy.

1.2
1.6
1.1

Body made of brass 1.4


1.5 R 2"

1.3

Remark
Order of spare parts:
Please use part list n.

1.5 Handle for top filling unit, aluminium


1 18000032
1.4 1 18000041 O-Ring seal 53x5 IF-TR-300021-4A
1.3 1 09000013 Scew for handle SW13

1.2 1 Quick coupling with relief valve


18000040 IF-TR-300002-3B

1.1 1 09000033 Safety valve 1/4"-6 bar IF-BP-300002-3B

Pos. Oty. IFEX Code Art.-n Description and type Drawing-n


Dimensions with out %
IFEX Technologies GmbH Scale
Surface
Hansestrae 18 tolerances acc. acc.
D-27419 S ittensen
Germany
DIN 71 68-m DIN ISO 1 302 IFEX Code: IF-3000
1996 Date Name
Drawn
IFEX 3035 und 3050 Trolley ,
05.08 . Bree se
Check
IFEX 3072 Skid
Norm
Instruction for test and refilling
1. Top filling unit
IFEX 3000
Impulse Fire
Extinguishing
IF-3000-130
Index Alteratio n Date Name Technology

Page | 20
Maintenance and test certification

IFEX 3000 IMPULSE FIRE EXTINGUISHING Nr.: IF3000-110


IFEX TECHNOLOGY
Technologies
GmbH Maintenance record for Page: 21
Hansestr. 18 IFEX 3001/72
27419 Sittensen Fire Extinguishing Equipment Date: 15.11.12

Maintenance record

Extinguisher test date: Expert:

Maintenance record

Extinguisher test date: Expert:

Maintenance record

Extinguisher test date: Expert:

Page | 21
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130
Appendix A
Instruction Manual
Instructions for Use and Operation Page |1

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Appendix A/ Tests

1. Testing the extinguishing agent container (by an expert)


The air pressure cylinder needs to be checked by an expert as per directive 2009/104/EC:

external check every 2 years


internal check every 5 years
pressure test every 10 years

Reduce the pressure in the container and emty the container completely. Disconnect all
fittings except the air pressure fitting and close the connections. Remove the safety valve
from the filling unit and close the connections. Fill the container with water through the
filling opening and close the filling unit. Fill the container with 10,4 bar through the air
pressure connector. Check the pressure by a test manometer. The pressure must be held
for 10 minutes. Emty the container and remount the fittings after testing.
Enter results of test in maintenance record Appendix A page 2.

2. Testing the air pressure container of the Impulse Gun (by an expert)
The air pressure container needs to be checked by an expert as per directive
2009/104/EC:

external check every 2 years


Pressure test every 10 years

Remove the bursting disc or safety valve and close the opening with a cylinder screw.
Connect the air pressure hose from the pressure source via a pressure regulator. The
pressure regulator must supply a secondary pressure of 60 bar to the air pressure
coupling of the gun. Put the Gun in a water basin, slowly open the valve at the pressure
source, observe the manometer and close the valve as soon as the pressure is 60 bar.
This pressure must be held for 30 seconds. After testing re-install the bursting disc or
safety valve.
(TV-bursting test at 03.02.96, Pall=45 bar, V= 0,8l, PTest = 58,5bar),TV agreed rounded
PTest Wert = 60,0 bar)
(TV= German Technical inspection authority)

Enter results of test in maintenance record Appendix A page 3.

Appendix A Page |1
3. Tests according to national regulations for extinguishing agent container 72l

User Invoice address Place of use

Test certification as per Type Nr.: IFEX 3072 Skid


directive 2009/104/EC Serial-Nr.: ___________
Extinguishing agent container IFEX 3012 Constr. date: _____________
Type approv.: / TV
- Out of order Volume: 72 Liter
Cert. pressure: 13,0 bar Test pressure: 19 bar Use: Fire exting. agent container

- Inside test - Reg. every 10 years


- Pressure test with water
- other test

Test result no minor major dangerous deficienies

Deficiencies:

Notes:

Futher use is:

No problem. Not advisible.


We will notify the appropriate
No problem, if faults are adjusted. authority.

,Date
(Place)
Next regular inside test _____________

Next regular pressure test _____________


Expert

IFEX 3000 Impulse Fire Extinguishing Technology Nr.: IF3000-110

IFEX Appendix A
Technologies Directive 2009/104/EC
GmbH Page: 2
Hansestr. 18
D-27419 Sittensen Extinguishing Agent Container 72 Liter

Date:22.11.12

Appendix A Page | 2
4. Tests according to national regulations for air pressure chamber of Impulse Gun

User Invoice address Place of use

Test certification as per Type Nr.: IFEX 3001


directive 2009/104/EC Serial-Nr.: ___________
Extinguishing agent container IFEX 3012 Constr. date: _____________
Type approv./ TV:07/95/0016
- Out of order Volume: 0,8 Liter
Cert. pressure: 45,0 bar Test pressure: 60 bar Use: Fire exting. agent container

- Inside test - Reg. every 10 years


- Pressure test with water
- other test

Test result no minor major dangerous deficienies

Deficiencies:

Notes:

Futher use is:

No problem. Not advisible.


We will notify the appropriate
No problem, if faults are adjusted. authority.

,date
(Place)
Next regular inside test _____________

Next regular pressure test _____________


Expert

IFEX 3000 Impulse Fire Extinguishing Technology Nr.: IF3000-110


IFEX
Technologies Appendix A
GmbH Directive 2009/104/EC
Hansestr. 18 Page: 3
D-27419 Sittensen Gun Air Power Chamber

Date:22.11.12

Appendix A Page | 3
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130
Appendix B
Instruction Manual
Instructions for Use and Operation Page |1

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

Appendix B/ fitting and maintenance

1. Introduction
Part B provides information for the operation of the reel, maintenance and basic repairs, as
well as spare parts. Regular maintenance assures ease of use of the unit. Should you have
any further questions, please contact your local IFEX dealer or IFEX Technologies GmbH in
Sittensen, Germany. This manual refers to the manual rewind hose reel as a part of the IFEX
3072 fire extinguishing unit. The fire extinguishing unit IFEX 3072 consists of the following
main components: sliding skid frame with a basic frame with sliding skid plus air cylinders
mounted with:
- Hose reel with 55m hose.
- extinguishing agent container 72 litre content.
- 2 air cylinders; 6 l/200 bar
- Air pressure hose unit consisting of 2 pressure regulators and hoses.
- Co-axial hose unit 55 m.
- IFEX 3001 Impulse Gun.

Refer to components of the IFEX 3072 Fire Extinguishing Unit manual page 16.

Mounting the IFEX 3072 unit


The skid with the mounted components can be raised onto the front of the vehicle where it
can be mounted.

Hose reel
The hose reel is powder coated /colour red RAL 3000 according to BS 381C538. The hose
reel with the other components on the sliding skid is supplied by IFEX Technologies GmbH
ready fitted.
The hose reel is the first component mounted on the skid in the direction of the extraction.
The rewind device is usually on the left side, the brake is on the right front side (custom
made skids with right side rewind devices can be supplied on order).
The grease nipple for the bearing is on the right on left front side of the reel.

Please note
The fire extinguishing unit with sliding skid can be removed from the
vehicle for a more detailed maintenance. Refer to manual page 16.

Appendix B Page |1
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130
Appendix B
Instruction Manual
Instructions for Use and Operation Page |2

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

2. Routine maintenance
Every 6 months: (regular operating conditions). Lubricate the drum bearings and the spindle
of the rewind mechanism with general purpose grease through the grease nipples. Release
the brake and check the reel for easy rotation.

3. Operation of the drum brakes


a) Lower (rewind) position:
The drum is unbraked.
This position should be selected when the hose is being rewound.
b) Middle (braked) position:
The brake is partially applied. This position will allow a control of the drum during
unwind of the hose. This position will prevent the drum from rocking excessively when
the pressure is turned on and off.
c) Upper (locked) position:
The brake is fully applied. This position should be selected during transit or when the
hose is in use if a positive lock on the drum is required.

4. Brake adjustment
Move the brake lever to the lower rewind bottom position.
Apply pressure to the end of the brake rod. Sufficient pressure must be applied to
compress the spring and move the nut on the end of the rod clear of the brake shoe, so
that the nut can be rotated. Rotate the nut (clockwise when viewed from the back of the
reel to increase braking and anti-clockwise to decrease braking). The adjustments should
be made a little at a time. After each adjustment, move the brake lever to the braked
(middle) position and test the effectiveness of the brake. Repeat the operation until the
desired effect is achieved.

5. Rewind problems
If it should be difficult to rewind the hose to the reel, check the following:
Check that the hand wind brake is released. The brake should be in the lower (rewind)
position. Check that the drum bearings are lubricated, apply grease to the nipples.
If the drum is still tight, it is probably because the frame is mounted with a twist in it. Try
loosening the bolts which fasten the reel down and if necessary put a packing piece
under one corner of the frame when re-tightening.
If the reel has been damaged during operation or otherwise, please contact your local
IFEX dealer or IFEX Technologies GmbH Sittensen, Germany.

Appendix B Page | 2
IFEX Technologies GmbH IFEX 3000 Impulse Fire Fighting Technology N: IF3000-130
Appendix B
Instruction Manual
Instructions for Use and Operation Page |3

Hansestrae 18, 27419 Sittensen Type IFEX 3072 Fire Extinguishing Unit with hose reel Date: 30.11.12

6. Leaky rotating swing joint- 3/4 water


When the reel is properly installed and maintained the rotating swing joint will have a
long life. Premature wear can occur if the joint is subjected to external strain from the
inlet connection. The connecting pipe must be flexible and should be fitted without
exerting any force on the rotating joint.
If the rotating joint should leak, replace the seals.
A self contained rotating swing joint is fitted externally. It can be serviced in-situ and can
be replaced without dismantling the hose reel.

6.1. Replacement of the rotating swing joint- 3/4 seal


Refer to IF-HR-300001-4-1.

Please note the caution notice: Manual


test and filling instructions Nr. IF3000-130 page 7.

Equipment needed: - external circlip pliers


- plug- 2 mm, setting 7 - 20 mm
Seal: - two nitril seals Nr. 0216.00T

Procedure: Empty co-axial hose. Disconnect the water hose from the rotating swing joint.
Remove the circlip and the washer from the end of the hose fitting and pull off the sleeve.
Remove the seals from the socket (pick them out with a sharp tool, but take care not to
scratch the bottom of the groove where the seals fits).
Wipe all the parts clean, fit new seals into the grooves and the socket to the hose fitting.
Fit the washer and re-mount the circlip. Fit the water hose to the rotating swing joint.

If leakage still occurs after replacing the seals, it is possible that the rotating joint is worn
and may need to be replaced. In this case please contact your local IFEX dealer or IFEX
Technologies GmbH Sittensen, Germany.

Appendix B Page | 3
Technical drawings

1. Sliding skid, support for air cylinders

A 3.7 A
3. Support for air cylinder

5
5 x 45
A-A

46
20
5,2 3.5
3.3
5 3.6
R7 3.4

405
welding

welding

85

60
70 3.2 tack-welding
50

5
180
10 40

3.1

110
140
After completion
coating with
colour RAL 3000 455
weight: 4,2 kg 485

3,7 4 countersink screw M5x15 with nut ss AISI 316 DIN 965/985
3,6 2 18000052 mounting strap for air cylinders compl. IF-TR-300002-1
3.5 2 sheet metal 40 x160 x 3
3.4 4 sheet metal 60 x 50 x 5
3.3 2 sheet metal 40 x 5 x 400 lg.
3.2 2 pipe 139,7 x 4,5 x 50
3.1 1 sheet metal 485 x 140 x 50
3 1 65000001 support for air cylinder, complete IF-HR-300001-2-1
Pos. Oty. IFEX Code Art.-n. Description and type Dawing-n

IFEX Technologies GmbH General Surface Scale %


tolerance acc. acc.
Hansestrae 18 ISO 2768 mK
DIN ISO
D-27419 Sittensen IFEX Code: IF-3000
1302
Germany
1999 Date Name
Drawn 12.04. Breese
Check
IFEX 3072 Sliding skid
Norm Support for air cylinders
IFEX 3000 Page 4
Impulse Fire IF-HR-300001-2-1
Extinguishing
Index Alteration Date Name Technology Skid Att. B page 4 HR-002-1

Appendix B Seite |4
1 - Skid, base frame
B B-B
1.1 1.6 1.7
10 Drills for M8 fixing screws
1.6 580

40
70 II
1.3 II
1.2
to weld
1.9
1.4 "X"
1.8

90

334
500
305
470
540
610
Part 1.8

25
10 70
20 30
sagging from underneath
1.2 20 1.8
All drills 10
II 1.4
35 "X"
90
120

10
230 135 1.5
560 335
1135
A Part 1.5
B Part 1.3
A 50 40
17
1.7 17
A-A 34
1.5.2

60
7
35

40

49
15
15

II
15

34
60

395 1.5.1
2. Sliding skid, base frame

1.5.2
1.5.3

1.9 2 Countersink screw M8x15 with nut DIN 965/985


1.8 1 Securing angle 50 x 50 x 5 x 120 long
1.1 sheet metal bevor edging 1.7 8 Srews M6x 12
1135 1.6 2 65000157 Locking bolt for skid
1.5.3 2 Roller bearing 15 x35 x 11
1.5.2 2 Shaft
edging line 1.5.1 2 Plate 40 x 35 x 12
1.5 2 Skid slide bearing
edging line
35

1.4 2 Flat steel 30 x 25 x 8


140

Appendix B
t = 4 mm 1.3 2 65000156 Flat steel50 x 60 x 5
70

1.2 2 Plate 470 x 70 x 4


1.1 2 65000156 Plate 1135 x 140 x 4
1 1 Skid, base frame IF-HR-30000-1-2-2
Pos. Oty. IFEX Code Art.-n Description and type Drawing-N
IFEX Technologies GmbH Dimen sion wi thout Surface Scale %
tol erance acc. acc.
Hansestrae 18
DIN ISO
D-27419 Sittensen DIN 7168-m IFEX Code: IF-3000
1302
GERMANY
1999 Date Name

Drawn 12.04. Breese


Check. IFEX 3072 Sliding skid
After completation Norm base frame
galvanized Page 5
IFEX 3000
Impulse Fire
Extinguishing
IF-HR-300001-2-2
Index Alteration Date Name Technology Skid Appendix A Page 5 HR-002-2

Page |5
3. Water connection at hose reel

71
KS 36 G3/4"

48
75

G3/4"

1 1 FPC.109 Circlip

Pos. Oty. IFEX Art.-n Description and Type Drawing-n


Code
IFEX Technologies GmbH General Surface Scale 1:1
Hansestrae 18 tolerance acc. acc
D-27419 Sittensen DIN ISO
Germany ISO 2768 mk
1302
IFEX Code: IF-3072
1999
Drawn
Date Name
3/4" Water connection
Check.
19.04. Bre
at hose reel
(belongs to scope of reel supply)
Norm
3/4" Swing joint - water conn. at hose reel
IFEX 3000
Impulse Fire
Extinguishing
IF-HR-30001-4-1
Index Alteration Date Name Technology Skid Appendix B Page 7 HR-002-6

Appendix B Page |6
4. Air connection at hose reel

74.5

Circlip

G1/4"
35

KS 28

G1/4"

Art. N: 7512.00.M-1/4

IFEX Technologies GmbH General Surface Scale 1:1


Hansestrae 18 tolerance acc. acc.
D-27419 Sittensen DIN ISO
Germany ISO 2768 mk
1302
IFEX Code: IF-HR-3072
1999 Date Name
Drawn 19.04. Bre 1/4" Swingjoint - Air conn. at hosereel
Check
Norm
(belongs to scope of reel supply)

IFEX 3000
Impulse Fire
Extinguishing IF-HR-30001-4-2
Index Alteration Date Name
Technology Skid Appendix B Page 8 HR-002-7

Appendix B Page |7
Warranty
_____________________________________________________________________________________________________________

IFEX Technologies GmbH grants a warranty for the product purchased by the customer for a period of 24
months after purchasing.

The following information details the terms of the warranty offered by IFEX Technologies GmbH. You are
entitled to make a claim under this warranty in the event of any manufacturing or material defects on the
product you have purchased. The warranty provided is based on a voluntary obligation of IFEX Technologies
GmbH as the manufacturer. It only applies to end customers. No warranty rights other than those expressed
herein, whether given by IFEX Technologies sales partners or third parties, can be asserted against IFEX
Technologies GmbH.

The warranty begins on the day of purchase stated in the invoice. Please note that warranty claims can only be
processed if accompanied by the original invoice in combination with the approval certificate of the product.
Therefore, always keep the invoice and the approval certificate together with the warranty documents.

The invoice must show the type of the product and the serial number.

Warranty claims must be submitted immediately following discovery of the fault to the sales partner or to IFEX
Technologies GmbH.

Please check the availability of the sales partner in the documents given to you by the sales partner. IFEX
Technologies GmbH is available by phone: +49 (0) 4282/ 9306-0, by fax: +49 (0) 4282/ 9306-26 or by e-mail at
info@ifextechnologies.com.

After consulting IFEX Technologies GmbH the customer should return the defective product to IFEX
Technologies GmbH.

In the event of a warranty claim IFEX Technologies GmbH will pay the costs for the resulting labour and any
required materials or replacement parts.

The costs of the transport to and from IFEX Technologies GmbH will be accounted separately, without the
common additional charges net/ net.

The warranty is limited to restoring the performance features and condition of the original product prior to the
warranty claim. In this respect it is always sufficient for the affected product to fulfill the test requireme nts in
accordance with the IFEX Technologies specifications for the original product. The warranty is fulfilled at the
discretion of IFEX Technologies GmbH either by repairing or replacing the defective device. In cases of material
and/ or processing defects, defective parts shall be replaced with new or as-new reconditioned parts. If
necessary, the complete product should be exchanged for an identical product or an alternative product offering
the same level of functionality. The value of the warranty service is always limited to the value of the defective
product.

The defective parts removed or replaced from a product during the course of warranty action shall become the
property of IFEX Technologies GmbH.

Genuine IFEX Technologies parts installed under warranty in an IFEX Technologies product are only covered
by the remaining duration of the warranty of the overall device.
Warranty exclusions

Defects caused by improper use are excluded from the warranty. Improper use of the equipment is taken to be
any operation of the product under conditions which do not meet the terms of proper use described in the
operating manual or documentation of the product.

The warranty also does not cover the following points:

Wearing parts and consumable materials


Diagnosis and rectification of defects caused by improper use or improper maintenance of the
device by the customer or third parties. Improper actions include operations that are not
compatible with the instructions contained in the product manual.
Force majeure (lightning strike, floods, war etc.)
Dirt, seals or stickers
Any other circumstances for which IFEX Technologies cannot be held responsible.

The warranty is rendered null and void if:

IFEX Technologies products are operated or fitted with parts, components or peripherals which
have not been approved for that purpose by IFEX Technologies GmbH.
The device is covered with irremovable seals, stickers or similar.
The original warranty sticker at IFEX Technologies products is damaged or removed
respectively if manipulations at those stickers are apparently.
Services/ repairs or other changes to the product are carried out by persons who have not been
authorized by IFEX Technologies GmbH to carry out such work.

This clause is not valid if the customer can prove that any defects were neither caused by nor arose as a
consequence of such events.

Limitation of liability

Any claims of the party entitled to the warranty which exceed the scope of terms expressly mentioned in these
warranty conditions are excluded. This also applies in particular with regard to claims to compensation for
subsequent damages, loss of profits, data losses or information losses or damages following of the inoperability
or missing of the product due to maintenance or repair.

Applicable law

The warranty is subject to the applicable laws in the country of purchase and is to be interpreted in agreement
with the said laws.

Rev. 001/ 01 2011


IFEX 30002/72

FIRE EXTINGUISHING UNIT WITH

HOSE REEL

ATTENTION!

ANY UNAUTHORIZED ALTERATION TO

THE EQUIPMENT WOULD RESULT IN

LOSS OF APPROVAL AS WELL IN

LOSS OF GUARANTEE!

IFEX Technologies GmbH, Hansestr.18, D-27419 Sittensen


Telephone: +49 (0) 4282 93060 Fax: +49 (0) 4282 93026
Homepage: www.ifextechnologies.com
e-mail: info@ifextechnologies.com

Das könnte Ihnen auch gefallen