ENERGY EFFICIENT TRANSFORMER

- 3 Phase Isolation
- Dry Type
- ANN Self Cooled

Purchaser: TBA
PO#: TBA
SWO#: TBA
Qty: TBA

Coils: Copper Termination Location Lug Size Standards:


Cat. No.: BC75J-M/S1/T115/Z3 Primary: Front 2-14 AWG 1. CSA Certified
Secondary: Front 300MCM-6 - File No. LR34493
kVA: 75 2. UL Listed
Primary: 600 Delta Volts Wiring Connection: - File No. E108255
Secondary: 208 Y/120 Volts Primary: H1-H2-H3
Primary Taps: 2.5 % Voltage % Tap Jumpers To: Standard Features:
-Taps FCAN 2 630 105.0 1-1-1 1. Anti-vibration pads installed between the enclosure
-Taps FCBN 2 615 102.5 2-2-2 base and the core & coil assembly
600 100.0 3-3-3 2. Lug for Earth grounding provided
Frequency: 60 Hz 585 97.5 4-4-4 3. Seismic rated for USA zone 4 and Canada zone 6
570 95.0 5-5-5 4. Transformer meets DOE 2016 efficiency level
BIL: 10 kV
Insulation Class: 220 C Secondary: X0-X1-X2-X3 Special Features:
Temperature Rise: 115 C Voltage Phase Connect Loads To: S1=Electrostatic shield installed between primary
Impedance: 4.0 - 5.0 % 208 3 X1-X2-X3 and secondary windings
120 1 X0-X1, X0-X2,
Min. Efficiency: 98.60 % and/or X0-X3
- Calculated @ 35% Loaded H2 X2

X1 X0
Weight: 750 Lbs
H1 H3 X3

CSA Enclosure:
1. Type 3R (NEMA 3R)
- Sprinklerproof when the angle between sprinkler heads
and opening in the enclosure does not exceed 45 degree
from the vertical.
2. Ventilated
3. ASA 61 grey
4. Floor/Wall mounting

Rev. Remarks By Appr. By Date

Prepared by: RG
Approved by: VS
Date: NOV.25, 2015

X:\Drawings\DOE 2016\J-M\Copper DOE 2016 J-M with Shield\Copper S1-T115-Z3 J-M\BC75J-MS1T115Z3 (REV)_#712/1/2015