Beruflich Dokumente
Kultur Dokumente
for
Aker Yards 728
Preface
Wrtsil as supplier and the yard as contractor need to communicate installation specific information to
build an installation that is both reliable and economical in use. During the years this information has evolved
into what we today are calling the Installation Planning Instruction (IPI).
Instructions included in this file are installation specific and based on the best of our experience and
knowledge. The instructions shall be used as a recommendation with general guidelines. However, project
specific deviations can be accepted based on special consideration. Alternative solutions and design should
be separately agreed with Wrtsil.
The level of content maintained in the IPI is based on the assumption that the receiving contractor maintains
the workmanship required to design and build high quality ship installations.
The IPI is a living document that is updated according to the proceeding project and as far as technically
possible reflect the actual situation. Each updated issue of the IPI is identified by its own unique version
number ( e.g. "project xx" - a1) which should be referred to in any correspondence or discussion related
to the specific projects.
Issuing the first or any new version of IPI is proceeded by our internal quality assurance and approval by
the Project Manager. To ensure further development in our common interest we appreciate your comments
forwarded to us via the Project Manager.
Version History
Version Date History
a1 2008-01-07 Version 01
Table of Contents
1. Project Information ....................................................................................................................................... 1-1
1.1 Project administration .......................................................................................................................... 1-1
1.2 Project technical data ........................................................................................................................... 1-1
1.2.1 Ambient conditions ............................................................................................................. 1-1
1.2.2 Fuel oil specification ........................................................................................................... 1-1
1.2.3 Classification ...................................................................................................................... 1-1
1.2.4 Electric power supply ......................................................................................................... 1-2
1.2.5 Painting .............................................................................................................................. 1-2
1.2.6 Factory acceptance test ..................................................................................................... 1-2
1.3 Documents in this project ..................................................................................................................... 1-2
1.3.1 Comments to this document .............................................................................................. 1-2
1.3.2 Shipyard drawings .............................................................................................................. 1-2
1.4 Corrosion protection for the engines .................................................................................................... 1-2
1.4.1 Acceptance ........................................................................................................................ 1-2
1.4.2 Intermediate inspection ...................................................................................................... 1-2
1.4.3 Repeated inspection .......................................................................................................... 1-3
1.4.4 Long-term storing ............................................................................................................... 1-3
1.4.5 Subsequent work ............................................................................................................... 1-3
1.4.6 Recommended corrosion inhibitors ................................................................................... 1-3
1.5 Wrtsil scope of supply for project Aker Yards 728 ............................................................................ 1-4
1.6 Drawings .............................................................................................................................................. 1-4
List of Drawings
DBAA407004- Order technical specification ................................................................................................. 1-5
DBAA042536a Damage report form .............................................................................................................. 1-18
tobeadded Generating set drawing, W 9L20 ........................................................................................... 2-15
2V69C0278e Engine room arrangement ..................................................................................................... 2-16
DAAE006367- Service space requirements .................................................................................................. 2-17
tobeadded Location of sensors and el. components ............................................................................... 2-18
DBAA388012a Generator technical data sheet ............................................................................................. 2-19
DBAA406985- Tools for diesel engine ........................................................................................................... 2-20
DBAA406989- Spare parts for diesel engine ................................................................................................. 2-22
4V35A1591b Flexible pipe connection for fuel pipe ..................................................................................... 2-24
4V35A2939a Flexible pipe connection for fuel pipe ..................................................................................... 2-25
4V60B0093k Flexible hose .......................................................................................................................... 2-26
4V60B0095o Flexible hose .......................................................................................................................... 2-27
3V60D0025l Flexible rubber bellows for water pipe ................................................................................... 2-28
4V69L1585e Installation of the generating sets .......................................................................................... 2-29
DAAE002455a Factory acceptance test ........................................................................................................ 2-34
DAAE058154- Internal fuel oil system ........................................................................................................... 3-6
DAAE058155- Recommended fuel oil system .............................................................................................. 3-7
DAAE015263b Recommended transfer and separating system .................................................................... 3-8
DBAA406400- 1E04 - Cooler (MDF return line), dimensional drawing ......................................................... 3-9
DBAA406400- 1E04 - Cooler (MDF return line), technical data .................................................................... 3-10
Z102346- 1F07 - Suction strainer (MDF) dimensional drawing ............................................................. 3-11
DPI_4-36-2- 1F07 - Suction strainer (MDF) DPI ........................................................................................ 3-12
DBAA406434- 1P03 - Circulation pump (MDF) dimensional drawing ........................................................... 3-13
DBAA406434- 1P03 - Circulation pump (MDF) Driver specification ............................................................. 3-14
DBAA406434- 1P03 - Circulation pump (MDF) Pump calculation ................................................................ 3-15
DAAE058156- Internal lubricating oil system ................................................................................................ 4-6
DAAE058157- Recommended lubricating oil system .................................................................................... 4-7
4V76E2522a Recommended crankcase ventilation .................................................................................... 4-8
DAAE058158- Internal starting air system .................................................................................................... 5-3
DAAE058159- Recommended starting air system ........................................................................................ 5-4
DAAE058160- Internal cooling water system ................................................................................................ 6-6
DAAE058161- Recommended cooling water system .................................................................................... 6-7
4V60D0343- Recommended cooling water circuit deaerator ..................................................................... 6-8
DBAA396944- 4V02 - Temperature control valve (heat recovery), dimensional drawing .............................. 6-9
DBAA396944- 4V02 - Temperature control valve (heat recovery), installation instruction ............................ 6-10
10020-05 4N01 - Preheating unit, dimensional drawing ........................................................................ 6-12
11472-03 4N01 - Preheating unit, electrical drawing ............................................................................. 6-13
DBAA396949- 4V03 - Temperature control valve (LT), dimensional drawing ................................................ 6-15
DBAA396949- 4V03 - Temperature control valve (LT), el. PID valve controller ............................................. 6-16
DBAA396949- 4V03 - Temperature control valve (LT), temp sensor ............................................................. 6-17
DBAA396949- 4V03 - Temperature control valve (LT), installation instructions ............................................ 6-18
DAAE058162- Internal charge air and exhaust gas system .......................................................................... 8-6
3V37L0587a 5Z03 - Turbocharger cleaning device, dimensional drawing .................................................. 8-7
3V60A4945- 5Z01 - Connection piece, dimensional drawing ..................................................................... 8-8
3V60B0020r 5H01 - Exhaust gas bellows, dimensional drawing ............................................................... 8-9
3ES0342C 5R02 - Exhaust gas silencer with spark arrestor, dimensional drawing ................................ 8-10
4ES0061 5R02 - Exhaust gas silencer with spark arrestor, installation instruction ............................... 8-11
DAAE061024- Block- / Interconnection diagram ...........................................................................................10-10
DAAE061027- Power unit ..............................................................................................................................10-17
tobeadded Modbus list ............................................................................................................................10-20
4V50G1522h Pre-lubricating pump starter (recommended) ........................................................................10-21
1. Project Information
1.1 Project administration
Wrtsil internal order number: M/03093
Wrtsil project name: Aker Yards 728
Wrtsil project organisation:
Project manager Bjrn Nygrd
Project engineer: Tobias Knuts
Tel: +358 10 709 0000
Mobile: +359 50 589 2414
Fax: +358 6 356 7188
E-mail: tobias.knuts@wartsila.com
More detailed fuel oil requirements are specified in chapter "Fuel Oil System".
1.2.3 Classification
The equipment meets the requirements of DNV for unrestricted service at the date of order.
1.2.5 Painting
The generating set(s) will be painted with acrylic-based paint in colour RAL 5019 Capri Blue.
1.4.1 Acceptance
When the engine arrives at its destination, the packing must be checked for possible damage during
transport. If damage has occurred, please contact the insurance company concerned.
The engines must be stored indoors or tightly secured under a tarpaulin.
It is essential that oil reaches all parts of the engine, ensure this by opening the cylinder covers and inspect
that all of the valve mechanism gets oil during the procedure.
By aid of a pre-lubricating pump (manual or electrical) the oil should be circulated through the lubricating
system (for about 15 minutes) at the same time as the flywheel is turned a few times.
Repeat this procedure once a month in connection with the test mentioned in repeated control paragraph.
NOTE! Drain the crankcase of oil before starting up the engine and replace with fresh oil.
The indicator valves have to be kept shut except in case of turning. The cover of the turbocharger
air filter must not be removed before starting up the engine. The opening for the crankcase
ventilation has to be shut until starting up the engine.
For long time storing some turbocharger manufacturers require special arrangements e.g. sup-
porting of the rotor or change of the bearings. For details see turbocharger manufacturers
specification.
NOTE! To keep the protective film intact during transport, do not turn the crankshaft.
The valve mechanism, camshaft, crankshaft, connecting rods, cylinder liners, main bearings and gear
wheels are sprayed with protective oil B.
The other unpainted surfaces in the camshaft and crankshaft space are also protected with B.
The injection pumps, control shaft, fuel pipes and other unpainted surfaces in the hot box are sprayed
with protective oil C.
The indicating valves, screws and unpainted surfaces on the cylinder head are protected with D.
The edges of the crankcase and camshaft space openings and the side screws are protected with
E.
The flywheel and the counter borings of its fastening bolts, the oil dipstick, governor levers and other
unpainted surfaces are also protected with E.
1) Tectyl 502 EH, can alternatively be used in case of long-time outdoor storage.
Description Qty/Set
W20 - Wrtsil 9L20 4
1E04 - Cooler (MDF return line) 4
1I03 - Flow meter with pulse transmitter (MDF) 4
1M01 - Fuel circulation pump with el motor 2
1F07 - Suction strainer 0.5mm (MDF) 2
4V02 - Temperature control valve (heat recovery) 4
4N01 - Preheating unit 4
4V03 - Temperature control valve (LT) 4
5Z03 - Turbocharger cleaning device 2
5Z01 - Connection piece 4
5H01 - Exhaust gas bellows 4
5R02 - Exhaust gas silencer with spark arrestor 4
9N36 - Power Unit 4
6H01 - Flexible pipe connections spare set 1
6H01 - Flexible pipe connections 4
6N01 - Common base frame 4
7C01 - Flexible coupling (flywheel) 4
9A03 - Generator 690V 60Hz IP44 sleeve 4
0Y02 - Tools (engine) 1
0Y04 - Spare parts (engine) 1
0Z12 - VCI-coating 4
0Z11 - Tarpaulin 4
0J10 - Engine manuals 1
0J13 - ELDOC 1
0J21 - Green Passport 1
0J17 - Start-up support 40 man-days in 4 trips 1
1.6 Drawings
DBAA407004- Order technical specification ................................................................................ 1-5
DBAA042536a Damage report form ............................................................................................. 1-18
Damage Report
General information
Name of installation: Project number:
(Yard + NB no.) (Wrtsil ID)
Case no:
Reported by:
Description of damage
Probable cause
Actions taken
Damage photographed Yes No N/A Photographs enclosed Yes No
Insurance claim submitted Yes No N/A Claim enclosed Yes No
Separate report submitted Yes No N/A Report enclosed Yes No
________________________________________________________________________________________________ _______________________________________________________________________________________________
(Signature) (Signature)
2. Generating Set
2.1 About the generating set
The generating set comprises the diesel engine and the generator which are rigidly mounted on a common
base frame. The common base frame is a welded steel structure. The complete generating set is installed
on resilient mounts on the foundation in the ship.
The main dimensions, locations of pipe connections, location of sensors, space required for maintenance,
weight and centre of gravity are shown in enclosed drawings.
Main particulars
Type designation Wrtsil 9L20
Number of cylinders 9
Configuration in-line engine
Max. continous rating 1665 kW
Overload capacity 10 % for 1h every 12h
Nominal speed 900 rpm
Direction of rotation Clockwise
The generator is a two-bearing, brushless, 3-phase, synchronous alternator with built-on voltage regulator.
Main particulars
Maker AvK
Type designation DSG 99 L1-8 W
Rated output 2000
Power factor 0,80
Voltage 690V
Rated speed 900 rpm
Frequency 60 Hz
Overspeed capability 1,2 x nominal speed for 2 minutes
Bearing type Sleeve
Cable outlet Cable entry from the right side, 45 downwards
Cable entry from the left side, 45 downwards
Cable entry from the right side, 45 downwards
Cable entry from the left side, 45 downwards
Anticondensation heater Supply voltage 230V +-5% VAC 1-ph., Power required 500W
Cooling IC 81W, water cooled
Temperature sensors Yes
The generator is equipped with current transformers for differential protection. 3 pcs are mounted in neutral
wires within the terminal box, 3 pcs are delivered loose for panel mounting.
The generator is suitable for parallel operation, damper cage and droop transformers are built-in.
Wrtsil 9L20
Exhaust gas flow at 85% load 3,11 kg/s
Exhaust gas flow at 75% load 2,84 kg/s
Exhaust gas flow at 50% load 1,94 kg/s
Exhaust gas temperature after turbocharger at 100% load 320 C
Exhaust gas temperature after turbocharger at 85% load 290 C
Exhaust gas temperature after turbocharger at 75% load 285 C
Exhaust gas temperature after turbocharger at 50% load 300 C
Exhaust gas temperature after cylinder, alarm 400 C
Exhaust gas backpressure, max 3 (0.03) kPa (bar)
Turbocharger connection diameter 300 mm
Exhaust gas pipe diameter, min 450 mm
Calculated exhaust diameter for 35 m/s 462 mm
Wrtsil 9L20
HT cooling water system
Pressure at engine inlet, after pump, nom (+ static pressure) 200 (2.0) kPa (bar)
Pressure at engine inlet, after pump, alarm (+ static pressure) 100 (1.0) kPa (bar)
Pressure at engine inlet, after pump, max 500 (5.0) kPa (bar)
Temperature before engine, about 83 C
Temperature at the engine outlet, nom 91 C
Temperature after cylinders, alarm 105 C
Temperature after cylinders, stop 110 C
Pump capacity, nom 44 m3/h
Pressure drop over engine 50 (0.5) kPa (bar)
Water volume in engine 0.16 m3
Pressure from expansion tank 70...150 (0.7...1.5) kPa (bar)
Pressure drop over external system, max 120 (1.2) kPa (bar)
Notes:
Note 1 At ISO 3046-1 conditions (ambient air temperature 25C, LT-water 25C) and 100% load. Tolerance
5%.
Note 2 At ISO 3046-1 conditions (ambient air temperature 25C, LT-water 25C) and 100% load. Flow tol-
erance 5% and temperature tolerance 15C.
Note 3 At ISO 3046-1 conditions (ambient air temperature 25C, LT-water 25C) and 100% load. Tolerance
for cooling water heat 10%, tolerance for radiation heat 30%. Fouling factors and a margin to be
taken into account when dimensioning heat exchangers.
Note 4 According to ISO 3046/1, lower calorific value 42 700 kJ/kg, with engine driven pumps. Tolerance
5%. Load according to propeller law for mechanical propulsion engines (ME).
2.3.3 Foundation
For more information about the foundation design refer to section "Installation of the generating set".
1. The generating set (or engine) should be installed in its final position before any external pipes are con-
nected.
2. Fasten the flexible pipe connection to the connection on the engine according to the following procedure:
If there is a counter flange, remove it.
Fasten the fixed flange of the flexible pipe connection to the engine side with a gasket between the
flanges.
Oil the threads of the screws and nuts, fit all screws and tighten until finger tight.
Tighten screws in a crosswise sequence using a socket wrench. Increase the tightening torque
gradually until the final torque is achieved.
3. Connect the free end of the flexible pipe connections to the external piping.
The flange of the external pipe should be in line with the flange of the engine. No twisting, compression
or elongation of the flexible pipe connection is allowed, i.e. it should fit between the flanges with the
correct installation length (L). Align the external pipe and weld the counter flange to the pipe.
The flexible pipe connection can also be installed with a bending radius as stated in the flexible pipe
connection drawing.
Bolt the swivel flange side of the flexible pipe connection to the flange of the external pipe as described
in step 2.
4. Anchor the external pipe to the steel structure of the ship close to the flange. Observe that the pipe
clamping must be very rigid in order to prevent vibration and movement of the flexible pipe connection.
Most problems with bursting of the flexible connection originate from poor clamping.
5. The flexible pipe connection must be protected from external mechanical damage. There must be
enough space around the flexible pipe connection for regular supervision and maintenance.
1. The generating set (or engine) should be installed in its final position before any external pipes are con-
nected.
2. Fasten the flexible pipe connection to the connection on the engine according to the following procedure.
All stud coupling parts should be lubricated with engine oil.
Remove the nut from the stud coupling of the engine and put it on the pipe end of flexible connection.
Remove the ring from the stud coupling of the engine and slip it over the pipe end of flexible connection
with the thinner end outwards against the bottom of the stud coupling.
Screw the nut with flexible connection and ring manually to the stud coupling until finger tight.
Push the pipe of the flexible connection against the bottom of the internal cone of the fitting body.
Mark the position of the pipe as well as the nut with a marker pen.
Tighten the nut 1 1/2 turn while the pipe is prevented from turning.
3. When the flexible pipe connection is fitted to the engine, connect the external pipe to the end of the
flexible pipe provided with the stud coupling. The stud coupling on the flexible pipe is similar to the stud
coupling on the engine, i.e. a seamless steel pipe according to DIN 2391/c will fit directly to the stud.
The tightening procedure is the same as outlined in step 2.
If seamless steel pipe isn't available an adapter piece with a suitable outer diameter can be welded to
shipyards pipe in order to fit the stud coupling of the flexible pipe connection. Mild steel (St 35) is recom-
mended. The flexible pipe connection should be mounted in a straight position although some bending
radius is allowed.
The flexible pipe connection should be protected against external mechanical damage. The shipyards
pipe should be fixed with suitable pipe clamps close to the flexible connection in order to prevent vibration
and movements.
1. The generating set (or engine) should be installed in its final position before any external pipes are con-
nected.
2. Remove the counter flange from the engine connection. Fit the flexible pipe connection temporarily.
3. The flexible pipe connection should not be exposed to axial , lateral or angular deflection. Align the ex-
ternal pipe in order to achieve this.
The counter flange should have a smooth sealing surface against the rubber collar and the inner dia-
meter of the flange should not be larger than the inner diameter of the rubber compensator.
Fix the flange by small tack weldings at three points around the pipe. Take care not to heat the flange.
Protect the rubber against weld splash.
Remove the flexible pipe connection.
4. Weld the flange to the pipe and let it cool down before proceeding.
5. Fasten the flexible pipe connection to the connection to the engine according to the following procedure:
Both flanges of the flexible pipe connection are swivel flanges which means it can be installed with
either one of the flanges to the engine.
Oil the threads of the bolts and nuts, fit all bolts to the head on the compensator side and the nut on
the pipe side and tighten until finger tight. No gaskets are needed between the flanges as the rubber
collar is squeezed in between the flanges.
Tighten the nuts in a diagonal sequence with a wrench on the outside while the bolt head is held firmly
on the inside. Take care not to damage the rubber bellows with the tool. The tightening torque is
stated in drawing 3V60D0025.
6. Fasten the outer side of the flexible pipe connection in the same way as described in step 5.
7. Anchor the external pipe to the steel structure close to the flange. Observe that the pipe clamping must
be very rigid in order to prevent vibration and movement of the flexible pipe connection. Most problems
with bursting originate from poor clamping.
8. The flexible pipe connection must be protected from external mechanical damage. There must be
enough space around the flexible pipe connection for regular supervision and maintenance. The rubber
part must not be painted.
1. The generating set (or engine) should be installed in its final position before any external pipes are con-
nected.
2. Fasten the flexible pipe connection to the engine according to the following procedure. All parts should
be lubricated with engine oil.
Remove the nut from the stud coupling on the engine and put it on the pipe end of flexible pipe con-
nection.
Remove the ring from the stud coupling of the engine and slip it over the pipe end of flexible pipe
connection with the thinner end outwards against the bottom of the stud coupling.
Screw the nut with flexible connection and ring manually to the stud coupling until finger tight.
Push the flexible connection against the bottom of the internal cone of the fitting body.
Mark the position of the pipe as well as the nut with a marker pen.
Tighten the nut 1 1/2 turn while the pipe is prevented from turning.
3. When the flexible pipe connection is fitted to the engine, connect the external pipe to the stud of the
flexible pipe provided with the straight bulkhead fitting.
The flexible pipe connection must not be reshaped or welded. Enough space allowing maintenance
must be provided.
The pipe clamp should have a diameter of 38 mm hole into which the bulkhead fitting is fixed. The
pipe clamp bracket should be very rigid and welded to the steel structure of the foundation. Max.
thickness of the clamp is 16 mm.
Tighten the bulkhead fitting to the flexible pipe as described in step 2.
Align the external pipe to the bulkhead fitting. The external pipe should be seamless and have 28 mm.
If suitable pipe is not available an adapter piece with 28 0.1 mm outer diameter can be welded to
the shipyards pipe in order to fit the bulkhead connection. Mild steel (St 35) is recommended.
Tighten the external pipe to the bulkhead connection the same way as outlined in step 2.
1. The generating set (or engine) should be installed in its final position before any external pipes are con-
nected.
2. Fasten the flexible pipe connection to the engine according to the following procedure. All stud coupling
parts should be lubricated with engine oil.
Remove the nut from the stud coupling of the engine. In case of flexible pipe connection of type
4V35A1591, put the nut on the pipe end of flexible connection.
Remove the ring from the stud coupling of the engine. In case of flexible pipe connection of type
4V35A1591, slip the ring over the pipe end of flexible connection with the thinner end outwards against
the bottom of the stud coupling.
Screw the nut with flexible connection and ring manually to the stud coupling until finger tight.
Push the flexible pipe connection against the bottom of the internal cone of the fitting body.
Mark the position of the pipe as well as the nut with a marker pen. This will guide you to tighten the
nut the correct number of turns.
Tighten the nut 1 turn while the pipe is prevented from turning.
3. Connect the free end of the flexible pipe connection to the external piping.
The flange of the external pipe should be in line with the connection of the engine. No twisting, com-
pression or elongation of the flexible pipe connection is allowed, i.e. it should fit between the connec-
tions in a straight position without reshaping. Align the external pipe and weld the counter flange to
the pipe.
Fasten the fixed flange of the flexible pipe connection with a gasket between the flanges.
Oil the threads of the screws and nuts, fit all screws and tighten until finger tight.
Tighten screws in a crosswise sequence using a socket wrench. Increase the tightening torque
gradually until the final torque is achieved.
4. Anchor the external pipe to the steel structure of the ship close to the flange. Observe that the pipe
clamping must be very rigid in order to prevent vibration and movement of the flexible pipe connection.
Most problems with bursting of the flexible connection originate from poor clamping.
5. The flexible pipe connection must be protected from external mechanical damage. There must be
enough space around the flexible pipe connection for regular supervision and maintenance.
2.6 Drawings
tobeadded Generating set drawing, W 9L20 ......................................................................... 2-15
2V69C0278e Engine room arrangement ................................................................................... 2-16
DAAE006367- Service space requirements ................................................................................ 2-17
tobeadded Location of sensors and el. components ............................................................. 2-18
DBAA388012a Generator technical data sheet ............................................................................ 2-19
DBAA406985- Tools for diesel engine ......................................................................................... 2-20
DBAA406989- Spare parts for diesel engine ............................................................................... 2-22
4V35A1591b Flexible pipe connection for fuel pipe ................................................................... 2-24
4V35A2939a Flexible pipe connection for fuel pipe ................................................................... 2-25
4V60B0093k Flexible hose ........................................................................................................ 2-26
4V60B0095o Flexible hose ........................................................................................................ 2-27
3V60D0025l Flexible rubber bellows for water pipe .................................................................. 2-28
4V69L1585e Installation of the generating sets ........................................................................ 2-29
DAAE002455a Factory acceptance test ....................................................................................... 2-34
te d
da u p
e l b
wi l
i n g
w ra
d e
Th
te d
da u p
e l b
wi l
i n g
w ra
d e
Th
1. INTRODUCTION
This instruction applies to installation of Wrtsil 20 generating sets on RD 314 and
RD 315 resilient mounts.
Generating sets, comprising engine and generator mounted on a common base frame
are usually installed on resilient mounts on the foundation in the ship.
The resilient mounts reduce the structure borne noise transmitted to the ship and also
serve to protect the generating set bearings from possible fretting caused by hull
vibration.
The number of mounts and their location is calculated to avoid resonance with
excitations from the generating set engine, the main engine and the propeller. The exact
positions of the mounts are indicated in the generating set drawing.
Note!
To avoid induced oscillation of the generating set, the following data must be sent by
the shipyard to Wrtsil at the design stadium (not less than 16 weeks before
delivery).
Main engine: Speed (rpm) and number of cylinders.
Propeller: Shaft speed (rpm) and number of propeller blades.
2. FOUNDATION
The foundation for the common base frame must be rigid enough to carry the load from
the generating set. The recommended foundation design is shown in figure 1.
The seating top plate is to be machined at the locations of the resilient mounts in order to
provide an adequate load bearing surface and to ensure that the mounting surfaces are
in parallel.
The lateral distance between the mounts differs depending on the number of cylinders of
the engine and the type of generator. Refer to the generating set drawing.
2 (5) 4V69L1585 e
3. RUBBER MOUNTS
Conical resilient mounts, type RD 314 B or RD 315 HD from RUBBER DESIGN B.V. are
used, see figure 2.
The mounts are designed to withstand both compression and shear loads. Additional
side or end buffers are not required to limit the movements of the generating set since
the mounts are equipped with an internal, adjustable central limiter. The centre stud in
the mounts is split in order to facilitate replacement of the mounts, if required.
The rubber in the mounts is natural rubber and it must therefore be protected from oil,
oily water and fuel.
3 (5) 4V69L1585 e
1. Drill the holes in the seating top plate for the M16 fastening screws according to the
drilling scheme in the generating set drawing.
2. Machine the seating top plate at the locations of the resilient mounts.
3. Mount the flexible mounts to the common base frame, if not already mounted.
4. Lift in the generating set and lower it onto the foundation. Use M16 screws to verify
that the position of the drilled holes match the corresponding holes in the foot of
each resilient mount.
(Brackets with adjusting screws, temporarily welded to the ship foundation are useful
for the alignment in horizontal direction during this work step).
4 (5) 4V69L1585 e
5. Jacking screws are used for levelling the installation. The common base frame is
provided with threaded holes for M20 jacking screws, see figure 3. Install M20 x 160
DIN933 8.8 jacking screws in the threaded holes. The jacking screws are to be
supplied by the shipyard. Steel chocks should be used under the jacking screws in
order to avoid bending of the screws and to increase the lift.
6. It must be verified that the generating set is not resting on the internal limiters in the
mounts. Hold the stud with a 19 mm spanner and loosen the M27 nut, which fastens
the mount to the common base frame. Check that the stud can easily be turned with
the 19 mm spanner. If this is not possible, release the load on the generating set by
means of the jacking screws until the limiter can be easily turned. Turn the stud two
turns in anti-clockwise direction. Release the jacking screws and check again that
the stud can easily be turned.
NOTE! The central limiter and the stud are divided in order to facilitate easy
replacement of the mount. If the limiter is resting on the foundation due to foundation
height variations, or if the limiter has been tightened down too hard against the
foundation, then the stud will come out of the limiter, when the stud is turned in
counter-clockwise direction. If this happens, turn the stud back into the limiter
against the foundation. Then install four M12 screws in the threaded holes in the foot
of the mount and elevate the mount about 1 mm so that the limiter no longer touches
the foundation. Turn the stud two turns in counter-clockwise direction and remove
the M12 screws.
5 (5) 4V69L1585 e
In the normal case the limiter should be able to turn freely, when the mount is
compressed by the weight of the generating set. It is in such case convenient to use
a 4 mm feeler gauge to set the buffer clearance. There is a slot in the foot of the
mount, where a feeler gauge can be inserted. Turn the limiter down against the
feeler gauge (lightly) and pull out the feeler gauge.
If the limiter is turned down carefully against the foundation, it is also possible to
achieve the desired buffer clearance (4mm) by turning the stud two turns in counter-
clockwise direction.
Repeat the above procedure until all limiters can be turned freely with the full
installation load applied.
7. Check that each mount is level. Measure and record the vertical distance from the
machined surface on the foot of the mount to the top casting, on two sides of the
mount, in longitudinal direction of the generating set. The difference between
measured distances should not exceed 0.5 mm for the same mount. Calculate and
record the average value for each individual mount.
8. Check that all mounts are evenly compressed by comparing the average values
obtained in previous step. The maximum permissible difference in compression
between the mounts is 2 mm along one side of the generating set.
10. Fasten each mount to the seating top plate with four M16xL 8.8 DIN 931 screws and
DIN 985-8 self locking nuts. Suitable flat washers (17/30 s3 DIN 125A) must be
used. Lubricate the threads with engine oil and tighten to 200 Nm.
11. Set the internal buffer working clearance to 4 mm for each mount according to the
procedure explained in workstep 6.
12. Tighten the M27 nut. Hold the spindle with a 19 mm spanner and tighten the M27
nut to a torque of 300 Nm.
13. The mounts should preferably be allowed to settle for a minimum of 48 hours, due to
initial creeping, before lining up pipework, etc.
1 Introduction
The test is carried out as an overall check of the manufacturing quality and to establish that
the contractual commitments have been fulfilled. The Factory Acceptance Test (FAT)
comprises of a running-in part and an official FAT part.
The test is carried out in accordance with ISO 15550. The function of built on ancillary
systems and the performance of the engine is checked according to ISO 15550. Results are
recorded in a test report signed by Wrtsil, customer (if present) and a representative from
a classification society.
At the end of the factory acceptance test the engine is inspected by the same
representatives mentioned above.
After inspection, the engines are protected against corrosion, cleaned and painted before
packing and shipment.
2 Test setup
Auxiliary engines are tested as generating sets, i.e. mounted on a common base frame
together with the alternator. The alternator is loaded with resistive load using water resistor.
Auxliary engines without generator are tested as generating sets using in-house generator,
but without any load acceptance tests because of not identical inertia.
The alternator power cables are connected to the switchboard and Automatic Voltage
Regulator (AVR) is connected if it is supplied as a loose item.
The common base frame of the generating set is mounted on the same flexible mounts that
will be delivered for installation on board if vibration measurements are needed. Necessary
pipe connections between the engine and the test bed systems are made using in-house
flexible hoses.
The cold alignment of the crankshaft is checked in the main assembly line or in the
alternator assembly cell. The measurement record is available at the test run department.
If the engine is equipped with a mechanical governor and a speed setting motor, the motor
is connected to a PC from which raise and lower commands can be given and the running
speed selected. If the engine is fitted with an actuator and electronic governor, the running
speed is controlled by a mA-signal from the in-house Woodward 721 Digital Controller.
If the engine is equipped with Wrtsil Engine Control System (WECS) the measurement
logics and safety functions are located in the engine mounted control system. All engine
mounted measurements are shown in the control room operator station and customer
facility display.
2(10) DAAE002455 a
Check that measurements values in operator station are updated and that they are normal
for standstill condition. Check that there is no leakage when lubricating oil, fuel oil and
cooling water systems have been filled.
Check that there is no leakage in starting- and control air systems and that the engine starts
rotating when pressing the starting air solenoid valve.
Blow the engine by rotating it with starting air while keeping indication cocks open.
Check that there is no leakage in lubricating oil, fuel oil and cooling water systems.
Check the function of the local control buttons (start, stop and shutdown reset)
Verify that the engine speed (ST173 and ST174) are shown on the LDU
Verify that the engine speed is shown on the Oil Mist detector display
Verify that the backup meters are working and show correct values
Verify that the hour counter is working
Check the second lube oil pressure trip (at 2.0 bar, sensor PTZ201)
Check the function of the local control buttons (Emergency stop, start, remote start, stop
and shd. reset)
Verify that the meters are working and show correct values
Verify that the hour counter is working
Verify that the engine speed is shown on the local gauge
2.4 Testing of safeties with running engine
Check the first lube oil pressure trip (at 2.0 bar, sensor PT201)
Check the first overspeed trip (1,15 x nominal speed, sensor ST173) by manually increasing
the fuel rack
Check the second overspeed trip (1,18 x nominal speed, sensor ST174) by disabling the
first overspeed trip and manually increasing the fuel rack
Notes:
Set-points of pressure switches have factory settings and the switches are not recalibrated.
It is a classification society requirement that all shutdown functions and alarm set-points are
verified onboard when the ship is commissioned, regardless of any previous tests.
3(10) DAAE002455 a
3 Test Run
The test run is started with a running-in phase. The purpose of the running-in is to make
sure that possible manufacturing defects and leakages are eliminated and that all bearing
surfaces and piston rings are run in smoothly before the engine is delivered.
During the running in process the engine loaded in steps. Between each step the engine is
allowed to idle for five minutes, see Fig. 1. Marine Diesel Oil (MDO) is always used during
the running in process.
load
100%
75%
50%
25%
0%
0:00 0:30 1:00 1:30 2:00 2:30 3:00 3:30 4:00 time (h)
After running-in the test run is followed by the official FAT phase according to the program
stated in the contract. In addition to the running-in load-points auxiliary engines are tested at
100 and 110 % load. The duration of these is dependent on the requirements by the
classification society concerned. If stated in the contract the fuel type used at 100 and
110 % can be Heavy Fuel (HF) with a viscosity of 180 cSt. If so an additional 20 min at
100 % load on MDO is run after completion of HF running to clean the heavy fuel from the
engine. See examples of official FAT programs in Fig. 2 to 5 below.
load
100%
75%
50%
25%
0%
2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 time (h)
4(10) DAAE002455 a
Fig. 2 Official FAT program for Auxiliary engines for DNV, LR, CCS (MDO only)
load
100%
75%
50%
25%
0%
2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 time (h)
Fig. 3 Official FAT program for Auxiliary engines for DNV, LR, CCS (HF+MDO)
load
100%
75%
50%
25%
0%
2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 time (h)
Fig. 4 Official FAT program for Auxiliary engines for ABS, BV, RINA, MRS, KR, NK (MDO only)
load
100%
75%
50%
25%
0%
2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 time (h)
Fig. 5 Official FAT program for Auxiliary engines for ABS, BV, RINA, MRS, KR, NK (HF+MDO)
5(10) DAAE002455 a
Apart from these classification societies GL has same requirements as ABS, BV, RINA,
MRS, KR and NK apart from 110 % load that needs to be run 45 min. Other durations than
these can also be run depending on what has been agreed in the contract.
Performance data is recorded at 25, 50, 75, 100 and 110 % load. According to ISO 15550,
the following parameters are recommended to be measured:
6(10) DAAE002455 a
The firing pressure of each cylinder is measured by a pressure indicator. The acceptance
criteria at 100% load are:
- The mean value of all cylinders is to be kept within the tolerances of +- 6 bar
(HFO) and +- 7 bar MDO
- The maximum deviation for any two cylinders to be within 10 bar
- The maximum deviation from mean value for each cylinder is 6 bar and no
cylinder is allowed to exceed:
200 bar for 900/1000rpm (C3 model)
190 bar for 900/1000rpm
180 bar for 720/750rpm
The exhaust gas temperature is measured for each cylinder. The acceptance criteria at
100% load are:
7(10) DAAE002455 a
The charge air pressure is measured using the engine mounted pressure gauge.
B1 Brake power
B2 Specific fuel consumption
The brake power for the engine is calculated from the measured electrical active power and
the generator electrical efficiency. The efficiency of the generator is available from the
manufacturers data sheet and is provided by the marine department. Data sheets for in-
house generators are available at the test run department. The electrical power can be read
directly from the operator station.
The fuel oil consumption is measured with a scale. The consumption measuring system will
automatically measure the time the engine needs to consume a predetermined amount of
fuel, usually 2,5 - 20 kg, depending on the size of the engine.
The acceptance criteria for the engine fuel consumption are stated in the contract.
Samples of the fuel are periodically sent to an independent authority for analysis. The latest
analysis is available at the test run department on request.
To correct for ambient conditions during test differing from ISO 15550 standard reference
conditions, conversion formula as stated by ISO 3046-1, are used to obtain the specific fuel
consumption. See formula below.
In case the specific fuel consumption is presented as fuel consumption without engine
driven pumps the following reductions from the SFOC will be made since the engine is
equipped with following on-built engine driven pumps:
8(10) DAAE002455 a
Conversion Formula
1
= k 0.7(1 k ) 1
m
m n s
p T T
k = x r cr
pr Tx Tcx
M S MLS
BE = 3600 [g/kWh]
PS
Q
BISO = BE x EDP [g/kWh]
k Qr
Where: k = ratio of indicated power
= power adjustment factor
px = barometric pressure during test [kPa]
pr = standard reference barometric pressure [100 kPa]
Tx = air temperature during test [K]
Tr = reference air temperature [298 K]
Tcx = charge air coolant temperature during test [K]
Tcr = reference charge air coolant temperature [298 K]
m = 0,7
n = 1,2 exponents to be used for 4-cycle diesel engines acc. to ISO 3046-1, table 3
s = 1,0
m = mechanical efficiency, 0.8
Qx = net calorific value of the fuel during test [MJ/kg]
Qr = reference net calorific value of fuel [42.7 MJ/kg]
BE = fuel oil consumption on test bed [g/kWh]
BISO = fuel oil consumption according to ISO [g/kWh]
M = measured fuel quantity [g]
MLS = flow of clean leak fuel [0.1 g/s cyl]
P = engine output [kW]
S = time [s]
EDP = engine driven pumps [4 g/kWh]
9(10) DAAE002455 a
[ISO 15550] Functional checks which may additionally be carried out. Selection from list C shall be
made by agreement between the manufacturer and customer.
The speed governor and load acceptance of the generating set are tested by making rapid
load changes. The load is applied in three steps, normally 0-33-66-100%, or 0-40-70-100%.
According to the rules of the classification societies the instantaneous speed drop may not
exceed 10 % of rated speed. The recovery time is 5 seconds, which means that the speed
must be within 1% of the rated speed after 5 seconds. The minimum load steps
recommended by the International Association of Classification Societies (IACS) are
presented in Fig. 6.
The individual classification societies may specify different a load application scheme, but
three steps can normally be accepted by most classification societies if the load
management system onboard will be built accordingly. The customer has to clarify this with
the classification society concerned.
Load application tests onboard must be performed with the contracted fuel in order to
achieve the same performance as in the factory test run.
The speed governor performance can be followed in the historical trends in the operator
station where engine speed, generator voltage and output and turbocharger speed are
graphically recorded.
10(10) DAAE002455 a
Other tests or checks can be done in combination to the factory acceptance test if
specifically stated in the contract, i.e. noise-, vibration- or emission measurement.
For generating sets a hot crankshaft alignment is done when the test run is finished, the
control is done to check the straightness of the crankshaft when it is in running (hot)
condition and thereby verify correct installation on the common base frame. However, the
alignment in hot condition is to be verified after final installation on board as well.
5. Inspection of engine
After the test run, the customer and the representative of the classification society are
invited to supervise the inspection of the engine. See instruction 4V59L0169 for details of
the procedures.
6. Finishing
After the inspection of the engine, there are a number of different items checked, just before
delivery. A separate instruction 4V59L0171 describes the details and other routines after
the test run, as well as the internal and external anticorrosion protection treatment and
painting of the engine.
The tests are made according to the factory internal health and safety instructions and way
of working. These are governed by the ISO 18001 standard.
NOTE! This installation is designed for the fuel specified in section "Fuel oil specification". The limits
below are general for MDF operation.
1) Use of ISO-F-DMC category fuel is allowed provided that the fuel treatment system is equipped with a fuel oil separator.
2) Additional properties specified by the engine manufacturer, which are not included in the ISO specification or differ from
the ISO specification.
3) A sulphur limit of 1,5 % m/m will apply in SOx emission controlled areas designated by International Maritime Organization.
There may be also other local variations.
4) A fuel shall be considered to be free of used lubricating oil (ULO), if one or more of the elements calcium, zinc and phos-
phorus are below or at the specified limits. All three elements shall exceed the same limits before a fuel shall be deemed
to contain ULO.
where:
FE = Fuel oil consumption for the engine, site fuel [kg/h]
FSH = Fuel oil consumption for the engine at ISO conditions [g/kWh]. See section "Technical data".
Add a tolerance of 5%.
Adjust the stated fuel consumption according to the following:
Add 1 g/kWh since the fuel oil pump is built on the engine
QN = Site fuel caloric value [MJ/kg]
PS = Shaft output for the engine [kW]
Minimum flow requirement for a fuel oil system component or unit is calculated as follows:
where:
Q = Min. required capacity at injection temperature [m3/h] (for one engine)
FE = Fuel consumption for the engine, site fuel [kg/h]
CF = Circulation factor = 5:1
FUEL= Fuel oil density at injection temperature [kg/m3]
General remarks
The fuel treatment system should comprise a settling tank and separators to supply the engine(s) with
sufficiently clean fuel. The recommendations for the design of the separator should be closely followed.
Separator system
Also marine diesel fuel must be cleaned in an efficient centrifugal separator before entering the day tank
as fuel may be contaminated in the storage tanks.
Design data:
Pressure, max 0.5 MPa (5 bar)
Temperature 40 C
A suction filter should be fitted to protect the feed pump. The filter can be either a duplex filter with change
over valves or two separate simplex filters. Fineness 0.5 mm.
where:
P = heater capacity [kW]
m = capacity of the separator feed pump [l/h]
t = temperature rise in heater [C]
Separator (1S01)
The fuel oil separator should be sized according to the recommendations of the separator maker. The lower
the flow rate, the better the efficiency. The required service throughput of the separator is:
where:
QLFOS = Required capacity at 15C [m3/h] (for one engine)
FE = Fuel consumption for the engine, site fuel [kg/h]
FUEL = Density of the fuel at 15C [kg/m]
CS = Separator safety factor, e.g. 15%.
3.5 Drawings
DAAE058154- Internal fuel oil system ......................................................................................... 3-6
DAAE058155- Recommended fuel oil system ............................................................................. 3-7
DAAE015263b Recommended transfer and separating system .................................................. 3-8
DBAA406400- 1E04 - Cooler (MDF return line), dimensional drawing ........................................ 3-9
DBAA406400- 1E04 - Cooler (MDF return line), technical data .................................................. 3-10
Z102346- 1F07 - Suction strainer (MDF) dimensional drawing ............................................ 3-11
DPI_4-36-2- 1F07 - Suction strainer (MDF) DPI ...................................................................... 3-12
DBAA406434- 1P03 - Circulation pump (MDF) dimensional drawing ......................................... 3-13
DBAA406434- 1P03 - Circulation pump (MDF) Driver specification ............................................ 3-14
DBAA406434- 1P03 - Circulation pump (MDF) Pump calculation ............................................... 3-15
SPECIFICATION SHEET
Service : Fuel oil cooler Date : 26-apr-2007
Client : Wartsila Finland Ship Power Your ref.: Ulstein PX105-1/-2,
Coolertype : P10-3P-L=600 Our ref.: P070709-01-0
Version : PF/MV Drawing : PS10-0-0005
General
Fouling (extra surface) 20.00 %
Overall transfer rate (internal) 2440 W/(m2K)
Log mean temp diff. 9.66 C
Number of tubepasses 3 -
Nominal tube length 600 mm
Tube diameter 8.30 mm
Weight cooler empty (approx.) 14 kg
Materials
Tubes: Mat.nr 2.0872 - CuNi10Fe1Mn
Tubeplates: Mat.nr 2.0540 - CuZn35Ni
Baffles: Aluminium
Fins: Aluminium
Shell: C.Steel / nod.cast iron
Bonnet/cover: Bronze (with anodes)
Remarks
Design and Inspection: Bloksma
'''
(
%&'
) *
"! # $
23 45
%
C
Z , / 0 1
0,T p
T '
T
p '
p
' ,0
L
T '
T '
}~ s
>Nss H Q >QK s Q K sCK> >
> "> Hs >> KQsC
!"
#
$%&'()* +, -./0/
1
2
3 457698: ;< =
>@?BAC
D E7F GH I
JKL MNOP
Q
RTSU
V9WXBWYZ[
\
]^_
` abc
dfeg hi9jk
l mk no p
qr sutfvw x7y
z{x|}f~
u9 97
9
77
9
f
9
7
9
9u u9979
u
A5A5
S F 1
!"#%$
&'
()*+ , - . / 0 0 3
1 24%5 6 78 9 :
;< =%> ?
@%ACBD
E
FCGHJI
K LMNCO PQRS
TUV
W%XZY[Z\ ] ^3_`%a b cd
e f ghiCj
klmn opqr
stvu w w xzy{%| } ~
FHG IKJLNMHLNOQP>R SUTWVNXHYKZQZ>[HXY]\H^`_QaCbHc>dfe gh"i jQk>lmonqpsr"tNuwvNx yz{ |
Driver specification
Inquiry from
Our ref. No
Cust. ref. No. AKER Yards 728 MDF pumps
Item No
Selected pump ACE 025N3 NTBP
BC WU-DA 80MJ-D-2
Manufacturer BC
Model WU-DA 80MJ-D-2
Frequency 60 Hz
Power 1.25 kW
Nominal speed 3440 rpm
Voltage 690 V
Y/D Y
Current 1,6 A
Start current 10.2 A
IEC size 80
Weight 9.0 kg
Noise 59.0 dB(A)
Efficiency 81.0 %
cos(fi) 0.82
Isol/prot F/IP55
Classification Marine/Industrial
Mounting IM3001/B5
Cooling IC41
Cable 1xM20*1.5+M20*1.5
Material Aluminium
Inertia 0.0019 kgm
Torque 9.99 Nm
Pump calculation
Inquiry from
Our ref. No
Cust. ref. No. AKER Yards 728 MDF pumps
Item No
Fluid type Marine Diesel Oil
Driver WU-DA 80MJ-D-2 / 3440 rpm / 1.25 kW
Selected pump ACE 025N3 NTBP
NOTE! Contact Wrtsil before using a non approved lubricating oil. Lubricating oils that are not ap-
proved have to be tested according to our procedures. Should unapproved lubricating oils be
used during the engine warranty period, and there exist no agreement with the engine manufac-
turer about testing, the engine guarantee does not hold.
Fuel categories A and B, recommended in gas oil or marine diesel oil installations. If ISO-F-DMC is used
as fuel, the recommended lubricating oils are according to fuel category C.
Fuel category C, recommended in the first place when operating on HFO or an fuel with high sulphur content
in order to reach full service intervals. BN50...55 lubricating oils are preferred in the first place.
Table 4.2 Approved lubricating oils for fuel categories A and B.
BN 30 lubricating oils should be used in HFO in installations with SCR (Selective Catalyctic Reduction), if
better total economy can be achieved despite shorter oil change intervals. Lower BN may have a positive
influence on the lifetime of the SCR catalyst.
Design data:
Separating temperature 9095 C
Capacity according to the formula below:
where:
Q = actual flow through the separator [l/h]
P = total engine output [kW]
n = number of through-flows of the oil volume/day (4 for engines operated on MDF)
t = Separating time/day [h]
23h for separators with total discharge, 24h for separators with partial discharge
4.4 Drawings
DAAE058156- Internal lubricating oil system .............................................................................. 4-6
DAAE058157- Recommended lubricating oil system .................................................................. 4-7
4V76E2522a Recommended crankcase ventilation .................................................................. 4-8
where:
VAIR = Total air volume required [m3]
nST = Number of starts [pcs]
p = Allowed pressure difference [bar], max start pressure (30 bar) - min air pressure (18 bar).
where:
QST, i = Consumption for one start for engine i [Nm3/h]
where:
QC = Recommended capacity [m3/h]
VSAV = Starting air vessel volume [m3]
nSAV = Number of starting air vessels of equal size [pcs]
nC = Number of starting air compressors [pcs]
pN = Nominal pressure [bar]
t = Time for filling from atmospheric pressure to nominal pressure [h]
At least two starting air compressors must be installed. It is recommended that the compressors are capable
of filling the starting air receiver from minimum to maximum pressure in 15...30 minutes. For exact determ-
ination of the minimum capacity, the rules of the classification societies must be followed.
Separator (3S01)
An oil and water separator should always be installed in the pipe between the compressor and the air vessel.
Depending on the operating conditions of the installation, an oil and water separator may be needed in the
pipe between the air vessel and engine. The starting air pipes should always be drawn with slope and be
arranged with manual or automatic draining at the lowest points.
5.4 Drawings
DAAE058158- Internal starting air system .................................................................................. 5-3
DAAE058159- Recommended starting air system ...................................................................... 5-4
Property Limit
pH, min, 6.5
Hardness, max. 10 dH
Chlorides, max 80 mg/l
Sulphates, max. 150 mg/l
For raw water, evaporated water and a good quality tap water are normally recommended. If a reverse os-
mosis process results in water quality specified above, that can be used as well. Untreated sea water and
fresh water as well as rain water are unsuitable raw water qualities.
Product Supplier
CorrShield NT 4293 GE Betz Europe
CorrShield NT 4200 Interleuvenlaan 25
B-3001 Heverlee, Belgium
GE Betz
4636 Somerton Road
Trevose
PA 19053, United States
Cooltreat 651 Houseman Ltd
The Priory, Burnham
Slough SL1 7LS, UK
Product Supplier
DEWT-NC powder Ashland Specialty Chemical
Liquidewt Drew Marine
Maxigard One Drew Plaza
Boonton, NJ 07005, USA
Dieselguard NB Unitor ASA
Rocor NB liquid P.O. Box 300 Skyen
Cooltreat AL N-0212 Oslo, Norway
Drewgard 4109 Ashland Specialty Chemical
Drew Industrial
One Drew Plaza
Boonton, NJ 07005, USA
Havoline XLi S.A. Arteco N.V.
Technologiepark-Zwijnaarde 2
B-9052 Ghent/Zwijnaarde, Belgium
In order to prevent corrosion in the cooling water system, the instructions of right dosage and concentration
of active corrosion inhibitors should always be followed. The information can be found in the table below.
Table 6.3 Dosage instructions
Note 1 For many products the recommended minimum and maximum limits are listed in the table above. Since
the amount of active corrosion inhibitors, especially nitrites, is decreasing during the service of engines,
the engine manufacturer recommends to start the dosage from the upper level of indicated range.
Note 2 The nitrite content of nitrite-based cooling water additives tends to decrease in use. The risk of local
corrosion increases substantially when nitrite content goes below the recommended limit.
Note 3 Cooling water additive manufacturers can indicate the required nitrite content measured either as sodium
nitrite, NaNO2 or as nitrite, NO2. 1 mg/l as NO2 equals to 1.5 mg/l as NaNO2.
Design data:
Heat to be dissipated/engine see "Technical data" and drawing "Recommended cooling water system"
Fresh water flow/engine see "Technical data" and drawing "Recommended cooling water system"
Pressure drop on the FW side, max. 60 kPa (0.6 bar)
FW temp. after cooler, max 38 C
Sea water flow acc. to makers standard, normally 1.2...1.5 x FW flow
Pressure drop on the SW side, norm 80...140 kPa (0.8...1.4 bar)
Margin for fouling and safety, min 15%
Design data:
Pressure from the expansion tank at pump inlet 70 - 150 kPa (0.7...1.5 bar)
Volume min. 10% of the system, however min. 100 l.
6.3.5 Orifices
An orifice must be mounted in each cooling water circuit branch to be able to correctly balance the flow.
An orifice shall also be installed in each venting pipe directed to the expansion tank.
When a thermostatic valve is used to bypass a cooler, an orifice should be mounted in the bypass line so
that the valve "sees" equal back pressures in the cooler and the bypass line.
6.5 Drawings
DAAE058160- Internal cooling water system .............................................................................. 6-6
DAAE058161- Recommended cooling water system .................................................................. 6-7
4V60D0343- Recommended cooling water circuit deaerator .................................................... 6-8
DBAA396944- 4V02 - Temperature control valve (heat recovery), dimensional drawing ............ 6-9
DBAA396944- 4V02 - Temperature control valve (heat recovery), installation instruction ........... 6-10
10020-05 4N01 - Preheating unit, dimensional drawing ...................................................... 6-12
11472-03 4N01 - Preheating unit, electrical drawing ........................................................... 6-13
DBAA396949- 4V03 - Temperature control valve (LT), dimensional drawing .............................. 6-15
DBAA396949- 4V03 - Temperature control valve (LT), el. PID valve controller ........................... 6-16
DBAA396949- 4V03 - Temperature control valve (LT), temp sensor ........................................... 6-17
DBAA396949- 4V03 - Temperature control valve (LT), installation instructions ........................... 6-18
B
Inspection AMOT
THERMOSTAT
A
C
This sheet is distributed for information purposes only. It is not to be construed as becoming part of any contractual or warranty obligations of Amot Controls
Limited, unless expressly so stated in a sales contract. Amot Controls Limited reserves the right to make product design changes at any time without notice.
7 January 2008
Aker Yards 728 - a1
Installation Planning Instructions
11472-03 - 4N01 - Preheating unit, electrical drawing
79
Accessories
9.1.2 Installation
Dimensions
80
Accessories
81
Accessories
WARNING
Two holes for the mounting of the
controller are located under the flap
that covers the terminal connections.
The power supply to the controller
must be isolated before the flap is
lifted to prevent electric shock to
personnel.
Electrical Connections
Electrical connections to the 8072D are made through terminal connections
beneath the hinged flap as follows:
To maintain acceptable operating conditions for the engines and to ensure trouble free operation of all
equipment, attention shall be paid to the engine room ventilation and the supply of combustion air. The air
intakes to the engine room must be located in a way that water spray, rain water, dust and exhaust gases
cannot enter the ventilation ducts and the engine room. The dimensioning of blowers and extractors should
ensure that an over pressure of about 5 mmWC is maintained in the engine room in all running conditions.
For the minimum requirements concerning the engine room ventilation and more details, see applicable
standards, such as ISO 8861.
The amount of air required for ventilation is calculated from the total heat emission to evacuate. To de-
termine , all heat sources shall be considered, e.g.:
where:
Qv = Amount of ventilation air [m3/s]
= total heat emission to be evacuated [kW]
= density of ventilation air 1.13 kg/m3
t = Temperature rise in engine room [C]
c = Specific heat capacity of the ventilation air 1.01 kJ/kgK
The engine room ventilation has to be provided by separate ventilation fans. These fans should preferably
have two-speed electric motors (or variable speed). Thus flexible operation is possible, e.g. in port the ca-
pacity can be reduced during overhaul of the main engine when it is not preheated (and therefore not
heating the room). The ventilation air is to be equally distributed in the engine room considering air flows
from points of delivery towards the exits. This is usually done so that the funnel serves as an exit for the
majority of the air. To avoid stagnant air, extractors can be used. It is good practice to provide areas with
significant heat sources, such as separator rooms with their own air supply and extractors.
For very cold conditions a preheater in the system should be considered. Suitable media could be thermal
oil or water/glycol to avoid the risk for freezing. If steam is specified as a heating system for the ship the
preheater should be in a secondary circuit.
Example, according to the diagram: Figure 7.2 Condensation in charge air coolers
At an ambient air temperature of 35C and a relative humidity
of 80%, the content of water in the air is 0.029 kg water/ kg dry
air. If the air manifold pressure (receiver pressure) under these
conditions is 2.5 bar (= 3.5 bar absolute), the dew point will be
55C. If the air temperature in the air manifold is only 45C, the
air can only contain 0.018 kg/kg. The difference, 0.011 kg/kg
(0.029 - 0.018) will appear as condensed water.
where:
v = gas velocity [m/s]
m = exhaust gas mass flow [kg/s]
t = exhaust gas temperature [C]
D = exhaust gas pipe diameter [m]
Each exhaust pipe should be provided with a connection for measurement of the backpressure. The con-
nection should be close to the engine, but not closer than 4..5 pipe diameters from the transition to larger
pipe diameter after the bellows on the turbocharger. Neither should the connection be closer than 3..4 pipe
diameters after a 90 degree pipe bend. The connection should be installed while the exhaust gas outlet on
the turbocharger is protected with a cover.
The exhaust gas pipe should be provided with water separating pockets and drainage.
The exhaust pipe must be insulated all the way from the turbocharger and the insulation is to be protected
by a covering plate or similar to keep the insulation intact. Closest to the turbocharger the insulation should
consist of a hook on padding to facilitate maintenance. It is especially important to prevent the airstream
to the turbocharger from detaching insulation, which will clog the filters.
8.2.2 Supporting
It is very important that the exhaust pipe is properly fixed to a support rigid in all directions directly after
the bellows on the turbocharger. The bellows on the turbocharger may not be used to absorb thermal ex-
pansion from the exhaust pipe. The first fixing point must direct the thermal expansion away from the engine
and be located max. 3 diameters (bellows) away from the bellows on the turbocharger. There should be a
fixing point on both sides of the pipe at the support. Absolutely rigid mounting between the pipe and the
support is recommended at the first fixing point after the turbocharger. Resilient mounts can be accepted
for resiliently mounted engines with long bellows, provided that the mounts are self-captive; maximum
deflection at total failure being less than 2 mm radial and 4 mm axial with regards to the bellows. The nat-
ural frequencies of the mounting should be on a safe distance from the running speed, the firing frequency
of the engine and the blade passing frequency of the propeller. The resilient mounts can be rubber mounts
of conical type, or high damping stainless steel wire pads. Adequate thermal insulation must be provided
to protect rubber mounts from high temperatures. When using resilient mounting, the alignment of the exhaust
bellows must be checked on a regular basis and corrected when necessary.
After the first fixing point resilient mounts are recommended. The mounting supports should be positioned
at stiffened locations within the ships structure, e.g. decklevels, framewebs or specially constructed supports.
The supporting must allow thermal expansion and ships structural deflections.
Refer to section "Technical data" for the dimensions A and B in the figure above.
Installation procedure:
1. The engine or generating set should be installed in its final position before any external pipes are con-
nected.
2. Remove the protective cover from the exhaust gas outlet on the turbocharger. Be careful that no dirt
drops into the turbocharger.
3. Check the flow direction from the dimensional drawing of the bellows and install it on the turbocharger,
using the correct gasket between the flanges. Lubricate the threads of the screws with heat resistant
grease and tighten in a diagonal sequence.
NOTE! Do not remove the supports between the flanges of the bellows, until the installation procedure
has been completed and the exhaust pipe has been rigidly fixed. Should the supports (for
transport) have been removed, then prepare and install new supports so that the bellows is
stretched about 3 mm during installation.
4. Make a temporary protection cover and place it between the bellows flange and the smaller flange of
the connection piece. The thickness of the cover should be equal to the thickness of the gasket, which
will be installed between the flanges later. Preferably make the cover slightly larger than the flange dia-
meter.
5. Install the connection piece on the bellows with the protection cover between the flanges. Connect the
flanges temporarily with a number of screws. Use a sufficient number of screws to ensure that the
flanges are pulled together properly. If the bellows is aligned in a horizontal or tilted position, temporary
supporting of the connection piece and the bellows is needed during the installation.
6. Mount the counter flange to the larger flange of the connection piece, using the correct gasket between
the flanges. Use a sufficient number of screws to ensure that the flanges are pulled together properly.
7. Align the exhaust gas pipe to the counter flange. Do not force the connection piece in any direction.
NOTE! The exhaust gas outlet of a flexibly mounted engine will usually be displaced due to the
torque reaction as the load increases. In some cases it is necessary to compensate for the
torque reaction by installing the exhaust gas pipe with an initial lateral offset. Thus, if the
engine is flexibly mounted, Wrtsil should be contacted for further instructions.
In the case of a flexibly mounted generating set, which has a common base plate, there is
no lateral displacement due to the torque reaction.
8. Anchor the exhaust gas pipe to the ship structure as close as possible to the flange of the connection
piece. The supports must be made very rigid in order to prevent vibration and movement of the exhaust
gas pipe.
9. Weld the counter flange to the exhaust gas pipe.
10. Remove the connection piece and clean the exhaust gas pipe from slag and particles developed during
the welding. Remember to keep the entry into the turbocharger covered.
11. Remove the protection cover and install the connection piece with the appropriate gaskets.
12. Remove the temporary supports between the flanges of the flexible bellows.
13. Lubricate the threads of all screws with heat resistant grease and tighten in a diagonal sequence.
Refer to the drawing "exhaust gas bellows" drawing for dimensions and flow direction.
8.5 Drawings
DAAE058162- Internal charge air and exhaust gas system ........................................................ 8-6
3V37L0587a 5Z03 - Turbocharger cleaning device, dimensional drawing ................................ 8-7
3V60A4945- 5Z01 - Connection piece, dimensional drawing ................................................... 8-8
3V60B0020r 5H01 - Exhaust gas bellows, dimensional drawing .............................................. 8-9
3ES0342C 5R02 - Exhaust gas silencer with spark arrestor, dimensional drawing ............... 8-10
4ES0061 5R02 - Exhaust gas silencer with spark arrestor, installation instruction ............. 8-11
Transmission Loss, dB
5 20
0 0
31.5 63 125 250 500 1000 2000 4000 8000 20 25 30 35 40 45
1.20
1.00 4*m
0.80
v= ( m / s)
273
0.60
1,3 * * * NS 2
273 + t
0.40
v= flow velocity (m/s)
0.20
m= exhaust gas mass flow ( kg / s )
1
p = C * * *v2
2
3ES0342C - 5R02 - Exhaust gas silencer with spark arrestor, dimensional drawing
7 January 2008
Aker Yards 728 - a1
Installation Planning Instructions
4ES0061 - 5R02 - Exhaust gas silencer with spark arrestor, installation instruction
1/6
Rev. 09.03.2005 JH
12.7.2005 Date 20.8.1998
Author: T. Viitala
Doc. 4ES0061
INSTRUCTIONS FOR ASSEMBLY, OPERATION, AND MAINTENANCE OF EXHAUST
SILENCERS
These instructions can be applied to exhaust silencers with or without spark arrestors. Our silencer
models are suitable for attenuating noise generated by diesel engines, gas turbine engines,
compressors, vacuum pumps or out-blow pipes. Silencers equipped with spark arrestors are
suitable for shipbuilding and marine industry, and for environments, which are classified either as
inflammable or where there is a danger of explosion.
Weather conditions must be taken into account when choosing frame materials for silencers. In
normal inland weather conditions steel for general structural purposes is used as the material for
the frame structures. In corroding marine climate the most commonly used material is
weatherproof Cor-Ten steel. If there are corrosive gasiform acids in the environment, it is advisable
to choose acid proof stainless steel. The durability of a silencer can be maximized by paying
attention to the environment where the silencer is to be operated.
OPERATING PRINCIPLE
The operation of an exhaust silencer is based on absorptive and reactive attenuation, and on the
combination of the two, depending on the requirements set for noise attenuation. The type
designation on the dimensional drawing shows the silencer type.
ASSEMBLY
When the silencer is being stripped of its packing crate, lifting points and lugs should be checked.
Before assembly the silencer is checked visually. It is advisable to pay attention to possible
damages caused during the transport and to check the cleanliness of the inlet and outlet ducts of
the silencer. Note that there are plates at both ends of the silencer, which has to be removed
before checking the cleanliness and the final assembly. Impurities or extra objects are to be
removed. An exhaust silencer is equipped with a type plate that shows the type, model,
manufacturer, date of manufacture, flow direction, and total weight of the silencer.
Type:
Tag n:o
2/6
Before connecting an engine to exhaust piping, it is switched off or its exhaust fumes are by-
passed during the assembly of the silencer. The correct flow direction of the silencer is checked in
the type plate. Warning ! A wrong flow direction may damage the interior of the silencer and
decrease engine power due to increasing back pressure. In deliveries where counter-flanges for
the connection to exhaust piping are included, counter-flanges have to be unscrewed from the
flanges of the silencer.
When the silencer has been fitted and it is being connected to the piping, the intactness of the
seals should be checked. It is advisable to grease the sealing surfaces and hexagonal screws with
heatproof graphite-based lubricating oil. The flange joints are tightened in two stages, i.e. pre-
tightening and final torque tightening. The joints are tightened in turns from the opposite sides of
the flange joint.
LOCATION
The location of the silencer is important when choosing a suitable model. If the silencer is to be
placed high up, e.g. on the roof of a building or outdoors, one must also take into account the wind
loads on the silencer structures. If the silencer is placed in an environment likely to be exposed to
storms, it is advisable to contact the manufacturer of the silencer for further advice.
SUPPORTS
The silencer must be adequately supported. The perforation of the supports must accommodate
the increase of the length of the silencer. Oblong holes on the supports leave room for termal
expansion of the silencer structure during operation. In order to minimize vibration, flexible
fasteneres must be used as the supports to the frame of the exhaust silencer. Flexible fasteners
include the bellows compensator fitted between the piping and the silencer joint as well as the
isolation of the support structures and the silencer frame with the help of a fastening method that
damps vibrations.
3/6
If the silencer is equipped with sliding supports, the supports can be found from the silencer
package. The sliding supports are marked with a corresponding silencer drawing number. The
sliding supports are field welded to their right places during the assembly at the site.
The following aspects of supporting the silencer should be taken into account when choosing the
silencer type.
OPERATION
A silencer is designed for round-the-year, periodical, or round-the-clock operation. The maximum
temperature given in the type plate must not be exceeded during the operation. If the temperature
of the exhaust fumes is higher than that allowed for the silencer, the absorptive material in the
silencer may get damaged and the performance of the silencer deteriorate.
MAINTENANCE
4/6
Operation and Skeleton drawing of a Silencer Equipped with a Spark Arrestor.
Silencers equipped with spark arrestors are particularly well suited for marine industry and also for
other industry in cases where there is a danger of explosion or fire. The efficient collecting capacity
of the spark arrestor has been optimized with respect to back pressure and the nominal size of the
piping. Its operation is based on an in-built flow separator that directs the exhaust gas flows
towards the outer casing.
5/6
The top and bottom ends of a silencer may be loaded during operation up to a specified limit. The
maximum loads allowed are shown as static axial loads. Note! If there is a chimney pipe several
metres long and the chimney is longer than 3 metres, wind loads must also be taken into account.
When the total length of the silencer and the chimney pipe grows, the dynamic loads on the
structure will also have to be given proper attention. In unclear cases we recommend you to
contact the manufacturer.
Max Load F1
Max Load F2
Table 1. Reference values for static loads on the top and bottom flanges of a silencer.
6/6
9. Piping Arrangements
9.1 Recommendations regarding piping design
9.1.1 General
Fuel, lubricating oil, fresh water and compressed air piping is usually made in seamless carbon steel (DIN
2448) and seamless precision tubes in carbon or stainless steel (DIN 2391), exhaust gas piping in welded
pipes of corten or carbon steel (DIN 2458). Sea-water piping should be in Cunifer or hot dip galvanized
steel.
NOTE! The pipes in the freshwater side of the cooling water system must not be galvanized!
Attention must be paid to fire risk aspects. Fuel supply and return lines shall be designed so that they can
be fitted without tension. Flexible hoses must have an approval from the classification society. If flexible
hoses are used in the compressed air system, a purge valve shall be fitted in front of the hose(s).
It is recommended to make a fitting order plan prior to construction.
The following aspects shall be taken into consideration:
Pockets shall be avoided. When not possible, drain plugs and air vents shall be installed
Leak fuel drain pipes shall have continuous slope
Vent pipes shall be continuously rising
Flanged connections shall be used, cutting ring joints for precision tubes
Maintenance access and dismounting space of valves, coolers and other devices shall be taken into con-
sideration. Flange connections and other joints shall be located so that dismounting of the equipment can
be made with reasonable effort.
Table 9.1 Recommended maximum velocities on pump delivery side for guidance
NOTE! The diameter of gas fuel and compressed air piping depends only on the allowed pressure loss
in the piping, which has to be calculated project specifically.
Piping test pressure is normally 1.5 x the design pressure = 0.75 MPa (7.5 bar).
Standard pressure classes are PN4, PN6, PN10, PN16, PN25, PN40, etc.
9.1.6 Insulation
The following pipes shall be insulated:
All trace heated pipes
Exhaust gas pipes
Exposed parts of pipes with temperature > 60C
Insulation is also recommended for:
Pipes between engine or system oil tank and lubricating oil separator
Pipes between engine and jacket water preheater
System Methods
Fuel oil A,B,C,D,F
Lubricating oil A,B,C,D,F
Starting air A,B,C
Cooling water A,B,C
Exhaust gas A,B,C
System Methods
Charge air A,B,C
A = Washing with alkaline solution in hot water at 80C for degreasing (only if pipes have been greased)
B = Removal of rust and scale with steel brush (not required for seamless precision tubes)
C = Purging with compressed air
D = Pickling
F = Flushing
Pickling
Pipes are pickled in an acid solution of 10% hydrochloric acid and 10% formaline inhibitor for 4-5 hours,
rinsed with hot water and blown dry with compressed air.
After the acid treatment the pipes are treated with a neutralizing solution of 10% caustic soda and 50 grams
of trisodiumphosphate per litre of water for 20 minutes at 40...50C, rinsed with hot water and blown dry
with compressed air.
Fixed supports
Fixed supports are used:
Nearby equipment connections to protect equipment and flexible bellows from high tensions.
To direct thermal expansion in directions where it can be received.
To receive different forces acting on the pipeline.
Sliding supports
Sliding supports are used:
Sliding supports should be located to protect the pipeline, equipment and flexible bellows from high
tensions coming from thermal expansion.
To allow thermal expansion in directions where it can be received.
To receive different forces acting on the pipeline.
The first support after flexible bellows should be positioned as close as possible to the bellows. If the first
support is to far away from the bellows then the bellows lifetime will be shortened considerably, the pipe
is also exposed to increased forces that may injure the pipeline.
The second support should be positioned about 0.3...0.5 meter from the first support, the reason why it
should be so close to the first support is that this will reduce the vibrations of the pipe end.
The third support can be positioned about 0.8...1.1 meter from the second support. Pipe supports further
in the pipeline can be placed with the same distance from each other.
The minimum recommended flushing time is 24 hours. During this time the welds in the lubricating oil piping
should be gently knocked at with a hammer to release slag and the flushing filter inspected and cleaned
at regular intervals.
Either a separate flushing oil or the approved engine oil can be used for flushing.
When the major failure signal is activated, the engine will be shut down.
SI 518 TC A speed
This is a galvanically isolated analogue output signal. The signal type is 4-20 mA and max external load is
500 .
Range 0 75000 rpm.
The time between pulses shall be sufficiently long. After a correction it can take up to 30 seconds
before the actual adjustment has reached 95% of the set point change. The control system should
therefore wait at least 10 seconds before giving a new pulse.
The control system should preferably determine the length of the pulse based on the size of the desired
correction and then wait for 30 seconds or more before performing a new correction.
A control dead band should be implemented, allowing for an uneven load of min 2% of nominal
power and a frequency drift of min 1%.
The corrections should not be based on instantly sampled values. The corrections should be based
on the average value over several seconds. 10 seconds is a suitable time span.
10.7 Precautions
The automation system contains circuit boards that are sensitive both to damage by electrostatic discharge
(ESD) and mechanical damage. Therefore, the following precautions can significantly reduce the risk of
system failure or malfunction:
Protect all modules against moisture and uncleanness by using moisture proof covering during storing
at yard/site. If exposed to humidity during these stages, the components must be carefully dried.
Otherwise wiring connections may become unreliable.
Avoid ESD to modules by not touching circuit boards and module connectors without ESD protection.
Locate the communication cables between engine and control panels as far away as possible, at
least 300 mm, from power and high voltage cables. If this is not possible, pull the communication
cables in grounded steel conduits.
Make sure the engine is well grounded, not connected to external systems and that the power is
switched off before installation work is done near the engine. This is especially important during
electrical welding in the engine room.
When welding ensure that welding earth is close to the welding point.
Power-on of the automation system must not be done until a Wrtsil Service Engineer has checked
and approved the cabling/connections.
Cabling/connections should be done according to Wrtsil project specific drawings. Important is to
use shields and cable-pairs accordingly.
Keep cabinets and modules closed at all time, as far as practically possible. If opened for some
reason, avoid touching circuit boards and connector pins.
Avoid using RF-equipment near modules when covers are open or there are unconnected connectors
or wires.
WARNING!
Arc welding on or close to the engine must be avoided if cables are connected to the automation system.
10.9 Drawings
DAAE061024- Block- / Interconnection diagram ......................................................................... 10-10
DAAE061027- Power unit ............................................................................................................ 10-17
tobeadded Modbus list ........................................................................................................... 10-20
4V50G1522h Pre-lubricating pump starter (recommended) ...................................................... 10-21
te d
da u p
e l b
wi l
i n g
w ra
d e
Th
11. ANNEX
11.1 List of symbols
Figure 11.1 List of symbols (DAAE000806c).