Sie sind auf Seite 1von 7

Effects of the Synthetic Inertia from Wind Power on the Total System Inertia after a

Frequency Disturbance
F. Gonzalez-Longatt1, E. Chikuni2, E.Rashayi3
1
Department of Aerospace, Electrical and Electronic Engineering, Coventry University, Kingdom
1
Email: fglongatt@ieee.org
2
Department of Electrical Power Engineering, Cape Peninsula University of Technology, South Africa
2
Email: chikunie@cput.ac.za
3
Department of Electrical Engineering, University of Zimbabwe
3
Email: Rashayi@gmail.com

Abstract The future power systems face several challenges; one the ac grid [1]. The result is deeper frequency excursions of
of them is the use of high power converters that virtually decouple system disturbances. If considerable reduction in the ability
primary energy source from the AC power grid. An important to overcome system frequency's disturbances is expected, the
consequence of this situation is their effect on total system inertia inertia response may be decreased. The inertial response of
and the ability to overcome the system's frequency disturbances. the system might be negatively affected with devastating
The wind power industry has created a controller to enable inertial
response on wind turbines generators: Synthetic Inertial. This
consequences for system security and reliability [1].
paper evaluates the effects of the inertia emulation of wind The aim of this paper is to evaluate the effects of synthetic
turbines based on full-converters and their effect on total system inertia on wind turbines based on full-converters on the total
inertia after frequency disturbances happen. The main system inertia after a frequency disturbance. This paper is
contribution of this paper is to demonstrate (based on simulations) organized as follows: Section II describes the frequency
that during an under-frequency transients on future power response on power system after a frequency disturbance.
systems, synthetic inertia does not completely avoid worse Section III presents the concept of synthetic inertia and show
scenarios in terms of under-frequency load shedding. The extra two approaches used on WT (wind turbine) controller to
power delivered from a wind turbine during frequency create inertial responses. Section IV address aspects related to
disturbances can increase "momentary" the total system inertia
and substantially reduce the rate of change of frequency providing
system inertia, system frequency response and some potential
time for the active governors to respond. However, synthetic challenges for futures networks. Section V the results of
inertia might not completely avoid under-frequency load shedding. simulations that define the impact of synthetic inertia on the
protection/control schemes over a test system. Finally, the
I. INTRODUCTION advantages of this novel application are discussed at the
conclusions.
Future power systems face several challenges [1]: (i) the
high penetration level of renewable energy from highly II. FREQUENCY RESPONSE
variable generators connected over power converters, (ii)
several technologies for energy storage with very different The system frequency of a synchronous power system
time constants, some of them using power converters as an varies with the imbalance of energy supplied and the
interface to the grid, (iii) A complex European transmission electrical energy consumed [3], [4]. When large generating
network facilitating the integration of large-scale renewable blocks are lost, the system undergoes a frequency swing that
energy sources and the balancing and transportation of depends on to the size of the loss. Limits imposed on the
electricity based on underwater multi-terminal high voltage magnitude of frequency deviation prevent system collapse
direct current (MTDC) transmission. All of them have an [5]. In accordance with the Electricity Supply Regulations
element in common, high power converters that decouple the 1989 and hence the National Grid Companys (NGC)
new energy sources from the pre-existent AC power systems Transmission License, the frequency delivered to the
[1], [2]. consumer must not vary from the declared value by more
During a system frequency disturbance the than 1% [6].
generation/demand power balance is lost, the system In the event of a sudden loss of generation or sudden
frequency will change at a rate initially determined by the connection of a large load, the system frequency starts
total system inertia. However, future power systems will dropping (Region I of Fig. 1) at a rate mainly determined by
increase the installed power capacity (MVA) but the effective the total angular momentum of the system Mtotal, sum of the
system inertial response will stay the same as at present. This angular momenta of all generators (Mg,i) and spinning loads
is because the new generation units based on power connected to the system (ML,i).
converters create a decoupling effect of the real inertia and

978-1-4673-4569-9/13/$31.00 2013 IEEE 826


Continous Service
Primary
apparent power in MVA.
50.2
Response
Secondary Response A change in the generation/load balance, at one point in the
10s 30s 60s Time 30 mins system will be reflected throughout the system by a change in
50.0 frequency. The relationship between the power imbalance at
Frequency (Hz)

Secondary (to 30 mins)


49.8 the terminals of the i-th generator in p.u. (pi) and its
Primary frequency (fi), can be expressed as:
Reserve 2 H i df i
49.5 pm ,i pe ,i pi i = 1, 2, , N (2)
f n dt
where: pm,i is the mechanical turbine power in p.u., pe,i is the
49.2
Region I
Occasional Service electrical power in p.u., pi is the load generation imbalance
in p.u., Hi is the inertia constant in s, fi is the frequency in Hz,
Fig. 1. General Frequency System Response and Controller involved: The fn is the nominal system frequency in Hz and dfi/dt is the rate
operational limits show on the figure correspond to England and Wales.
of change of frequency in Hz/s. This is a simplified version of
the swing equation, which assumes that any damping effects
In the case where the frequency drops by more than 0.2
during the disturbance are relatively small.
Hz, generation plants are contracted to provide additional
frequency response duties. It follows, therefore, that if the instant of the disturbance is
Large frequency disturbances, particularly trips of large known (t =t0), and the size of the power imbalance, pi(t0),
generation plants, cause generation-demand unbalance that and the rate of change of frequency (ROCOF), dfi/dt at the
must be corrected by frequency control loops. These terminal of the i-th generator are known, then the unknown
controllers are provided in order improve the System inertia constant of this generator can be estimated (i) using
Frequency Response (SFR). The frequency controllers cover (2):
multiple time-frames [1]: (i) inertial response also know as p t f
fast primary response, (ii) governor response also known as H i i 0 n
df (3)
slow primary response, (iii) automatic generation control 2 i
(AGC), and (iv) tertiary control. These controllers define the dt t t0
dynamic changes associated to SFR. [3]. These services are It must be noted that (3) is only valid immediately after a
illustrated in Fig. 1 (tertiary control is not illustrated). disturbance, a time referred to as t=t0+. After this time other
factors, not accounted for in equation (3), begin to affect the
III. SYNTHETIC INERTIA dynamic behavior of the system. The ROCOF can be simply
determined from two consecutive measurements:
The frequency of a power system depends on real power df i f (t ) f (t )
balance: generation-demand. In the standard operation of a i 0 i 0 (4)
dt t t0 t0 t0
power system, the frequency is regulated within strict limits
by adjusting the electrical supply to meet the demand. If the where fi(t0+) and fi(t0-) are the frequency in Hz sampled after
balance between generation and demand is not reached, the and before the disturbance, and t0+ and t0- represent the
system frequency will change at a rate initially determined by corresponding sampling times. All of these values refer to the
the total system inertia. The total system inertia comprises the i-th generator. The power imbalance, pi, can be defined in
combined inertia of most of spinning generation and load terms of mechanical (Pm,i) and electrical power(Pe,i):
connected to the power system. pi t0 pe ,i (t0 ) pe ,i (t0 ) (5)
Using (3)-(5) the inertia constant of the N generators in the
A. Inertia constant and Swing Equation system can be calculated.
The total system inertia (HT) comprises the combined
The inertia constant of a rotating system (H), or individual
inertia of most of spinning generation and load connected to
generator, is used to define the energy stored in its rotating
the power system.
mass (Ec0). This definition consists of the time, in seconds,
that it would take to replace this stored energy when
B. Synthetic Inertia: Concept
operating at rated mechanical speed (sm) and rated apparent
power output (Sbase) [3], [7]: If during a system frequency disturbance the balance
1 J sm
2
between generation-demand is not reached, then the system
H (1)
2 Sbase frequency will change at a rate initially determined by the
where: J is the total moment of inertia in kg.m2, sm is the total system inertia (HT). The total system inertia comprises
rated mechanical speed in rad/s, and Sbase is the selected base the combined inertia of most of spinning generation and load
connected to the power system. The contribution of the

827
system inertia of a load or generator is dependent on whether power as reserve by using a pitch controller (pitching) or
the system frequency causes changes in its rotational speed increasing the rotational speed from the MPPT value (over-
and, therefore, its kinetic energy. speeding). These concepts are well understood and therefore
The power associated with this change in kinetic energy is will not be discussed further in this paper.
fed or taken from the power system and is known as the Hid den inertia emulatio n
inertial response [8]. During a system frequency event the d
d p 2 H synsys sys
total system inertial response of all electrical machines sy s Filter 2Hs ys dt
dt
connected to the system is the main factor that determine the 1 J sm
2
H syn
initial ROCOF. For a robust power system (system frequency 2 Sbase
is not overly sensitive to the power imbalances), it is
P r, ref r PM PPT Pref
Pmea s PI Converter
extremely important that a large proportion of generation and
MPPT r
load connected to the power system contributes to the total r ,meas
system inertia and then provide inertia response. Fig. 2. General Scheme for Releasing "Hidden" Inertia Controller
Modern WTGs (wind turbine generators) use power
electronics converters to enable variable speed operation in IV. SIMULATIONS AND RESULTS
order to capture wind energy over a wide range of speeds.
However, these converters isolate the rotational speed from This section presents simulations and results considering a
the system frequency so WTG based on back-to-back Test System representative of a future network which can be
AC/DC/AC converters offer no natural response to system obtained from [1]. This system consists of 8-generator, 8-bus,
frequency [9], [10]. In this paper, the adjective "natural" on 7-load, and 22-transmission lines and it has been divided in
the previous sentence is used because some manufacturers seven areas. DIgSILENT PowerFactoryTM is used for time-
have started to integrate controllers on modern WTGs in domain simulations and DIgSILENT Simulation Language
order to provide inertial response (and governor response on (DSL) is used for dynamic modeling.
some cases) for large, short-duration frequency deviations. The system has a total generation of 100.736 GW and a
The Wind turbine industry has created several names for this total load of 96.75GW and Fig. 3 shows steady state
control system that enable inertial responses on a WTG: conditions for case base where a power flow of about 15 GW
Artificial, Emulated, Simulated, or Synthetic Inertial. from the Top to Tail is depicted.
Examples of synthetic inertia controlled commercially In this paper, the operational-control criteria used for
available for WTG are: General Electric WindINERTIA system frequency analysis is based a specific criteria defined
[11], [12] ENERCON Inertia Emulation [13]. by the author, it is mainly an adapted version of the GB
The objective of the synthetic inertia control is to extract
Security and Quality of Supply Standards (GB SQSS). The
stored inertial energy from the moving part on WTGs. The
following assumptions are used in this paper:
idea is to produce incremental energy similar to that provided
(i) the level of infrequent loss of power infeed is set-up to
by a synchronous generator with real inertia. Synthetic inertia
1.800 GW, and frequency response must avoid a
controllers are based on two different approaches: (i)
deviation of system frequency outside statutory limits:
Releasing "hidden" inertia and (ii) Reserve capacity in pitch.
range 49.8 Hz to 50.2Hz for more than 5 cycles,
To release the "hidden" inertia a controller to the takes
(ii) frequency control devices (or speed governor) are set
kinetic energy from the wind turbine (WT)s rotating mass. A
up to operate with an overall speed Droop of 4% (GB
controller based on this concept increases the electric power
SQSS establishes between 3 and 5%),
output during the initial stages of a significant downward
(iii) Under Frequency Load Shedding (UFLS) is set to start
frequency event. The active power (inertial power, p) of the at 49.8Hz and the plan consists of six load shedding
control is achieved by:
steps of equal size pshed [14]. A delay for each load
df shedding step is td = 0.1 s (5 cycles).
p 2 H syn f sys sys (6)
dt Fig. 4 depicts the general structure of variable-speed wind
where Hsyn express the synthetic inertia (sec) and fsys system turbine with a direct-drive permanent magnet synchronous
frequency (p.u). Implementation of releasing hidden inertia generator (PMSG). The models used for back-to-back
controllers is depicted on Fig. 2. converter, detail of each model are taken from: [15], [16].
Traditional variable speed WTs are designed to always The parameter used for these models are escalated to simulate
operate at the maximum power point tracking (MPPT) so they an equivalent 5 MW wind turbine.
have no power reserve to support frequency control in the
steady state. Reserve capacity in pitch concept coerces a wind
standby power by maintaining reserve capacity in pitch. A
de-loading controller enable the WT to operate over de-
loading curves instead of MPPT and saves the available

828
power infeed from 0.3 to 3.2 GW are simulated and rate of

DIgSILENT
G1 L1a
~

22.80
G
11.15
change of frequency (ROCOF) of the frequency of inertia
Upper Top
centre (fc) is plotted on Fig. 6. Fig. 7 shows the total system
-0.13 2.26
76.00

1a

2
400.00
1.00
15.81
-4.62
2.95
-4.62
2.95
10.44
-4.14
10.44
-4.14
1
TOP inertia (HT) considering the increases on the loss of
generation infeed. The ROCOF and the minimum frequency
10.54 10.54 21.62 21.62 395.40
400.00
1.00 1a-1 I 0.99

1a-2 II
-9.88

1a-2 I
18.52 10.24

Top-Left Top-Rigth
5.08
21.62

(nadir) increases as the level of loss of power infeed increase


4.75
-2.73
10.54 1a-1 II -9.88
9.50 4.95
-5.45 5.08
G

1.01
~

G2 L1

and the total system inertia is kept constant. The small


36.52 21.62
4.75
-2.73
10.54 1-4 14.80

deviations of the total system inertia are consequence of


-11.16
36.09

1-3

3-4 numerical error during the inertia estimation method


Upper-Tail
-14.01
12.46
36.09
9.94
-5.37
21.74
-9.37
6.32
21.74
Tail-Right presented on Section III.A, the overall error is less than
4 400.00
1.00
3 400.00
1.00
0.0006s.

DIgSILENT
5.61 0.00
7.20
6.77
20.20
-5.41
14.13
2.87
17.34
-8.61
8.64
4.60
10.95
2.22
7.06
-3.94
50.20
32.94 69.71 37.26 32.61 15.55
50.00
G G G 6.602 s 16.252 s 56.722 s
~ ~ ~ 49.259 p.u. 49.560 p.u. 49.513 p.u.
G4(b) G4(a) L4 G3 L3
49.80

3-7
4-7
49.60
5-7
49.40
-8.21
5.46
8.65
-4.74
-15.66
11.38
-6.76
4.43 49.20
(a)
18.98 18.98 37.26 15.55
0.000 12.00 24.00 36.00 47.99 [s] 59.99
5 7
Lowest-Tail 400.00
1.00
-8.90
400.00
1.00
-4.01
30.00
9.51
8.76
43.08
17.34
3.52
0.38
-0.23
0.85
9.04
-4.94
19.83
11.40
9.40
49.27
16.14
3.28 Middle 25.00
5-6 20.00
G G
6-7

~ ~ 15.00
G5 L5 -0.38 -8.57 G7 L7
0.23 5.72 10.00
Load Flow Balanced
TAIL
0.85 19.83
5.00
Nodes Branches 6 400.00 0.00
(b)
Line-Line Voltage, Magnitude [kV] Active Power [GW] 1.00
0.000 12.00 24.00 36.00 47.99 [s] 59.99
-9.12
Voltage, Magnitude [p.u.] Reactive Power [Gvar]
17.11
11.24
68.23
26.05
5.29 Core+Tail
Voltage, Angle [deg] Loading [%] 14.00
G
~ 13.00
G6 L6
12.00
Benchmark System Project: DPSP 2012
fglongatt.org. 11.00
Francisco M. Gonzalez-Longatt Graphic: Benchmark Model
10.00
02/01/2012 Date: 2/13/2012
PowerFactory 14.0.525 fglongatt@ieee.org 9.00
Annex:
8.00
(c)
0.000 12.00 24.00 36.00 47.99 [s] 59.99
Fig. 3. Test Case: "TOP-TAIL" System: Steady-State Conditions fglongatt
Exceptional Loss of Infeed Response Date: 2/17/2012
Francisco M. Gonzalez-Longatt, PhD March 2012 Annex: /2

Active and Active and Fig. 5. System Frequency response to an exceptional loss of generation
Mechanical reactive
Wind power Model fo power
reactive
power
infeed (a) Frequency in Hz, Generation active power in GW (b) with and (c)
Mechanical
Speed
Power Shaft Pm direct drive Pac , Qac
Power Pac , Qac Fundamental without frequency response.
Rotor model Model synchro- Stator frequency
vw Pw r usnous converter Voltage
currents frequency grid model
Rotor generator
Is -4
Pitch Vs , f
Speed
Pset x 10
angle Rotor speed 5
Reactive
turb Qset power set 300MW
point 500MW
0 -4
Pitch angle Rotor speed Pset Terminal x 10 700MW
controller controller Active power voltage 5
df/dt (p.u./s)

set point controller -5 1350MW


0
1500MW
-10 -5 1800MW
Fig. 4. General structure of a model of a variable-speed wind turbine with a -10 2300MW
direct-drive synchronous generator and full power converter -15 -15
2800MW
3200MW
-20
-20 0 5 10
0 10 20 30 40 50 60
Time (s)
C. Results and Discussion
Fig. 6. ROCOF (p.u/s) considering level of loss of power infeed: Base Case.
An infrequent loss of infeed is used as system frequency
disturbance; it consists of tripping one generating unit s)( 5.3387
T
connected to Upper-Tail area at t=1.0s (generator G4(b) on H5.3386
ai
tr 5.3385
Fig. 3). Four generators providing governor frequency en
I 5.3384
response and three conventional generators (G2, G5, and G7) em 5.3383
sty
will be operating without active governors or at maximum S
lt
5.3382
a 5.3381
power. Fig 5 shows the plots of the system response for base o
T 0.3 0.5 0.7 1. 35 1.5 1.8 2.3 2.8 3.2
case considering an exceptional loss of power infeed, the Loss of Po wer I nfeed (GW)

UFLS is not active in this case and the frequency nadir Fig. 7. Total System Inertia (HT) considering level of loss of power infeed:
reaches fmin = 49.259Hz at tmin = 6.602s, Fig 5(a). Base Case.
The impact of synthetic inertia (Hsyn) provided by WT into
the total system inertia (HT) is quantitatively analyzed An exceptional loss of power infeed triggers a substantial
through time-domain simulations. Several levels of loss of excursion on the system frequency. The ROCOF for each

829
generation unit is shown on Fig 8, and Fig 9 shows the inertia the synthetic inertia provided by the wind farm, values from
constant of each generator (Hi) is calculated using the 0.1 to 10.0 s has been conceded the system frequency (fc)
estimation method presented in Section III.A. The ROCOF are plotted on Fig 9 and the total system inertia
exceptional loss of power infeed produce a frequency nadir of results are shown on Fig. 10 .
it is more than 741 mHz and persist for more than 5 cycles 50 0.1

(see Fig. 8 and Case I). 49.8 0

Frequency (Hz)

df/dt (Hz/s)
I
0.2 49.6 -0.1 II
III
G1
49.4 -0.2 IV
G2
0 Hsyn= 0.1s IV
G3
Frequency (Hz/s)

0.2 49.2 -0.3


G4(a)
0 50 0.1
-0.2 G5

Frequency (Hz)
-0.2 G6 49.8 0

df/dt (Hz/s)
G7
-0.4 -0.4 49.6 -0.1

-0.6 49.4 -0.2


-0.6
0.8 1 1.2 1.4 1.6 1.8 Hsyn= 1.0s
0 10 20 30 40 50 60 49.2 -0.3
0 10 20 30
Time (s) 50

Frequency (Hz)
49.8 0

df/dt (Hz/s)
Fig. 8. ROCOF (Hz/s) considering an exceptional loss of power infeed: Base
Case. 49.6
-0.1
49.4
Hsyn= 5.0s
Inertia Constant Hi (s)

3.5
49.2 -0.2
3 0 10 20 30
2.5 50.2 0.05
2
Hsyn= 10.0s
Frequency (Hz)
50 0

df/dt (Hz/s)
1.5
1 49.8 -0.05
0.5
49.6 -0.1
0
G1 G2 G3 G4(a ) G5 G6 G7
Loss of Power Infeed (GW) 0 10 20 30 0 5 10 15 20
Time (s) Time (s)
Fig. 9. Generator Inertia Constant (Hi) considering an exceptional loss of
power infeed: Base Case.
Fig. 9. System Frequency (fc) and ROCOF (Hz/s) considering different
UFLS schemes: Wind Integration (Hsyn). pshed = 20%.
50.5
0.1
Frequency (Hz)

Total System Inertia HT (s)

0
df/dt (Hz/s)

50 I 8
II 7
-0.1 6
49.5 III
5
-0.2 IV
4
V 3
49 -0.3 2
0 10 20 30 0 5 10 15 20
1
Time (s) Time (s)
0
Fig. 9. System Frequency (fc) and ROCOF (Hz/s) considering different 0.1 1 2.5 5 10
UFLS schemes: Base Case. pshed = 20%. Synthetic Inertia Hsyn (s)

Fig. 10. Total System Inertia (HT) considering different UFLS schemes:
ULFS is activated to avoid a prohibitive frequency nadir Wind Integration considering several values of Synthetic Inertia (Hsyn).
and to allow the integration of the wind power. Several UFLS
schemes on demand side of Tail area are tested, loads: L4, An increase on the synthetic inertia increases the total
L5, L6, L7 (see Fig. 3). Initially, a UFLS scheme base on six system inertia and the increase depends on the value o the
load shedding steps of equal size pshed = 20% is examined, synthetic inertia. This is a very positive effect and it is
the results of system frequency and ROCOF are shown on independent from the load shedding scheme used. This
Fig. 9 (load shedding Case I: 0 GW, II: 2.8260GW, III: increase on the total system inertia is consequence of the
6.2940 GW, IV: 5.7520GW, V: 7.3660GW). active power contribution during the inertial response, as
A cluster of wind farm is connected on bus 3 at Tail-Right consequence the ROCOF at the very beginning of the
area and it is generating 30 GW and control loop for releasing dynamic process is decreased (considering the same loss of
"hidden" inertia (Hsyn= 3.75s) is included. Benefits of the generation infeed).
integration of this wind farm include the increase on 164
mHz the minimum frequency during at exceptional loss of
power infeed. A better evaluation include vary the value of

830
D. Discussion: Impact on the Load Shedding Schemes details is presented for the second trip, the time delays on the
trips is observed between the system considering a synthetic
Synthetic inertia changes the total system inertia and this inertia of 1.0 and 2.5s.
situation has two important consequences on the under- 0
frequency protection schemes: (i) reduce the system (a) Hsyn = 1.0s
-200
frequency exclusion and the minimum frequency reached -100

Load Shedding (MW)


after the disturbance, and (ii) change the ROCOF. -400
-200
These effects are evaluated considering changes on the -600 -300
synthetic inertia (Hsys = 0.1, 1.0, 2.5, 5.0 and 10.0 s) and the
-800 -400 L4
step size of the load-shedding (pshed) are varied on the UFLS -500 L5
scheme: 1%, 2.5%, 5%, 10% and 20% (see Fig. 11) -1000
-600
L6
L7
(a) Base Case (b) Hsyn = 0.1s 3.05 3.055 3.06 3.065 3.07 3.075 3.08
-1200
15
0 0.5 1 1.5 2 2.5 3 3.5 4
15
Time (s)
10
Power (GW)

10
Power (GW)

0
5 5 (b) Hsyn = 2.5s
-200
0

Load Shedding (MW)


0 0
-400
20% 20%
10% 10% -200
5% 5%
IV
-600
pshed 2.5% III
IV pshed 2.5% III
1% II 1% II
Load Shedding Case I Load Shedding Case I -800 -400
Case Case

(c) Hsyn = 1.0s (d) Hsyn = 2.5s -1000


15
-600
15 3.13 3.135 3.14 3.145 3.15
-1200
10
0 0.5 1 1.5 2 2.5 3 3.5 4
Power (GW)

10
Power (GW)

Time (s)
5 5
Fig. 12. Power shed (GW) considering different a UFLS of six step pshed =
0 0 1%, Tdelay = 0.1s. Wind Integration considering Hsyn= 1.0s and 2.0s. Case IV:
20% 20% UFLS relays on L4, L5, L6 and L7.
10% 10%
5% 5%
IV
pshed 2.5% III pshed 2.5% III
IV
1% II 1% II
Load Shedding Case I Load Shedding Case I
Case Case
E. Discussion: Impact on the WT Power Converter
(e) Hsyn = 5.0s (f) Hsyn = 10.0s
15
15 The hidden inertia reduces the maximum ROCOF and
10
increase the frequency nadir, and this mechanism of inertia
Power (GW)

10
Power (GW)

5
5 emulation is based on release the kinetic energy of the
0
rotating masses on the WT. This mechanism has two
0

20%
20% important consequences that require to be carefully be
10%
10%
5%
5%
IV
evaluated: (i) the variable speed wind turbines have a lower
IV
pshed 2.5%
pshed 2.5%
1% II
III
Load Shedding Case
1%
I
II
III
inertia than classical synchronous generators, as consequence
Load Shedding Case I
Case Case
the value of the synthetic inertia must be correctly defined to
Fig. 11. Power shed (GW) considering different UFLS schemes (pshed): avoid an potentially dangerous decrease on the rotational
Wind Integration considering several values of Synthetic Inertia (Hsyn). speed with all the consequences on the drive train, and (ii)
releasing the hidden inertia imply a sudden increase on the
Synthetic inertia not completely avoid the ULFS for electrical power output as consequence the full power
system frequency disturbances like an exceptional loss of converter must provided this sudden increase of current.
power infeed however there are two important aspects: (i) Old wind turbines did not include controllers to provide
increases of synthetic inertia values and moderate to small synthetic inertia. However an upgrade of the power control
step size on the setting on the UFLS might decrease the total loops allows this feature, and special evaluations are required
power during the load shedding and, (ii) increases on the in order to avoid a fatal failure on the wind turbine systems.
synthetic inertia might delay the operation of the under- The power devices used on power converter are quite
frequency protection schemes. The last conclusion is depicted sensible to changes on the electrical variables, the synthetic
on Fig. 9 where the delay is observed for the second trip of inertia imposes electrical transient conditions which must be
the UFLS on Case III for synthetic inertia less than 10s, in the evaluated and it is especially true during the inertia release
particular case of Hsyn = 10s, the second operation of UFLS is period and the recovery period.
avoided. Fig 12 shows the operation of the UFLS, special

831
V. CONCLUSIONS controls: Impacts on grid performance," in Power and Energy Society
General Meeting, 2011 IEEE, 2011, pp. 1-8.
[13] S. Wachtel and A. Beekmann, "Contribution of Wind Energy
This paper evaluates the effects of the inertia emulation of Converters with Inertia Emulation to Frequency Control and Frequency
wind turbines based on full-converters and their effect on Stability in Power Systems," presented at the 8th International
total system inertia after a frequency disturbances happen. Workshop on Large-Scale Integration of Wind Power into Power
Systems as well as on Transmission Networks for Offshore Wind
The substantial effect of synthetic inertia is on total system Farms, Bremen, Germany, 2009.
inertia and system inertial response: (i) the extra power [14] P. M. Anderson and M. Mirheydar, "An adaptive method for setting
delivered from WT can substantially reduce the ROCOF (ii) underfrequency load shedding relays," Power Systems, IEEE
it provides time for the active governors to respond. However Transactions on, vol. 7, pp. 647-655, 1992.
[15] F. Gonzlez-Longatt, P. Wall, and V. Terzija, "A Simplified Model for
a coordination between controllers looks desirable (iii) Dynamic Behavior of Permanent Magnet Synchronous Generator for
increasing synthetic inertia helps to delay the UFLS and Direct Drive Wind Turbines," in IEEE PES Trondheim PowerTech
avoid repeated operations at exceptionally high values of 2011, Trondheim, Norway, 2011.
synthetic inertia, (iv) synthetic inertia might not completely [16] S. Achilles and M. Poller. Direct drive synchronous machine models for
stability assessment of wind farm. Available:
avoid UFLS, (v) ROCOF immediately after a system http://www.digsilent.de/Consulting/Publications/DirectDrive_Modeling
disturbance is independent on the UFLS scheme, (vi) UFLS .pdf
helps to reduce the negative recovery effect caused by
synthetic inertia. The main contribution of this paper is to
demonstrate the potential positive effect on the total system
inertia on future power systems that integrate synthetic
inertia, however the under-frequency protection schemes
must be rethought because synthetic inertia cannot
completely avoid worse scenarios in terms of UFLS.

REFERENCES

[1] F. Gonzalez-Longatt, "Impact of Synthetic Inertia from Wind Power on


the Protection/Control Schemes of Future Power Systems: Simulation
Study," presented at the DPSP 2012 - Protecting the Smart Grid, The
11th International Conference on Developments in Power System
Protection, Birmingham, United Kingdom, 2012.
[2] F. Gonzalez-Longatt;, P. Regulski;, H. Novanda;, and V. Terzija;,
"Impact od Shaft Stiffness on Inertial Response of Fixed Speed Wind
Turbines," Automation of Electric Power Systems, vol. 36, pp. 191-197,
2012.
[3] J. Machowski, J. W. Bialek, and J. R. Bumby, Power System Dynamics:
Stability and Control, 2nd ed. ed. Oxford: John Wiley, 2008.
[4] B. Pal and B. Chaudhuri, Robust control in power systems. New York:
Springer, 2005.
[5] GB. (2009). Security and Quality of Supply Standard (SQSS).
Available:
http://www.nationalgrid.com/uk/Electricity/Codes/gbsqsscode/
[6] L. Holdsworth, J. B. Ekanayake, and N. Jenkins, "Power system
frequency response from fixed speed and doubly fed induction
generator-based wind turbines," Wind Energy, vol. 7, pp. 21-35, 2004.
[7] P. Kundur, N. J. Balu, and M. G. Lauby, Power system stability and
control. New York; London: McGraw-Hill, 1994.
[8] A. Mullane, G. Bryans, and M. O'Malley, "Kinetic energy and
frequency response comparison for renewable generation systems," in
Future Power Systems, 2005 International Conference on, 2005, pp. 6
pp.-6.
[9] G. Lalor, A. Mullane, and M. O'Malley, "Frequency control and wind
turbine technologies," Power Systems, IEEE Transactions on, vol. 20,
pp. 1905-1913, 2005.
[10] S. Yuan-zhang, Z. Zhao-sui, L. Guo-jie, and L. Jin, "Review on
frequency control of power systems with wind power penetration," in
Power System Technology (POWERCON), 2010 International
Conference on, 2010, pp. 1-8.
[11] N. Miller, K. Clark, and R. Walling, "WindINERTIA: Controlled
Inertial Response from GE Wind Turbine Generators," presented at the
45th Annual Minnesota Power Systems Conference, Minneapolis,
Minnesota, 2009.
[12] N. W. Miller, K. Clark, and M. Shao, "Frequency responsive wind plant

832

Powered by TCPDF (www.tcpdf.org)

Das könnte Ihnen auch gefallen