Beruflich Dokumente
Kultur Dokumente
1.0 INTRODUCTION :
i) Are made aware of the risk of explosions and fires emanating from
pulverized fuel (P.F.) and hot fly ash.
ii) Are provided with the necessary understanding as to how they can
arise.
2.0 SCOPE :
Two factors, brought together can cause either a P.F. or coal gas
explosion, namely :
iii) In the case of mills which each have an associated primary air fan;
the discharge of the primary air fan.
iv) For all other mills, the points at which the hot air and tempering air
ducts leave their respective main supply ducts.
The mill system is that part of the P.F. plant bounded by the bunker
outlet(s) and (ii), (iii) or (ii) and (iv) above.
In addition the plant areas encompassing the furnace, the gas passes and
precipitator sections also need to be considered.
Whilst this Directive deals primarily with mills and P.F. pipe work system, it
is important to remember that conditions in the coal bunker and the
primary air ducting can influence the development of an explosion in the
mill and, conversely, the bunker and the primary air ducting may be
affected as a result of a mill explosion.
In the vertical spindle mills the blockage of mill rejects passage will cause
accumulation of rejects in the chamber and the friction between pyrites
scraper and accumulated rejects, in the presence of primary air, presents
a fire risk.
More clearance than specified between Scrapper and mill bottom plate
also will lead to accumulation of rejects in scraper chamber which is prone
to fire risk. Trimming of mills shall be done regularly, ensuring specified
clearance to minimize coal rejects.
Any passing of pyrites hopper valves or leakages at pyrites hopper flanges
will be prone to spontaneous combustion in rejects hopper.
Excessive temperature of pulverized fuel in the mill shall be avoided, and
should not be allowed to exceed a temperature of 95 degree C.
Coal deposit in feeder body takes place due to failure of clean out
conveyor which in turn lead to spontaneous combustion particularly in
summer. Continuous operation of clean out conveyor is to be ensured.
The most likely causes of ignition from the furnace into a running or
incoming mill and P.F. pipe work system are :
i) A pressure disturbance in the furnace that reverses the forward flow
of air / fuel, so that a flame may be propagated, or carried from the
furnace into the P.F. pipe work.
ii) Failure of the primary air supply to the mill, with the mill open to the
furnace and continuing to pulverize coal.
iii) Failure to ensure that the hot and cold air supplies to running mills
are not unduly disturbed by incoming mills.
iv) Failure to ensure, when bringing additional suction mills into service
that the exhausters are running before the mill outlet dampers are
opened.
6.2 Ignition in the Boiler furnace other than the Normal Flame :
Other sources of ignition in the furnace are hot refractory, ash and slag
deposits.
7.2 At each site a glossary of standard terms related to the Plant shall be
compiled and included in the station P.F. operating instructions.
Contd.on Page 7
Page 7 of 17
LMI/OD/OPS/SYST/009
Issue 1
7.3 Each person concerned with the operation or maintenance of P.F. Plant
shall be trained to a competent level and the continuing competence of
operations staff shall be reviewed annually. Personnel who might be
promoted temporarily into a post where they will be directly concerned
with the operation of P.F. Plant shall also be instructed and trained
accordingly. Records of training shall be maintained.
8.1 The basis of safe firing of P.F. rests upon the availability and reliability of
oil burners. Without oil burners, P.F. firing would not be possible and it is,
therefore, essential that the oil installation is fully understood by all staff
operating P.F. Plant.
8.2 Milling systems shall not be put into service if a fire is suspected in any
part including the coal feeder or bunker.
8.3 P.F., fuel oil and gas shall not be allowed to accumulate as a consequence
of leakage.
8.4 The velocities in the P.F. pipes on a running mill shall be sufficient to
minimize deposition of fuel ( 27 28 m/sec. based on Dirty Air Flow Test).
8.5 The minimum number of personnel shall be allowed in the vicinity of P.F.
plant and only then under controlled conditions when unstable operating
conditions are suspected.
8.8 All P.F. Stations must have evacuation procedure, adequate for the risk
category of the particular plant. The evacuation zone and procedure shall
be detailed in the Location P.F. Operating Instructions.
Contd.on Page 8
Page 8 of 17
LMI/OD/OPS/SYST/009
Issue 1
8.11 On a running mill, the maximum working mill outlet temperature permitted
in normal operation will depend on the nature of the coal and the design of
the milling system. Establish an acceptable maximum mill outlet
temperature for each individual installation. The alarm temperature shall
be set 5 degree C higher than this maximum temperature.
9.1 Maintain the design features, e.g. mill fire detectors, that protect against
fires and explosions. Management shall define these features, specify
the inspection frequencies, record inspection results and any remedial
action taken and the action to be taken in the event of defects arising.
9.2 All practicable steps shall be taken to eliminate sites in the mill system
where P.F. and raw coal may lodge.
9.3 All leaks of P.F. fuel oil and gas shall be dealt with promptly.
9.4 Air leaks on suction system may render the air / fuel mixture explosive and
must be rectified.
9.5 All modification to plant shall be dealt with in accordance with the
procedure laid down in the operation Directive OD/GEN/006. Plant
Modifications and LMI derived from the above Directive.
10.1.1 Do not start or shut down a mill without checking for evidence of a
fire in the system.
10.1.2 Care shall be taken not to confuse the high mill outlet temperature
caused by a fire with that caused by loss of coal feed. If an
operator receives indication from the pulverized fuel plant
instrumentation, especially during a transient situation which either:
i) Appears to be misleading or inconsistent
ii) Which may lead to an emergency situation.
He shall :
i) Evacuate restricted areas to minimum staffing levels.
ii) If the emergency has not been pre-determined, consider,
together with his supervisor, the appropriate course of
action.
Within the Location P.F. operating Instructions, an appropriate
course of action shall be defined for pre-determined emergency
situations.
10.2.1 When a fire is detected in the mill body or classifier and does not
appear to be in mechanical danger, increase coal feed to the
maximum practicable with the coal feeder on manual control.
Increase cold air flow to the maximum practicable and evacuate the
personnel in the vicinity of the affected mill system. Run like this for
a period specified in the P.F. Operating Instructions, and then
reduce coal feed to normal.
10.2.2 If the fire persists, or the mill is in mechanical danger, or the coal
feed is lost, withdraw personnel from the area and prepare to
shutdown the mill system.
The following methods are for dealing with confirmed fires in the
mill systems.
a) Stop the air flow through the system by closing the isolating
damper / valves.
b) Trip the primary air fan or exhauster, mill, coal feeder, seal
air fan and classifier.
c) After the fire has been positively extinguished and the mill
has cooled off, purge the mill system thoroughly. If advice
on the length of the necessary purge time is required, the
operation services, Boiler Group will assist.
d) In cases where fire fighting equipment is installed, the P.F.
Operating Instructions shall give guidance on the
circumstances and methods of use.
e) Water should not be admitted to mill having fire to avoid
cracking of mill internals.
f) To quench the fire, admit inert gas or steam to the mill.
10.3.2 On tube ball mills, establish grinding first by starting the mill motor
before opening the hot air damper and output control damper.
10.3.3 On medium and high speed mills, it is necessary to establish the air
flow before coal is admitted and, therefore, for these types of mill,
the mill outlet isolating valves have to be opened first in the start-up
sequence. At this point, carry out a check on the mill fire detection
instrumentation, where this equipment is fitted, to ensure that there
is no indication of a fire in the mill.
10.3.4 When the mills are in service, maintain air / fuel mixture velocities in
the P.F. lines above the minimum transport velocity for the
installation, determined as follows:
i) Where no estimate has been made of the velocity to
minimize deposition, the minimum transport velocity shall be
taken as in case of Vindhyachal Station.
ii) Where an estimate of the minimum velocity to minimize
deposition has been made, then that estimate shall be
regarded as the minimum transport velocity. In our Stage # I
Units this velocity is 27 28 m/sec.
10.3.5 Very high primary air flow (Too much high air fuel velocity) will lift
the Coarse particle from mill and due to this, deposition will take
place in fuel piping. Hence maximum velocity in fuel piping is also
to be limited by limiting air/fuel ratio near to 1.8:1, so that coal
velocities in PF pipes remain around 27 to 28 m/sec.
i) Firstly, stop the coal feed increase the proportion of cold air in the
primary air-flow, if necessary, to control the rise in mill outlet
temperature. On medium and high speed mills, run the mill to
remove as much coal as possible. On tube ball mills, run the mill
until the remaining coal is at or above the minimum level.
Contdon Page 12
Page 12 of 17
LMI/OD/OPS/SYST/009
Issue 1
ii) In the case of medium and high speed mills increase the air flow
through the mill as the mill empties, adjusting the mill air inlet
temperature to control the outlet temperature within the specified
limit. When the mill is judged to be empty, stop the mill motor and
trip the primary air fan, exhauster or inlet dampers.
iii) In the case of tube ball mills, stop the mill and isolate the mill body.
Purge the P.F. lines at as high a velocity as practicable for atleast 2
mins.
vi) Ensure that any non-return valves in the P.F. lines have closed.
10.6.1 Before lighting up a boiler, purge the furnace and all appropriate
boiler passes with an air flow at least 30% of full load for 5 mins. Or
as recommended by the original equipment manufacturer and
accepted by NTPC.
10.6.2 Before first admitting pulverized fuel to the furnace, commission the
associated lighting up burners and check for efficient operation.
Ignition of pulverized fuel from any main burner shall be effected
only by the lighting-up burner associated with it.
i) Trip all mill groups, and shut off all other fuel supplies to the
furnace.
ii) Do not insert lighting-up burners.
iii) Maintain an air flow at least 30% of full load for at least 5
mins. Or the time as recommended by manufacturer of
Boiler.
Contd.on Page 12
Page 14 of 17
LMI/OD/OPS/SYST/009
Issue 1
10.6.8 When shutting down, purge the furnace and boiler passes with an
air flow at least 30% of full load for a minimum of 5 mins. Or the
time as recommended by Boiler manufacturer after cessation of
firing.
10.6.9 If a mill system trips out whilst containing coal it shall, if possible, be
purged into the furnace with the appropriate oil burners in service
after checking for fire in that mill system.
11.0 BUNKERS :
11.1 Fires in bunkers are caused by the spontaneous combustion of
stagnant regions of coal. Bunkers associated with mills that are out
of service are always in danger of spontaneous combustion and
shall be emptied if the plant is be off-load to an extended period.
Contd.on Page 13
Page 15 of 17
LMI/OD/OPS/SYST/009
Issue 1
On pressure mill systems, a small primary air flow is always present from
the mill to the feeder whenever the mill is in service. This flow increases if
the coal level in the bunker is low and can dry out coal in the bunker outlet
area. Depending on the nature and effectiveness of the isolation, similar
conditions can exist with the mill group out of service.
On an operating bunker, coal can stagnate against the walls due to bad
flow characteristics of the bunker, or by partially open bunker gates or
rods. This can be minimised by ensuring the satisfactory operation of
bunker outlet closing devices.
11.2 The method of regularly communicating mill status and bunker level shall
be clearly established in the location P.F. Operating Instructions.
11.3 If it is suspected that there is a fire in a coal bunker, the primary aim shall
be to empty the contents of the bunker directly into lorries for disposal.
Depending on the way in which the bunker is emptied, consideration
should be given to the use of protective clothing and spraying the coal with
water as it emerges. Any hot spots on the bunker or feeder wall shall
be cooled by spraying with water.
If this is not practicable, the coal must be passed through a running mill.
This operation shall be subject to a well defined procedure to be
established in the Location P.F. Operating Instructions. This procedure
shall specify that :-
If the mill has to be shut down, with a known bunker fire, even if
there are no indications of ignition sources within the mill, the mill
shall be shut down as though there were a fire in it.
12.2 On-load ash removal from boilers, through open doors, shall only be
carried out by personnel wearing appropriate protective clothing.
12.5 The removal of unburnt fuel immediately after its deposition is particularly
important. When temporary equipment has to be used for extracting
unburnt fuel from the hoppers, the temporary method to be used must
have been the subject of a study to ensure that it is safe. Indiscriminate
removal of dust from hoppers shall be banned. The prime aim of any
abnormal method of handling dust containing, or suspected of containing,
unburnt fuel shall be to prevent its release into the open air unless it is
fully wetted and cooled. The system to be used will be subject of a safety
study carried out by a person nominated by the Station General Manager.
This study shall assume that blockage will occur during the temporary
process and that the prime requirements must not be infringed in dealing
with it. The use of air lances to overcome blocking during such
procedures shall be banned.
Contd.on Page 15
Page 17 of 17
LMI/OD/OPS/SYST/009
Issue 1
12.6 Dry dust shall only be emptied out of a Boiler or precipitator hopper into
the open air after a person nominated by the Station General Manager
has confirmed and recorded that there is negligible risk of a fire or an
explosion resulting, taking into account the environmental and safety
considerations associated with this practice.
*****