Sie sind auf Seite 1von 10

Electrical Power and Energy Systems 33 (2011) 13261335

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Distribution systems fault analysis considering fault resistance estimation


Andr D. Filomena a,d,, Mariana Resener b, Rodrigo H. Salim c, Arturo S. Bretas d
a
Companhia Estadual de Gerao e Transmisso de Energia Eltrica (CEEE-GT), Av. Joaquim Porto Villanova 201, Porto Alegre, Brazil
b
Companhia Estadual de Distribuio de Energia Eltrica (CEEE-D), Av. Joaquim Porto Villanova 201, Porto Alegre, Brazil
c
Electrical Engineering Department, University of So Paulo (USP), Av. Trabalhador So Carlense 400, So Carlos, Brazil
d
Electrical Engineering Department, Federal University of Rio Grande do Sul (UFRGS), Av. Osvaldo Aranha 103, Porto Alegre, Brazil

a r t i c l e i n f o a b s t r a c t

Article history: Fault resistance is a critical component of electric power systems operation due to its stochastic nature. If
Received 18 April 2009 not considered, this parameter may interfere in fault analysis studies. This paper presents an iterative
Received in revised form 7 February 2011 fault analysis algorithm for unbalanced three-phase distribution systems that considers a fault resistance
Accepted 1 June 2011
estimate. The proposed algorithm is composed by two sub-routines, namely the fault resistance and the
Available online 5 July 2011
bus impedance. The fault resistance sub-routine, based on local fault records, estimates the fault resis-
tance. The bus impedance sub-routine, based on the previously estimated fault resistance, estimates
Keywords:
the system voltages and currents. Numeric simulations on the IEEE 37-bus distribution system demon-
Bus impedance matrix
Power distribution systems
strate the algorithms robustness and potential for ofine applications, providing additional fault infor-
Fault analysis mation to Distribution Operation Centers and enhancing the system restoration process.
Fault resistance 2011 Elsevier Ltd. All rights reserved.
Power systems protection

1. Introduction Fault analysis methods are an important tool used by protection


engineers to estimate power system currents and voltages during
Electric power systems are daily exposed to service interruption disturbances. It provides information for protection system setting,
mainly due to faults and human accidental interference. A power coordination and efciency analysis studies. Today, three
system fault is dened as any failure which interferes with the approaches are used in the industry for such analysis: classical
normal current ow [1]. The fault phenomenon affects systems symmetrical components, phase variable approach and complete
reliability, security, and energy quality, and can be considered time-domain simulations [4]. Classical fault analysis of unbalanced
stochastic. Different events such as lightning, insulation break- power systems is based on symmetrical components approach
down and trees falling across lines are common overhead power [5,6]. However, in untransposed feeders with single-phase or dou-
system fault causes. ble-phase laterals, the symmetrical component methods do not
Power system faults may be classied as temporary or perma- consider accurately these specic characteristics [7]. Hence, sym-
nent. Temporary faults in overhead lines are usually caused by metrical components based techniques may not provide accurate
lightning. In this case, system service can be automatically restored results for power distribution systems, which are normally charac-
after approximately 20 fundamental frequency cycles, with the cir- terized by those asymmetries.
cuit breakers opened, to allow deionization. However, permanent With industrial computer facilities improvement, the fault anal-
faults are associated with different events, like trees falling across ysis phase variable approach has been proposed to substitute the
lines. On these situations, system restoration is maintenance crew symmetrical components methods on distribution systems [8]. In
dependant. Facility maintenance crew must search and repair the the phase variable approach, system voltages and currents are re-
system using a fault location estimate. For non-negligible fault lated through impedance and admittance matrices based on phase
resistances (RF), which are commonly associated with permanent frame representation, considering the typical distribution systems
faults, standard fault location algorithms may present poor perfor- asymmetries.
mance [2,3]. However, fault analysis is still fault resistance dependant [9].
Due to fault resistance stochastic nature, typical fault analysis
studies consider the fault paths as an ideal short-circuit. To over-
Corresponding author at: Companhia Estadual de Gerao e Transmisso de come this limitation, recent studies suggest the usage of fault resis-
Energia Eltrica (CEEE-GT), Av. Joaquim Porto Villanova 201, Porto Alegre, Brazil. tance estimation algorithms [1012]. These works provide a fault
Tel.: +55 51 33825220; fax: +55 51 33824349.
resistance estimate using symmetrical components or modal anal-
E-mail addresses: alomena@ece.ufrgs.br (A.D. Filomena), mariana@ece.ufrgs.br
(M. Resener), rhsalim@usp.br (R.H. Salim), abretas@ece.ufrgs.br (A.S. Bretas). ysis techniques, restricting the application on balanced systems

0142-0615/$ - see front matter 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.ijepes.2011.06.010
A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335 1327

with equally transposed lines. The usage of articial intelligence V Sfp V Fp x  zpa  ISfa zpb  ISfb zpc  ISfc 2
has also been recently proposed in order to overcome the fault
resistance effects in classical power system protection [13] and where
fault location [14] applications. V Fp Z F  IFp 3
Considering the above mentioned limitations of state-of-the-art
fault analysis methods, this paper proposes an iterative fault anal- whereas ZF is the fault impedance between line-to-ground, the sub-
ysis algorithm that considers typical distribution systems charac- script p represents the faulted phase, and IFp is the phase p fault
teristics, and a fault resistance estimate. The proposed fault current.
analysis algorithm is composed by two sub-routines, namely the Considering the fault impedance strictly resistive and constant,
fault resistance and the bus impedance sub-routines. The fault (2) may be expanded into its real and imaginary parts:
resistance sub-routine is based on an iterative formulation exe- " # " #  
cuted to estimate the fault resistance through one-terminal fault V Sfpr M 1p IF pr x
 4
records. The bus impedance sub-routine considers the estimated V Sfpi M 2p IF pi RF
fault resistance values, and uses a bus impedance matrix based for-
mulation to estimate the fault system voltages and currents. where the subscripts r and i represent the real and imaginary com-
In order to validate the proposed fault analysis algorithm, the ponents, RF is the fault resistance, and:
formulation was implemented in MATLAB [15] and had its perfor- X
mance evaluated using a modied IEEE 37 Node Test Feeder [16], M 1p zpkr  ISfkr  zpki  ISfki  5
kfa;b;cg
simulated under BPAs ATP/EMTP software [17]. X
The remaining of this paper is organized as follows. The second M 2p zpkr  ISfki zpki  ISfkr  6
section presents the fault resistance sub-routine. Section 3 de- kfa;b;cg

scribes the bus impedance sub-routine. A case study is presented


where zpk is the mutual impedance between the faulted phase p and
in Section 4. Finally, Sections 5 and 6 discuss the results and con-
non-faulted phase k (X/m).
clusions obtained from this work.
Evaluating (4), the fault distance and resistance may be calcu-
lated as function of the sending-end voltages and currents, as well
2. Fault resistance sub-routine as the line parameters, as given by (7):
  " # " #
Fault resistance represents the fault impedance path between x 1 IF pi IF pr V Sfpr
phase or ground faults [18]. The proposed fault resistance sub-rou-  7
RF M1p IF pi  M 2p IF pr M2p M 1p V Sfpi
tine uses as input data, the sending-end voltages and currents. In
the following subsections the fault resistance sub-routine is From (7), fault resistance and distance independent mathemat-
presented. ical expressions for single line-to-ground faults are obtained, given
by (8) and (9), respectively:
2.1. Mathematical development
V Sfpr  IF pi  V Sfpi  IF pr
x 8
Referring to the power system of Fig. 1, the sending-end volt- M 1p  IF pi  M 2p  IF pr
ages are given by (1), which describes the steady-state fault M 1p  V Sfpi  M 2p  V Sfpr
conditions: RF 9
M 1p  IF pi  M 2p  IF pr
2 3 2 3 2 3 2 3
V Sfa zaa zab zac ISfa V Fa
6 7 6 7 6 7 6 7 As a result of the procedure described above, the fault distance
4 V Sfb 5 x  4 zba zbb zbc 5  4 ISfb 5 4 V Fb 5 1 and resistance may be estimated. To obtain such estimates, the
V Sfc zca zcb zcc ISfc V Fc system parameters, sending-end voltages and currents should be
where VSfm is the phase m sending-end voltage (V); x the distance known. The fault current is the only unknown variable on such
between the sending-end and the fault location (m); zmm the phase expressions and is calculated by an iterative procedure, as pre-
m line self impedance (X/m); zmn the mutual impedance between sented in the following.
phases m and n (X/m); ISfm the phase m sending-end current (A);
VFm the phase m fault location voltage (V); m, n is the phases a, b, 2.2. Fault current estimation
or c.
For the single line-to-ground fault (SLG) illustrated in Fig. 1, the Referring to Fig. 1, the fault current (IFp) may be estimated
faulted phase sending-end voltage from (1) can be expanded to (2): through the difference between the load current and the send-
ing-end current, as given by (10):

IF  ISf   IL  10

where [ISf] is the sending-end three-phase current vector; [IL] is the


three-phase load current vector.
Considering the fault period load current different from the pre-
fault load current, due to system dynamics, an iterative formula-
tion is developed to estimate the rst [19], as follows:

(I) Fault period load current is initially considered equal to the


pre-fault load current.
(II) Fault current is calculated using (10).
(III) Fault location and resistance are determined by (8) and (9),
respectively.
Fig. 1. Single line-to-ground fault. (IV) Fault location voltages are estimated through (11):
1328 A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335

2 3 2 3 2 3 2 3
V Fa V Sfa zaa zab zac ISfa (I) Three different power ow analyses, such as described in
6 7 6 7 6 7 6 7 [20], are executed. In each one of the PFA, consider different
4 V F b 5 4 V Sfb 5  x  4 zba zbb zbc 5  4 ISfb 5 11
V Fc V Sfc zca zcb zcc ISfc voltage conditions at the substation, in order to obtain dif-
ferent operating points of the system. The system loading
(V) An equivalent admittance matrix between the load and the must be held constant in the three PFA. The different operat-
line impedance between the fault location and the receiv- ing points are given by the different voltage conditions at the
ing-end is calculated by (12): substation terminals. Initially is considered a balanced volt-
Y L  L  x  Z Z L 1 12 age condition at the substation terminals, as given by (16):

where [Z] is the line impedance matrix per unit length, [ZL] is V S  jV S j\0 jV S j\  120 jV S j\120 T 16
the load impedance matrix, and L is the line length.
(VI) The three-phase load current vector is updated using the The rst PFA considers the balanced voltage condition, as given by
equivalent admittance matrix obtained by (12) and the fault (16). The other two PFA are executed considering slightly different
location voltages: voltage conditions, which should be unbalanced in order to avoid
IL  Y L   V F  13 linearly dependent results. The voltage conditions considered in
the subsequent PFA can be described by (17):
(VI) The algorithm veries if the fault resistance and distance
have converged, using (14) and (15): V Sk  jV S j  1 bk 17
jRF n  RF n  1j < d1 14
where bk is a voltage deviation per unit value, which can be either a
jxn  xn  1j < d2 15 positive or a negative value. Its value should be small, such as
0.01 p.u., and different for each phase k. This avoids convergence
where n is the iteration number and d1,2 are the error toler-
problems in the power ow algorithm. The voltage angles, however,
ances, which are previously dened according to the accuracy
are kept constant.
and computational time desired. In this work, d1 and d2 have
(II) Calculate the equivalent impedances for each phase, from
been considered equal to 1  107 and 1  104, respectively.
each node p to its adjacent nodes q, using (18):
(VI) If the fault resistance and distance have converged, stop the 2 3 2 31 2 3
iterative procedure, otherwise return to step II. Z ta I a1 I b1 I c1 V t1
From the iterative formulation presented in this section, 6 7 6 I c2 7 6 7
Z t pq 4 Z tb 5 4 I a2 I b2 5  4 V t2 5 18
fault resistance and distance can be considered as outputs. Z tc I a3 I b3 I c3 V t3 p
pq pq
Thus, the fault distance can also be used as a fault location
estimate. However, as typical impedance-based fault loca- for t = {a, b, c}, where the subscripts {1, 2, 3} represent the index of
tion techniques, for higher fault resistance values the fault the three different PFA; and p, q is the adjacent nodes; Zmn the
distance estimate may be inaccurate [19]. An additive error impedance between phases m and n; V the resulting voltage from
in the fault current estimate provides a much higher nega- PFA; I is the resulting current from PFA.
tive effect in the fault distance estimate than in the fault (II) Determine a three-phase equivalent matrix, [Zeq]pq, for each
resistance one [19]. lateral that starts with a section connecting the adjacent
nodes p and q, using the vectors dened on (18), applied in
2.3. Distribution systems laterals (19):
Z eq pq Z a pq Z b pq Z c pq T 19
Power distribution feeders are typically radial networks com-
posed by a main feeder, laterals, and sub-laterals. The faulted The algorithm considers initially the voltages and currents mea-
branch identication is a research eld still under development, sured at the substation terminal. With the previously known infor-
which exceeds the scope of this paper. The proposed fault analysis mation of the faulted section and the equivalent laterals, it is
algorithm considers the faulted lateral to be previously known possible to calculate the voltages and currents at all nodes up-
data. The extension of the proposed fault resistance sub-routine stream to the faulted section.
for systems with laterals, however, is still necessary. To obtain such Since voltages and currents are measured only at the substation
extension, the proposed method obtains equivalent networks asso- terminals, voltages and currents at the downstream bus (k + 1) are
ciated with each one of the systems laterals. estimated by (20) and (21), respectively:
In this work, each system lateral is replaced by an equivalent
V k1  V k   Z k   Ik  20
network that is represented as a three-phase constant impedance
X n
matrix. Thus, each system lateral can be represented by a tapped Ik1  Ikm   ILk  21
off equivalent network. Considering a distribution system with n m1
laterals, n different equivalent networks are obtained, one for each mk1

lateral. These equivalents are obtained considering the systems


where [Zk] is the line impedance matrix between buses k and k + 1;
pre-fault steady state operating conditions.
[Ik] the three-phase current vector between buses k and k + 1; [Ik-m]
The lateral equivalents are calculated through a technique
the three-phase current vector between buses k and m; n is the total
based on [20]. It uses estimated voltages and currents at each
system bus number.
bus, considering several different systems conditions. The load
Considering a constant impedance load model, the local bus
impedance, however, must be maintained constant during the
load current (ILk) is calculated through (22):
analysis. Hence, in this work, loads are represented as constant
impedances. As opposed to [20], three-phase power ow analyses ILk  V k   Z Lk 1 22
(PFA) are used to determine the equivalents. By the use of this ap-
proach, all equivalent networks are determined, and the system is where [ZLk] is the bus k load impedance matrix.
reduced to the main path between the substation and the faulted The voltages and currents are updated until the rst node up-
sections downstream bus. The steps to obtain such equivalent net- stream to the faulted section. These values are used for the fault
works are detailed in the following: resistance estimation procedure previously described.
A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335 1329

2.4. Fault type extension

Sections 2.12.3 presented a fault resistance sub-routine for


SLG faults. The technique may be extended to all remaining faults
types through specic equations. For each fault type, the fault
resistance sub-routine remains the same as presented previously.
However, the fault resistance and distance equations (8) and (9),
respectively, are replaced by the specic expressions for each fault
type, as follows.

2.4.1. Line-to-line fault


Consider a line-to-line fault (LL), as illustrated in Fig. 2. Follow-
ing the same procedure presented in Section 2.1, a new set of
expressions is obtained for fault location and resistance, given in
a matrix form by (23): Fig. 3. Double line-to-ground fault.
  " #1 " #
x M3 IF pr V Sfpr  V Sfqr
23
RF M4 IF pi V Sfpi  V Sfqi

where
X
M3 zpkr  zqkr ISfkr  zpki  zqki ISfki  24
kfa;b;cg
X
M4 zpkr  zqkr ISfki zpki  zqki ISfkr  25
kfa;b;cg

zpm is the mutual impedance between phases p and m (X/m); zqm


the mutual impedance between phases q and m (X/m); m the
phases a, b, and c; p, q is the faulted phases a, b, or c.

2.4.2. Double line-to-ground fault


A double line-to-ground fault (DLG) is illustrated in Fig. 3. The
mathematical expressions for this fault type are given by: Fig. 4. Three-phase fault.

2 3 2 31 2 3
x M 1p IF pr 0 IF pr IF qr V Sfpr Finally, from (9), (23), (26), and (27) it is possible to estimate all
6 RF 7 6 M2 IF pi IF qi 7 6 7
6 p 7 6 p IF pi 0 7 6 V Sfpi 7 26
fault resistances for any fault type. Based on these estimated val-
6 76 7 6 7 ues, the bus impedance sub-routine can be developed, as presented
4 RF q 5 4 M 1q 0 IF qr IF pr IF qr 5 4 V Sfqr 5
in the following.
RF pq M 2q 0 IF qi IF pi IF qi V Sfqi

where M1 and M2 are given by (5) and (6). 3. Bus impedance sub-routine

2.4.3. Three-phase fault Power distribution systems are typically unbalanced, with
For the three-phase fault (3PH), which is illustrated in Fig. 4, the untransposed feeders and single-phase loads. In these conditions,
expressions for the fault distance and the three fault resistances the bus impedance matrix technique is the most suitable choice
are given by (27): available for fault system voltages and currents state estimation.
Using this method it is possible to analyze any fault type by mod-
2 3 2 31 2 3
x M 1a IF ar 0 0 V Sfar ifying the phase coordinate base-case impedance matrix, consider-
6 R 7 6 M2 IF ai 0 0 7 6 V Sf 7 ing the systems asymmetries. The bus impedance sub-routine,
6 Fa 7 6 a 7 6 ai 7 27
6 76 7 6 7 which was initially proposed in [7], is described in the following
4 RFb 5 4 M1b 0 IF br 0 5 4 V Sfbr 5
subsections.
RF c M 1c 0 0 IF cr V Sfci
3.1. Bus impedance matrix
where M1 and M2 are given by (5) and (6).

Three-phase admittance matrix Ybus is calculated from the


three-phase sub-matrices feeders components. The diagonal sub-
matrix of a hypothetical bus p is calculated through (28), which
represents the sum of all sub-matrices representing the M ele-
ments adjacent to bus p.
M h
X i
Y abc p;p Y~ abc 28
i;p
i1

The off-diagonal sub-matrices are obtained from (29), where


~ abc  is the admittance matrix element between buses p and j.
Y p;j
h i
Y abc p;j  Y~ abc 29
p;j
Fig. 2. Line-to-line fault.
1330 A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335

From (28) and (29), 3n  3n three-phase admittance and Adding the superimposed voltages to each pre-fault bus voltage
impedance matrices are built, as presented in (30) and (31), (VPF), the fault period bus voltages (VF) are estimated through (36):
respectively.
V F i V PF i DV i 36
2 3
Y abc 1;1 Y abc 1;2    Y abc 1;n
6 Y  Finally, from the three-phase bus voltages and the admittance ma-
6 abc 2;1 Y abc 2;2    Y abc 2;n 7
7 trix, it is possible to calculate the three-phase currents during the
6 7
Y bus  6 .. .. .. 7 30 fault period at each feeder (Igh):
6 . .  . 7
4 5
Y abc n;1 Y abc n;2    Y abc n;n Igh  Y abc g;h  V Fg   V Fh  37

where [Yabc]g,h is the admittance matrix between buses g and h;


Z bus  Y bus 1 31 [VFg] the bus g three-phase voltage vector; [VFh] is the bus h
three-phase voltage vector.
where n is the total system bus number. where g, h = 1 ? (n + 1), in which n is the total bus number.

3.2. Pre-fault state calculation 3.3.2. Line-to-line fault


A similar procedure may be applied for line-to-line faults,
The bus impedance sub-routine uses a ladder based three-phase where Zbus must be modied to include the fault resistance
load ow technique [21], considering the non-linear characteristics between the two faulted nodes (r and s), as given by (38) and (39)
of the feeder to estimate the pre-fault voltages on each bus. For the
estimated voltages convergence analysis, the three-phase load ow Z new r; r Z bus r; r 0:5RF 38
also considers the pre-fault voltages measured at the substation on Z new s; s Z bus s; s 0:5RF 39
each fault record and compares to the calculated voltages at the
where RF is the fault resistance estimated by (23).
substation bus.
From the modied impedance matrix, it is possible to deter-
mine the relation between the fault voltages and currents:
3.3. Fault calculation      
V Fr Z new r; r Z new r; s IFr
 40
The bus impedance sub-routine is based on the superposition V Fs Z new s; r Z new s; s IFr
technique. The fault condition is simulated by two voltages sources
Manipulating algebraically (40), the fault current for a line-to-
series connected. The rst voltage source represents the pre-fault
line fault can be calculated using (41):
voltage, whereas the second source is dened to satisfy each fault
type boundary condition. V PF r  V PF s
IFq 41
For each fault type, a different bus impedance matrix (Zbus) Z new r; r  Z new r; s Z new s; s
modication must be developed to include the fault resistance
where VPFr and VPFs are the nodes r and s pre-fault voltages.
estimate, calculated by the fault resistance algorithm presented
With the estimated fault current, the superimposed voltages are
in Section 2. The Zbus modications for each fault type are pre-
calculated though (42):
sented in the following.
2 3 2 3
DV 1 0
3.3.1. Single line-to-ground fault 6 . 7 6 .. 7
6 .. 7 6 . 7
6 7 6 7
For a single line-to-ground fault, Zbus must be modied to in- 6 7 6 7
6 DV r 7 6 IFr 7
clude the fault resistance of the path between the faulted line 6 7 6 7
6 DV 7 Z new   6 IFr 7 42
and ground. The fault resistance is included in the bus impedance 6 s 7 6 7
6 . 7 6 . 7
matrix through a fault node r. As result, a new impedance matrix 6 . 7 6 . 7
4 . 5 4 . 5
Znew of dimension (3n + 3)  (3n + 3) is obtained. For a SLG fault,
the fault current may be calculated using (32): DV n 0

V Fr or
IFr 32 X
Z new r; r DV i Z new i; j  IFj 43
j1
where VFr is the node r pre-fault voltage, and
where i, j = 1 ? (3n + 3) represent the node indexes.
Z new r; r Z bus r; r RF 33
From the superimposed and pre-fault voltages, the three-phase
where RF is the fault resistance, estimated by (9). voltages and currents at each feeder can also be calculated through
The superimposed voltages at each bus due to the injected fault (36) and (37), respectively.
current (IFr) may be calculated using the impedance matrix Znew:
2 3.3.3. Double line-to-ground fault
DV 1 3 2
0
3
Considering a DLG fault, as illustrated in Fig. 3, the Zbus matrix
6 .. 7 6 .. 7 must be modied to include in the two faulted nodes (r and s)
6 . 7 6 . 7
6 7 6 7 the three fault resistances of the fault model. Following the same
6 7 6 7
6 DV r 7 Z new   6 IFr 7 34 procedure as presented previously:
6 7 6 7
6 .. 7 6 .. 7
4 . 5 4 . 5
Z new r; r Z bus r; r RF r 0:5RF rs 44
DV n 0 Z new s; s Z bus s; s RF s 0:5RF rs 45
where (34) can also be rewritten as: where RFR, RFs, and RFrs are the fault resistances estimates obtained
DV i Z new i; r  IFr 35 from (26).
Using the modied three-phase impedance matrix Znew, the
whereas i = 1 ? (3n + 3) represents the node index. fault currents (IFr and IFs) are calculated through (46):
A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335 1331

   1  
IF r Z new r; r Z new r; s V PF r  All loads modeled as constant impedance Y-connected with
 46 neutral grounding.
IF s Z new s; r Z new s; s V PF s
where VPFr, VPFs, are the pre-fault voltages on the faulted nodes r and The modied test system, composed by 36 buses and illustrated
s, respectively. by Fig. 5, was simulated using BPAs ATP/EMTP [17]. The fault anal-
From the fault currents estimated through (46), the superim- ysis algorithm was implemented in MATLAB [15]. A modied
posed voltages are calculated using (47): Fourier lter [22] was also implemented in MATLAB to remove
2 3 2 3 the decaying DC component and estimate the voltages and cur-
DV 1 0
6 . 7 6 .. 7 rents fundamental components measured at the substation termi-
6 .. 7 6 . 7 nal. The simulations were executed considering the following fault
6 7 6 7
6 7 6 7
6 DV r 7 6 I 7 conditions:
6 7 Z new   6 Fr 7 47
6 DV 7 6 IFs 7
6 s 7 6 7
6 . 7 6 . 7  103 different fault locations (covering all system laterals and
6 . 7 6 . 7
4 . 5 4 . 5 sections).
DV n 0  Five different fault resistances: 0, 10, 20, 50, and 100 X.
 10 fault types: A-g, B-g, C-g, AB, BC, AC, AB-g, BC-g, AC-g, and
From the superimposed voltages, the fault period bus voltages ABC-g.
and currents can be obtained through (36) and (37), respectively.  Total: 5150 faults.

3.3.4. Three-phase fault The simulation set was divided in two different case tests,
Three-phase fault is the most severe fault type, and is normally which are summarized in the following scenarios:
used for rotating machines fault analysis. However, this fault type
represents only 5% of the fault events on transmission lines [1]. For  Set I:
three-phase faults the bus impedance matrix must be modied to 103 fault locations.
include the phases a, b, and c fault resistances, whose estimates are Five fault resistances.
obtained from (27):
Z new r; r Z bus r; r RF a 48 10 fault types.
Z new s; s Z bus s; s RF b 49 Total: 5150 fault cases.
Z new t; t Z bus t; t RF c 50
 Set II:
where r, s, and t are the fault nodes indexes.
Two fault locations (K1 = 2.063 km, K2 = 1.649 km).
From the modied three-phase bus impedance (Znew), the fault
Five fault resistances.
currents are calculated using (51):
10 fault types.
2 3 2 31 2 3 Total: 100 fault cases.
IF r Z new r; r Z new r; s Z new r; t V PF r
6 7 6 7 6 7 51
4 IF s 5 4 Z new s; r Z new s; s Z new s; t 5  4 V PF s 5
IF t Z new t; r Z new t; s Z new t; t V PF t
where VPFr, VPFs, VPFt are the pre-fault voltages on the faulted nodes
r, s, and t, respectively.
From the fault currents calculated through (51), the bus super-
imposed voltages are obtained by (52):
2 3 2 3
DV 1 0
6 . 7 .
6 . 7
6 .. 7 6 . 7
6 7 6 7
6 7 6 I 7
6 DV r 7 6 Fr 7
6 7 6 7
6 7
6 DV s 7 Z new   6 7
6 IFs 7 52
6 7 6 I 7
6 DV t 7 6 Ft 7
6 7 6 7
6 . 7 6 .. 7
6 . 7 4 . 5
4 . 5
DV n 0

Finally, as presented previously, the bus voltages and currents


during the fault period are calculated by (36) and (37).

4. Case study

In order to validate the proposed algorithm, a modied version of


IEEE 37 Node Test Feeder has been chosen for numeric test simula-
tions. The original IEEE 37-bus system [16] has been modied to in-
clude some Brazilians distribution systems typical characteristics:

 Base voltage: 13.8 kV.


 Three wire Y-connected with neutral grounding.
 No voltage regulator. Fig. 5. Modied IEEE 37 node test feeder.
1332 A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335

The errors in the fault resistances estimates were calculated scenario. The fault resistance effect in the proposed algorithm
considering the absolute difference between estimated and simu- may be explained by the erroneous estimation of the fault current
lated fault resistances, as given by (53): for high fault resistances values [16], also associated to the so-
called reactance error [23]. As given in (10), the proposed formula-
e jRF calc  RF real j 53
tion is fault period load current estimate dependent. For faults with
where RFcalc and RFreal are the estimated and the real fault resis- small fault resistances values, the current divider circuit of the
tances values, respectively. faulted system is composed by the load impedance and a negligible
fault resistance. In this scenario, the source current will mainly
feed the fault and the fault current will be close to the rst. There-
5. Results fore, small variation on the calculated fault current does not affect
the fault resistance estimate. As illustrated by Tables 1 and 2, as the
In the following subsections, the obtained results from the pro- fault resistance increases, this effect became more signicant.
posed fault analysis algorithm are presented and discussed. Ini- However, even to the most critical analyzed fault scenario, the
tially, the effects of different fault resistance and distance values maximum error obtained was 2.30%.
on the fault resistance estimate are veried. After, the buses volt-
ages and fault currents estimates are also compared to the BPAs 5.1.2. Fault distance effect
ATP/EMTP simulations. To analyze the fault distance effect on the fault resistance esti-
mate, the obtained results from Set I were used. Figs. 6 and 7 illus-
5.1. Fault resistance estimation trate the fault resistance estimates over each one of the 103
simulated fault locations for single line-to-ground and line-to-line
Set I test results were used to analyze the fault analysis algo- faults, respectively.
rithm performance. The results are analyzed over two aspects: The fault resistance estimates demonstrate that the proposed
fault resistance and distance effects. algorithm efciency is fault location independent. As provided by
Tables 1 and 2, on faults up to 100-X, a small difference between
5.1.1. Fault resistance effects maximum and average errors can be observed for the four fault
Table 1 presents the results for single line-to-ground and line- types. Also, as illustrated by Figs. 6 and 7, a small variation over
to-line faults for ve simulated fault resistances. The results show the 103 fault points can only be visually observed for the most crit-
that the errors associated to the fault resistances estimates slightly ical simulated fault condition. However, as discussed previously,
increase for higher fault resistances values. The algorithm yielded a these differences can be neglected.
highest average error equal to 1.13 X for SLG faults and 0.19 X for
LL faults. Still, the maximum errors produced by the algorithm 5.2. System voltages and currents estimation
were 1.66 X and 1.13 X for single line-to-ground and line-to-line
faults, respectively. Considering Set test II, the proposed fault analysis algorithm
Table 2 shows the fault resistances estimate results for double performance is discussed over two aspects: fault current at the
line-to-ground and three-phase faults. The comparison between faulty bus and bus voltages during the disturbance. In this section
the calculated and the simulated fault resistances values also dem- two different fault locations have been analyzed. The investigated
onstrate negligible errors on both fault types. In double line-to- fault points K1 and K2, which are coincident to buses 707 and 737,
ground faults, the average and maximum errors obtained were, are located 2063 and 1649 meters from the substation, as illus-
respectively, 0.97 X and 1.43 X, both occurred on the 100-X fault trated in Fig. 5. The results discussed in this section represents
scenario. The algorithm provided for three-phase faults a maxi- not only the inaccuracy associated to the Zbus analysis technique,
mum error equal to 2.30 X, for a 100-X fault. Also for this fault but the hole fault analysis method proposed in this paper, includ-
type, the highest average errors for 50-X and 100-X fault resis- ing the errors introduced by the fault resistance estimates.
tances were 0.22 X and 1.05 X, respectively.
The results presented in Table 2 show slight differences be- 5.2.1. Fault current
tween the estimated fault resistances in each faulted phase, re- Fault analysis performance was rst evaluated considering the
sulted by system unbalances and the fundamental components fault current at faulty buses K1 and K2. Tables 3 and 4 show the
determination process, due to different fault inception angles. fault current errors, demonstrating the inaccuracies of absolute
However, as described in Table 2, these inaccuracies provide small and angular components between calculated fault current and
differences which will not affect the proposed fault analysis meth- BPAs ATP/EMTP simulations.
od performance. The obtained results for single line-to-ground and line-to-line
As expected from an impedance-based formulation, the highest faults at K1 and K2 are presented in Table 3. During SLG faults with-
errors were obtained during the most critical fault resistance test out fault resistance, the method provided maximum errors to this

Table 1
Fault resistance estimates for single line-to-ground and line-to-line faults.

Fault type Simulated RF (X) Maximum error (X) Minimum error (X) Average error (X)
A-g 0 0 0 0
A-g 10 0.02 0 0.01
A-g 20 0.06 0.01 0.03
A-g 50 0.35 0.03 0.21
A-g 100 1.66 0.11 1.13
BC 0 0 0 0
BC 10 0.01 0 0
BC 20 0.03 0 0
BC 50 0.11 0 0.03
BC 100 1.13 0 0.19
A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335 1333

Table 2
Fault resistances estimates for double line-to-ground and three-phase faults.

Fault type Simulated RF (X) Maximum error (X) Minimum error (X) Average error (X)
RFa RFb RFc RFa RFb RFc RFa RFb RFc RFa RFb RFc
AC-g 0 0 0 0 0 0 0 0
AC-g 10 10 0.01 0.01 0 0 0.01 0
AC-g 20 20 0.04 0.04 0.01 0 0.03 0.02
AC-g 50 50 0.29 0.27 0.03 0.01 0.18 0.12
AC-g 100 100 1.43 1.03 0.11 0.04 0.97 0.66
ABC-g 0 0 0 0 0 0.01 0 0 0 0 0 0
ABC-g 10 10 10 0.02 0.02 0.01 0 0 0 0.01 0 0.01
ABC-g 20 20 20 0.06 0.05 0.05 0.01 0 0.01 0.03 0.02 0.02
ABC-g 50 50 50 0.42 0.62 0.49 0.03 0 0.02 0.22 0.13 0.19
ABC-g 100 100 100 1.53 2.30 2.25 0.10 0.01 0.06 1.05 0.48 0.92

Fig. 6. Distance effect on RF estimation for SLG faults (A-g).

Fig. 7. Distance effect on RF estimation for LL faults (BC).

has also been obtained, providing maximum errors of 0.54%, or


Table 3
Fault current errors at K1 and K2 for single line-to-ground and line-line faults. 39 A, and 0.17, both occurred at K2. For 2LG and 3PH faults, which
results at K1 are shown in Table 4, the proposed fault analysis con-
Fault K1 K2
rms its accuracy with small errors for all fault conditions. During
A-g BC A-g BC double line-to-ground faults, the maximum error was 0.47% and
RF (X) |Ifa| (%) H () |Ifbc| (%) H () |Ifa| (%) H () |Ifbc| (%) H () 0.41, once again occurred during solid faults. For three-phase
0 0.22 0.31 0.45 0.28 0.30 0.16 0.54 0.17 faults the method also achieved negligible errors, equal to 0.59%
10 0.01 0.34 0.08 0.32 0.05 0.19 0.08 0.17 and 0.37.
20 0.01 0.34 0.04 0.32 0.03 0.19 0.04 0.17 The above mentioned results demonstrate that the proposed
50 0 0.34 0.02 0.32 0.02 0.19 0.02 0.17
fault analysis method has always produced the highest absolute er-
100 0.01 0.34 0.01 0.32 0.02 0.19 0.03 0.17
rors during solid faults, oppositely as the fault resistance estimate
process, as discussed previously. However, the highest obtained er-
ror was 43 A, or 0.59%, and could be neglected. As shown by Tables
fault type equal to 0.22% at K1 and 0.30% at K2, which represents 3 and 4, the inaccuracy associated to the absolute fault currents be-
negligible absolute errors of 16 and 21 A, respectively. Still in this came insignicant for higher fault resistances values. Therefore,
fault scenario, the highest fault current angle errors were 0.31 and the fault resistance increase does not interfere in the fault current
0.16. In line-to-line disturbances, a similar behavior as SLG faults estimate accuracy.
1334 A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335

Table 4
Fault current errors at K1 for double line-to-ground and three-phase faults.

Fault type AC-g ABC


RF (X) |Ifa| (%) H () |Ifc| (%) H () |Ifa| (%) H () |Ifb| (%) H () |Ifc| (%) H ()
0 0.21 0.41 0.47 0.40 0.27 0.32 0.37 0.24 0.59 0.36
10 0.01 0.35 0.06 0.38 0.01 0.34 0.04 0.35 0.06 0.37
20 0.01 0.35 0.03 0.37 0.01 0.34 0.02 0.35 0.03 0.37
50 0 0.34 0.01 0.37 0 0.34 0.01 0.35 0.01 0.37
100 0.01 0.34 0.01 0.37 0.01 0.34 0.01 0.36 0.01 0.37

Table 5
Bus voltages errors for faults at K1.

RF (X) Fault type 0 10 20 50 100


Bus |V| (%) H () |V| (%) H () |V| (%) H () |V| (%) H () |V| (%) H ()
702 A-g 0.25 0.2 0.25 0.19 0.25 0.19 0.25 0.19 0.25 0.19
BC 0.21 0.17 0.24 0.18 0.25 0.19 0.25 0.19 0.25 0.19
AC-g 0.20 0.16 0.24 0.19 0.25 0.19 0.19 0.25 0.25 0.19
ABC 0.18 0.14 0.24 0.19 0.25 0.19 0.25 0.19 0.25 0.19
709 A-g 0.17 0.31 0.18 0.31 0.18 0.31 0.18 0.31 0.18 0.32
BC 0.12 0.31 0.17 0.31 0.18 0.31 0.18 0.31 0.18 0.31
AC-g 0.21 0.30 0.19 0.32 0.18 0.32 0.18 0.31 0.18 0.31
ABC 0.11 0.31 0.17 0.31 0.18 0.31 0.18 0.31 0.18 0.32
720 A-g 0.71 0.50 0.82 0.51 0.82 0.50 0.82 0.50 0.82 0.50
BC 0.75 0.64 0.81 0.51 0.82 0.51 0.82 0.50 0.82 0.50
AC-g 0.77 0.48 0.82 0.50 0.82 0.50 0.82 0.50 0.82 0.50
ABC 0.76 0.51 0.82 0.50 0.82 0.50 0.82 0.50 0.82 0.50
734 A-g 0.37 0.43 0.40 0.39 0.40 0.39 0.40 0.39 0.40 0.38
BC 0.15 0.72 0.37 0.39 0.38 0.39 0.39 0.39 0.39 0.39
AC-g 0.18 0.47 0.37 0.39 0.38 0.39 0.39 0.39 0.39 0.39
ABC 0.20 0.62 0.38 0.39 0.39 0.39 0.39 0.39 0.39 0.38

5.2.2. Bus voltages technique has been developed to be suitable for generic unbalanced
The fault analysis algorithm performance was also evaluated power distribution systems with ramications, and only requires
through comparisons between BPAs ATP/EMTP simulations and the disturbance sending-end voltages and currents.
the estimated voltages in four different buses: 702, 709, 720, and Test results demonstrate an accurate and robust fault analysis
734. Table 5 presents the maximum absolute and angular errors method. The fault resistance estimate algorithm provided accurate
for all analyzed faults at K1. Considering the bus voltages estimated results to all analyzed cases, for faults up to 100 X, with a small
from the calculated fault current and pre-fault voltages, this sec- dependence with the fault resistance value. Besides, the fault resis-
tion discusses the inaccuracies introduced by three different pro- tance sub-routine is invariant to the fault location. The proposed
cesses: fault resistance, fault current and three-phase load ow. fault analysis algorithm performance is also independent to fault
The estimated bus voltages accuracy is demonstrated by Table 5 resistance values and fault location. The obtained results demon-
results: the highest absolute error was 0.82%, which represents an strate the technique accuracy to all analyzed conditions, showing
error equal to 113 Volts and it is associated to bus 720. A maximum that the discussed aspects do not affect the proposed fault analysis
error of 0.72 has also been obtained at bus 734. As consequence performance.
from the already discussed fault current estimate accuracy, the re- In this work the fault impedance was modeled as a constant
sults provided by Table 5 also demonstrate the bus voltage esti- resistance and the distribution system considered radial. It is ex-
mate invariance to different fault resistances values. Besides, pected that the proposed method performance decreases when
these results demonstrate that the main error source is the pre- fault impedance is not strictly resistive and constant or when dis-
fault bus voltages, which were estimated in this paper through a tributed generation are connected to network buses. Parameter
three-phase load ow based on the ladder technique [21]. There- identication is a research topic of great interest of the power sys-
fore, the bus voltage estimates are dependent to the bus and also tems community. In this work however this issue was not ad-
the fault location, resulting in different error levels (absolute and dressed. The proposed formulation considers known accurate
angular) to each analyzed bus. However, even the highest obtained system data. It is expected that the proposed method performance
error may be neglected due its small value. decreases with data inaccuracy.

6. Conclusions References

In this paper, an iterative fault analysis algorithm is proposed. [1] Grainger JJ, Stevenson Jr WD. Power system analysis. New York
(USA): McGraw-Hill; 1994.
The proposed method is based on two instances: fault resistance
[2] Filomena AD, Resener M, Salim RH, Bretas AS. Fault location for underground
estimation process, through an iterative impedance-based formula- distribution feeders: an extended impedance-based formulation with
tion; and the fault voltages and currents estimation process, which capacitive current compensation. Int J Electr Power Energy Syst
are carried out through a bus impedance matrix based formulation. 2009;31(9):48996.
[3] Salim RH, Resener M, Filomena AD, Oliveira KRC, Bretas AS. Extended fault
The proposed technique aims to help post-disturbance analysis, pro- location formulation for power distribution systems. IEEE Trans Power Deliv
viding information to Distribution Operation Centers. The proposed 2009;24(2):50816.
A.D. Filomena et al. / Electrical Power and Energy Systems 33 (2011) 13261335 1335

[4] Halpin SM, Grigsby LL. A comparison of fault calculation procedures for [21] Kersting WH. Distribution system modeling and analysis. Boca Raton
industrial power distribution systems: the past, the present and the future. In: (USA): CRC Press; 2002.
Proceedings of the IEEE international conference on industrial technology; [22] Lin YH, Liu CW. A new DFT-based phasor computation algorithm for
1994. transmission line digital protection. In: Proceedings of the IEEE/PES
[5] Halpin SM, Grigsby LL, Gross CA, Nelms RM. An improved fault analysis transmission and distribution conference and exhibition 2002: Asia Pacic,
algorithm for unbalanced multi-phase power distribution systems. IEEE Trans vol. 3; 2002. p. 173337.
Power Deliv 1994;9(3):13328. [23] IEEE guide for determining fault location on AC transmission and distribution
[6] Anderson PM. Analysis of faulted power systems. New York (USA): IEEE; 1995. lines. IEEE standard C37.114; June 2005.
[7] Makram EB, Bou-Rabee MA, Girgis AA. Three-phase modeling of unbalanced
distribution systems during open conductors and/or shunt fault conditions
Andr Dars Filomena was born in Porto Alegre, Rio Grande do Sul, Brazil, on
using the bus impedance matrix. Electr Power Syst Res 1987;13(3):17383.
October 27, 1982. He received his B.Sc. and M.Sc. degrees in Electrical Engineering
[8] Halpin SM, Grigsby LL. Fault analysis of multi-phase unbalanced non radial
power distribution systems. IEEE Trans Ind Appl 1995;31(3):52834. from Federal University of Rio Grande do Sul (UFRGS), Brazil, in 2005 and 2008,
[9] Dagenhart J. The 40-X ground-fault phenomenon. IEEE Trans Ind Appl respectively. He is currently with CEEE-GT (Companhia Estadual de Gerao e
2000;36(1):302. Transmisso de Energia Eltrica), in Porto Alegre, RS, Brazil and also pursuing his
[10] Waikar DL, Elangovan S, Liew A. Fault resistance estimation algorithm for Ph.D. degree at UFRGS. His research interests include power system protection,
digital distance relaying. IEEE Trans Power Deliv 1994;9(3):137583. modeling and analysis.
[11] Waikar DL, Elangovan S, Liew A. Further enhancements in the symmetrical
components based improved fault impedance estimation method. Part I. Mariana Resener was born in Passo Fundo, Rio Grande do Sul, Brazil, on April 8,
Mathematical modeling. Electr Power Syst Res 1997;40:18994. 1985. She received her B.Sc. and M.Sc. degrees in Electrical Engineering from
[12] Waikar DL, Elangovan S, Liew A. Fast and accurate parameter estimation Federal University of Rio Grande do Sul (UFRGS), Brazil, in 2008 and 2011,
algorithm for digital distance relaying. Electr Power Syst Res 1998;40:5360. respectively. She is currently with CEEE-D (Companhia Estadual de Distribuio de
[13] Samantaray SR, Dash PK, Upadhyay SK. Adaptive Kalman lter and neural Energia Eltrica), in Porto Alegre, RS, Brazil. Her research interests include power
network based high impedance fault detection power distribution networks. system control, stability, and distributed generation.
Int J Electr Power Energy Syst 2009;31(4):16772.
[14] Samantaray SR, Dash PK. A novel distance protection scheme using time-
Rodrigo Hartstein Salim was born in Porto Alegre, Rio Grande do Sul, Brazil, on
frequency analysis and pattern recognition approach. Int J Electr Power Energy
September 15, 1983. He received his B.Sc. and M.Sc. degrees in Electrical Engi-
Syst 2007;29(2):12937.
neering from Federal University of Rio Grande do Sul (UFRGS), Brazil, in 2006 and
[15] The Mathworks Inc. Mathworks Matlab. <http://www.mathworks.com/>.
[16] Kersting WH. Radial distribution test feeders. In: Proceedings of the power 2008, respectively. In 2011 he received the Ph.D. degree in electrical engineering
engineering society winter meeting, vol. 2; 2001. p. 90812. from University of So Paulo, So Carlos, Brazil. His research interests include power
[17] Prikler L, Hoidalen HK. Atpdraw version 3.5 users manual: preliminary release system protection, control, and distributed generation.
no. 1; 2002.
[18] Horowitz S, Phadke A. Power system relaying. Tauton (USA): Research Studies Arturo Suman Bretas was born in Bauru, So Paulo, Brazil, on July 5, 1972. He
Press; 1995. received the B.Sc. and M.Sc. degrees in Electrical Engineering from the University of
[19] Filomena AD, Salim RH, Resener M, Bretas AS. Ground distance relaying with So Paulo, Brazil, in 1995 and 1998 respectively. In 2001 he received the Ph.D.
fault resistance compensation for unbalanced systems. IEEE Trans Power Deliv degree in electrical engineering from Virginia Tech, Blacksburg, VA. Currently, he is
2008;23(3):131926. an Associate Professor of the Federal University of Rio Grande do Sul (UFRGS), Porto
[20] Nagpal M, Xu W, Sawada J. Harmonic impedance measurement using three- Alegre, Brazil. His research interests include power system protection, analysis and
phase transients. IEEE Trans Power Deliv 1998;13(1):2727. restoration.

Das könnte Ihnen auch gefallen