3 Call bell point with bell push switch and 2 pin socket
outlet near bell/ buzzer.(including cost of buzzer) point 1.00
Page 1 of 6
S.no.Description Unit Quantity Rate Amount
(Rs) (Rs.)
4 Providing 5/15 A (6 pin) switch socket with outlet
boxes, with 650/ 1100 V grade ISI marked PVC
insulated copper conductor, i.e. 2 nos. of 4 sqmm
and 1 no. of 2.5 sqmm multistrand single PVC
insulated copper conductor wires and modular
switches/ boxes/ access etc. to the satisfaction of
the architect (DB to 15A Plug point) complete in all
respects with controlling switch, box and cover plate
complete.(complete with metal clad a/cbox of havells)
(wiring to be paid for seperately) each 4.00
5 Same as above but without a/c box , in server room each 4.00
/ ups room (wiring to be paid for seperately)
Page 2 of 6
S.no.Description Unit Quantity Rate Amount
(Rs.) (Rs.)
11 Wiring for the following power circuit / submains
with pvc insulated copper conductor cable in recessed
pvc conduit including copper connections as required
a 2 nos. 4 sqmm plus 1.5 sq.mm earth(from main panel metre 75.00
to individual a/c s)
b 2 nos. 6 sqmm plus 1.5 sq.mm earth metre 45.00
(for light fan db and computer outlets db/ ups db))
(seperately from main to each db)
c 4 nos. 10 sqmm plus 4 sqmm earth metre 15.00
(for ups db)(seperately from main)
15 Earthing
Earthing the installation as per IE rules conforming to
IS 3043-1987 or latest amendment by making earth
station with 600mm x 600mm x 6mm minimum
thick copper plate electrode to be installed such that
its top edge shall be at a minimum depth of 1.5m
below ground level after preparation of ground with
charcoal and salt and connecting the 25mm x 6mm
copper earth load-in-stop (upto panel by
bolting and then brazing to the copper plate
complete with copper bolts of suitable length, double
nuts and washer pipe with funnel for watering
arrangement. All copper insulating strips shall be
PVC sleeved/ insulated through the total length.The
earthing installation shall be provided by 300mm x 300
mm and 300mm depth inside dimensions masonry
inspection pit with c.i. hinged cover having locking
arrangement. each 2.00
Page 3 of 6
S.no.Description Unit Quantity Rate Amount
(Rs.) (Rs.)
16 Providing and fixing main panel
250 A TP MCCB (1 no.) as incoming
250 A Euroload change over ( 1 no.)
Cable Alley
Bus bars
Ammeter and Voltmeter with selector switches
Phase indicator lamps phase wise for UPSEB and
DG supply indications
Outgoing feeder_
63 A TPN MCB( 1 nos.)(to ups room)
63 A TPN MCB(1no. For light/ fan db)
125 A TPN MCB (for A/C Main)
32 A DP MCB (for pump)
20 A SP MCB ( 4nos. For A/C- future)
16A SP MCB( 6 nos.spare)
All complete as per detailed drawing, shop drawing
to be provided by the contractor for approval.
aproximate panel size of 1200mm x 1200mm/ or each 1.00
as per space available .
Page 4 of 6
S.no.Description Unit Quantity Rate Amount
(Rs.) (Rs.)
SUBHEAD `B' -SUPPLY AND ERECTION OF FIXTURES
total
(Rupees only)
Page 5 of 6
APPROVED LIST OF MATERIALS
Page 6 of 6