Sie sind auf Seite 1von 4

PowerChain Management solutions

Eaton IQ 250 and IQ 260


Electronic Power Meters


Compact, digital meter delivers high-end power management performance
Verify meter accuracy with converters that sample at more
KYZ test pulse self-certifica- than 400 samples per cycle and
tion capabilities meet ANSI C12.20 standards for
accuracy of 0.2 percent. With
Optional 128KB for data
such high-performance measure-
logging which guards against
ment capability, these meters
loss of historical data
can be confidently used for
Standard Modbus RTU primary revenue metering and
communications sub-metering applications.
Available as transducer only Eatons IQ 250/260 meters pro-
or with display vide direct-reading metered val-
ues for the most critical power
Field upgradeable to a Power aspects, such as watts, watt
Xpert Meter 2000 demand, watt-hours, voltage-
Integrate into Eatons Power amperes (VA), VA-hours, vars,
Xpert Architecture for a var-hours and power factor. They
holistic system-level view have high sampling speed and
accuracy. The IQ 260 meter also
Introduction measures power quality, such as
total harmonic distortion (THD)
With energy costs skyrocketing, up to the 40th order. The IQ 260
IQ 250/260 Electronic Power Meter you need the ability to verify the also provides configurable limit
accuracy of utility billing and allo- alarming/control capability of up
cation of energy costs among to eight measured parameters
Typical applications business units, different manu- for more sophisticated power
facturing areas or facilities, and management. In addition, the
Utility and commercial tenants. Production equipment
metering optional 128KB onboard storage
and IT systems are vulnerable to protects against data loss in the
Substations, industrial facili- power anomalies; therefore you event of a communication loss.
ties, power generation sites must ensure power is always
and campuses up to specifications. If your Is the utility company billing
infrastructure is an established accurately? The IQ 250/260 pro-
Sub-metering facility, you may have addressed vide a traceable KYZ watt-hour
Load studies and voltage these concerns in the past by test pulse (used with a watt-
recording deploying a variety of analog hour pulse recorder or totalizer),
gauges and meters one for so you can verify the accuracy
Analog meter replacement volts, one for amperes, and so of your meter, and in turn, the
on, with separate meters for accuracy of billing from the
Features and benets each measurement. If youre utility company and to internal
Measure and display real- planning an upgrade or new customers.
time information about criti- power infrastructure, no doubt
In addition, Eatons IQ 250/260
cal power parameters with a you would like to capitalize on
meters provide flexible input/
sampling rate of 400 samples the latest technology to improve
output options for access to
per cycle upon that cumbersome architec-
future upgrades. The meters are
ture and its patchwork view.
Monitor power utilization and also designed to integrate into
quality with ANSI C12.20 Eatons Power Xpert Architecture
High-end capabilities you
accuracy (0.2 percent) for end-to-end management of
would not expect from an
your entire power system, giving
ultra-compact meter
you a holistic system-level view.
Providing the first line of For example, using a Power
defense against costly power Xpert Meter 2000 Gateway Card
problems, Eatons IQ 250 and Kit, this meter can quickly and
IQ 260 electronic power meters easily become a Power Xpert
(IQ 250/260) can perform the Meter 2000, which offers addi-
work of an entire wall of legacy tional features such as Ethernet
metering equipment utiliz- connectivity and emailing of
ing todays technology. The IQ alarms.
250/260 meters use 24-bit A/D
Features of IQ 250/260 Electronic Power meters Mix-and-match input/output options
Features IQ 250 IQ 260 Perhaps you need to:
Instrumentation Monitor the status of a piece of equipment
Current, per phase X X Activate a warning light if voltage exceeds a certain threshold
Current demand X X
Trigger a relay contact-closure device
Calculated neutral current X X
Transmit power information directly to a process-control system or
Voltage, per phase (L-L, L-N) X X
building management system, or to a legacy system that doesnt
Frequency X X use Modbus
Power, energy & demand For any of these scenarios, IQ 250/260 meters provide optional
Real, reactive & apparent power, total & per phase X X input/output (I/O) cards that meet the need for either manual or
(kW, kvar, kVA) automatic operation.
Real, reactive & apparent energy, total & per phase X X The IQ 250/260 meters provide flexible configuration, with four
(kWh, kvarh, kVAh) optional cards available (analog and digital), which can be combined
in any fashion in two universal communication slots. The meters
Real, reactive & apparent power demand X X
auto-detect the installed I/O modules, so you can easily add or
Power factor, total & per phase X X change I/O cards after installation, giving you the ability to upgrade
Min./max. readings, I, V, PF, F, THD (IQ260), kW, kvar, kVA X X as needed.
Demand methods Industry-standard communication protocols
Block interval (sliding, fixed) X X
The IQ 250/260 meters use the open Modbus protocol. This
Communications industry-standard protocol provides serial communications with
RS-485 X X Eaton or third-party platforms, such as a building management
system, power management system, or Eatons Power Xpert
KYZ output X X
Gateway for Web-based monitoring.
Modbus RTU X X
Modbus ASCII X X Integrated with Eatons Power Xpert Architecture
DNP 3.0 X X IQ 250/260 meters integrate into Eatons Power Xpert Architecture,
where meters, gateways and monitoring devices collaborate to
Data Logging
create a unified, centralized view of the end-to-end power and
128KB for data logging Opt. Opt. facilitys infrastructure.
I/O When used in this architecture and in conjunction with Eatons
2 digital in / 2 digital out 1 Opt. Opt. Power Xpert Gateway, IQ 260/260 meters can provide Web-based
graphics of current power conditions. Simply connect your meter
4 digital in / 4 KYZ out Opt. Opt.
to a Power Xpert Gateway or upgrade to a Power Xpert Meter 2000
4 analog output (4 20 mA) 2 Opt. Opt. to translate Modbus-based information from the meter into HTML-
4 analog output (0 1 mA) Opt. Opt. based Web pages, accessible from any standard Web browser. With
access to accurate, real-time information from IQ 250/260 meters,
Power quality analysis the Power Xpert Architecture can transform your power system into
Total harmonic distortion (THD) voltage and current per phase X an integrated, agile system, an easily managed entity that performs
Alarming better and costs less.
Set point driven alarm X Designed for the user
1 Digital out with the IQ 250 requires external command. When space is at a premium, yet you need ANSI C12.20 accuracy,
2 Requires external power supply. Eaton IQ 250/260 meters fit the bill. These ultra-compact meters are
ideal for electrical equipment assemblies, machine control panels,
such as panelboard and switchboard mains and feeders, low voltage
metal-enclosed switchgear feeders and motor control centers.
Requiring far less space than other meters with similar functionality,
IQ 250/260 meters fit into a standard ANSI or IEC cutout on a
panelboard or other electrical equipment, and therefore fit easily into
retrofit applications.
Most meters in this class have small or dark displays that can be
hard to see, especially from a distance. IQ 250/260 meters have
a large, bright red, three-line LED display, each line more than a
half-inch tall. This display is very easy to read, even if the meter is
installed at a height or distance. Using the keypad and menus on the
local display, users can display a variety of electrical system values
or program the meter (see Figure 1). The IQ 250/260 meters can
also be configured remotely using Eaton configuration software,
provided with the meter.
In addition, the meters are available with or without the display mod-
ule. You might choose to forego the display for applications where
there is no need to configure or read the meter locally. This option
reduces costs, especially where many meters will be monitored
from a central operations system.

IQ 250/260 Meter (rear view) with connection and communication ports

2 EATON CORPORATION IQ 250/260 Electronic Power Meters


The Reading Type indica-
tor shows what type of The Parameter Designator
information youre viewing, shows the parameter
such as minimum, maxi- being displayed, such as
mum or %THD and above volts, amps, frequency,
or below limits exceeded power or energy.
(IQ 260).

These lights show The watt-hour test pulse


how loaded the is used to verify the
circuit is, from 10 to accuracy of the meter.
100 percent, relative
to the programmed
maximum.

Configurable Auto Scroll


The scaling factor to display all key values
shows the scale of in turn or fixed display.
the displayed value,
which varies between
low- and high-voltage
applications.

Figure 1 IQ 250/260 Meter faceplatedisplay

IQ 250/260 Meter dimensions

4.85 (123.2) 4.97 (126.2) 4.93 (125.2)


4.20 (106.7) 4.16 (105.7)

4.85 5.02 3.54


(123.2) (127.5) (89.9)

3.25 (82.6) 3.25 (82.6)

IQ 250/260 Face IQ 250/260M Side IQ 250/260T Side

IQ 250/260 Meter dimensions face and side views Expandable I/O componentry

IQ 250/260 Meter ordering information

IQ 250 M A 6 5 1 1 0

Model Series I/O Slot 2


250 = Energy 0 = None
260 = Power Quality Data Logging Frequency Power Supply
1 = 2 Relay Outputs/2 Status Inputs
A = None 5 = 50 Hz System 1 = 90 265 Vac/dc 2 = 4 KYZ Pulses/4 Status Inputs
L = Data logging 6 = 60 Hz System 4 = 24 48 Vdc 3 = 4 Analog Outputs: 0 1 mA
Meter Type
4 = 4 Analog Outputs: 4 20 mA
M = Meter (with integral display)
Current Input
T = Transducer Only (no display)
1 = 1 Amp Secondary I/O Slot 1
5 = 5 Amp Secondary 0 = None
1 = 2 Relay Outputs/2 Status Inputs
2 = 4 KYZ Pulses/4 Status Inputs
3 = 4 Analog Outputs: 0 1 mA
4 = 4 Analog Outputs: 4 20 mA

EATON CORPORATION www.eaton.com/powerxpert 3


IQ 250/260 Electronic Power Meter technical specifications

Current inputs Update rate


Class 10 5 amp nominal, 10 amp max. Watts, Var and VA 100 msec at 60 Hz
Class 2 1 amp nominal, 2 amp max. All other parameters 1 second at 60 Hz
Fault current withstand
Power supply
100 amps for: 10 seconds
AC/DC voltage option 90 265 Vac at 50/60 Hz or
300 amps for: 3 seconds
100 370 Vdc, universal AC/DC supply
500 amps for: 1 second
DC voltage option 18 60 Vdc
Continuous current 20 amps for screw terminated or
Burden 10 VA max.
withstand pass-through connections
Programmable current Full scale to any CT ratio Standard communications format
Burden 0.005 VA per phase max. at 11 amps Connection type RS-485 (through back plate)
Pickup current 0.1% of nominal Com port baud rate 9600 57,600 bauds
Class 10 5 mA Com port address 01 247
Class 2 1 mA Data format 8-bit, no parity
Connections Protocols Modbus ASCII, RTU or DNP 3.0
Pass-through wire 0.177 inches (4.5 mm)
gauge dimension KYZ pulse
Quick connect 0.25-inch male tab Contacts 1 form A
On resistance, max. 35 ohms
Voltage inputs
Peak switching voltage 350 Vdc
Range
Continuous load current 120 mA
Line-to-neutral 20 576 Vac
Peak load current 350 mA (10 ms)
Line-to-line 0 721 Vac
Off-state leakage 1 uA
Programmable Full scale to any PT ratio current at 350 Vdc
voltage range
Opto-isolation 3750 Vac
Supported systems 3 element wye, 2.5 element wye,
2 element delta, 4-wire delta systems Dimensions and shipping
Input impedance 1 meg ohm/phase Weight 2 lbs.
Burden 0.36 VA/phase max. at 600 V; Basic unit H 5.00 x W 4.90 x L 5.00 inches
0.014 VA at 120 Volts
IQ 250/260 Mounts in 92 mm DIN and ANSI
Connection 7-pin 0.400-inch pluggable terminal C39.1 round cut-outs
block, AWG #12 26 (0.129 3.31 mm2)
Shipping container 6-inch cube
dimensions
Isolation
Tolerance +/-0.1 inches (2.54 mm)
All inputs and outputs are galvanically isolated to 2500 volts.

Compliance
Environmental ratings
IEC 687 0.2% accuracy
Operating temperature -20C to +70C
ANSI C12.20 0.2% accuracy
Storage temperature -20C to +70C
ANSI C62.41 Burst
Operating humidity To 95% RH non-condensing
UL/cUL/CE Electrical & electronic
Faceplate rating NEMA 12
Measuring & test
Water-resistant Equipment 22CZ
Mounting gasket included
NNote: Features and specifications listed in this document are subject to change without
notice and represent the maximum capabilities of the software and products with all options
Sensing method installed. This is not a complete feature list. Features and functionality may vary depending
on selected options.
Voltage, current True RMS
Power Sampling at over 400 samples per cycle
on all channels
Harmonics resolution 40th order

Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com/meters

2011 Eaton Corporation Eaton and Power Xpert are registered


All Rights Reserved trademarks of Eaton Corporation.
Printed in USA
PA02601007E / TN All other trademarks are property of their
September 2011 respective owners.

Das könnte Ihnen auch gefallen