HYDRANT INSTALLATION NOTES:

1. CONCRETE BASE AND BLOCKING MATERIAL SHALL NOT


BLOCK OR OBSTRUCT HYDRANT DRAINAGE.

2. BOTH DRAINAGE STONE AND EARTH FILL ABOVE THE


STONE SHALL BE TAMPED

3. DRAINAGE STONE MUST BE COVERED WITH FILTER FABRIC

GROUND "WATER" ON LID


4. A VALVE BOX ADAPTER/ CENTERING DEVICE OF THE
APPROPRIATE SIZE AND TYPE MANUFACTURED BY ADAPTER SURFACE
INC. SHALL BE UTILIZED WITH ALL VALVE BOX
INSTALLATIONS
MUELLER SUPER CENTURION
WITH INTEGRAL 5" STORZ
5. REFER TO TYPICAL VALVE DETAIL FOR INSTALLATION OF
DRILL A HOLE IN VALVE BOX
CONNECTION CONFORMING TO
AUXILIARY VALVE AND VALVE BOX. WITHIN 12" OF TOP AND EXTEND
A.W.W.A. SPECIFICATIONS
TRACER WIRE INTO VALVE BOX.
6. TRACER WIRE TO BE INSTALLED IN ALL VALVE BOXES AS PROVIDE 4 MIN. OF WIRE
ILLUSTRATED.
TWO PIECE HEAVY DUTY INSIDE OF VALVE BOX.
EXISTING OR
BREAK AWAY COUPLING SCREW TYPE VALVE BOX,

18" TO 24"
7. IF MANUFACTURED WEDGES ARE USED TO ASSIST WITH PROPOSED CURB
BLOCKING TO CREATE A TIGHT FIT BETWEEN THE BLOCKING STAR PRODUCTS, VB-0002
3 MIN. CLEARANCE
AND THE FITTING, THE MATERIAL SHALL BE CAST IRON, OR EQUAL
HARD PLASTIC, OR OTHER MATERIAL APPROVED BY THE FINISHED GRADE TRACER WIRE
ENGINEER (NO WOOD OR OTHER MATERIAL WHICH COULD
DETERIORATE SHALL BE USED) CENTERING DEVICE,
SEE NOTE GATE VALVE SHALL BE MUELLER
VALVE BOX A-2360 RESILIENT WEDGE GATE
CENTERING DEVICE, BURY LINE SHALL BE SET VALVE - M.JxM.J. OR APPROVED
SEE NOTE 4 TO FINISHED GRADE LINE
EQUAL
AUXILIARY VALVE, INSTALL LAYER OF
REFER TO VALVE FILTER FABRIC
MINIMUM OF 5 FT.

OVER DRAIN FIELD


DEPTH OF BURY

BOX DETAIL

PRECAST 1" SIZE, WASHED RIVER GRAVEL


CONCRETE DRAIN FIELD (NO FINES) 1"
THRUST CUBIC YARD MINIMUM
UNDISTURBED SOIL

BLOCK

2 HORIZ. 8"x16"x4" PRECAST PROPOSED WATER PROVIDE CONCRETE BASE AND


SOLID CONCRETE UNITS, & 1
MAIN BLOCKING AGAINST
VERT. MIN BLOCKING AGAINST
UNDISTURBED EARTH UNDISTURBED EARTH

HYDRANT ANCHOR TEE


PRECAST NOTE:
(SWIVEL TEE), VALVE TO
CONCRETE WEDGES AS REQUIRED A VALVE BOX ADAPTER/
BE INSTALLED DIRECTLY
BLOCK SEE NOTE 7
ON ANCHOR TEE CENTERING DEVICE OF THE
PRECAST APPROPRIATE SIZE AND TYPE
6" SDR-21, CLASS
CONCRETE
200 HYDRANT LEAD MANUFACTURED BY ADAPTER
2 MINIMUM BLOCK BASE
MECHANICAL JOINT HYDRANT WIDTH
INC. SHALL BE UTILIZED WITH
DRAIN ALL VALVE BOX
INLET CONNECTION
OPENINGS
INSTALLATIONS, SEE WRITTEN
SPECIFICATION FOR APPROVED
HYDRANT INSTALLATION DETAIL PRODUCT

DATE: 9/28/2012 DATE: 6/10/2011

CHECKED: KC/JB CHECKED: KC/JB


CITY OF MACOMB, ILLINOIS CITY OF MACOMB, ILLINOIS
PUBLIC WORKS DEPARTMENT SHEET NO. PUBLIC WORKS DEPARTMENT SHEET NO.

233 CENTER STREET


TYPICAL FIRE HYDRANT 233 CENTER STREET
TYPICAL WATER VALVE
MACOMB, ILLINOIS 61455 INSTALLATION DETAIL 1 MACOMB, ILLINOIS 61455 INSTALLATION DETAIL 1
(309) 833-2821 (309) 833-2821
of 1 of 1

F.A.P. TOTAL SHEET


FILE NAME = USER NAME = jdeen DESIGNED - JRB REVISED - SECTION COUNTY
FAP 407 (IL RTE 336) RTE. SHEETS NO.
v:\transportation\2891\grading plans\W001.dgn DRAWN - RLR REVISED - STATE OF ILLINOIS 407 (55-3)A McDONOUGH 671 174
- -
UTILITY SPECIAL DETAILS
PLOT SCALE = 1.00 / IN. CHECKED AWM REVISED DEPARTMENT OF TRANSPORTATION CONTRACT NO. 68A42
PLOT DATE = 12/12/2012 DATE - 12-12-12 REVISED - SCALE: 1"=50 SHEET NO. 1 OF 4 SHEETS STA. TO STA. ILLINOIS FED. AID PROJECT