Sie sind auf Seite 1von 2

result in long term gains including a reduction in the time and on technical references relating to the reliability of substa-

expense of data transmission. tions which step down from a primary voltage to a secondary
distribution system voltage of 46 kV or below.
Requirements from Data Compression Algorithms The references are arranged alphabetically by the last name
of the first author appearing in the publication. Organization
Data compression schemes need to provide wide system names are used as the author when the individuals preparing
frequency response and also provide reasonable compression the document could not be identified. In some cases, no
ratios. This implies some very stringent requirements from author or organization could be identified on magazine
the data compression technique. First, the compression articles. These articles are credited to the magazine staff and
technique should not attenuate or accentuate any of the are so listed.
frequencies below the specification on the system frequency The vast majority of these references are readily available
response. Second, the compression algorithm should not in industry literature and in technical libraries.
corrupt the waveform data by adding higher frequency
components. Third, the compression technique should be
able to specify the slew rates in the input analog data beyond
which it fails. Certain accuracy specifications will also have
to be met by the compression technique. These specifica-
tions could limit the maximum variance of the magnitude of a
reconstructed sample from the actual measured value. The 88 SM 714-8
magnitude variance specification may also be tiered along the July 1989
magnitude of the input signal. Other requirements can be
expected to arise as more experience is gained in this area.
Increasing of Ground Resistance of Human Foot
Recommended Schemes In Substations Yards
A number of data compression schemes have been evalu- B. Thapar, Sr. Member IEEE
ated using data typical to a power systems environment. Two Ziad A. Alaywan, Member, IEEE
promising schemes have been identified. One of the schemes Montana State University
involves the use of the Fast Fourier Transform. This transform Bozeman, Montana
is applied on a cycle by cycle basis. A value for the upper
frequency limit on the data uploaded is set by the user during Summary
setup. Harmonics upto this upper frequency limit are up-
loaded. The second scheme, known as Differential Pulse Tolerable step and touch voltages for a person largely
Code Modulation (DPCM), is a differential coding or predictive depend on the grounding resistance of the foot. In a
coding system where waveform redundancy is utilized in substation switchyard a 0.08 to 0.1 5 m layer of crushed rock
time-domain operations to realize straightforward reductions is often spread on the surface of the earth to increase the
in transmission times. DPCM coders are based on the notion grounding resistance of the feet of the people in the substa-
of quantizing a prediction error signal, the prediction error tion area. However, if the thickness of the layer of crushed
being the difference between a predicted value and the actual rock is small and the soil underneath is of low resistivity, a
sample value. The performance of each of these techniques high value of the footing resistance is not obtained. Cement
has been evaluated using various data sets. concrete pathways in a switchyard when wet may result in a
low grounding resistance of the foot. For designing a safe
Conclusion grounding system a high value of footing resistance is
desirable. A simple method that can be adopted to obtain high
The search for a suitable compression method has just footing resistance is the use of a sheet of plastic material
begun. However, the results obtained from this effort have such as polyethylene, permalon, etc., immediately below the
provided insights into the requirements for any data compres- layer of crushed rock or the cement concrete pathway, at
sion scheme. Two promising approaches to compression of places in a substation where high footing resistance is
power systems data have been identified. Variations and needed. Plastic sheets having tear and puncture resistant
modifications of these fundamental approaches are recom- qualities are available and if used properly should last for a
mended so as to obtain optimum performance. Characteriza- long time.
tion of the disturbance data should also be performed to tune Analysis of the footing resistance when a plastic sheet is
the basic algorithms for power systems data. spread below the surface of earth is presented in this paper.
Scale model tests have been conducted to obtain results and
a simple method has been developed to obtain the grounding
resistance of the foot when a plastic sheet is used below the
surface of the soil.
Footing Resistance with Plastic Sheet
89 WM 063-9
A human foot is adequately represented by a conducting
July 1989 metallic disk having 8 cm radius. A circular plastic sheet
spread horizontally at a depth h below the surface of the soil
with its center below the center of the disk representing the
Bibliography for Reliability and Availability foot is considered.
Models prepared on a scale 1:4 were tested in a small
Engineering for Substations swimming pool filled with tap water. It was observed that if
IEEE Working Group Dl on Operating and Reliability the depth at which the plastic sheet was placed was not more
Aspects for Substation Design than 20 cm and the diameter of the sheet was more than 1 m,
the resistance offered by the soil to the flow of the current
Summary beyond the edge of the sheet was very small as compared to
the resistance offered by the soil above the sheet, therefore,
This paper presents a bibliography of 107 references only the region above the sheet was considered to evaluate
pertaining to the reliability and availability of substations. the resistance of the foot. Mathematics involved to determine
An extensive search has been made to identify technical the resistance offered by the soil above the plastic sheet to
papers, articles and books which are applicable to the study the flow of the current from an electrode is easiest when the
of substation reliability and availability. Emphasis was placed electrode is in the form of a vertical cylinder of length h placed
IEEE Power Engineering Review, July 1989 IEEE Power Engineering Review, July 1989.
53
at the center of the plastic sheet. With the help of scale model 89 WM 065-4
studies equivalent radius of the cylindrical conductor that July 1989
gave the same grounding resistance as the metallic disk of
radius 8 cm placed at the surface of the soil was determined
for different values of h. Seismic Behavior of Toughened Glass Station
Post Insulators for 800 kV Networks
Hole in the Plastic Sheet
J. Grases and A. 0. Lopez
To evaluate the effect of an opening in the sheet on the Central University of Caracas
grounding resistance of the foot circular holes are considered. Venezuela
A hole of irregular shape may be replaced by a circular hole R. Parraud, Member, R. Joulie
having the same area as the irregular hole. Through the hole and G. Bourdier
the current flows in the soil below the plastic sheet. The flow Sediver
of the current in the soil below the sheet will be almost the
same as from a disk of the same size of the hole placed at P, Saint-Yorre, France
the location of the hole. The total grounding resistance of the
foot can be determined by considering the resistance offered To prevent damage to the equipment in substations during
by the soil between the equivalent cylindrical conductor and earthquakes and ensure essential functions both during and
point P in series with the parallel combination of: (a) the after the events, special care must be taken in design and
resistance offered by the soil between point P and the rim of selection of each component, especially station post insula-
the plastic sheet and (b) the resistance offered by the soil tors used to insulate busbars and disconnecting switches. In
below the hole at P. the past, studies of seismic behavior of substation insulating
The grounding resistance of the foot when a plastic sheet components concentrated on porcelain members.
having a hole was spread below the surface of the soil was The test results, investigations and analysis reported
measured with the scale models for a large variation of hereafter represent a complete seismic characterization of
parameters within practical limits. The results obtained for 800 kV toughened glass station post insulators comprising
various values of the parameters through scaled model the following stages:
studies are quite close to those calculated with the above - verification of the ability of the post insulators to
mentioned method. withstand the seismic specifications of EDELCA (VENE-
The model studies indicate that if a hole in the sheet is ZUELA),
covered with a piece of plastic sheet the grounding resistance tests to determine the resistance limit under forced
of the foot is restored to that with no hole in the sheet. The -

vibrations,
covering sheet need not be sealed around the hole. - analytical study by mathematical model allowing analy-
sis of the behavior of the insulator in its real configura-
Surface Potential tion under combined exceptional stresses,
- definition of safety factors,
Through analog model studies comparison of the surface statistical study of failure probability in two well known
potentials with and without a plastic sheet is made for a 9 -

high earthquake risk areas: San Andreas fault (Califor-


mesh square grid. Depending on its location use of the plastic nia) and Bocono fault (Venezuela)
sheet may decrease or increase the touch voltage. However,
if the plastic sheet is located so as to increase the touch
voltage, even under the worst condition an increase in the Conclusion
touch voltage will be less than 30% Analytical as well as experimental studies of 800 kV
toughened glass post insulators have shown that they have
Conclusions more than sufficient capacity to withstand the seismic
Typical examples given in the paper show that a plastic actions established in modern specifications, with design
sheet used under a layer of crushed rock or a cement spectra anchored at 0.5 g, duly combined with simultaneous
concrete pathway in a substation significantly increases the gravity, conductor and short circuit effects. Shaking-table
grounding resistance of the foot. With the data presented in tests show that toughened glass post insulators withstand
this paper the grounding resistance of the foot, when a plastic earthquake forces which are at least 3 times larger than those
sheet is used, can be evaluated. The effect of any damage to required in present standards. Under extremely hazardous
the sheet, resulting in a hole, on the grounding resistance of seismic scenarios, for example near the San Andreas fault,
the foot can be estimated. In most situations use of the the probability of failure for 50-year lifespan hardly exceeds
plastic sheet extending 1 m from the foot will increase the 1%.
grounding resistance of the foot by more than 100%. These studies confirm that toughened glass station post
Advantage gained by the increase in the footing resistance insulators offer a new solution to problems of seismic
will not be offset by the increase in the touch voltage if at all resistance.
the increase in the touch voltage occurs.
Discussers: J. K. Arora and H.R. Seedher.

5454 IEEE Power Engineering


IEEE Power Engineering Review,
Review, July
July 1989

Das könnte Ihnen auch gefallen