Project No.

Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR A1

1. Input Data:

No. of levels (including ground floor) : 48


Average level height : 4.7896 m
Floor Area : m2
Exterior building wall area per floor : 584.6 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
Stairwell wall area per floor : 111.12 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
Elevator shaft walls : m2
Wall Tightness : (1=Tight, 2=Average, 3=Loose)
The area gap around each stairwell door : 0.024 m2
Outside design temperature : 46 deg C
Stairwell temperature : 27 deg C

Stairwell door width : 1 m


Stairwell door height : 2.1 m
Force to overcome door closer : 55 N
Distance from door knob to
edge of knob side of door : 75 mm

2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa

Critical Velocity : 1.524 m/s

4. Height Limit Check:

Maximum allowable pressure difference


between the stairwell and the building = 68.714 Pa
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR A1

Height limit below which satisfactory


pressuriation is possible = 92.7 m

5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.036 m2

B Pressure difference per height due to stack effect = 0.6869 Pa/m


Psb Pressure difference between stairwell top and the buildin = 151.81 Pa

5.a Simple stairwell pressurization:


Q Flow rate of the pressurization air = 12.736 m3/s (= 26986 cfm)

5.b Detailed stairwell pressurization:

In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.

I. Opened doors section:


Pressure difference at the bottom of the section = 12.4 Pa
Pressure difference at the top of the section = 18.209 Pa
Flow factor = 3.2753 m/s
Open stairwell flow area = 1.0831 m2
Effective flow area = 0.099 m2
Flow rate from this section = 0.6483 m3/s (= 1374 cfm)

II. Closed doors section:


Pressure difference at the bottom of the section = 20.628 Pa
Pressure difference at the top of the section = 172 Pa
Flow factor = 7.9838 m/s
Effective flow area = 0.036 m2
Flow rate from this section = 13.303 m3/s (= 28188 cfm)

III. Exterior stairwell door:


Pressure difference at the exterior door
(~ at 1.5m height) = 15.078 Pa
Open exterior stairwell door effective flow area = 1.0831 m2
Flow rate from this section = 3.5291 m3/s (= 7478 cfm)

The total flow needed to pressurize the stairwell


Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR A1

at the above conditions is the sum of these three


separate flows = 0.6483 + 13.303 + 3.5291
= 17.48 m /s
3

(= 37039 cfm)
No of SPAF = 3 sets

Flow rate per each fan = 13,581 cfm


+ 10% service factor = 23,074 m3/hr use = 24,000 m3/hr
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR A2

1. Input Data:

No. of levels (including ground floor) : 48


Average level height : 4.7896 m
Floor Area : m2
Exterior building wall area per floor : 584.6 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
Stairwell wall area per floor : 105.13 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
Elevator shaft walls : m2
Wall Tightness : (1=Tight, 2=Average, 3=Loose)
The area gap around each stairwell door : 0.024 m2
Outside design temperature : 46 deg C
Stairwell temperature : 27 deg C

Stairwell door width : 1 m


Stairwell door height : 2.1 m
Force to overcome door closer : 55 N
Distance from door knob to
edge of knob side of door : 75 mm

2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa

Critical Velocity : 1.524 m/s

4. Height Limit Check:

Maximum allowable pressure difference


between the stairwell and the building = 68.714 Pa
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR A2

Height limit below which satisfactory


pressuriation is possible = 92.3 m

5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.036 m2

B Pressure difference per height due to stack effect = 0.6869 Pa/m


Psb Pressure difference between stairwell top and the buildin = 152.4 Pa

5.a Simple stairwell pressurization:


Q Flow rate of the pressurization air = 12.526 m3/s (= 26541 cfm)

5.b Detailed stairwell pressurization:

In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.

I. Opened doors section:


Pressure difference at the bottom of the section = 12.4 Pa
Pressure difference at the top of the section = 18.233 Pa
Flow factor = 3.2766 m/s
Open stairwell flow area = 1.0831 m2
Effective flow area = 0.099 m2
Flow rate from this section = 0.6485 m3/s (= 1374 cfm)

II. Closed doors section:


Pressure difference at the bottom of the section = 20.568 Pa
Pressure difference at the top of the section = 171.92 Pa
Flow factor = 7.9809 m/s
Effective flow area = 0.036 m2
Flow rate from this section = 13.057 m3/s (= 27665 cfm)

III. Exterior stairwell door:


Pressure difference at the exterior door
(~ at 1.5m height) = 15.018 Pa
Open exterior stairwell door effective flow area = 1.0831 m2
Flow rate from this section = 3.5221 m3/s (= 7463 cfm)

The total flow needed to pressurize the stairwell


Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR A2

at the above conditions is the sum of these three


separate flows = 0.6485 + 13.057 + 3.5221
= 17.227 m /s
3

(= 36502 cfm)
No of SPAF = 3 sets

Flow rate per each fan = 13,384 cfm


+ 10% service factor = 22,740 m3/hr use = 24,000 m3/hr
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR B1

1. Input Data:

No. of levels (including ground floor) : 46


Average level height : 5.5196 m
Floor Area : m2
Exterior building wall area per floor : 584.6 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
Stairwell wall area per floor : 120.08 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
Elevator shaft walls : m2
Wall Tightness : (1=Tight, 2=Average, 3=Loose)
The area gap around each stairwell door : 0.024 m2
Outside design temperature : 46 deg C
Stairwell temperature : 27 deg C

Stairwell door width : 1 m


Stairwell door height : 2.1 m
Force to overcome door closer : 55 N
Distance from door knob to
edge of knob side of door : 75 mm

2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa

Critical Velocity : 1.524 m/s

4. Height Limit Check:

Maximum allowable pressure difference


between the stairwell and the building = 68.714 Pa
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR B1

Height limit below which satisfactory


pressuriation is possible = 93.3 m

5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.037 m2

B Pressure difference per height due to stack effect = 0.6869 Pa/m


Psb Pressure difference between stairwell top and the buildin = 165.37 Pa

5.a Simple stairwell pressurization:


Q Flow rate of the pressurization air = 13.028 m3/s (= 27605 cfm)

5.b Detailed stairwell pressurization:

In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.

I. Opened doors section:


Pressure difference at the bottom of the section = 12.4 Pa
Pressure difference at the top of the section = 19.051 Pa
Flow factor = 3.3189 m/s
Open stairwell flow area = 1.0831 m2
Effective flow area = 0.099 m2
Flow rate from this section = 0.6569 m3/s (= 1392 cfm)

II. Closed doors section:


Pressure difference at the bottom of the section = 21.721 Pa
Pressure difference at the top of the section = 188.55 Pa
Flow factor = 8.3361 m/s
Effective flow area = 0.037 m2
Flow rate from this section = 13.648 m3/s (= 28918 cfm)

III. Exterior stairwell door:


Pressure difference at the exterior door
(~ at 1.5m height) = 15.169 Pa
Open exterior stairwell door effective flow area = 1.0831 m2
Flow rate from this section = 3.5397 m3/s (= 7500 cfm)

The total flow needed to pressurize the stairwell


Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR B1

at the above conditions is the sum of these three


separate flows = 0.6569 + 13.648 + 3.5397
= 17.844 m /s
3

(= 37810 cfm)
No of SPAF = 3 sets

Flow rate oer each fan = 13,864 cfm


+ 10% service factor = 23,554 m3/hr use = 25,000 m3/hr
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR B2

1. Input Data:

No. of levels (including ground floor) : 46


Average level height : 5.5196 m
Floor Area : m2
Exterior building wall area per floor : 584.6 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
Stairwell wall area per floor : 134.24 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
Elevator shaft walls : m2
Wall Tightness : (1=Tight, 2=Average, 3=Loose)
The area gap around each stairwell door : 0.024 m2
Outside design temperature : 46 deg C
Stairwell temperature : 27 deg C

Stairwell door width : 1 m


Stairwell door height : 2.1 m
Force to overcome door closer : 55 N
Distance from door knob to
edge of knob side of door : 75 mm

2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa

Critical Velocity : 1.524 m/s

4. Height Limit Check:

Maximum allowable pressure difference


between the stairwell and the building = 68.714 Pa
Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR B2

Height limit below which satisfactory


pressuriation is possible = 94.3 m

5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.039 m2

B Pressure difference per height due to stack effect = 0.6869 Pa/m


Psb Pressure difference between stairwell top and the buildin = 163.78 Pa

5.a Simple stairwell pressurization:


Q Flow rate of the pressurization air = 13.515 m3/s (= 28636 cfm)

5.b Detailed stairwell pressurization:

In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.

I. Opened doors section:


Pressure difference at the bottom of the section = 12.4 Pa
Pressure difference at the top of the section = 18.982 Pa
Flow factor = 3.3153 m/s
Open stairwell flow area = 1.0831 m2
Effective flow area = 0.099 m2
Flow rate from this section = 0.6562 m3/s (= 1390 cfm)

II. Closed doors section:


Pressure difference at the bottom of the section = 21.87 Pa
Pressure difference at the top of the section = 188.7 Pa
Flow factor = 8.3428 m/s
Effective flow area = 0.039 m2
Flow rate from this section = 14.23 m3/s (= 30152 cfm)

III. Exterior stairwell door:


Pressure difference at the exterior door
(~ at 1.5m height) = 15.317 Pa
Open exterior stairwell door effective flow area = 1.0831 m2
Flow rate from this section = 3.557 m3/s (= 7537 cfm)

The total flow needed to pressurize the stairwell


Project No. Date
DESIGN CALCULATION 24-9-2017

Sheet No. Computed by


SHEET
1 xxx

Subject STAIR PRESSURIZATION CALCULATION Checked by Approved by


Building PALM 360 TOWER A, STAIR B2

at the above conditions is the sum of these three


separate flows = 0.6562 + 14.23 + 3.557
= 18.444 m /s
3

(= 39080 cfm)
No of SPAF = 3 sets

Flow rate oer each fan = 14,329 cfm


+ 10% service factor = 24,345 m3/hr use = 25,000 m3/hr
Wall Tightness - Area ratio
Construction element Tight Av. Loose V. Loose
1 2 3 4
Exterior building walls 0.00005 0.00017 0.00035 0.0012
Stairwell walls 0.000014 0.00011 0.00035
Elevator shaft walls 0.00018 0.00084 0.0018
Floors 6.6E-06 0.000052 0.00017

Door Width (mm)


Door Closer Force (N)
800 900 1000 1100 1200
25 113 102 92 84 78
30 108 97 88 80 74
35 103 93 83 77 71
40 98 88 79 73 67
45 92 83 75 69 64
50 87 78 71 65 60
55 82 74 66 61 56
60 77 69 62 57 53
62