DESIGN CALCULATION 24-9-2017
1. Input Data:
2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa
5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.036 m2
In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.
(= 37039 cfm)
No of SPAF = 3 sets
1. Input Data:
2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa
5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.036 m2
In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.
(= 36502 cfm)
No of SPAF = 3 sets
1. Input Data:
2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa
5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.037 m2
In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.
(= 37810 cfm)
No of SPAF = 3 sets
1. Input Data:
2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa
5. Calculations:
Abo Flow area between the building and outside per floor = 0.099 m2
Asb Flow area between stairwell and the building per floor = 0.039 m2
In this system, an exterior stairwell door opens automatically upon system activation. In addition, the upper
two floors will be considered opened, while the others doors will be considered closed.
(= 39080 cfm)
No of SPAF = 3 sets