Milwaukee, WI 53212 Day Tank Ph: 414.967.8800 Fx: 414.967.8811 www.tramont.com
A. Manufacturer Qualifications C. Fuel Containment Basin
Manufacturer shall have a minimum ten The day tank shall include a welded steel years experience in the design and containment basin to prevent escape of construction of Underwriters Laboratories fuel into the environment in the event of a (UL) listed day tank systems. tank rupture.
B. Construction Rupture basin (indoor applications only):
Day tank shall be Tramont Model TRX or The basin shall consist of an open-top, approved equivalent, and constructed in welded heavy gauge steel structure sized accordance with Underwriters Laboratories at a minimum of 150% of the tank Standard UL-142. The day tank shall also capacity. The basin shall be primed and be constructed in accordance with finish painted. Flammable and Combustible Liquids Code, NFPA 30; and The Standard for Installation Double wall basin (outdoor applications and use of Stationary Combustible Engine and indoor applications where required by and Gas Turbines, NFPA 37. Day tank shall local codes): The basin shall consist of a be made of heavy gauge steel welded heavy gauge steel structure sized construction. Tank shall be coated with rust at a minimum of 150% of the tank inhibitor inside, primed and finish painted capacity. The exterior of the basin shall be outside. Required tank connections include: primed and finish painted. The basin shall include a welded steel top with an 1 NPT engine supply appropriately sized NPT fitting for 1 NPT engine return emergency vent, and appropriately sized NPT fitting for emergency vent, zinc-plated emergency vent cap. sized as appropriate. Emergency vent cap shall be spring- 1 NPT overflow. pressure operated. Opening pressure shall 2 NPT normal vent be 0.5 psig; full opening pressure 2.5 psig. 4 square inspection port Limits shall be marked on top of each vent. with manual fuel level gauge and manual fill cap D. Leak Detection System A rupture basin leak detector switch shall It shall be provided with atmospheric be wired into the electronic control module (normal) vent cap with screen and (ECM). This will shut down the supply appropriately sized zinc-plated emergency pump and motor in case of a fuel leak into vent cap. Emergency vent cap shall be the containment basin. spring-pressure operated. Opening pressure shall be 0.5 psig; full opening pressure shall be 2.5 psig. Limits shall be marked on top of each vent.
C:\Documents and Settings\Tracyb\My Documents\Manuals\Updated Specifications\Spec Diesel Fuel Primary DT_revb.dot
Specification: Tramont Corporation Diesel Fuel Primary 3701 N. Humboldt Blvd. Milwaukee, WI 53212 Day Tank Ph: 414.967.8800 Fx: 414.967.8811 www.tramont.com
E. Electronic Control Module (ECM) Appropriate, and provide a minimum of 17
The electronic control module (ECM) shall feet of vertical lift at sea level. A motor be Tramont System 2000PLUS or shall be provided of sufficient horsepower approved equivalent. The system shall to operate the pump; electrical have a single electrical analog float sensor characteristics designated as appropriate. to provide level signal to the ECM. The following shall be provided as part of the G. Duplex Pumping System system: In applications requiring a duplex LED fuel level indicator pumping system the tank shall include two High fuel level warning pump and motor combinations. The (activates at 106% of tank pump/motors shall alternate as the lead capacity) when the tank is pumping fuel. The lead Low fuel level warning pump shall activate when the fuel level (activates at 62% of tank declines to 87% of tank capacity; the capacity) second pump shall activate and operate in Critical low level shut off tandem with the lead pump if the fuel level (activates at 6% of tank declines to 75% of capacity. Appropriately capacity) sized solenoid valves with strainers shall be Fuel in basin alarm provided on the pump fuel inlets. Pump control (Pump on at 87% of capacity, off at 100% of H. Reverse Pumping System capacity) A reverse pumping system shall be ECM functional signal provided in applications where the main tanks maximum fuel level is at a higher All warnings shall provide contacts for level than the day tank. The reverse remote annunciation (3 amps @ 120 VAC). pump/motor will return fuel to the main All signals and warnings shall be indicated tank in the event the day tank level by LED lights. All warnings shall be exceeds 110% of its normal capacity. The provided with normally open and normally reverse pump shall be activated by a closed contacts for remote annunciation. separate, critical high level float switch. The ECM shall be capable of being The reverse pump capacity will be equal to manually controlled with On, Off, and or greater than the capacity of the supply Test buttons. A secure internal test pump. If the tank includes a duplex supply button shall be provided to verify relays pumping system, the reverse pump shall functionality. The system shall be UL-508 be equal to or greater than the combined listed. Electrical characteristics shall be 120 capacity of the two supply pumps. VAC, 1 phase, 60 Hz.
F. Pumps The tank shall include a fuel oil pump to draw fuel oil from the main tank to the day tank. Pump capacity shall be sized as
C:\Documents and Settings\Tracyb\My Documents\Manuals\Updated Specifications\Spec Diesel Fuel Primary DT_revb.dot