1) POLYCAB REACTANCE AND IMPEDANCE OF XLPE POWER A2XFY

XLPE, ALUMINIUM,
Stranded
TYPE CV 650/1100V MULTI-CORE (ALUMINIUM) Running Starting
Cos 0.8 0.2
Sin 0.6 0.97
1 2 3 4 5 6 7 8 9 10 11 12 13
Nominal A.C. Resistance Reactance In Running In Starting As per In Air at 40C Three Core Three & Half Four Core In Ground at 25C
Sectional at 90C Catalogue
Area Vc- Vc-Calculated Vc-Voltage 3C, 3.5C & 4C
Cable Core Cable Cable 3C, 3.5C, 4C
Calculated Drop
mm2 Ohm/km Ohm/km MV/M/A Mv/amp./Mtr. Mv/amp./Mtr. Current in WEIGHT DIA in mm WEIGHT in DIA in mm WEIGHT in DIA in Current in AMP.
AMP. in Kg./Km Kg./Km Kg./Km mm

A2XWY 2.5 9.48 0.0985 13.24 3.98 24 350 16 560 17.5


A2XWY 4 5.9 0.0927 9.55 2.54 36 530 15 610 17.5 34
A2XWY 6 3.94 0.0884 6.41 1.75 47 640 16 730 18.5
A2XWY 10 2.34 0.0837 3.84 1.10 62 865 19 1010 20.5 57
A2XFY 16 2.44 0.0808 4.00 1.13 4.20 70 530 18.5 715 20 73
A2XFY 25 1.54 0.0805 2.56 0.77 2.70 96 770 20.5 850 23 940 23 94
A2XFY 35 1.11 0.0783 1.87 0.60 1.90 117 900 23 980 25 1050 25 113
A2XFY 50 0.82 0.075 1.40 0.47 1.40 142 1100 25.5 1240 28 1280 28 133
A2XFY 70 0.567 0.074 1.00 0.37 0.99 179 1425 30 1600 32 1700 32 164
A2XFY 95 0.41 0.0724 0.74 0.30 0.72 221 1735 33.5 1900 36 2100 35 196
A2XFY 120 0.324 0.0712 0.60 0.27 0.58 257 2050 35.5 2300 39 2600 39 223
A2XFY 150 0.264 0.0716 0.51 0.24 0.48 292 2100 40.5 2650 42 3000 43.5 249
A2XFY 185 0.21 0.0718 0.42 0.22 0.39 337 2500 44.5 3250 47.5 3650 48 282
A2XFY 240 0.16 0.071 0.34 0.20 0.31 399 3700 49 4100 53.5 4700 54 326
A2XFY 300 0.128 0.0705 0.29 0.19 0.26 455 4500 53 4950 57 5600 59.5 367
A2XFY 400 0.1 0.0704 0.24 0.18 0.21 530 5700 58.5 6150 65 7000 66.5 418
A2XFY 500 0.0774 0.0702 0.21 0.17 - 612 6900 67 7600 73.5 - - 470
A2XFY 630 0.06 0.0698 0.18 0.16 - 707 8700 73 - - - - 529
A2XFY 800 0.047 - - - -
A2XFY 1000 0.0372 - - - -

Page :- 1 of 10
2) POLYCAB DATA REACTANCE AND IMPEDANCE OF XLPE POWER 2XWY / 2XFY
XLPE COPPER,
Stranded
TYPE CV 600/1000V MULTI-CORE (COPPER)
1 2 3 4 5 6 7 8 9 10 11 12 13
Norminal Sectional A.C. Resistance Reactance In Running In Starting As per In Air at 40C Three Core Three & Half Four Core In Ground at 25C
at 90C Catalogue
Area Vc- Vc-Calculated Vc-Voltage 3C, 3.5C & 4C
Cable Core Cable Cable 3C, 3.5C, 4C
Calculated Drop
mm2 Ohm/km Ohm/km MV/M/A Mv/amp./Mtr. Mv/amp./Mtr. Current in WEIGHT DIA in mm WEIGHT in DIA in mm WEIGHT in DIA in Current in AMP.
AMP. in Kg./Km Kg./Km Kg./Km mm
2XWY 1.5 15.5 0.107 24.93 6.41 22 390 13 - 415 13.5 25

2XWY 2.5 9.48 0.0985 13.24 3.98 30 425 14 - 500 14.5 34

2XWY 4 5.9 0.0927 8.27 2.54 36 580 16 - 610 17.5 43


2XWY 6 3.94 0.0884 5.55 1.75 47 680 17 - 660 18.5 54

2XWY 10 2.34 0.0837 3.33 1.10 62 865 19 - 730 20.5 72

2XFY 16 1.47 0.0808 2.12 0.74 4.20 79 825 18.5 - 1050 20 92

2XFY 25 0.93 0.0805 1.37 0.53 2.70 108 1235 20.5 1410 23 1520 23 119
2XFY 35 0.671 0.0783 1.01 0.42 1.90 132 1550 23 1725 25 1915 25 144

2XFY 50 0.495 0.075 0.76 0.34 0.88 162 2020 25.5 2325 28 2510 28 174

2XFY 70 0.343 0.074 0.55 0.28 0.99 198 2720 30 3110 32 3430 32 210

2XFY 95 0.247 0.0724 0.42 0.24 0.72 240 3500 33.5 8975 36 4450 35 252

2XFY 120 0.196 0.0712 0.35 0.22 0.58 276 4320 35.5 4960 40 5575 39 288

2XFY 150 0.159 0.0716 0.29 0.20 0.48 318 5280 40.5 5870 44 6710 43.5 324

2XFY 185 0.127 0.0718 0.25 0.19 0.39 366 6385 44.5 7275 50 8225 48 360

2XFY 240 0.0965 0.071 0.21 0.176 0.31 426 8150 49 9300 55 10340 54 414
2XFY 300 0.0769 0.0705 0.18 0.17 0.26 480 10060 53 11500 58 13025 59.5 462

Page :- 2 of 10
3) POLYCAB DATA REACTANCE AND IMPEDANCE OF PVC/PVC POWER YWY/ AYWY/AYFY
PVC Copper, 1 2 3 4 5 6 7 8 9 10 11 12 13
ALUMINIUM,
Stranded
Norminal A.C. Resistance Reactance In Running In Starting As per In Air at 40C Three Core Three & Half Four Core In Ground at 25C
Sectional at 85C Catalogue
Area Vc- Vc-Calculated Vc-Voltage 3C, 3.5C & 4C
Cable Core Cable Cable 3C, 3.5C, 4C
Calculated Drop
mm2 Ohm/km Ohm/km MV/M/A MV/M/A Mv/amp./Mtr. Current in WEIGHT DIA in mm WEIGHT in DIA in mm WEIGHT in DIA in Current in AMP.
AMP. in Kg./Km Kg./Km Kg./Km mm
YWY 1.5 15.2 0.114 24.46 6.30 26.300 17 405 12.5 440 15 21
YWY 2.5 9.3 0.11 15.01 3.93 16.100 24 475 14 550 16.5 27
YWY 4 5.79 0.106 9.39 2.52 10.000 30 580 15.5 650 18 36
YWY 6 3.87 0.1001 6.31 1.74 6.700 39 700 17 800 19.5 45
AYWY 10 3.89 0.0938 6.34 1.74 6.730 40 700 19 660 20 46
AYFY 16 2.41 0.0862 3.96 1.13 4.180 51 650 20 750 23 60
AYFY 25 1.51 0.0854 2.52 0.77 2.630 70 800 22 900 23.5 950 24 76
AYFY 35 1.01 0.0827 1.72 0.56 1.900 86 950 25 1030 26 1165 27 92
AYFY 50 0.809 0.0825 1.39 0.48 1.410 105 1200 27 1350 30 1540 31 110
AYFY 70 0.559 0.0771 0.99 0.37 0.978 130 1500 31 1725 32.5 1800 35 135
AYFY 95 0.404 0.0767 0.74 0.31 0.713 155 1900 34 2130 36.5 2400 38 165
AYFY 120 0.32 0.0744 0.60 0.27 0.569 180 2240 38 2580 40.5 2800 42 185
AYFY 150 0.261 0.0745 0.51 0.25 0.470 205 2700 42 3050 44 3350 46 210
AYFY 185 0.208 0.0744 0.42 0.23 0.383 240 3200 46 3650 50 4000 51 235
AYFY 240 0.159 0.074 0.34 0.21 0.304 280 3990 52 4580 55 5050 58 275
AYFY 300 0.128 0.0732 0.29 0.19 0.256 315 4850 56.5 5500 61 6200 66 305
AYFY 400 0.101 0.0727 0.25 0.18 0.215 375 6100 64 7000 68 7850 72 335
AYFY 500 0.00 0.00 410 7600 72 8600 75 9600 80 350
AYFY 630 0.00 0.00
AYFY 800 0.00 0.00

Page :- 3 of 10
CABLE LAID ON CABLE TRAY EXPOSED TO AIR WITH TOUCHING EACH OTHER

SUPPLY VOLTAGE 425


SINGLE PHASE
246
VOLTAGE
ALLOWABLE VOLTAGE
5%
DROP

TEMPERATURE
RATING FACTOR FOR
1.00
CABLE LAYING IN AIR
@ 40C
CABLE LAID IN AIR
NOT LAID DIRECT IN 1.00
THE GROUND
NO. OF CABLE TRAYS IN TIER No. of cable
CABLE LAID ON 1 3 9
TRAYS EXPOSED TO 1 1 0.8 0.73
AIR WITH TOUCHING 2 1 0.76 0.69
EACH OTHER 3 1 0.74 0.68
6 1 0.72 0.66
CABLE LAID ON
TRAYS EXPOSED TO
0.690 1.73
AIR WITH TOUCHING
EACH OTHER DERATING FACTOR
NO OF TRAYS IN TIER
1 NOS. WITH 9 NOS. 0.793 1.830587 1.739057848
OF CABLE LAID

0.657

Cable Schedule

PHASE or ONE RUN Vd in


CONNECTED ROUTE TOTAL DE RATING CABLE
DIVERSIFIED NO OF CABLE CABLE Running
LOAD LENGTH LENGTH CURRENT CAPACITY
CABLE TAG NO. FROM TO CURRENT RATING Condition %

KW Amp Meter RUNs CORE SIZE TYPE Meter Amp 0.690 Amp %

AHU- 01_Blower 2.2 4 10 1 3 2.5 2XWY 10 24 17 17 0.12

AHU- 01_Heater 12.0 21 10 2 3 2.5 2XWY 20 24 17 33 0.32

VU-01_Supply Blower 5.5 10 15 1 3 2.5 2XWY 15 24 17 17 0.44

VU-01_Return Blower 3.7 6 15 1 3 2.5 2XWY 15 24 17 17 0.30

Deduster 5.0 9 25 1 4 2.5 2XWY 25 24 17 17 0.67


HVAC & Service
Equipment Panel
Dispensing Booth-01 3.0 5 15 1 4 2.5 2XWY 15 24 17 17 0.24

Dispensing Booth-02 3.0 5 10 1 4 2.5 2XWY 10 24 17 17 0.16

Ex. Fan 1.0 6 22 1 2 2.5 2XWY 22 24 17 17 0.38

UPS (3 kVA) 2.5 14 10 1 2 2.5 2XWY 10 24 17 17 0.43

SPDB- 01 6.0 10 10 1 4 2.5 2XWY 10 24 17 17 0.32

UPS (3 kVA) UPSDB- 01 2.0 3 10 1 2 2.5 2XWY 10 24 17 17 0.11


Applicable CORE CORE CORE CORE CORE
for Motor 3.5C A2XFY 3.5C A2XFY 3.5C A2XFY 3.5C A2XFY 3.5C A2XFY
feeders
V02

V03

V04

V05

Vd in Weight in
No. OF
Starting Dia Total Dia Weight Kg/m x no. of 300 240 185 150 120
TERM.
Condition% runs

Weather Weather Weather Weather Weather


% SC mm mm Kg/Km Kg/Km Meter SC Meter SC Meter SC Meter SC Meter SC
proof proof proof proof proof

0.25 2 20.5 20.5 730 0.73

1.36 4 20.5 41.0 730 1.46

0.94 2 20.5 20.5 730 0.73

0.63 2 20.5 20.5 730 0.73

1.42 2 20.5 20.5 730 0.73

0.51 2 20.5 20.5 730 0.73

0.34 2 20.5 20.5 730 0.73

0.79 2 0.0 0.00

0.90 2 0.0 0.00

0.68 2 0.0 0.00

0.23 2 0.0 0.00


CORE CORE CORE CORE CORE CORE CORE CORE
3.5C A2XFY 3.5C A2XFY 3.5C A2XFY 3.5C A2XFY 3C A2XFY 3.5C A2XFY 4C A2XFY 4C

95 70 50 35 35 25 16

Weather Weather Weather Weather Weather Weather Weather


Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter
proof proof proof proof proof proof proof
CORE CORE CORE CORE CORE CORE CORE
2XWY 4C 2XWY 4C 2XWY 4C 2XWY 4C YWY 3C A2XFY 3C A2XFY 3C A2XFY

10 6 4 2.5 1.5 25 16 10

Weather Weather Weather Weather Weather Weather Weather


SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC
proof proof proof proof proof proof proof
CORE CORE
3C 2XWY 3C 2XWY 3C 2XWY 5G 100I 5G 100I 5G 100I 5G 100I

6 4 2.5 2.5 4 6 10

Weather Weather Weather Weather Weather Weather Weather Weather


Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC
proof proof proof proof proof proof proof proof
5G 100I 5G 100I 5G 100I 5G 100I 5G 100I 5G 100I 5G 100I 5G

16 25 35 50 70 95 120

Weather Weather Weather Weather Weather Weather Weather


Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter SC Meter
proof proof proof proof proof proof proof
100I 5G 100I 5G 100I

ACTUAL LENGTH
150 185 240
VARIFIED

Weather Weather Weather


SC Meter SC Meter SC Meter
proof proof proof

Das könnte Ihnen auch gefallen