Ambient conditions
Ambient temperature
during operation -20...+60C
during storage -50...+80C
Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current- 9...12.5A
dependent overload release
Operating voltage
rated value 690V
at AC-3 rated value maximum 690V
Operating current
at AC-3
at 400 V rated value 12.5A
Operating power
at AC-3
at 400 V rated value 5.5kW
Operating frequency
at AC-3 maximum 151/h
Auxiliary circuit
Number of CO contacts
for auxiliary contacts 0
Short-circuit protection
Design of the overcurrent release and short-circuit thermomagnetic
release
Connections/Terminals
Product function
removable terminal for auxiliary and control No
circuit
Type of electrical connection
for main current circuit screw-type terminals
for auxiliary and control current circuit screw-type terminals
Arrangement of electrical connectors for main current front side
circuit
Type of connectable conductor cross-sections
for main contacts
solid 2x (1 ... 2.5 mm), 2x (2.5 ... 6 mm)
stranded 2x (1 ... 2.5 mm), 2x (2.5 ... 6 mm)
finely stranded with core end processing 2x (1 ... 2.5 mm), 2x (2.5 ... 6 mm)
at AWG conductors for main contacts 2x (14 ... 10)
Certificates/approvals
General Product Approval For use in hazardous locations Declaration of
Conformity
other
Environmental
Confirmations
Further information