Sie sind auf Seite 1von 1

' TSNPDCL' DP STRUCTURE CT/PT DP STRUCTURE CONSUMER DP STRUCTURE

11KV/433V
315KVA
11 KV 200 A 11KV 11KV 400 A TRANSFORMER
11 KV TSNPDCL 11 KV 11KV 500A
AB SWITCH HG FUSE AB SWITCH
SUPPLY HG FUSE HG FUSE MCCB
2RX3.5CX240SQ.MM 2RX3.5CX240SQ.MM
CT/PT AR. AL. CABLE AR. AL. CABLE
TO MV PANEL

9KV/5KA 9KV/5KA
LA'S LA'S

615 910 910 615


11KV,3P,400A;AB SWITCH

400 A AB SWITCH
ISMC 100 x 50 MM
1400

'O' SIZE COPPER


11 KV PIN INSULATORS 125 125 C.I. COVER
9 KV;5KA;LA'S 400 WITH FRAME

40

1400
1400

11 KV HG FUSE
6

150 250
457
FUNNEL WITH
ISMC 100 x 50 MM 203

60
F.G.L WIRW MESH

1250
175 X 25 RS JOIST
GAY INSULATOR
1250 150 150
175 X 85 ISMB

11KV STAY SET 600


4500

T.R OPERATING HANDLE A HOMOGENOUS LAYER OF COKE/


3080

CHARCOAL SALT AND SAND


315 KVA

2750

508
COIL EARTHING
50 X 50 X 6 MM ANGLE
1800

1500
40 MM METAL

1200

2750
1500

900 2000 CI PIPE 100 ID


N1 N2 13 THICK
11KV HG FUSE SET DETAILS
LA'S B2
B1
SIDE VIEW OF CONSUMER DP STRUCTURE
1500 3000 1500

ELEVATION OF CONSUMER DP STRUCTURE 1. ALL DIMENSIONS ARE IN mm UNLESS OTHER WISE SPECIFIED.
2. ALL THE JOIST POLES ARE OF ISMB-200 AND A LENGTH OF 6500mm. EARTH PIT DETAILS
3. ALL THE CHANELS ARE OF ISMC-100.
4. 60mm H.B.G METAL WILL BE SPREDED IN THE SWITCH YARD.
5. NO WORK SPACE WILL BE PROVIDED ON THE TRANSFORMER PLINTHS.
6. THE TRANSFORMER WILL BE CONNECTED WITH TWO SEPARATE AND DISTINCT
G A T E

EARTH CONNECTIONS. SIZE OF EARTH CONDUCTOR 2RX50X6mm G.I STRIP.


1500

7. THE NEUTRAL OF THE TRANSFORMER WILL BE CONNECTED TO TWO DIFFERENT


EARTH ELECTRODES. SIZE OF THE EARTH CONDUCTOR 25X6 mm CU STRIP.
BE
8. A CLEAR SPACE OF ONE METER IN FRONT OF THE PANEL BOARDS WILL BE
NE
E2 PROVIDED.
9. THE EARTH ELECTRODES USED ARE 100MM DIA. X2.75MTS CI PIPE.
OVER HEAD LINES
CT/PT DP

6100
315 KVA
3050

LA'S
TXR

P L A N

CONSUMER DP
1550

NE BE E1
1500

GATE CLENT ::

1500 1500 3050 5000


CONTRACTOR ::
1500
10980
TITLE ::
CONSUMER DP STRUCTURE
SCALE :: NTS DRAWING NO: 1 SHEET NO: 1 OF 3

Das könnte Ihnen auch gefallen